OMICRON Page 1 of 19
Contents
1 General .................................................................................................................................................. 6
2 Global Features..................................................................................................................................... 6
2.1 #58900: Windows 10 compatibility ................................................................................................ 6
2.2 Improved handling of high-resolution screens ............................................................................... 6
2.3 #47583: Korean language support ................................................................................................ 6
2.4 #26384: Better visualization of data in small cell sizes ................................................................. 6
2.5 #57028: Context menu for phase-wise rotation ............................................................................. 6
2.6 #39205: Copy and Paste from Status History................................................................................ 7
2.7 #66652 (Build 4820): CMGPS firmware upgrade failed ................................................................ 7
2.8 #70848 (Build 4820): Firmware upgrade failed via USB connection ............................................. 7
2.9 #44568 (Build 4850): Status History content not properly scrolled ............................................... 7
3 Advanced Differential modules ........................................................................................................... 7
3.1 #47540: Enhanced trip treatment during pre-fault ......................................................................... 7
4 Advanced Distance .............................................................................................................................. 7
4.1 #64411: Support copy&paste of the Z/t diagram ........................................................................... 7
4.2 #68913 (Build 4820): Problem with load current in Constant source impedance mode.............. 7
5 Advanced TransPlay ............................................................................................................................ 7
5.1 #39838: Fine-positioning of synthetic pre-fault .............................................................................. 7
5.2 #39837/#41865: All COMTRADE 2013 file formats supported. .................................................... 8
5.3 #71906 (Build 4820): Opening COMTRADE files with unlabeled binary tracks ............................ 8
5.4 #87410 (Build 4850): Problem opening certain CSV files with improper content.......................... 8
6 Annunciation Checker ......................................................................................................................... 8
6.1 #63493: Support of all virtual binary inputs and outputs ............................................................... 8
6.2 #56986: Copy/Paste between tables of the test module and Microsoft Excel .............................. 8
7 Automation Interface ............................................................................................................................ 8
7.1 #19972 (Build 4850): Method SetPauseMode not working ......................................................... 8
8 Autoreclosure ....................................................................................................................................... 8
8.1 #64572: Test Object: CB Configuration: CB close time: Maximum increased .............................. 8
9 Binary I/O Monitor................................................................................................................................. 9
9.1 #25521 (Build 4850): Input names cut off after , or ; characters ................................................ 9
10 CMC ........................................................................................................................................................ 9
10.1 #40683: The AuxDC LED will light up when any voltage >0V is output. ....................................... 9
10.2 #40684: Power-up sequence with default AuxDC voltage: ........................................................... 9
2 Global Features
2.8 #70848 (Build 4820): Firmware upgrade failed via USB connection
The upgrade of the CMC firmware could not be performed if the PC was connected to the CMC via USB.
This is fixed now.
2.9 #44568 (Build 4850): Status History content not properly scrolled
When the Status History window (in unpinned, i.e. hidden state) is opened then the latest messages were
not automatically shown (you had to scroll to see them) so these were easy to miss. This is fixed now.
4 Advanced Distance
4.2 #68913 (Build 4820): Problem with load current in Constant source
impedance mode
A Value out of range error was caused in this combination. This is fixed now.
5 Advanced TransPlay
5.3 #71906 (Build 4820): Opening COMTRADE files with unlabeled binary tracks
These files which are not according to the COMTRADE specification have been rejected in the past. They
are now opened.
5.4 #87410 (Build 4850): Problem opening certain CSV files with improper
content
When opening some CSV files which do not comply with the content structure specifications Advanced
TransPlay could closed unexpectedly. This is fixed now an error message hints at the problem with the file
format.
6 Annunciation Checker
6.2 #56986: Copy/Paste between tables of the test module and Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
7 Automation Interface
8 Autoreclosure
9.1 #25521 (Build 4850): Input names cut off after , or ; characters
If the signal names contained one of these characters then the text following these characters was not
shown. This is fixed now.
10 CMC
The firmware update included with Test Universe 3.10 enhances the AuxDC behavior of the CMC test sets
for safety reasons:
10.1 #40683: The AuxDC LED will light up when any voltage >0V is output.
11 Control Center
11.4 #73126 (Build 4850): System setting Creating a OCC document from a
template is not properly applied
Selecting one of the options Take over from Templates or Set to n/a on the User Information tab in System
Settings was not properly applied for Title, Subject, Category, Keywords and Comments when creating a
new OCC document. This is fixed now.
13 Differential
14 Fault Calculator
This relates to all data entries where a set mode (such as Direct or Z-I const) may be selected (e.g.
QuickCMC, State Sequencer).
14.1 #26560 (Build 4850): 100% Line Length problem switching to Impedances
in primary values
When using the context menu entry 100% line length on the magnitude cell of ZFault the value taken over
from the Distance block in the Test Object was not corrected when later on changing the Test Object setting
to Impedances in primary values. This is fixed now.
15 GOOSE Configuration
15.1 #54435/#72421 (Build 4850): Incorrect GOOSE infos from SCL file with
multiple Access Points
Problem reading from an ACD data type and from SCL with multiple Access Points. This is fixed now.
16.2 #56977: Show connector, display name and connection terminal in report
This feature, per default shown in the Long Report setting, enhances the wiring documentation of the test.
For ease of report tailoring, two new context menu entries now allow to add all neutral terminals for
documentation and/or to remove all un-routed signals.
17 Harmonics
17.2 #67676 (Build 4850): Wrong Value out of range for a given amplifier range
and output signal
For certain harmonic content it could happen that the test could not be carried out although the resulting
signal would have been inside the specified output range. This is fixed now.
18.1 #69330 (Build 4820): Authentication mode always trying to use password
This happened even if none was selected. Fixed now.
18.2 #69920 (Build 4820): Display update problem when selecting a tab other than
Output and changing the static state
Fixed.
18.3 #69970 (Build 4820): Wrong assessment for values with unit frequency
The values were wrongly multiplied with the nominal frequency. Fixed now.
NOTE: Old test results cannot be corrected by this update. For a correct representation and assessment the
tests would need to be repeated after clearing the results.
18.5 #70838 (Build 4820): Wrong trigger condition for frequency values
E.g. 50 Hz was taken as 1000 Hz. Fixed now.
20 License Manager
21 Meter
22 Overcurrent
22.9 #68703 (Build 4820): Improper trip assessment with inverse trip contact logic
With the trip signal permanently active a `trip during prefault was indicated, ignoring the specified signal
inversion. This is fixed now.
23 PQ Signal Generator
23.2 #67019 (Build 4760): Interharmonics state: More than one interharmonic
If more than one interharmonic was defined then only the fundamental was generated. This is fixed now.
24 Pulse Ramping
24.1 #56986: Copy/Paste between the fault state table of the test module and
Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
24.2 #68035 (Build 4820): Activated binary outputs worked only for the first pulse
(fault state)
They should have been activated for all pulses. This is fixed now.
25 QuickCMC
25.3 #56986: Copy/Paste between tables of the test module and Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
26 Ramping Module
26.2 #67753 / #68499 (Build 4820): The display of some linked values was not
immediately updated in test view and assessment view
When entering a LinkToXRIO link for a data field or changing the linked value in the Test Object the
displayed number was not adapted accordingly until e.g. a different data field was selected. This is fixed
now.
26.3 #68736: Problem with some assessments with virtual (GOOSE) inputs
The assessment regarding the timing of the virtual signals sometimes was not correct (buffer content order
not according to time stamping). This is fixed now.
27 State Sequencer
27.1 #56986: Copy/Paste between tables of the test module and Microsoft Excel
Copy/paste is supported in both directions. Make sure that you paste valid data and select a data table size
in Excel which corresponds with the table size in the test module for pasting.
27.3 #63878 (Build 4850): Fault type of Z% I-const might change from three-phase
to phase-ground
If a state with set mode Line-Line is present it might happen that the fault type L1-L2-L3 / A-B-C of a state
with Z% I-const changes to L1N / A-N while switching between selected states. This is fixed now.
29 Synchronizer
29.1 #67438(Build 4760): Problem when re-using certain files with test results
An issue has been fixed which caused the test module to not properly behave when executing a certain test
file, created with an older TU version, after clearing test results and starting the test.
31.3 #68798 (Build 4820): SVScout Help not showing from right-click option
Right-clicking on the SVScout entry on the TU Start screen should open the SVScout user manual. This is
working now.
32.1 #50315: Setting the time delay compensation via command line option
A defined time delay compensation is matching the characteristic of the CMC test sets. In case the output is
routed to third-party amplifiers via the low-level outputs this compensation should be deselected. You can
now deselect it also when launching TransPlay via command line for batch processing. The syntax is:
transplay.exe /bat /nodelaycomp
For further details see Test Universe Help, Starting TransPlay with Command Line Parameters.
33 TransView
When you are working with our products we want to provide you with the greatest
possible benefits. If you need any support, we are here to assist you!
At our technical support hotline, you can reach well-educated technicians for all of
your questions. Around the clock competent and free of charge.
Make use of our 24/7 technical support hotline:
Americas: +1 713 830-4660 or +1 800-OMICRON
Asia-Pacific: +852 3767 5500
Europe/Middle East/Africa: +43 59495 4444