Beruflich Dokumente
Kultur Dokumente
Pared A
BTU BTU
(
Q A =AUD= ( 303.54 ft 2 ) 0.5536 2
hft f )
( 66.2 f )=11124.23
h
Pared B
BTU
U A =U B =0.5536
hft 2 f
Pared C
C=1.40
K1=5
f0=1.65
fi=1.65
K2=5
1 BTU
U C= =0.4624
1 0.59 1 1 0.59 2
hft f
+ + + +
1.65 5 1.4 1.65 5
BTU BTU
(
QC = AUD=( 139.16 ft 2 ) 0.4624 2
hft f )
( 66.2 f ) =3953.70
h
Pared D
BTU
U A =U D=0.5536
hft 2 f
BTU BTU
(
QD =( 78.14 ft 2 ) 0.5536 2
hft f)( 66.2 f ) =2863.69
h
Vidrio
K=0.40
f0=4
fi=1.65
1 BTU
U v= =0.6915
1 1 0.236 hft 2 f
+ +
1.65 4 0.40
BTU BTU
(
Q A =AUD= ( 28.416 ft 2 ) 0.6915 2
hft f)( 66.2 f )=1300.80
h
Aluminio
A= 22.604 ft2
f =19 C=66.2 f
1 BTU
U v= =1.1673
1 1 0.0787 hft 2 f
+ +
1.65 4 142.7
BTU BTU
(
Q A =( 22.6 ft 2 ) 1.1673 2
hft f)( 66.2 f )=1746.7299
h
Q total de pared D
BTU
QD =2863.69+1300.80+1746.7299=5911.219
h
Techo
A=37.6 m2= 404.72 ft2
f =19 C=66.2 f
1 BTU
U v= =0.6105
1 1 5.11 hft 2 f
+ +
1.65 1.65 12
BTU BTU
(
QTecho=( 404.72 ft 2 ) 0.6105 2
hft f )
( 66.2 f )=16356.79
h
BTU
QTP =11124.23+11124.23+3953.70+5911.21=32113.378
h
QT =QTP +QTecho
BTU
QT =32113 .37+16356.79=4847016
h
=23 C=73.4 f
T
Q=V iCAf
=60
Calcular CA
Ti= 73.4f
Tc=107.6 f
=85%
Calcular f
3
V i=3980.177 ft
f =8.2
Calcular Q
BTU
Q=3980.177 ft 31.958.2=63643.03
24 hr
BTU
Q=23651.79
h
Tasa de calor metablico dependiendo al nivel de actividad
El saln contiene 18 alumnos
Actividad=Sentado con actividad ligera = 115 watts/persona
18 personas * 115 watts/personas = 2070 watts
2070 watts = 7063.13 BTU/hr
Alumbrado
BTU
A=watt3.42
watth
BTU BTU
Alumbrado=162 watts3.42 =554.04
Wh h
Misma aula
Ladrillo con placa de corcho de 1 in y enjarre cemento 0.5 in lado-lado
Pared A
K1=5
f0=1.65
fi=4
K2=5
K3=5
K4=0.3
1 BTU
U A= =0.1927
1 4 1 0.5 0.5 1 2
hft f
+ + + + +
1.65 5 0.3 5 5 4
A= 303.54 ft2
f =19 C=66.2 f
BTU BTU
(
Q A =AUD= ( 303.54 ft 2 ) 0.1927 2
hft f)( 66.2 f )=3872.18
h
Pared B
BTU
U A =U B =0.1927
hft 2 f
BTU
Q A =QB=3872.18
h
Pared C
1 BTU
U C= =0.1803
1 4 1 0.5 0.5 1 hft 2 f
+ + + + +
1.65 5 0.3 5 5 1.65
BTU BTU
QC = AUD=( 129.16 ft 2 ) 0.1803
( 2
hft f)( 66.2 f )=1541.60
h
Pared D
BTU
U A =U D=0.1927
hft 2 f
BTU BTU
(
QD =( 78.14 ft 2 ) 0.1927 2
hft f)( 66.2 f )=996.81
h
Vidrio
1 BTU
U v= =0.6915
1 1 0.236 hft 2 f
+ +
1.65 4 0.40
BTU BTU
(
Q A =AUD= ( 28.416 ft 2 ) 0.6915 2
hft f)( 66.2 f )=1300.80
h
A=22.604 ft2
f =19 C=66.2 f
BTU BTU
(
Q A =AUD= ( 22.604 ft 2 ) 0.5584 2
hft f )
( 66.2 f )=835.58
h
Q total de pared D
BTU
QD =996.81+1300.8+835.58=3133.19
h
Techo
A=37.6 m2= 404.72 ft2
f =19 C=66.2 f
1 BTU
U v= =0.6105
1 1 5.11 hft 2 f
+ +
1.65 1.65 12
BTU BTU
(
QTecho=( 404.72 ft 2 ) 0.6105 2
hft f )
( 66.2 f )=16336.79
h
BTU
QTP =3872.18+3982.18+1541.63+3133.19=12419.18
h
QT =QTP +QTecho
BTU
QT =12419.18+ 16336.79=28755.97
h
Misma aula
Barro bloque hueco 4 in, con capa de poliuretano expandido lado-lado, 1 in de
grosor
K1=0.17
f0=4
fi=1.65
K2=0.17
C=0.90
1 BTU
U A= =0.0.0728
1 1 1 1 1 hft 2 f
+ + + +
1.65 0.17 0.9 0.17 4
A= 303.54 ft2
f =19 C=66.2 f
BTU BTU
(
Q A =AUD= ( 303.54 ft 2 ) 0.0728 2
hft f )
( 66.2 f )=1462.86
h
Pared B
BTU
U A =U B =0.0728
hft 2 f
Pared C
1 BTU
U C= =0.7098
1 1 1 1 1 hft 2 f
+ + + +
1.65 0.17 0.90 0.17 1.65
BTU BTU
(
QC = AUD=( 129.16 ft 2 ) 0.07098 2
hft f )
( 66.2 f )=606.22
h
Pared D
BTU
U A =U D=0.0728
hft 2 f
Vidrio
1 BTU
U v= =0.6915
1 1 0.236 hft 2 f
+ +
1.65 4 0.40
BTU BTU
(
Q A =AUD= ( 28.416 ft 2 ) 0.6915 2
hft f)( 66.2 f )=1300.80
h
1 BTU
U v= =0.1169
1 2 1 hft 2 f
+ +
1.65 0.26 4
A=22.604 ft2
f =19 C=66.2 f
BTU BTU
(
Q A =AUD= ( 22.604 ft 2 ) 0.1169 2
hft f)( 66.2 f )=174.92
h
Q total de pared D
BTU
QD =375.91+1300.80+174.92=1851.63
h
Techo
A=37.6 m2= 404.72 ft2
f =19 C=66.2 f
1 BTU
U v= =0.6105
1 1 5.11 2
hft f
+ +
1.65 1.65 12
BTU BTU
(
QTecho=( 404.72 ft 2 ) 0.6105 2
hft f)( 66.2 f )=16336.79
h
BTU
QTP =1462.86+1462.86+606.22+1851.60=5383.57
h
QT =QTP +QTecho
BTU
QT =5383.57+16336.79=21720.36
h
1 BTU
U A= =0.0459
1 2 2 1 1 hft 2 f
+ + + +
1.65 0.2 0.2 1.1 4
A= 303.54 ft2
f =19 C=66.2 f
BTU BTU
(
Q A =AUD= ( 303.54 ft 2 ) 0.0459 2
hft f )
( 66.2 f )=922.33
h
Pared B
BTU
U A =U B =0.0459 2
hft f
Pared C
1 BTU
U C= =0.0452
1 2 2 1 1 2
hft f
+ + + +
1.65 0.2 0.2 1.1 1.65
BTU BTU
QC = AUD=( 129.16 ft 2 ) 0.0456
( 2
hft f)( 66.2 f )=606.22
h
Pared D
BTU
U A =U D=0.0459 2
hft f
BTU BTU
(
QD =( 78.14 ft 2 ) 0.0459 2
hft f )
( 66.2 f ) =298.20
h
Vidrio
1 BTU
U v= =0.6915
1 1 0.236 hft 2 f
+ +
1.65 4 0.40
BTU BTU
(
Q A =AUD= ( 28.416 ft 2 ) 0.6915 2
hft f)( 66.2 f )=1300.80
h
A=22.604 ft2
f =19 C=66.2 f
BTU BTU
(
Q A =AUD= ( 22.604 ft 2 ) 0.1329 2
hft f )
( 66.2 f )=198.86
h
Q total de pared D
BTU
QD =298.20+1300.8+198.86=1797.86
h
Techo
A=37.6 m2= 404.72 ft2
f =19 C=66.2 f
1 BTU
U v= =0.6105
1 1 5.11 2
hft f
+ +
1.65 1.65 12
BTU BTU
(
QTecho=( 404.72 ft 2 ) 0.6105 2
hft f)( 66.2 f )=16336.79
h
BTU
QTP =922.33+922.33+386.47+1797.86=4028.99
h
QT =QTP +QTecho
BTU
QT =4028.99+16336.79=20365.78
h