Sie sind auf Seite 1von 4

Structural

A s3 (typ.)
12" Barrier
Wall A s4 (typ.)
P = 6k

Design 18" 27" A s1


A s2

design issues for Slab


structural engineers 12"
Beam

Elevation Section

Figure 1. Load assumed to be resisted by 1-foot width of the wall. Figure 2. Distribute-and-
Spread scheme for a single load.

E
he perimeter of parking garages, and maximum load effect. The load shall be applied
the edges of split ramps in the inte- on an area not to exceed 12 inches by 12 inches

R
rior of parking garages, are required to (305 mm by 305 mm), and located as to produce
have barriers, restraints or guardrails the maximum load effects

U
to stop the vehicles inside ht the structure from
yrig The two underlined clauses (underline added by

T
Cop
plunging down. The design
author) are prescribed in the Code to be used
and detailing of the perim-

C
in design of barrier systems. The author asked
Design of Vehicular eter walls has been a concern
the ASCE Standards Committee, ASCE 7, for
e
U
to public safety. The author
Barrier Walls has published three articles
n
a formal interpretation of the clauses. The ques-

i tions submitted for the formal interpretation are

R
in STRUCTURE magazine
z summarized below:

T
on the subject calling for a
ASCE 7-10 Requirements a
rational design method for vehicular barrier sys-
g
1) Are the clauses ambiguous?

S
2) Are the clauses superfluous and can be
tems. The first two articles presented a method
By Mohammad Iqbal, D.Sc., P.E., a
on how to calculate the impact load on rigid
ignored in design?
S.E., Esq.
m
and linearly elastic barrier systems. It was shown
that the magnitude of the vehicular impact force
3) Does the clause to produce the maximum
load effects mean that the single load of
6,000 lb distributed over an area of 12
depends on four factors: mass, speed, crushing
inches by 12 inches (305 mm by 305
characteristics of the vehicle, and barrier stiffness.
mm) shall produce the maximum shear
It was also shown that the code-prescribed load
force, the maximum bending moment
to design the barriers was unreasonable and arbi-
and the maximum deflection in the
trarily set too low, and that there was a need for a
12-inch wide strip of wall directly under
rational approach to design the vehicular barriers.
the area, such as shown in Figure 1?
Mohammad Iqbal is a licensed The third article discussed the deficiency in the
4) Does the phrase to produce the maximum
attorney in the state of Illinois. A wall-slab joint, which causes cantilever concrete
load effects mean that the single load of
fellow and life-time member of barrier walls to fail prematurely. The scope of this
6,000-lb shall be distributed over an area not
ASCE, he serves on several ACI and article is limited to the barrier walls. The article
to exceed 12 inches by 12 inches (305 mm
ASCE committees. Dr. Iqbal can be reviews the code requirements for design of the
by 305 mm) and then spread down to the
reached at mi@iqbalgroup.us. barrier walls using language of the current code,
wall base at the maximum slope reducing
and provides suggestions on analysis and design of
the wall bending moment on per unit length
the walls. Specifically, it addresses the provisions
basis, such as shown in Figure 2?
of section 4.5.3 of ASCE 7-10 Minimum Design
The ASCE Standards Committee responded that
Loads for Buildings and Other Structures which
the language in the section 4.5.3 was not ambigu-
prescribes the loads on vehicle barrier systems:
ous, and would not be clearer if the words to
4.5.3 Loads on Vehicle Barrier Systems. produce the maximum load effect were removed.
Vehicle barrier systems for passenger vehicles shall The author concurs with Standards Committees
be designed to resist a single load of 6,000 lb response. This paper provides a historical perspec-
(26.70kN) applied horizontally in any direction tive of the reinforced concrete barrier wall design
to the barrier system, and shall have anchorages and provides design guidelines.
or attachments capable of transferring this load Barrier walls are commonly termed bumper
to the structure. For design of the system, the load walls. A bumper wall design example was pub-
shall be assumed to act at heights between 1 ft 6 lished in the 1970s in the Handbook of Concrete
in. (460 mm) and 2 ft 3 in. (686 mm) above Engineering (Editor: Mark Fintel). The design
the floor or ramp surface, selected to produce the example used a 6-inch thick cantilevered concrete

12 November 2015
Distance above Base (in)
25
21
17
13
9
5
1
0 2 4 6 8 10 12 14 Calculate base
Bending Moment (kip-ft) plate connection
45 spread No spread designs
Figure 3. Comparison of wall moments for No-spread and Distribute-and-Spread for a
6-kip load applied 27 inches above wall. Accessa large library of
calculations and create

E
wall reinforced with a single layer (A s1-type) may have another. The ASCE 7 standards sec-
of steel. No other longitudinal, transverse or tion 4.5.3 defines the influence surface within high quality

R
temperature reinforcement was provided in which the load should be applied strategically
the example. It was assumed that the point in order to produce the maximum load effects. documentation

U
load, P, spreads over a 4-foot width of wall. For bumper walls,rigthis
ht influence area is the full
Work with:

T
The load spread scheme used in the Handbook opy in the horizontal direction
length of the Cwall
is shown in Figure 2. It was shown that for a and from 18 to 27 inches in height above the

C
10,000-lb point ultimate load, which equals a floor in the vertical direction. ! Axial, lateral and

ADVERTISEMENTFor Advertiser Information, visit www.STRUCTUREmag.org


e
U
6,000-lb allowable load, applied at 18 inches Building codes generally do not prescribe
moments
above the floor, the wall reinforced with A s1 how the single load should be resisted by a
i n
R
= # 4 @12 inches on center was OK. No barrier wall. There are many ways the wall ! Lateral loads via
z
T
justification for the load spread was given in can be designed for the load to flow from the
the Handbook. Though the design example a
point of application to the wall base, and then
g
friction, anchor bolt

S
has been commonly followed in the design into the structure. The wall segment that par-
shear, embedment
and construction of bumper walls in con- a
ticipates in resisting the point load depends
crete parking garages, the underlying 1:1 load
spread assumption has not been examined m
on the amount and pattern of the wall rein-
forcement. Consider the code-prescribed load
or shear lugs
! Grouted,
or tested for validity. Assuming any failure spread provision of not to exceed 12 inches
pattern or load spread in structural design by 12 inches. Two examples of load-carrying
is generally unsafe and has been termed mechanisms concerning the provision are
non-grouted and
half-truth in the treatise Yield Analysis of shown in Figures 1 and 2. The figures show embedded base plates
Slabs (Jones et al., 1967) A proper failure the part of wall assumed to resist the point
mechanism is one that requires the maximum load, P. In Figure 1, a 1-foot wide wall strip
reinforcement in the bumper wall. This article is assumed to act as a cantilever. Using the
examines cantilever bumper wall design in
light of the ASCE 7-10 language and the
principles of structural mechanics. Design
strip mode, the wall requires only A s1-type
reinforcement. The temperature reinforce-
ment is required by the code but is excluded
See It Live
guidelines are provided at the conclusion. from being part of the flexural reinforcement. Tekla.com/TryTEDDSNow
For the 6-inch concrete wall referenced earlier,
To Produce the Maximum subjected to the 10,000-lb point ultimate load
at 18 inches above the floor, the steel require-
Load Effect ment is about #4@3 inches on center, when
In engineering terms, the phrase to produce considering only a 12-inch wide strip. For
the maximum load effect(s) means to pro- the ultimate point load applied at 27 inches
duce the maximum shear, torsion, bending above the floor, the steel requirement would
moment and deflection in a barrier system increase further for each strip. Such closely-
under a single point live load. Generally, this spaced reinforcement may not be desirable or
point live load needs to be moved and applied practical and, therefore, an increase in wall
at various points within the system to produce thickness and other design options need to be
the maximum load effects. It is foreseeable considered. As such, the strip or non-spread
that applying the load at any one point may method provides a safe, lower bound and
not produce the maximum effects everywhere. conservative design for the bumper wall.
For example, the load applied at a wall corner Figure 2 shows the point load, P, distributed
may have one set of maximum load effects over a 12-inch (305 mm) length and then
and the load applied at the walls free edge assumed to spread downward at 45-degree

STRUCTURE magazine 13 November 2015


This is because the implicit assumption in this
failure mode is that the wall has sufficient posi-
tive reinforcement to eliminate formation of
positive yield-lines. Because the bumper wall
has no positive reinforcement and is only
singly-reinforced with As1-type negative steel,
its capacity is expected to be lower than that
anticipated by the Figure 4 mechanism.
If a bumper wall is reinforced with both posi-
tive and negative steel, a fan-type mechanism
may form which has radial and circumfer-
Figure 4. Corner break-off mode with a point load Figure 5. Fan mechanism formation with a point ential yield-lines, as shown in Figure 5. The
at the corner of the barrier wall. load on the corner of a long wall. circumferential yield-lines are formed when
the negative steel yields and the radial yield-
inclinations on both sides of the load. The length of the yield-line formed at an angle lines are formed when positive steel yields. If
spread assumption connotes that a 4-foot with the x-axis is given by: the positive steel
is omitted altogether, then a

E
length of the wall at the floor level would quarter-circle of radius, r, could develop with
m = m x cos2 + my sin2 Equation 1
be engaged in resisting the load. It further no resistance along the radial lines. Further,

R
implies that the wall design moment reduces where mx and my are moment capacities of the moment capacity As1-type steel varies
to 25% of the no-spread moment. For a bar- the reinforcement about the x- and y-axis, along the periphery of the quarter-circle as

U
rier load located 27 inches above floor, the respectively. righ
t angle changes. Therefore, the average moment

T
wall moment at its base reduces to a mere opy finite element method, which
In contrast toCthe capacity along the circumferential yield-line,
18% of the strip mode (Figure 3, page 13). is a computer-based method, the yield-line m is one-half of the maximum moment the

C
This means an 82% reduction in the design method requires hand-calculations along with steel can develop. Thus, the failure load, P,

e
U
moment. The load spread assumption mini- some knowledge of how a bumper wall could can be computed as follows:
mizes the design by distributing the load over fail. The yield-line method is an upper-bound
i n Moment at the circumferential yield-line =

R
a larger load. Therefore, the use of the load method and provides the bumper wall load-car- P * r = m (2r/4)
z
T
spread scheme and the associated moment rying bending capacity when a proper yield-line Therefore P = (2)(/2) = 3.14 kips < 10 kip
reduction must be justified using structural a
mechanism is used. For example, consider the
g
Now, consider an 8-inch thick cantilever

S
mechanics and experimental work in order to cantilever wall shown in Figure 1 subjected to a bumper wall reinforced with both positive and
avoid design deficiency in the wall. a
single point load, P. In order to design the wall, negative steel in longitudinal and transverse

The ACI-318 Approach


m
the load should be moved and applied at various
points within the influence surface area in order
directions, i.e. each way, each face, (As1 thru
As4) with #4@ 12 inches on center. Using
to produce the maximum load effects. Two load a concrete cover of 1.5 inches, the average
The ACI-318 code permits a new structural locations significant for design are: the corner moment capacity in both the x- and y-direc-
system or a new design approach if its ade- and the free edge of the wall. tions is approximately 5.2 ft-kip/ft length of
quacy has been shown. One way to show the wall. It has been shown that, with positive
this is to successfully test the new system. Point Load at the Corner and negative reinforcements being equal, the
However, no test data on the 6-inch thick fan type mechanism would not materialize
cantilever bumper wall system or the spread
of the Bumper Wall and it would be replaced by the single yield-
assumption could be found. Analytically, the Consider a single load, P, applied at the corner line mechanism (Figure 4). Using Equation 1,
load-carrying mechanism that produces the of the wall, as shown in Figure 4. The simplest
mx = my = 5.2 (ft-k)/ft
maximum load effects can be determined failure mode occurs when the wall corner fails
= 45
using the principles of structural mechanics. as a triangular piece with a negative yield-line at
m = (5.2)(cos2 45) + (5.2)(sin2 45 ) = 5.2
Both elastic and plastic methods are available distance, a, from the corner. Consider the 6-inch
(kip-ft)/ft
for analysis and design of the barrier wall. thick concrete wall reinforced with #4@12
Yield-line length, l = 2a
Finite element analysis is one method and inches on center next to the interior (vehicle
Moment at the yield-line = P * a = m * l
yield-line theory is another method. The ACI side) face of the wall, with the moment capacity
Therefore, P * a = (5.2)(2a) or P = 10.4
Code commentary refers specifically to the of approximately 4ft-kip/ft. Using Equation 1,
kips >10 kips
yield-line analysis as an acceptable approach.
mx = 4 (ft-k)/ft
In addition to the failure modes described
my = 0
above, other modes are also possible. The
Yield-line Analysis = 45
failure mode that predicts the lowest capacity
m = (4)(cos2 45) + (0)(sin2 45) = 2 (kip-ft)/ft
A yield-line in a slab (or a bumper wall in this is the most credible upper-bound solution.
Yield-line length, l = a + a = 2a
case) corresponds to a plastic hinge in concrete
Moment at the yield-line = P * a = m * l
beams. There are two types of yield-lines.
Therefore, P * a = (2) (2a) or P = 4 kips <
Point Load on the Free Edge
A yield-line formed by yielding of positive
reinforcement is called a positive yield line.
10 kips of a Long Wall
Similarly, a yield-line formed by yielding of Though the anticipated failure load of 4,000-lb Similarly, for a point load on the free edge of a
negative reinforcement is called a negative is much less than the design load of 10,000-lb, long wall, both failure modes shown in Figures 6
yield-line. The moment capacity per unit it is still an upper-bound and unsafe solution. and 7 are possible. The mechanisms are similar

STRUCTURE magazine 14 November 2015


Positive yield Negative
line (typ.) P yield line

Wall

Fixed Base

Figure 6. Fan system of yield-lines in wall caused Figure 7. Total collapse mode under a point load
by a point load on the free edge. applied on the free edge of a wall.

in nature to the mechanisms discussed while Simply put, one needs to find the worst (i.e.
addressing the corner load earlier. Figure 6 shows gravest) layout for the system of yield-lines
References
a general fan mechanism in which the fan and that produces the smallest load the wall can Arthur Nilson,Design of Concrete

E
the adjacent yield lines meet. For a wall rein- carry. In corollary, for a prescribed load, one Structures (1997)
forced with only As1-type steel, the half-circle needs to determine the system of yield-lines

R
L.L. Jones and R. H. Wood, Yield Analysis
long yield negative line could develop with no that produces the maximum load effects.
of Slabs (1967)
moment resistance along the radial yield-lines. Thus, every assumption regarding the load-

U
As noted in the quarter-circle case, the solution carrying mechanism ht should be verified using Gerald Kennedy and C. Goodchild,
yrig

T
is independent of the radius, r, and thus the Cop solution.
the lower-bound Practical Yield line Design
anticipated failure load is given by:
P = (2)() = 6.28 kips
The mode in Figure 7 shows the collapse

U C Summary
It is the customary duty of a design pro-
i n e
R
of the entire wall, with the wall-floor joint fessional to determine the failure pattern
z
T
being the weakest link and developing the which is the most critical and produces
yield-line. There are several ways this failure a
the maximum load effects. The ASCE
g
S
mode can form. One way is to reinforce the 7-10 phrase to produce the maximum load
wall sufficiently with positive steel to elimi- a
effect is proper as a design requirement.
nate formation of positive yield-lines. The
wall may also collapse as a whole if the wall- m
The yield-line theory provides a satisfac-
tory method in predicting the ultimate load
slab joint is inefficient. This type of failure a bumper wall would be able to resist. A
mode was also discussed by the author in the proper yield-line or failure mechanism is
April 2014 issue of STRUCTURE magazine. one that requires the maximum reinforce-
Another reason the entire wall may collapse is ment in the wall, consistent with analytical
the limited extent of the wall length, so that and experimental work. While there is a
the wall acts as a one strip. Additional failure dire need for the code load requirements
modes, such as progressive failure or zipper to be rationally-based, conservative design
effect, are also possible. guidelines for barrier walls using the ASCE
The above examples show how the yield-line 7 code language are:
method can be used in the analysis and design 1) Before assuming any load spread
of the barrier walls. This is generally an upper- or failure mechanism, verify it
bound method, and consequently the true load experimentally.
a wall can resist may be less than the calculated 2) If no experimental data is available,
load. This is a recognized concern, since a rea- use the strip mode shown in Figure 1.
sonably prudent design professional prefers to be 3) Provide reinforcement each way on
correct and limit his/her liability by being some- each face of the wall, as shown in
what conservative. Therefore, the upper-bound Figure 1 and use a minimum bumper
solution used in the design of a barrier wall must wall thickness of 8 inches.
coincide with the lower-bound solution which 4) Provide a fully efficient wall-floor
gives a conservative or, at most, correct value of joint which can transfer the load
the collapse load. Its conditions are: from the wall to the structure. One
1) A complete stress field must be found, way to achieve this is to have the wall
everywhere satisfying the differential supported on a beam, as shown in
equation of equilibrium. Figure 1.
2) The forces and moments at the edges 5) Use the single load application
must satisfy the boundary conditions. provision on an area not to exceed 12
3) At no point can the principal stresses inches by 12 inches for the punching
violate the yield criterion. shear check.

STRUCTURE magazine 15 November 2015

Das könnte Ihnen auch gefallen