UPS Maintenance

About
Uninterruptible
Power Supply (UPS)

A UPS is essentially a series of batteries that


maintains power to critical pieces of equipment
that cannot withstand a power interruption.
A UPS protects equipment from such elements
as power interruptions, voltage variations,
frequency variations, and transient disturbances.

As technology evolves, more parts of equipment


require uninterruptible power, making a reliable
UPS increasingly crucial in any facility. Upon
losing utility power to a facility, it often takes
10 seconds or more for the genset to start and
supply the electricity as an emergency source,
but most electronic equipment cannot tolerate
more than a few cycles of power disruption
without shutting down. Repeated maintenance
is indispensable for prolonging the UPS life-
span and ensuring long-lasting reliability.
UPS
Maintenance

Like any other complex electronic equipment, all UPS products require
maintenance to ensure optimal performance and reliability. During a maintenance
visit Neeco technicians inspect, test, calibrate, update, and clean components.
A written report is provided detailing the results of the inspection, and specific recommendations
are made for remedial actions, proactive replacements, and upgrades.
With more than 5 years of experience servicing industry-leading UPSs, Neeco can help you
maintain the reliable performance of your UPS, resulting in a higher return on your investment.

Preventive Corrective
Maintenance Maintenance
Preventive maintenance consists of Corrective Maintenance is done in
a scheduled list of activities whose order to identify, isolate, and rectify
main goal is to minimize equipment a particular fault of a UPS. This is
operating problems and prevent failures performed in order to restore the
by making minor or necessary repairs failed UPS equipment to operational
before major operating difficulties condition.
occur. One of the most important
activities is periodic maintenance to Carrying out recurrent corrective
ensure the integrity and lifetime of maintenance will have a negative
the batteries as well as your own impact on operational costs. Performing
electronic equipment. Without proper regular preventive maintenance will
PM, a UPS will eventually deteriorate prolong the UPS lifetime and minimize
and expose the facility to an electrical the impact on operational costs. Less
malfunction or equipment failure. corrective maintenance also leads
A scheduled preventive maintenance to less downtime, increased uptime,
program for the UPS will ensure increased production, and improved
equipment reliability and benefit the service to clients.
organizations bottom line.
UPS
Maintenance

Upgrade or retrofit solutions

Risk and condition-based


maintenance

Repair

No maintenance

Neeco proposes risk and condition-based maintenance


strategies to ensure maximum reliability.

Maintenance is carried out at Equipment condition is continuously


predetermined intervals or according assessed by the on-line detection of
to prescribed criteria aimed at reducing significant working device parameters and
the risk of failure or performance their automatic comparison with average
degradation of the equipment. values and performance. Maintenance is
Because maintenance cycles are planned carried out when certain indicators signal
according to the need to take the device that the equipment is deteriorating and
out of service, the incidence of operating the probability of failure has increased.
faults is reduced. This strategy, in the long term, allows a
Maintenance and corrective actions drastic reduction in the costs associated
are based on equipment performance with maintenance, thereby minimizing
monitoring. the occurrence of serious faults and
optimizing available economic resources.
Preventive
Maintenance
Checklist
Our trained technicians regularly test your UPS systems safety functions, control functions, batteries, and
connections to ensure proper operation. This also includes load testing and determining the backup time available
on your batteries, spare parts, or time and material services which are available for customers who do not have a
full maintenance contract. Last but not least, detailed reports are provided after every PM visit.

Regular equipment testing should be part of a facilitys UPS maintenance schedule. The testing framework and
its activities are customizable and significantly depend on Client requirements, but most typically include the
following procedures:

Quarterly: Semiannually: Annually:


Visual inspection of Replacement of the air filters. Conduction of thermal scans on electrical
equipment for loose Visual check for liquid connections to ensure all are tight and
connections, burned contamination from batteries and not generating heat, which is the first and
insulation, or any other capacitors. sometimes only indication of a problem.
signs of wear. Cleaning and vacuuming of UPS A non-evasive diagnostic tool helps technicians
Functional checkout equipment enclosures. identify hot spots invisible to the human eye.
and test of the UPS Check of HVAC equipment Provisioning of a complete operational test
diagnostic systems. and performance related to of the system, including a monitored battery-
Check of environment, temperature and humidity. rundown test to determine if any battery strings
temperature, dust, Check and calibration of each or cells are near the end of their useful lives.
moisture, room vents, system, to include switchgear and Off-line load test the UPS system to ensure that
etc. circuit breakers, meters, and alarm the system is completely functional.
Inspection of all power levels for frequency, voltage,
cabling for abrasions current, transfer, trip, alarm, etc.
and burn spots, signs of Cleaning and tightening all power Biennially:
overheating, swelling, connections at the input and Control battery replacement: if the control
leaking, etc. output terminals, at all circuit batteries have been used without an inverter
Examination of printed breakers, and at the terminal or bypass AC power, they may need replacement
circuit board alignments. posts and fuses on the rectifier sooner.
and inverter legs. Testing the UPS transfer switches, circuit
breakers, and bypasses.

Whenever UPS testing occurs, our technicians place the system into bypass mode or transfer the load to
the redundant system, if designed this way. They are especially cautious when maintaining the equipment
to prevent an outage. Our technicians are also familiar with most standard UPS equipment, manufacturers
testing requirements, specifications, and of course, safety precautions.
Corrective
Maintenance

Additionally, just in case any unexpected


issues happen to our clients with their
UPS devices, Neeco is able to immediately
provision the spare parts from our local
from
warehouses and field engineers to deliver
remedial support activities on a global
2474
up to
basis. We supply our clients withrobust
247 remote support as well as SLA
based on-site support, which all together
significantly smoothen and speed up the
corrective maintenance process. There NBD
are several SLA options at disposal.

Warehousing and Spare Parts Management


A comprehensive spectrum of warehousing services is offered at the
central warehousing locations (typically one or two per region) that are
the fundamental part of Neeco Supply Chain solutions. The storage areas
include larger hub locations in major regions, as well as smaller warehousing
facilities in remote areas, with a total of 60.000+ m2 of available storage
space worldwide.

Once Neeco receives the list of sites and the on-site equipment as
fundamental information for the spare management, an assessment for
reliable and time efficient solutions is prepared. As a part of the assessment,
spare parts identification and forecasting will be done by a service delivery
team to define the amount of spare parts needed at each local warehouse in
the vicinity of a site, using the spare management analytics.
Why to use
Neeco

Benefits of Annual Maintenance from Neeco


Guaranteed protection Reliable service response
of the significant times according the
investment into UPS by agreed SLAs which
prolonging equipment significantly lowers the
life through preventive mean time between
maintenance. failure and repair.

Complex maintenance If any UPS reaches


packages with its end of life, Neeco
customizable services provides upgrade
and fixed costs for recommendations
ease of use and peace which will minimize the
of mind. probability of failure.

Spare parts (most 24/7 remote support


common battery sets, DC provided by our
capacitors, fans, cables, multilingual TAC.
etc.) are available at Neeco
warehouses located all
around the world.
For more information
For more information about Neeco UPS
Preventive Maintenance Services, send an email
to us at info@neeco.com or contact your account
representative.

Headquarter Neeco Hong Kong


Korunni 104/810, Building D Unit 905, 9/F, Kowloon Centre
Vinohrady, Prague 10 33 Ashley Road, Tsim Sha Tsui
101 00 Czech Republic, Europe Kowloon, Hong Kong
Tel: +44 203 290 99 09 Tel.: +852 81 24 12 24

Neeco India Neeco Singapore


423, Level-4 10 Collyer Quay #40-00
6/24, East Patel Nagar Ocean Financial Centre
New Delhi, Delhi 110008 Singapore 049315
Tel.: +91 99 3058 1626 Tel.: +85 281 241 224

Neeco UK Neeco United States


207 Regent Street 111 Shamrock Blvd.,
W1B 3HH London Venice, Florida,
United Kingdom 34293-5438, USA
Tel.: +44 2032 909 909 Tel.: +1 646 652 651

Das könnte Ihnen auch gefallen