Sie sind auf Seite 1von 2

Your Reliable Guide for Power Solutions

Wet Stacking and how to Avoid it


Information Sheet # 17

Most standby generator systems up to five megawatts use the reciprocating internal combustion engine as the power source to drive the
generator that produces the electrical power. The engines of choice are either diesel, natural gas or LPG fueled. A large percentage of
standby power systems use the diesel engine. Diesel is a convenient independent fuel source and the compression ignition systems of
diesel engines have a much higher thermal efficiency than the spark ignition system used by gas engines. However, one factor to be
considered when selecting a diesel power source is the potential for wet stacking.

The National Fire Protection Agency (NFPA), in their NFPA 110 Code for Emergency and Standby Power Systems section 6 - 4.2 (1996
edition) refer to wet stacking as a field term indicating the presence of unburned fuel or carbon in the exhaust system. The later 1999
edition suggests a more quantitative method for determining the presence of wet stacking by measuring the exhaust gas temperature,
explained later in this information sheet.

This information sheet discusses the causes of wet stacking, its effect on the engine, why it should be avoided and methods
for eliminating the condition.

The designer of a generator system must take into account the potential for wet stacking when determining equipment for the system,
load calculations and maintenance and service programs. The system designer should consider the following.
Causes - Like all internal combustion engines, to operate at maximum efficiency a diesel engine has to have exactly the right air-to-fuel
ratio and be able to sustain its designed operational temperature for a complete burn of fuel. When a diesel engine is operated on light
loads, it will not attain its correct operating temperature.
When the diesel engine runs below its designed operating temperature for extended periods, unburned fuel is exhausted and noticed as
wetness in the exhaust system, hence the phrase wet stacking.
Engine Effect - When unburned fuel is exhausted out of the combustion chamber, it starts to build up in the exhaust side of the engine,
resulting in fouled injectors and a buildup of carbon on the exhaust valves, turbo charger and exhaust.
Excessive deposits can result in a loss of engine performance as gases bypass valve seatings, exhaust buildup produces back pressure,
and deposits on the turbo blades reduces turbo efficiency.
Permanent damage will not be incurred over short periods, but over longer periods, deposits will scar and erode key engine surfaces.
(See diagram one)
Also, when engines run below the designed operational temperature, the piston rings do not expand sufficiently to adequately seal the
space between the pistons and the cylinder walls. This results in unburned fuel and gases escaping into the oil pan and diluting the
lubricating properties of the oil, leading to premature engine wear.
Why Avoid - In addition to the adverse engine effect, the designer and user of a system have to consider:
Expense Excessive wet stacking will shorten engine life by many years and before planned replacement.
Pollution Many urban areas restrict the level of smoke emissions wet stacking produces.
Power Even before an engine is damaged, deposits will reduce maximum power. A prematurely worn
engine will have a lower maximum power than it was designed to develop.
Maintenance An engine experiencing wet stacking will require considerable more maintenance
than an engine that is adequately loaded.

NFPA Guidelines
Wet stacking is a recognized condition with organizations that write codes for standby generator set systems, such as the National Fire
Protection Association (NFPA) which has issued several guide lines for controlling the effects. The NFPA guidelines in Level 1 and 2
applications require exercising the unit at least monthly for 30 minutes under either of two methods:
1 - Under operating temperature conditions and not less than 30 percent of the EPS name plate kW rating, or
2 - Loading to maintain the minimum exhaust gas temperature as recommended by the manufacturer.
(See NFPA 8.4.2.)
Exhaust gas temperature specifications are available from the manufacturer of the unit.

Additional Conditions
The Joint Commission on Accreditation of Health Care Organizations (JCAHO), the organization that accredits health care institutions,
has taken this testing to a level beyond the NFPA. They require testing of 12 times per year with testing intervals between 20-40 days.
Testing generators for at least 30 minutes under a dynamic load of 30% or greater of the name plate rating. (Continued over)

To fulfill our commitment to be the leading supplier in the power generation industry, the Kraft Power Corporation team
ensures they are always up-to-date with the current power industry standards as well as industry trends. As a service, our
Information Sheets are circulated on a regular basis to existing and potential power customers to maintain their awareness
of changes and developments in standards, codes and technology within the power industry.
The installation information provided in this information sheet is informational in nature only, and should not be considered the advice of a properly licensed and qualified electrician or used in place of a detailed review of the applicable National
Electric Codes and local codes. Specific questions about how this information may affect any particular situation should be addressed to a licensed and qualified electrician.
Systems that do not meet the 30% load capacity have three options.
1) Increase the load to meet or exceed 30% of the name plate rating,
2) Maintain the minimum exhaust temperature as recommended by the engine manufacturer, or
3) Undertake load bank testing for a total of 2 hours continuous loading as follows:
a) Load at 25% of name plate for 30 minutes
b) 50% for 30 minutes
c) 75% for 60 minutes.
JCAHO also recommends that all automatic transfer switches (ATS) are tested 12 times per year at 20 and 40 day intervals. The provider
of the power system through planned maintenance programs can undertake load testing when testing the ATS.
Solutions to wet stacking:
The obvious solution is to always run the generator set with an electrical load that reaches the designed operational temperature of the
diesel, or approximately 75% of full load. Built-up fuel deposits and carbon can be removed by running the diesel engine at the required
operational temperature for several hours if wet stacking has not yet reached the level where carbon buildup can only be removed by a
major engine overhaul.
The following load bank solutions should prevent a reoccurrence of wet stacking.
Automatic auxiliary loadinng - This solution is usually used only when the diesel generator set is the primary source of power. The
auxiliary load bank will be switched into the system when only the lighter loads are present and switched out when the larger load is
connected.
Facility manual load bank - Operated as described for the automatic load bank, but a manually operated system for use with light loads
and when the larger load is also manually initiated. The load bank can also be used for load testing a system primarily used for standby
power.
Portable load bank - The distributor for the diesel generator set is often the best qualified to undertake the
maintenance of the system. Today it is very common for the owner of a standby generator system to outsource complete
maintenance of the system and have a planned maintenance (PM) contract with a full service generator-set supplier.
During a regularly scheduled planned maintenance call, the distributor will bring in a portable load bank to run the generator at a load that
maintains the designed operational temperature.
Portable load banks range from a few kWs to 3MW units mounted on large trailers. (See photo)

The effects of Wet Stacking on a Diesel Engine Diagram One


Injector Turbo-charger
Deposits will foul injectors and reduce
Deposits on turbo blades will reduce performance
engine performance and could lead to failure

The first sign of wet stacking is drips from the


exhaust and pooling fuel oil

Valve
Deposits on valve seats and stems will lower
performance and cause wear

Typical Portable Load Bank


The load bank shown above is
used for loading sets up to 600kW
Lube Oil Piston The professional power distributor
Bypass of rings into oil pan
Deposits start building up on piston and rings
leading to wear and loss of performance has available portable load banks
from 10kW to more than 2MW
will dilute the oils
lubricating properties
Copyright PLC Enterprises LLC

8 convenient Kraft Power locations, one website: www.kraftpower.com


199 Wildwood Ave 601 Cambridge Ave 241 West Parkway 519 W Second Street 4039 Millennium Blvd., SE 10615 Texland Blvd. 1000B Northbrook Pkwy 1510 S. Sylvania Ave.
Woburn, MA 01888 Syracuse, NY 13208 Pompton Plains, NJ 07444 Gaylord, MI 49735 Massillon, OH 44646 Charlotte, NC 28273 Suwanee, GA 30024 Sturtevant, WI 53177
781-938-9100 T 315-455-6200 T 973-835-9800 T 989-748-4040 T 330-830-4158 T 704-504-3033 T 770-963-6288 T 262-884-8666 T
781-933-7812 F 315-455-6300 F 973-835-5595 F 989-748-4042 F 330-830-5175 F 704-504-5160 F 770-963-9678 F 262-884-8681 F

Email: info@kraftpower.com

KPC-Info#17-2008PLC Enterprises

Das könnte Ihnen auch gefallen