Sie sind auf Seite 1von 18

ASIA-PACIFIC JOURNAL OF CHEMICAL ENGINEERING

Asia-Pac. J. Chem. Eng. 2012; 7: 93110


Published online 20 September 2010 in Wiley Online Library
(wileyonlinelibrary.com) DOI:10.1002/apj.497

Research article
Design of IMC filter for PID control strategy of open-loop
unstable processes with time delay
M. Shamsuzzoha,1 Mikhail Skliar2 and Moonyong Lee3 *
1
Department of Chemical Engineering, Norwegian University of Science and Technology, Trondheim, Norway
2
Department of Chemical Engineering, University of Utah, Salt Lake City, Ut 84112, USA
3
School of Chemical Engineering and Technology, Yeungnam University, Kyongsan 712-749, Korea

Received 3 February 2010; Revised 14 June 2010; Accepted 27 June 2010

ABSTRACT: A modified internal model control (IMC) filter has been proposed for the open-loop unstable process
with time delay and a further IMCproportional-integral-derivative (PID) tuning rule is derived on the basis of the
proposed IMC filter. Investigation of the IMC filter structure clearly demonstrates that a critically damped filter does not
always provide satisfactory response and that this is probably due to lack of sufficient integral action. The conventional,
critically damped filter is therefore replaced with a more general, second-order IMC filter for improved integral action.
The present investigation shows that for the most unstable processes, the underdamped IMC filter provides the desired
integral action and improves the closed-loop performance of the system except for the unstable processes with a strong
lead term. An exhaustive simulation studies has been performed to show the advantage of the proposed method in both
nominal and robust cases. By incorporating Kharitonovs theorem, closed-loop time constant () guidelines have been
provided for the first-order delayed unstable process (FODUP). 2010 Curtin University of Technology and John
Wiley & Sons, Ltd.

KEYWORDS: unstable process; PID controller tuning; dead time process; IMCPID design; robust analysis; IMC
filter

INTRODUCTION variability. Clearly, the tuning of controllers to stabilize


these processes and to impart adequate disturbance
In process control, majority of control loops are rejection is critical.
proportional-integral-derivative (PID) type, primarily Paor and Malley[4] proposed the tuning method
due to its relatively simple structure, which can be for the first-order delayed unstable process (FODUP).
easily understood and implemented in practice. It is The method is based on the gain and phase mar-
well-known that control system design for an open-loop gins criterion. Visioli[5] proposed tuning formulas to
unstable process is more difficult than that for a stable optimize PID parameters in terms of integral error
one because of the unstable nature of the dynamics, for specifications via a genetic algorithm. However, these
which most design tools cannot be used. Many of the conventional PID design methods show excessive
important chemical processing units in industrial and overshoots and large settling times. To solve these
chemical practice are open-loop unstable processes that problems, double-loop schemes have been employed
are difficult to control, especially in the presence of a for performance enhancement.[6,7] Huang and Chen[8]
time delay, such as in the case of continuous stirred tank suggested a three-element structure for controlling the
reactors, polymerization reactors and bioreactors which open-loop unstable processes. However, PID controllers
are inherently open-loop unstable by design.[1 3] tuned by this method give about 100% overshoot
Furthermore, many of these processes are usually for set-point change. Jung et al .[9] suggested a tuning
run batchwise, and as a result of possible formulation method by using a first-order set-point filter to construct
changes, may operate with significant batch-to-batch a two-degree-of-freedom (2DOF) control structure for
first-order unstable processes.
The effectiveness of the internal model control (IMC)
*Correspondence to: Moonyong Lee, School of Chemical design principle has made this method attractive in the
Engineering and Technology, Yeungnam University, Kyongsan
712-749, Korea. E-mail: mynlee@ynu.ac.kr process industry and concentrated efforts on exploit-

This work was conducted at Yeungnam University, Korea during ing the IMC principle to design equivalent feedback
Shamsuzzohas PhD period. controllers for unstable processes.[10] The IMC-based
2010 Curtin University of Technology and John Wiley & Sons, Ltd.
Curtin University is a trademark of Curtin University of Technology
94 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

PID tuning rules have the advantage of using only one disturbance rejection. Excessive overshoot in the set-
tuning parameter to achieve a clear trade-off between point response is eliminated by a set-point filter. On the
closed-loop performance and robustness. basis of extensive simulation study, closed-loop time
The IMC structure is very powerful for controlling constant () guidelines are proposed for 5% and 10%
stable processes with time delay, but it cannot be dead time uncertainty by using Kharitonovs theorem[21]
directly used for unstable processes because of the at different damping coefficient ( ) values. The simu-
internal instability.[10] For this reason, some modified lation studies confirm the advantage of the proposed
IMC methods of 2DOF control were developed for method over other recently published methods for sev-
controlling unstable processes with time delay.[7,11 14] eral representative classes of the process model while
In addition, 2DOF control methods based on the Smith maintaining the same robustness according to the mea-
predictor (SP) were proposed by several authors[15 17] sure of maximum sensitivity, Ms.
to achieve a smooth nominal set-point response without
overshoot for the FODUP. Both the modified IMC
and modified SP methods feature the worthy advantage IMCPID CONTROLLER DESIGN PROCEDURE
of the nominal set-point response tending to be faster
without overshoot for unstable processes. In fact, the Figure 1(a) presents a block diagram of the IMC control
common characteristic of these modified IMC and SP structure, where Gp is the process, G p the process
methods is the use of a nominal process model in model, and q the IMC controller. In the IMC control
their control structures, which is responsible for their structure, the controlled variable is related as follows:
good performance in this respect. Most existing 2DOF Gp q
C =   fR R
control methods are restricted to unstable processes in
1 + q Gp G p
the form of a first-order rational part plus time delay,
which, in fact, cannot sufficiently represent a variety
1 G p q
of industrial and chemical unstable processes. Besides, +   Gp d (1)
there usually exist unmodeled dynamics that inevitably 1 + q Gp Gp
tend to deteriorate the control system performance.
Zhou et al .[18] have conducted a comparative study For the nominal case (i.e. Gp = G p ), the set-point and
for understanding the time-delayed effect on unstable disturbance responses are simplified as below:
processes. On the bases of performance and robust-
ness, Zhou et al .[18] suggested that the tuning methods C
= Gp qfR (2)
presented by Lee et al .[11] and Yang et al .[12] are appli- R
cable in large normalized dead time . Xiang C
and Nguyen[19] have suggested a control design method = (1 Gp q)Gp (3)
d
for the FODUP with a complicated three-element con-
trol structure. This method is advantageous in the set-
Disturbance
point performance but in the disturbance rejection it IMC
setpoint d
shows big overshoot and long settling time. The con- filter controller Process
R u(t) C
troller design for second-order delayed unstable pro- fR +- q ++ Gp
cess (SODUP) systems with two unstable poles and a
negative zero has been described by Lee et al .[11] and Process model
Wang and Hwang[20] . However, the controller design for ~
Gp -+
SODUP systems with one/two right-half-plane (RHP)
poles and an RHP zero has not yet been addressed
The IMC structure
properly.
It is apparent from the literature that only few tuning Disturbance
d
methods are available for dead time dominant unstable
setpoint
processes and the processes which contain one/two filter Controller Process
R u(t) C
unstable poles and positive and negative zeros. The fR +- Gc ++ Gp
above discussion demonstrates that a tuning method is
required to cover several classes of the process model,
including positive and negative zeros, and also various
dead time dominant unstable processes.
Classical feedback control structure
In this study, the dead time dominant unstable pro-
cess with positive and negative zeros was investigated. Figure 1. Block diagram of IMC and classical feedback
The modified IMC filter has been suggested and cate- control. (a) The IMC structure. (b) Classical feedback control
gorized for several classes of the process for improved structure.
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
Asia-Pacific Journal of Chemical Engineering PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES 95

In the classical feedback control structure shown in Gp , and r is selected as being large enough to make the
Fig. 1(b), the set-point and disturbance responses are IMC controller proper.
represented by
1 Gp q|s=up1 ,up2 ,,upm =

C Gc Gp fR  m
= (4) PA ( i s + 1)
i
R 1 + Gc Gp

1 i =1 = 0 (8)
C Gp ( s + 2 s + 1)
2 2 r
= (5)
d 1 + Gc Gp

s=up1 ,up2 ,,upm

where Gc denotes the feedback controller. The IMC Then, the IMC controller is
controller is a competent method for control system
m
design.[10] However, for unstable processes, the IMC 
i s + 1
i
structure cannot be implemented because any bounded
1 i =1
input, d , will produce unbound output, C , if Gp is unsta- q = PM (9)
ble. As discussed by Morari and Zafiriou,[10] the IMC ( s + 2 s + 1)r
2 2

approach to designing a controller for an unstable pro- Thus, the resulting set-point and disturbance responses
cess is possible for Gp = G p if the following conditions are obtained as
are satisfied for the internal stability of the closed-loop
m
system: 
i s i + 1
C i =1
1. q is stable. = Gp qfR = PA 2 2 fR (10)
2. Gp q is stable.
R ( s + 2 s + 1)r
3. (1 Gp q)Gp is stable. C
= 1 Gp q Gp
d

m
These three conditions result in the well-known, stan- 
dard interpolation conditions:[10] i s i + 1

If the process model, Gp , has unstable poles, up1 , i =1
= 1 PA 2 2 r
G (11)
up2 , , upm , then q should have zeros at up1 , up2 , , ( s + 2 s + 1) p
upm and 1 Gp q should have zeros at up1 , up2 , ,
upm .
According to the IMC parameterization, the process m
i =1 i s + 1 , in the numerator in
i
model G p is decomposed into two parts: The expression,
Eqn (10) causes an unreasonable overshoot in the servo
response, which can be eliminated by designing the set-
G p = PM PA (6) point filter fR as
1
where PM and PA are the portions of the model inverted fR =
(12)

m
and not inverted, respectively, by the controller (PA is i s i + 1
usually a nonminimum phase and contains dead times i =1
and/or RHP zeros); PA (0) = 1.
Since the IMC controller, q, is designed as q = PM1 f The resulting IMC controller in Eqn (9) has a stable
in which the IMC filter, f , is stable and PM1 includes the response. A classical feedback controller equivalent to
inverse of the unstable portion, the controller satisfies the IMC controller can be obtained from the following
the first two conditions. The third condition could be relationship:
q
satisfied through the design of the IMC filter, f . For Gc = (13)
this, the filter is designed as 1 G p q
Thus the feedback controller is given as

m
m
i s i + 1 
i =1
PM 1 i s i + 1
f = (7) i =1
( s + 2 s + 1)r
2 2
Gc =


m
(2 s 2 + 2 s + 1)r PA i s i + 1
where m is the number of poles to be canceled, i is i =1
determined by Eqn (8) to cancel the unstable poles in (14)
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
96 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

The resulting feedback controller given by Eqn (14) is The analytical PID formula can be obtained from
physically realizable, but it lacks the standard PID con- Eqn (18) as
troller form. Therefore, the next step is to design the PID
I
controller that most closely approximates the equivalent Kc = (21)
feedback controller. The Maclaurin series approxima- K ( + 2 )
  
tion has been utilized to approximate Eqn (14) to the
2 2 2 +
PID controller.
I = ( + ) (22)
Lee et al .[22] proposed an efficient method for con- ( + 2 )
verting the ideal feedback controller Gc to a standard    
PID controller. Since Gc has an integral term, it can be 3 6 2 2
expressed as ()
( + 2 )
g(s) D =
Gc = (15) I
s   
2 2 2 +
(23)
Expanding Gc in the Maclaurin series in s gives ( + 2 )

  The extra DOF is calculated by solving (1


1 g  (0) 2 Gq)|s=1 = 0. This means is chosen so that the
Gc = g(0) + g  (0)s + s + ... (16)
s 2 term
 (1 Gq) = 0 at the pole of G p , which leaves
1 (s + 1)e s (2 s 2 + 2 s + 1) s=1 = 0.
The first three terms of the above expansion can be The value of after some simplification is
interpreted as the standard PID controller, which is    
given by   = ( + 2 + )e
2 2
1
2
(24)
1
Gc = Kc 1 + + D s (17)
I s On the basis of the above design principle, the PID
tuning formulas for several process models are obtained
where and listed in Table 1.
Remark 1. The design of the IMCPID controller
based on the proposed method is not applicable to
Kc = g  (0) (18a) the second-order process with complex conjugate pairs.

 It is due to the value of 1 and 2 comes out
I = g (0) g(0) (18b) complex conjugate pairs during the calculation of the
 PID parameters, which gives unrealistic PID controller
D = g  (0) 2g  (0) (18c)
settings.
Remark 2. The processes E1, E2, E3, and E4 may
have negative zero in the process transfer function in
the form of (a s + 1). For illustration purposes, the
Design method for proposed tuning rule second-order unstable process with negative zero is
given as Gp = (a s + 1)K e s /(1 s 1)(2 s 1). An
Consider a FODUP as a representative model of the additional filter of the form fa = 1/(a s + 1) with PID
form controller is obtained for the processes with the negative
K e s zero and the resulting PID controller should be in the
Gp = (19)
s 1 form Gc = Kc (1 + 1/I s + D s).fa .
In the process with the positive zero or inverse
response, the negative numerator time constant is
where K is the gain, the time constant, and the time approximated as a time delay (a s + 1 ea s ).
 The proposed IMC filter is found as f = (s +
delay. This is reasonable since an inverse response has a
1) (2 s 2 + 2 s + 1). The resulting
 IMC controller deteriorating effect on control, similar to that of a
becomes q = ( s 1)(s + 1) K ( s + 2 s + 1).
2 2
time delay.[23] The proposed method is applicable for
Therefore, the ideal feedback controller equivalent to any positive zero after approximation of the neg-
the IMC controller is ative numerator time constant as an effective time
delay, e.g. Gp = (a + 1)e s /(1 s 1)(2 s + 1) =
( s 1)(s + 1) e( +a )s /(1 s 1)(2 s + 1) and this is illustrated in
Gc =  2 2  (20) Examples 5 and 6.
K ( s + 2 s + 1) e s (s + 1)
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
Table 1. IMCPID controller-tuning rules for unstable processes.

Case Process model Kc I D




3 2
Asia-Pacific Journal of Chemical Engineering


6 2   

E1 K e s I ( )
( + 2 )
=
(2 + 2 + 2 )e
1
s 1 K ( + 2 ) I 2



2 2 2
+
2 +
2 2

2010 Curtin University of Technology and John Wiley & Sons, Ltd.
( + 2 ) ( + 2 )

(2 1 ) 1 2


3 2

6 2


2 2
1
s + 2 1 + 1 e
E2 Ke I ( 1 + 2 )
( + 2 )
= 1 1
(1 s 1)(2 s + 1) K ( + 2 ) I 1 2



22 2 2
+ +
2 2

( + 2 ) ( + 2 )

DOI: 10.1002/apj
Asia-Pac. J. Chem. Eng. 2012; 7: 93110
PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES
97
98

Table 1. (Continued).

Case Process model Kc I D


 2 
2 2 + 2 1 + 1 2
2 (1 + 2 )1 + 1 2 1 e 1

1 2
 2 2 
3 1 2 3 + 2 2 + 2 2
+ 2 + 4 2 2 2 e 1
6 2 2
1 2 2 2
E3 K e s I (1 1 2 )
( 1 + 4 )
1 =
(1 s 1)(2 s 1) K ( 1 + 4 ) I (1 2 )
2
M. SHAMSUZZOHA, M. SKLIAR AND M. LEE




2 + 1 2
2 2 2 2
+22 + 42 2 + 1 2 + 2 + 4
2

( 1 + 4 ) ( 1 + 4 )  2 2 
+ 2 1 + 1 2
2 = 1 2 2 e 1
  1

2010 Curtin University of Technology and John Wiley & Sons, Ltd.
1 + 1
1

 2 
2 + 2 1 + 1 2
2 (1 + )1 + 1 1 2 e 1

1 2
 2 
2 2 
3 1 2 3 2 + 2 +
+ 2 + 4 e
6 2 2 2
1 2
E4 K e s I (1 1 )
( 1 + 4 )
1 =
s(1 s 1) K ( 1 + 4 ) I (1 )
2


2 + 1 2
2 2 2 2
+22 + 42 2 + 1 2 + 2 + 4
K e s 2
=
(s 1)(1 s 1) ( 1 + 4 ) ( 1 + 4 )  2 
22 + 2 1 + 1 2 1
2 = 1 2 e
  1

1 + 1
1

DOI: 10.1002/apj
Asia-Pac. J. Chem. Eng. 2012; 7: 93110
Asia-Pacific Journal of Chemical Engineering
Asia-Pacific Journal of Chemical Engineering PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES 99

SIMULATION STUDY Lee et al .[11] However, for the set-point response, Liu
et al .[14] used a modified IMC structure, while Lee
This section demonstrates the simulation study of sev- et al .[11] applied a set-point filter. For the methods of
eral representative unstable processes with dead time, both Liu et al .[14] and Lee et al .,[11] = 0.4 was used
including positive and negative zeros. in the simulation, producing Ms = 3.65. To obtain a fair
To evaluate the closed-loop performance, the integral comparison, is also adjusted in the proposed method
of the time-weighted absolute error (ITAE) criterion was ( = 0.401) to obtain Ms = 3.65. The controller param-
considered in the case of both a step set-point change eters, including the performance and robustness matrix,
and a step load disturbance. The ITAE is defined as are listed in Table 2.
 Figure 2 presents a comparison of the proposed
method with other methods by introducing a unit
ITAE = t|e(t)|dt (25)
0 step change in the set-point at t = 0 and an inverse
unit step change of load disturbance at t = 4. For
For the evaluation of the smoothness of a signal, the servo response, the set-point filter is used for
the total variation (TV) of the input u(t), TV =
 both the proposed method and that of Lee et al .[11]

i =1 |ui +1 ui |, is computed. Overshoot, which is whereas a three-controller element structure is used for
a measure of how much the response exceeds the the method of Liu et al .[14] As it is apparent from
ultimate value following a step change in the set-point Fig. 2 and Table 2, the proposed method improves the
and/or disturbance, has been also calculated for each load disturbance response. Since the design of the
simulation example. disturbance rejection is identical for the methods of Liu
The maximum sensitivity Ms[23] , which is defined et al .[14] and Lee et al .,[11] the same PID tuning setting
as Ms = max |1/[1 + Gp Gc (i )]|, was used to evaluate and consequently an identical disturbance rejection
the robustness of the control system. Since Ms is the response is obtained in both cases. For the servo
inverse of the shortest distance from the Nyquist curve response, the method of Liu et al .[14] seems to be better,
of the loop transfer function to the critical point (1, 0), but the settling times in the method of Liu et al .[14] and
a small Ms value indicates that the control system has a the proposed method are comparable, while the method
large stability margin. To ensure a fair comparison, it is of Lee et al .[11] shows the slowest response with the
widely accepted that the model-based controllers (IMC longest settling time.
and direct synthesis) need to be tuned by adjusting to The well-known, modified IMC structure has the
give the same Ms values. theoretical advantage of eliminating the time delay
Throughout all the simulation examples, all the from the characteristic equation. Unfortunately, this
controllers compared were designed to have the same advantage is lost if the process model is inaccurate.
robustness level in terms of Ms and the performance Besides, real process plants usually incorporate unmod-
indices such as ITAE, overshoot, and TV values are eled dynamics that inevitably tend to deteriorate the
compared. control system performance severely. The robustness
In this article, the simulation study has been con- of the controller was investigated by inserting a pertur-
ducted using the PID controller in the form of bation uncertainty of 5% in all three parameters simul-
Eqn (17). However, for real implementation, the par- taneously towardthe worst case model mismatch, i.e.
allel form of the PID controller, Gc = Kc (1 + 1/I s + Gp = 1.05e0.42s (0.95s 1).
D s/0.1D s + 1), which is widely used in the real pro- The simulation results for model mismatch are also
cesses, can be applied to approximately the same perfor- presented in Table 2 for both the set-point and the
mance. The other form of the PID controller can easily disturbance rejection. The table indicates that the pro-
be converted from parallel form.[24] posed controller-tuning method has an almost similar
Example 1 Lag time dominant FODUP. An exten- load response, while the modified IMC controller cor-
sively published FODUP model[8,11,13,14,25] was consid- responding to method of Liu et al .s[14] has the better
ered for a comparison of the performance: set-point response for model mismatch and the method
of Lee et al .[11] shows the highest ITAE value.
e0.4s Example 2. Dead time dominant FODUP. Consider
Gp = (26)
(s 1) the following dead time dominant ( = 1.5) unstable
process:[18,19]
For the above FODUP model, the recently published e1.5s
paper of Liu et al .[14] demonstrated the improvement Gp = (27)
(s 1)
of their method over those of Tan et al .[13] and Majhi
and Atherton.[25] In this simulation study, the proposed Recently, Zhou et al .[18] conducted a comparative study
method is compared with those of Liu et al .[14] and to show the applicability of several existing controller
Lee et al .[11] The design of the disturbance rejection design methods and evaluated their control perfor-
is identical for the methods of both Liu et al .[14] and mance and robustness and concluded that for the large
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
100 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

Overshoot
1

0.782

0.770
0.777
5% Mismatch
0.8

Process Response
1.714

1.756
1.771
ITAE
0.6
Disturbance

4.120

4.048
4.060
0.4
TV

0.2
Proposed
Overshoot
Nominal

Liu et al.
0.678

0.666
0.665

Lee et al.
0
0 2 4 6 8 9
Time
0.791

1.012
1.008
ITAE

Figure 2. Response of the nominal system for Exam-


ple 1. This figure is available in colour online at
www.apjChemEng.com.
Table 2. Controller parameters and resulting performance indices for Example 1, Gp = e0.4s (s 1).

Overshoot


1.057

1.018
5% Mismatch

1.03

dead time ( = 1.5) process, only the methods of




Lee et al .[11] and Yang et al .[12] are applicable among


several other tuning methods.[5 7,15,25] Although Zhou
et al .[18] argued that the methods of both Lee et al .[11]
1.018

1.237
0.819
ITAE

and Yang et al .[12] are different, both methods have an


identical PID controller setting and thus the same per-
Set-point

formance for the same Ms value. For the performance


2.63
3.50
2.30
TV

comparison, the proposed method is compared with


the method of Lee et al .[11] and the recently published
Xiang and Nguyen[19] method. The controller setting
Overshoot

parameters are listed in Table 3. To test the performance


Nominal

1.01

1.01

of the control system, a set-point with a magnitude of


1.0

1.0 is added at t = 0 and a load disturbance with a


step change of magnitude 0.1 at t = 50. The simula-
tion results are presented in Fig. 3 and the performance
0.616

0.894
ITAE

0.40

indices in Table 3, where the proposed method produces


improved performance in both disturbance rejection and
set-point tracking. The servo response of the methods
of Lee et al .[11] and Xiang and Nguyen[19] is slow,
0.152
0.161
0.161
D

whereas that of the proposed method is fast with little


overshoot. Although the Xiang and Nguyen[19] method
used a modified control structure comprising three indi-
1.759
2.097
2.101
I

vidual controllers for a smooth set-point response, the


disturbance rejection shows a very high peak and long
Kc = 2, C (s) = (s + 1) (0.4s + 1).

settling time.
2.857
2.897
2.894

fR = 1 (1.5932s + 1), = 0.72.

The robustness of the controller is evaluated by


Kc

simultaneously inserting a perturbation uncertainty of


1% in all three parameters to obtain the  worst case


1.515s
Lee et al .[11] = 0.4c

model mismatch, i.e. Gp = 1.01e (0.99s 1),


Liu et al .[14] = 0.4b

fR = 1 (1.9282s + 1).
Proposed = 0.4a

as an actual process, whereas the controller settings


are those calculated based on the nominal model. In
Table 3, the performance matrix is also listed both for
Ms = 3.65.

the set-point and disturbance responses in the model





Method

mismatch case. The controller setting in the Xiang


and Nguyen[19] method provides robust performance for
b
a

2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
Asia-Pacific Journal of Chemical Engineering PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES 101

Overshoot
1.0% Mismatch
2

1.60
1.61
3.21
1

4.711 464.6
4.697 600.0
11.538 497.0
ITAE

Output Response
Disturbance

0
TV

-1
Overshoot
Nominal

1.506
1.509
3.153
Proposed
Lee et al.
-2 Xiang and Nguyen
140.90
366.20
916.20

0 20 40 60 80 100 120
ITAE

Time

Figure 3. Response of the nominal system for Exam-


Overshoot

ple 2. This figure is available in colour online at


1.0% Mismatch

1.083

1.020

www.apjChemEng.com.
1.0
Table 3. Controller parameters and resulting performance indices for Example 2, Gp = e1.5s (s 1).

the servo problem but a big overshoot in disturbance


1.353 92.06

1.257 84.84
ITAE

1.013 238.0

rejection. The proposed method and that of Lee et al .[11]




have almost similar performance in both the servo and


Set-point

regulatory problems.
TV

Example 3. Second-order delayed unstable process


(SODUP). The following unstable process is considered
Overshoot

for the present study:[8,11 13]


Nominal

1.12

1.06
1.0

e0.5s
Gp = (28)
(5s 1)(2s + 1)(0.5s + 1)
0.757 63.49

76.82
0.763 155.30
ITAE

The model presented above is a high-order unstable


process and is approximated with an unstable pole with
dead time.[8,11 13]
1.4815 9.05
D

e0.939s
Gp = (29)
(5s 1)(2.07s + 1)
1.065 106.72
1.064 254.75
I

Tan et al .[13] have already explained the advantage of


their method over those of Huang and Chen,[8] and
0.008

Lee et al .[11] For this reason, the proposed method is


Kc

compared with the methods of Tan et al .[13] and Yang


C2 (s) = 1.019 + 0.59s, F (s) = 1 (5s + 1).

et al .[12] to show its improvement over other methods.


Lee et al .[11] /Yang et al .[12] = 6.543b

The value for the proposed method is adjusted to


obtain the same Ms = 2.21 as the method of Yang

fR = 1 (105.9639s + 1), = 0.5.

et al .[12] and the controller setting parameters with


performance indices are listed in Table 4.
For the simulation of the above process, both the set-
fR = 1 (253.994s + 1).

point and load disturbance that has a step change of


Xiang and Nguyen[19]c
Proposed = 4.308a

magnitude 1 and 1 are inserted at t = 0 and at t = 30,


respectively. The output response for both the servo and
regulatory problem is shown in Fig. 4. The proposed
Ms = 29.70.

tuning method has a faster settling time than that of





the other existing methods. Tan et al .s method,[13]


Method

b
a

2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
102 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

Overshoot
1

0.321
0.495
0.270
10% Mismatch
Table 4. Controller parameters and resulting performance indices for Example 3, Gp = e0.5s (5s 1)(2s + 1)(0.5s + 1) e0.939s (5s 1)(2.07s + 1). 0.8

Process Response
15.04
38.12
27.58
ITAE
0.6
Disturbance

2.725
2.928
2.471
0.4
TV


0.2
Overshoot

Proposed
Nominal

0.322
0.505
0.275
Tan et al.
Yang et al.
0
0 10 20 30 40 50 60
Time
15.37
36.47
26.79
ITAE

Figure 4. Response of the nominal system for Exam-


ple 3. This figure is available in colour online at
www.apjChemEng.com.
Overshoot
10% Mismatch

1.0
1.0
1.0

particularly, has a slow response for both the servo and


the regulatory problems.


Table 4 presents the performance index as well, with


10% uncertainties in gain
 and dead time, and a time con-
14.40
24.91
45.60
ITAE

stant Gp = 1.1e0.55s (4.5s 1)(1.8s + 1)(0.45s + 1)


toward the worst case model mismatch. The proposed
Set-point

method clearly shows better response for both the set-


3.044
2.345
5.999
TV

point tracking and disturbance rejection for the nominal


as well as the model mismatch case.
Example 4. Consider the following unstable process
Overshoot

with a strong lead-time constant[11,26] and two unstable


Nominal

1.023
1.020

poles:
1.0

2(5s + 1)e0.3s
Gp = (30)
(3s 1)(1s 1)
14.20
19.40
39.94
ITAE

The methods of Lee et al .[11] , Rames[26] and the pro-


posed study were used to design the PID controller. For
K0 = 2(2.07s + 1), K1 = s + 1/0.2s + 1, K2 = 3.58(2.4s + 1).

both the proposed method and the method of Lee et al .,


1.750
1.562

is adjusted to obtain Ms = 4.5 and the controller set-


D

ting parameters are listed in Table 5. The reported value


of the Rames method[26] has been also used for com-
fR = (3.1230s + 1) (19.9858s2 + 12.7991s + 1).
8.705
12.799

parison with the proposed method. Figure 5(a) shows


I

the closed-loop output response for a unit-step, set-


point change occurring at t = 0, and an inverse unit
step change of load at t = 10. Figure 5(a) demonstrates
4.108
2.989

fR = 1 (105.9639s + 1), = 0.71.

that the proposed controller provides excellent enhance-


Kc

ment for both the servo and regulatory problems over


the other methods. For the servo response, the pro-
Yang et al .[12] = 1.5b

posed study utilizes a single DOF controller, whereas


the method of Lee et al .[11] employs a set-point filter
Proposed = 2.352a

to reduce the overshoot in the set-point response. For


the disturbance rejection, both overshoot and under-
Tan et al .[13]c

shoot are significantly small in the proposed method


Ms = 2.21.


whereas the method of Lee et al . method shows an


Method

aggressive undershoot, which is undesirable in real con-


trol practices. The Rames method[26] shows quite a
b
a

2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
Asia-Pacific Journal of Chemical Engineering PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES 103

Not stable response


slow response for the set-point tracking and oscillatory

overshoot
3.6657
3.9924
behavior in the disturbance rejection and the resulting

3% Mismatch
Ms value is also high.
The robust performance is evaluated by simultane-
ously inserting a perturbation uncertainty of 3% in

19.69
18.73
ITAE
all three parameters in the worst direction and find- 
ing the actual process as Gp = 2.06(5.15s + 1)e0.309s
(2.91s 1)(0.97s 1). The simulation results for the
Disturbance

6.3218
6.6977
18.7564
model mismatch are also given in Table 5 where the
TV

Rames method[26] is unable to provide the stable closed-


loop response. The robustness indices demonstrate that
the proposed method has more robust performance in
Nominal
overshoot

terms of Integral of Absolute Error (IAE) and Integral


3.3905
3.7391
2.6808

of Squared Error (ISE) for the disturbance rejection,


Table 5. Controller parameters and resulting performance indices for Example 4, Gp = 2(5s + 1)e0.3s (3s 1)(s 1).

although it is not listed, while the ITAE value is slightly


more in the proposed study because of the sluggish
14.99

92.15
18.68

response.
ITAE

The effect of measurement noise on the model


parameters is evaluated by adding white noise with
No stable response


No set-point filter and PID controller in the form of Gc = Kc (1 + 1/I s + D s) 1/(10.05s + 1) and resulting Ms = 10.63.

noise power 0.001 and sample time 0.1 s to the process


overshoot

1.0292
3% Mismatch

1.055

output. The process output and control action are shown


in Fig. 5(b) and (c). It is clear that robust control
performance can be obtained against measurement noise
in the system.
4.880
7.082
ITAE

Example 5. SODUP with one stable pole and a


positive zero. Consider the following SODUP with one
stable pole, which was studied in Example 3:
Set-point

0.9865
1.002
0.764
TV

e0.5s
Gp =
(5s 1)(2s + 1)(0.5s + 1)
overshoot
Nominal

e0.939s
1.0058
1.1524
1.027

(31)
(5s 1)(2.07s + 1)
The above process is modified for this section with a
6.065
3.71

positive zero as given below:


ITAE

125.3

(s + 1)e0.5s
Gp =
(5s 1)(2s + 1)(0.5s + 1)
4.7182
4.3397

For both the proposed and Lee et al .[11] methods Ms = 4.5.


D

(s + 1)e0.939s
12.1

filter is used, = 1.6 and fa = 1/(5s + 1).

= (32)
(5s 1)(2.07s + 1)
fR = 1 (8.187s2 + 1.876s + 1) and fa = 1/(5s + 1).
2.8178
1.8973
5.110

It is difficult to directly design the PID controller for


I

unstable processes with a positive zero. For the con-


troller design, the above process can be approximated as
0.8166
0.7959
0.881
Kc

e1.939s
Gp = (33)
(5s 1)(2.07s + 1)
Lee et al .[11] = 0.692b

The positive zero term is approximated as a time delay


a

(a s + 1 ea s ). This is reasonable since an inverse


Rames C. Panda[26]c
Proposed = 0.657

response has a deteriorating effect on control similar to


that of a time delay.
No set-point

For the proposed method, Lee et al .[11] and Rao and




Chidambaram[2] , is adjusted to obtain Ms = 3.5.  The


Method

simulation is conducted for Gp = (s + 1)e0.5s (5s


1)(2s + 1)(0.5s + 1) and the resulting performance
b
a

2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
104 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

3
(a) 2 (b)

2
1
1

Process Response
Process Response

0 0

-1
-1

-2
-2 Proposed
Lee et al. -3 Proposed
Lee et al.
Rames C. Panda Rames C. Panda
-3 -4
0 5 10 15 20 25 0 10 20 30 40 50
Time Time

(c) 2.5
Proposed
Lee et al.
2 Rames C. Panda
Manipulated Variable

1.5

0.5

-0.5

-1
0 10 20 30 40 50
Time

Figure 5. (a)Response of the nominal system for Example 4. (b) Response of the nominal system with
white noise of power 0.001 and sample time 0.1 s to the process output for Example 4. (c) Controller
output of the nominal system with white noise of power 0.001 and sample time 0.1 s to the process
output for Example 4. This figure is available in colour online at www.apjChemEng.com.

indices are presented in Table 6. Figure 6 shows the No tuning method able to deal with such an integrating
closed-loop output responses for a unit-step set-point unstable process, which also has a strong positive zero
change occurring at t = 0, and an inverse unit-step and dead time, has been presented in the literature. The
disturbance at t = 60. The proposed method improves above process has been approximated as containing two
the load disturbance and set-point response. unstable poles and dead time according to the following
For the robustness study, performance is evalu- equation:
ated by simultaneously inserting a perturbation uncer- 100e0.7s
tainty of 5% in all three parameters in the worst Gp = (35)
(100s 1)(s 1)
direction and finding the actual process according to
Gp = 1.05(1.05s + 1)e0.525s (4.5s 1)(1.9s + 1) Although Lee et al .[11] have not proposed a design
(0.475s + 1). The simulation results for the model mis- of a PID controller for the FODIUP with a positive
match are given in Table 6, where the proposed method zero, such a design is available using the approximated
has clear advantage over others. The method by Rao and model. For a performance comparison, the proposed
Chidambaram[2] has a PID with cascaded lead lag filter. method and those of Rao and Chidambaram[2] and
Although, it has one additional filter term, the method Lee et al .[11] are considered and the PID setting with
shows a big overshoot both in the set-point tracking and performance matrix is listed in Table 7. The value is
disturbance rejection. selected to obtain Ms = 12 for each method except that
Example 6. First-order delayed integrating unstable of Rao and Chidambaram.[2] The method of Rao and
process (FODIUP) with a positive zero. Consider the Chidambaram[2] has been used to obtain the PID setting
following FODIUP with a positive zero: for the approximated process of Gp = 100(0.5s +
1)e0.2s (100s 1)(s 1) as mentioned by them. The
(0.5s + 1)e0.2s Rao and Chidambaram[2] method is not able to give any
Gp = (34) stable closed-loop response and this is probably due to
s(s 1)
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
Asia-Pacific Journal of Chemical Engineering PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES 105

Table 6. Controller parameters and resulting performance indices for Example 5, Gp = (s + 1)e0.5s (5s 1)(2s + 1)(0.5s + 1) (s + 1)e0.939s (5s 1)

Overshoot
Proposed

2.514
1.140
1.125
5% Mismatch
Lee et al.
 2 Rao and Chidambaram

165.5
321.7
ITAE

2433

Process Response
1
Disturbance

4.670
4.477
TV

6.79
0
Overshoot
Nominal

2.56
1.0
1.0

-1
181.4
308.2
ITAE

0 30 60 90 120 130
2140

Time
Overshoot

Figure 6. Response of the nominal system for Exam-


ple 5. This figure is available in colour online at
2.06
5% Mismatch

1.0
1.0


www.apjChemEng.com.
An additional lead lag filter cascaded with PID controller fa = (0.4695s + 1) (0.2406s + 1) and fR = 1 (21.749s + 1).
71.15

an unstable lag filter. The denominator term of the lead


178.9
ITAE

3584

lag filter has negative parameters for any value of the


for the above process. For this reason, the only PID part

Set-point

of their suggested controller form has been compared


4.168
1.696
1.421

for = 4.
TV

A unit step change is added to the set-point at t = 0


and an inverse step change of magnitude 0.1 is intro-
Overshoot

duced to the load disturbance at t = 40. The simula-


Nominal

2.345
1.034
1.001

tion results are provided in Fig. 7 and the performance


matrix in Table 7. These results demonstrate the advan-
tage of the proposed method in both the set-point and
75.72


144.0
ITAE

load disturbance responses.


3559

In the case of a 5% error for estimating the pro-


cess parameters toward the worst  case model mismatch,
i.e. Gp = (0.525s + 1)e0.21s s(0.95s 1), the per-
1.549
2.399
2.488
D

turbed system responses and performance matrix are


also listed in Table 7. The results demonstrate that the
24.389
34.985

proposed method facilitates robust stability in the pres-


105.83
I

ence of process uncertainty over other methods.


1.986
1.956
1.342
Kc

DISCUSSION
Performance of proposed controller
Rao and Chidambaram[2] = 8.35c

with variation in
fR = 1 (21.749s + 1), = 0.71.

An investigation of the consequences of the variation in


Lee et al .[11] = 6.2537b

the IMC filter parameter is significant because it is the


fR = 1 (32.328s + 1).

sole parameter determining performance improvement.


Proposed = 5.302a

 the example of the FODUP model Gp =


Consider
e1.5s (s 1) studied above. A comparative study by
(2.07s + 1).

Zhou et al .[18] revealed that the PID tuning rulereported


Ms = 3.5.

in the literature[5 7,15,25] is not valid for large ratios




Method

and that only the method of Yang et al .[12] and Lee


et al .[11] is viable. Although simulation results of Zhou
b
a

2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
106 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

Overshoot

1.9177
5% Mismatch

2.037
1.871
1

222.5
493.4
607.8
ITAE

Process Response
0.5
Disturbance

1.8441
2.096
2.005
TV
0
Overshoot
Nominal

1.6432
-0.5
1.806
1.646

Proposed
Lee et al.
Rao and Chidambaram
-1
0 20 40 60 80 90
161.0
187.1
359.7
ITAE
Table 7. Controller parameters and resulting performance indices for Example 6, Gp = (0.5s + 1)e0.2s s(s 1).

Time
to achieve the lower Ms value and due to that we have selected Ms = 12.0 except in the method of Rao and Chidambaram[2] .

Figure 7. Response of the nominal system for Exam-


Overshoot


ple 6. This figure is available in colour online at


1.115
1.087
1.396
5% Mismatch

www.apjChemEng.com.

et al .[18] presented different output responses, for the


58.92
84.58
ITAE

methods of Yang et al .[12] and Lee et al .[11] , this was


260.2

due to the selection of different values between the


two methods. When the same Ms value is applied, the
Set-point

0.8163

resulting performance is identical for the methods of


0.342
0.252
TV

Lee et al .[11] and Yang et al .[12] .


The simulation study was conducted to visualize the
effect of for the above FODUP over a wide range
Overshoot
Nominal

1.119
1.076
1.273

of values. The value was adjusted for each


value to obtain Ms = 29.07, the same as Yang et al .[12]
The PID parameter setting and performance matrix are
listed in Table 8 for several values. Figure 8 shows
53.52
65.97
ITAE

97.8

the output response of the above process for set-point


tracking and disturbance rejection. Figure 9 shows the
variation of ITAE value with for both the set-point
24.586
24.073
28.466

and disturbance rejection. Although the ITAE value is


D

minimized for in the range 0.30.4, a value in


the range 0.50.6 is recommended because it provides
6.318
7.840
10.335

an acceptable trade-off between a fast response and


I

reduced oscillation. It appears from Figs 8 and 9 and


Table 8 that = 1, which has normally been used
by many researchers,[11,12,15] is not the best selection
0.049
0.051
0.044

fR = 1 (154.935s2 + 6.245s + 1), = 0.8.


Kc

for the IMC filter. The integral action is inadequate


with = 1 and this causes the slow response, which
Rao and Chidambaram[2] = 4.0

is, however, increased with decreasing value. The


fR = 1 (188.019s2 + 7.740s + 1).

performance can be improved by increasing the integral


action, which can be achieved by utilizing small
Lee et al .[11] = 2.144b

values in the IMC filter. The desired Ms level and the


a

corresponding optimal value can be varied by altering


Proposed = 2.135

the normalized time .


The simplest filter structure widely used is f =
1 (s + 1)n , which has the main potential merit of

Unable 

good robustness characteristics with a maximum peak of


Method

1 for |f |.However, for the underdamped filter structure


of f = 1 (2 s 2 + 2 s + 1)n , the maximum peak for
b
a

2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
Asia-Pacific Journal of Chemical Engineering PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES 107

Overshoot
1.4

1.506
1.507
1.507
1.506
1.506
1.506
1.508
1.514
1.528
1

Disturbance

Output Response
0.6

366.0
283.4
226.6
187.7
163.6
140.9
130.9
117.7
128.6
ITAE

0.2 = 1.0
= 0.9
= 0.8
4.701
4.697
4.690
4.692
4.701
4.711
4.731
4.789
4.892
= 0.7
TV

-0.2 = 0.6
= 0.5
= 0.4
= 0.3
-0.6
Overshoot

0 20 40 60 80 100 120
0.996
1.002
1.015
1.038
1.084
1.125
1.199
1.240
1.381
Time

Figure 8. Simulation results for different values of damping


coefficient . This figure is available in colour online at
www.apjChemEng.com.
Set-point

98.81
84.47

63.49

61.48
ITAE
155.3
114.4

69.1

57.7

72.0

400
Disturbance rejection
Set-point
1.013
1.032
1.069
1.133
1.225
1.353
1.554
1.719
2.238
TV

300
0.765
0.763
0.762
0.761
0.759
0.757
0.754
0.751
0.746
Table 8. Performance comparison for different value for Gp = e1.5s (s 1).

ITAE

200


253.323
218.028
184.936
155.366
129.463
106.724
87.472
71.342
58.455
I

100
1.064
1.064
1.064
1.064
1.065
1.065
1.065
1.065
1.065
Kc

0
0 0.3 0.6 0.9 1.2
z

Figure 9. Variation of ITAE with . This figure is


6.543
6.065
5.599
5.148
4.719
4.308
3.928
3.581
3.284

available in colour online at www.apjChemEng.


com.
Lee et al .[11] /Yang et al .[12] = 1.0

|f | is 1 for 0.707. Therefore, in practice, choosing


a filter with 0.707 does not introduce any inherent
robustness problem in designing the IMC controller.

Analysis of the and guidelines for FODUP


Tuning methods

This section presents the and guidelines at a fixed


Ms = 29.70.

dead time uncertainty margin. Kharitonovs theorem[21]


is used to obtain the uncertainty margin in the process
= 0.9
= 0.8
= 0.7
= 0.6
= 0.5
= 0.4
= 0.3
= 0.2

parameter. The dead time uncertainty is selected for


the analysis because among all the parameters it shows
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
108 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

one of the most deleterious effects on the control The time delay term in Eqn (38) can be approximated
performance. The analysis can also be performed in a by using the third-order Pade approximation:
similar manner for other parameter uncertainties such
as gain and time constant. 120 60 s + 12 2 s 2 3 s 3
e s = (39)
Kharitonovs theorem (Bhattacharyya et al .[21] ) states 120 + 60 s + 12 2 s 2 + 3 s 3
that the Hurwitz stability of the real (or complex)
interval polynomial family can be guaranteed by the Since the process is dead time dominant, the high-
Hurwitz stability of four prescribed critical vertex order Pade approximation has to be utilized to minimize
polynomials in this family. The result is significant the approximation error and the coefficient of the
since it reduces the checking stability of infinitely characteristic equation is given below:
many polynomials, and the number of critical vertex
polynomials to be checked is independent of the order 0 = 120Kc K (40a)
of the polynomial family. 1 = 120I 60Kc K + 120Kc K I (40b)
Every polynomial in the family (s) is Hurwitz stable
if and only if the following four extreme polynomials 2 = 12Kc K 60Kc K I + 120Kc K I D 60I
2

are Hurwitz stable: + 120I (40c)


3 = Kc K + 12Kc K I 60Kc K I D 12I 2
3 2
k1 (s) = 0 + 1 s + 2 s 2 + 3 s 3 + 4 s 4 + 5 s 5
+ 60I (40d)
+ 6s 6 . . . (36a)
4 = I + 12I Kc K I
3 2 3
k2 (s) = 0 + 1 s + 2 s 2 + 3 s 3 + 4 s 4 + 5 s 5
+ 12Kc K I D 2 (40e)
+ 6s . . .
6
(36b)
5 = I 3

k3 (s) = 0 + 1 s + 2 s 2 + 3 s 3 + 4 s 4 + 5 s 5
Kc K I D 3 (40f)
+ 6s 6 . . . (36c)
Equation (40) provides the coefficients of the character-
k4 (s) = 0 + 1 s + 2 s 2 + 3 s 3 + 4 s 4 + 5 s 5 istic equation given by Eqn (37) and the uncertainty in
the process parameters can be checked for stability of all
+ 6s 6 . . . (36d) four Kharitonov polynomials in Eqn (36). On the basis
of Kharitonovs theorem described above, the dead time
The stability of the above four equations formed from uncertainty margin is fixed to obtain the guideline.
Kharitonov polynomials is to be checked. For fixed The closed-loop time constant is a user-defined, tun-
values of gain K and time constant , a perturbation ing parameter in the proposed tuning rule and is directly
in time delay , i.e. ( ) ( + ), is related to the performance and robustness of the con-
substituted in the above coefficients and Kharitonovs trol system. For this reason, it is important to have a
four equations are checked for stability using the guideline which can give a fast and robust response for
RouthHurwitz method. Similar perturbation analysis a given ratio.
can also be performed for K , i.e. (K K ) K In the proposed study, the value is selected such that
(K + K ) (for fixed and ), and , i.e. ( ) it improves the integral actionand thus the performance.
( + ) (for fixed K and ). Figure 10 shows the plot of verses for FODUP
The characteristic equation for the closed-loop system over a wide range of values for 5% dead time
is 1 + GOL = 0. By substitution of GOL and approximat- uncertainty margin. The value is obtained for the 5%
ing the dead time term by a high-order Pade approxi- dead time uncertainty at different values by using
mation, the general form of the characteristic equation Kharitonovs
 theorem,
 as shown above. Similarly, the
1 + GOL = 0 for FODUP can be extracted as verses plot for 10% dead time uncertainty
margin is presented in Fig. 11. To visualize the effect in
(s) = 0 + 1 s + 2 s 2 + 3 s 3 + 4 s 4 + 5 s 5 (37) terms of performance improvement,  Fig. 12 shows the
ITAE values according to the ratio for 5% dead
i i i , (i = 0, 1, 2, 3, 4, 5) where i and i time uncertainty margin. The same trend is evident at
are, respectively, the lower and upper bounds for i . different uncertainty
 margins. Figures 10 and 12 show
Consider the control system design of the FODUP that, for a fixed ratio, decreases with decreasing
by the PID controller. The characteristic equation is , which improves ITAE for a fixed ratio. As seen 
given by from the figures, as the value increases, the
value to secure stability grows
 rapidly. It is important to
Kc K 1 + I s + I D s 2 e s mention that for a large , it is not possible
 to obtain
+1=0 (38)
I s( s 1) a stable response even by using a high value.
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
Asia-Pacific Journal of Chemical Engineering PID CONTROL STRATEGY OF OPEN-LOOP UNSTABLE PROCESSES 109

22 10000
= 1.0
= 0.9 = 1.0
= 0.9
= 0.8 = 0.8
19
= 0.7 = 0.7
= 0.6 1000 = 0.6
= 0.5
= 0.5 = 0.4
16
= 0.4

ITAE
13 100
l/t

10

10
7

4
1
1 1.1 1.2 1.3 1.4 1.5 1.6 1.7
q/t
1
1 1.2 1.4 1.6 
Figure 12. ITAE variation with ratio at several
q/t values for the FODUP. This figure is available in
colour online at www.apjChemEng.com.
Figure 10. Guidelines for 5% uncertainty for
the FODUP. This figure is available in colour online
at www.apjChemEng.com. rejection is given by

C K (2 s 2 + 2 s + 1)e s K (s + 1)e2 s
30 =
= 1.0 d ( s 1)(2 s 2 + 2 s + 1)
= 0.9
= 0.8
(41)
= 0.7 Since is designed so that the denominator in Eqn (41)
25 = 0.6
= 0.5
contains ( s 1), the speed of the output response is
= 0.4 dependent only on (2 s 2 + 2 s + 1). The significant
observation as perceived earlier (Figs 10 and 11) is
20 that the required value for the same robustness
level decreases with decreasing . Values of in
the range 0.40.8 are often suitable for a desired
control system response in which the controlled variable
l/t

15
reaches the set-point faster and in a stable manner than
that with = 1.
10

CONCLUSIONS
5
The present study is focused on unstable processes
comprising negative and positive zeros with dead time.
0
The following key conclusions are made:
1 1.1 1.2 1.3 1.4 1.5 1.6
q/t 1. The IMC filter is modified from a critically damped
to an underdamped structure for the dead time dom-
Figure 11. Guidelines for 10% uncertainty for inant unstable process. The underdamped filter pro-
the FODUP. This figure is available in colour online vides the desired level of integral action and thereby
at www.apjChemEng.com.
improves the performance at the same robustness
level.
2. The inverse response time constant in unstable pro-
For the FODUP, the suggested  IMC filter in the cesses with a positive zero can be approximated as a
proposed study is f = (s + 1) 2 s 2 + 2 s + 1 time delay for the design of the PID controller which
and the resulting output response for the disturbance simplifies the design for improved performance.
2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj
110 M. SHAMSUZZOHA, M. SKLIAR AND M. LEE Asia-Pacific Journal of Chemical Engineering

3. For unstable processes with a strong lead-time con- [6] J.H. Park, S.W. Sung, I.B. Lee. Automatica, 1998; 34(6),
stant, an overdamped filter is suggested because it 751756.
[7] Y.G. Wang, W.J. Cai. Ind. Eng. Chem. Res., 2002; 41,
significantly reduces both the overshoot and under- 29102914.
shoot. In this case, a set-point filter is not required for [8] H.P. Huang, C.C. Chen. IEE Process-Control Theory Appl.,
the servo response, whereas it is needed to eliminate 1997; 144, 334.
[9] C.S. Jung, H.K. Song, J.C. Hyun. J. Process Control, 1999; 9,
the overshoot for = 1. 265269.
4. The simulation study conducted to show the effect of [10] M. Morari, E. Zafiriou. Robust Process Control, Prentice-Hall:
variation on the performance at a fixed Ms value Englewood Cliffs, NJ, 1989.
[11] Y. Lee, J. Lee, S. Park. Chem. Eng. Sci., 2000; 55,
clearly reveals that a critically damped filter is not 34813493.
the best option for PID controller design. [12] X.P. Yang, Q.G. Wang, C.C. Hang, C. Lin. Ind. Eng. Chem.
5. By using Kharitonovs theorem, closed-loop time Res., 2002; 41(17), 42884294.
[13] W. Tan, H.J. Marquez, T. Chen. J. Process Control, 2003; 13,
constant guidelines are suggested for the 5% and 203213.
10% dead time uncertainty margins at several [14] T. Liu, W. Zhang, D. Gu. J. Process Control, 2005; 15,
values. 559572.
[15] S. Majhi, D.P. Atherton. IEE Proc. Part D, 2000; 147(4),
6. The simulation studies conducted for several process 421427.
classes clearly demonstrate the clear advantage of the [16] H.J. Kwak, S.W. Sung, I.B. Lee, J.Y. Park. Ind. Eng. Chem.
proposed method over others previously reported. Res., 1999; 38(2), 405411.
[17] W.D. Zhang, D. Gu, W. Wang, X. Xu. Ind. Eng. Chem. Res.,
2004; 43(1), 5662.
[18] H.Q. Zhou, Q.G. Wang, L.S. Shieh. J. Chem. Eng. Jpn, 2007;
40(2), 145163.
[19] C. Xiang, L.A. Nguyen. Control of unstable processes with
Acknowledgements dead time by PID controllers. Paper No. TP-2.6, Proceeding
of the International Conference on Control and Automation
(ICCA 2005 ), Budapest, Hungary, 2005.
This research was supported by Yeungnam University [20] L.W. Wang, S.H. Hwang. Chem. Eng. Commun., 2005; 192,
research grants in 2009. 3461.
[21] S.P. Bhattacharyya, H. Chapellat, L.H. Keel. Robust Control:
The Parametric Approach, Prentice-Hall, Information and
System Sciences: NJ, 1995.
REFERENCES [22] Y. Lee, S. Park, M. Lee, C. Brosilow. AIChE J., 1998; 44(1),
106115.
[23] S. Skogestad, I. Postlethwaite. Multivariable Feedback Con-
[1] T. Chiu, P.D. Christofides. AIChE J., 1999; 45(6), 12791297.
trol, Analysis and Design, Wiley: NY, 1996.
[2] A.S. Rao, M. Chidambaram. Asia Pac. J. Chem. Eng., 2006;
[24] G.K. McMillan. Tuning and Control Loop Performance, 3rd
1, 6369.
edn, Instrument Society of America: Research Triangle Park,
[3] S. Uma, M. Chidambaram, A.S. Rao. Ind. Eng. Chem. Res.,
NC, 1994.
2009; 48, 30983111.
[25] S. Majhi, D.P. Atherton. Automatica, 2000; 36, 16511658.
[4] A.M. De Paor, M.O. Malley. Int. J. Control, 1989; 49(4),
[26] R.C. Panda. Chem. Eng. Sci., 2009; 64, 28072816.
12731284.
[5] A. Visioli. IEE Proc. Part D, 2001; 148(2), 180184.

2010 Curtin University of Technology and John Wiley & Sons, Ltd. Asia-Pac. J. Chem. Eng. 2012; 7: 93110
DOI: 10.1002/apj

Das könnte Ihnen auch gefallen