Sie sind auf Seite 1von 2

Generator Set

3406 320kVA 365kVA


Prime Power 256 kW 292 kW

Leading the power generation marketplace with Power


Solutions engineered to deliver unmatched flexibility,
expandability, reliability, and cost-effectiveness.

ApplicationEngineering PerformanceAnalysis
LoadAnalysis&GensetSizing
y g CommissioningServices
g
CaptivePowerFeasibility Monitoring&FieldService
InstallationServices OnSiteRepairServices
PlantEngineering AnnualserviceContract
Turnkeysupply&Iinstallation CustomerSupportAgreement

Engine AC Generator
Caterpillar 3406B DITA, 4 Stroke, 6 Cylinders, Designed & manufactured for caterpillar engines
Water Cooled Class H insulation & temperature rise
Diesel Engine Prime Rated at 1500 RPM AREP windings for better short-circuit
Reliable, Rugged, Durable engine with longer life & capabilities
consistent performance Single bearing, self-excited & self regulated
Long-term Fuel Economy Brushless
Brushless generator with automatic voltage
Certified to meet emission regulations in India regulator
Meeting Indian & internal standards
Standard Scope
After cooler Acoustic Enclosure
Battery, starting system 24 VDC Sheet steel fabricated for outdoor application
Caterpillar Governor Noise reduction lining & insulation inside
Charging alternator enclosure
Coolant conditioner Integrating
I t ti louvers
l for
f ventilation
til ti air
i inlet
i l t & outlet
tl t
Coolant drain line with valve Access doors for operation & maintenance
Coolant level sensor Oversized for easy maintenance
Crankcase breather Weatherproof paint
Flexible fuel lines Certified to meet CPCB noise regulations in India
Fuel transfer pump Internal illumination for maintenance & operations
Fumes disposal Engine day fuel tank
Instrument panel engine Genset
Genset anti-vibration
anti vibration mountings
Lube oil level indicator
Lubrication oil in sump & filter Control Panel
Oil drain with valve Sheet steel enclosed, vertical floor mounting
Primary & secondary fuel filters Circuit breaker with protection
Priming pump hand-operated Meters, lamps, switches
Radiator fan & guard Current transformers for metering
Safety shut-offs Busbars, power & control terminations
Air cleaner-heavy
cleaner heavy duty (optional) Special
S i l panels
l ((optional
ti l ffor custom
t needs)
d )
Heat exchanger cooling (optional) Auto mains-failure panels (optional)
Paralleling / Synchronization (optional)

ONE SOURCE FOR RELIABLE AND UNINTERRUPTED POWER


Generator Set
3406 320kVA 365kVA
Prime Power 256 kW 292 kW
TECHNICAL DATA SHEET
PACKAGE GENSET 3406 DITA-GP-1 3406 DITA-GP-2
Prime Power Rating with radiator fan ekVA 320 365
ekW 256 292
Voltage, Phase, Hz VAC/Hz 415 VAC, 3 Ph, 50 HZ 415 VAC, 3 Ph, 50 Hz
Package size Length X Width X Height mms 6000 X 2200 X 2500 6000 X 2200 X 2500
Weight of complete package kGs 6500 6500

ENGINE 3406 DITA-GP-1 3406 DITA-GP-2


Nos. Of Cylinders / Aspirations 6 Cyl / Turbocharged After-cooled
137 X 165 mms, 14.6Ltrs, 14.5:1
Bore X Stroke, Displacement, Compression Ratio
Fuel System:
Fuel Consumption with Fan @ 100% Rating Ltrs/Hr 69.9 79.5
Fuel Consumption with Fan @ 75% Rating Ltrs/Hr 52.2 58.6
Fuel Consumption with Fan @ 50% Rating Ltrs/Hr 36.6 40.3
Day Diesel Fuel Tank Capacity L
Ltrs 750
0 750
0
Cooling System:
Ambient Air Temperature (Design) Deg C 50 50
Engine Coolant Capacity with Radiator Ltrs 56 56
Cooling Water Flow (HE Cooled Option) Ltrs/Min 175 175
Cooling Water Inlet / Outlet Temperature Deg C 36/52 36/52
Lube Oil System:
Lube Oil Sump Capacity with Filter Ltrs. 38 34.1
E h
Exhaust t System:
S t
Exhaust Stack Gas Temperature Deg C 529 532
Exhaust Gas Flow Rate M3/Min 54.2 59.1
Exhaust System Back-pressure at engine outlet
kPa 6.7 6.7
(max.)
Exhaust Flange (Outlet Pipe / Muffler) Size mms 152.4 152.4
Intake Air System:
Combustion Air Inlet Flow Rate M3/Min 19.3 21
Heat Rejections:
Heat Rejection to Coolant Total kW 173 209
Heat Rejection to Exhaust kW 235 257
Heat Rejection to Atmosphere from Engine &
kW 69.56 76.3
Generator
AC Generator kVA 320 365
Enclosure Protection IP23 IP23
Nos. of Bearings Single Single
Insulation & Temperature Rise Class H Class H
Terminal Box Top with Terminals Top with Terminals
Generator Cooling Internal Fan Internal Fan
Voltage Regulation +/- 1% +/- 1%
Total Harmonic Distortion < 3% < 3%
Telephonic Influence Factor < 2% < 2%
Conditions&Definitions:
Prime: Output
p available with varying
y g loads for an unlimited time. Prime p
power in accordance with ISO 8528. 10% overload p
power in
accordance with ISO3046/1, BS5514, DIN6271, AS2789
Ratings: Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO 3046/1, BS5514 & DIN6271 standard
conditions. ISO 3046 tolerances shall apply.
Fuel: Fuel rates are based on fuel oil of 35 Deg API (16 Deg C or 60 Deg F) gravity having an LHV of 42,780 kJ/kG (18,390 Btu/lb)
when used at 29 deg C (85 Deg F) and weighing 850 Gms/Ltr.