Sie sind auf Seite 1von 1

SECTION OF CABLE TRENCH

150MM 1000MM 150MM

75 MM CABLE TRENCH COVER 75

200
125
Y.L Y.L
75 X 10 MM THK MS PLATE
1M C/C
VERT ON EACH FACE
10mm TOR @ 150 C/C STR

50MM PVC WEEP 1250


HORZ ON EACH FACE 75 X 75 X 6 MM ANGLE BRACKET HOLE C/C 2 M T/B
8mm TOR @ 300 C/C STR
1125

10mm TOR @ 150 C/C STR


AT TOP & BOTTOM
450

8mm TOR @300 C/C STR


AT TOP & BOTTOM R.C.C. M-20 RAFT 200 300

P.C.C. 1:3:6 100

230

100 100 150 1000 150 100 100

TYP. REINE DETAILS OF CABLE TRENCH

NOTES:- M/s. PUSHPGIRI CONSTRUCTIONS


1. ALL DIMENSIONS ARE IN MM AND LEVELS ARE IN METERS.
CIVIL WORKS FOR CONSTRUCTION OF 22KV
2. UNLESS OTHERWISE STATED ALL CONCRETE FOR R.C.C. WORK GIS PANEL ROOM, POWER CABLE TRENCH
SHALL BE IN M-20 GRADE TO GIVE STRENGTH OF 20N/mm2 AT 28 DAYS AND METAL SPREADING AT 220/ 22KV
3. ALL STEEL USED FOR R.C.C. SHALL BE HIGH YIELD STRENGTH MULUND SUBSTATION
DEFORMED BARS (TOR STEEL) CONFIRMING TO IS 1786 (GRADE Fe 415)
( TYP. REINE DETAILS OF CABLE TRENCH)
SUCH BARS ARE DENOTED BY SYMBOL
4. ALL CONCRETE FOR R.C.C. WORK SHALL BE MACHINE MIXED
AND VIBRATED WITH VIBRATOR DRAWN CHECKED RECOMMEND DRG NO. SR.NO
5. CLEAR CONCRETE COVER TO REINFORCING BARS BE AS FOLLOWS 01
a) PILE CAP 50MM ON BOTTOM/ SIDE. b) COLUMNS 50MM. c) PILE 50MM
APPROVED DATE SCALE PGC/MULUND/01
6. MINIMUM LAP LENGTH SHALL BE 47 TIMES THE BAR DIAMETER REV.NO
LAPS SHALL BE STAGGERED AND NEVER LOCATED AT ONE PLACE. 01
7. IF DUE TO SITE CONDITIONS OR PRACTICAL DIFFICULTIES IN
EXECUTING THE WORK, ANY CHANGES ARE REQUIRED IN
DESIGN / DRAWING, THE SAME SHALL BE REFERRED TO THE
APPROVING AUTHORITY

Das könnte Ihnen auch gefallen