MiCOM P141, P142, P143,

P144, P145

Technical Data Sheet


Feeder Management Relay
Publication Reference: P14x/EN TDS/Ff7

MiCOM P141, P142, P143, P144, P145/EN/TM/A XXXX. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of
ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is
provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty
(whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated.
GRID
ALSTOM reserves the right to revise or change this data at any time without further notice.
GRID
IEC 2nd Remote Remote Local Fault records Disturbance
61850 comm. port comm. port Communication Record

Measurements
Self monitoring

X 50/51
50N/ 67/ 67N/67W 51V 46 49
37P/
YN 49SR CTS
51N 67N /64 37N
Vref

IE sen

27/ 81U/81O
59N 47 50BF VTS 79 25 PSL LEDs
59 /81R

Y Binary
Input / output
always available
optional
Feeder management P14x
I DIFF
Operate
K1 0% to 20%
K2 K2 0% to 150%
I s1 0.08 to 1. 0 I n
Restrain I s2 0.10 to 1. 5 I n
K1
I s1
I s2 I BIAS
GRID
Technical Data Rear Communications Port
EIA(RS)485 signal levels, two wire
Connections located on general purpose block,
Mechanical Specifications M4 screw.
For screened twisted pair cable, multi-drop,
Design 1000m max.
Modular MiCOM Px40 platform relay, For K-Bus, IEC-870-5-103, or DNP3 protocol
P141/142/P144-40TE (206mm (8)) case and (ordering options).
P143/P145 (309.6mm (12)) case. Mounting is Isolation to SELV level.
front of panel flush mounting, or 19 rack
mounted (ordering options).
Optional Second Rear Communications
Port
Enclosure Protection EIA(RS)232, 9 pin D-type female connector,
Per IEC 60529: 1992 socket SK4.
IP 52 Protection (front panel) against dust and Courier protocol: K-Bus, EIA(RS)232, or
dripping water. EIA(RS)485 connection.
IP 50 Protection for the rear and sides of the Isolation to SELV level.
case against dust.
IP 10 Product safety protection for the rear due
to live connections on the terminal block. Optional Rear IRIG-B Interface modulated
or un-modulated
BNC socket
Weight Isolation to SELV level.
Case 40TE: approx. 7.3 kg 50 ohm coaxial cable.
Case 60TE: approx. 9.2 kg
Optional Rear Fiber Connection for
Terminals SCADA/DCS
BFOC 2.5 -(ST)-interface for glass fiber, as
AC Current and Voltage Measuring Inputs per IEC 874-10.
Located on heavy duty (black) terminal block: 850nm short-haul fibers, one Tx and one Rx.
Threaded M4 terminals, for ring lug For Courier, IEC-870-5-103, DNP3 or
connection. MODBUS protocol (ordering options).
CT inputs have integral safety shorting, upon
removal of the terminal block. Optional Rear Ethernet Connection for IEC
61850 or DNP3.0
General Input/Output Terminals
For power supply, opto inputs, output contacts Optional redundant Rear Ethernet
and COM1 rear communications. Connection (optical)
Located on general purpose (grey) blocks:
Threaded M4 terminals, for ring lug
10BaseT/100BaseTX Communications
connection.
Interface in accordance with IEEE802.3 and
IEC 61850
Case Protective Earth Connection Isolation: 1.5kV
Two rear stud connections, threaded M4. Connector type: RJ45
Must be earthed (grounded) for safety, Cable type: Screened Twisted Pair (STP)
minimum earth wire size 2.5mm2.
100 Base FX Interface
Front Port Serial PC Interface Interface in accordance with IEEE802.3 and
EIA(RS)232 DTE, 9 pin D-type female IEC 61850
connector. Wavelength: 1300nm
Courier protocol for interface to MiCOM S1 Fiber: multi-mode 50/125m or 62.5/125m
software. Connector style: BFOC 2.5 -(ST)
Isolation to ELV level.
Maximum cable length 15m.
Ratings
Front Download/Monitor Port
EIA(RS)232, 25 pin D-type female connector. AC Measuring Inputs
For firmware downloads. Nominal frequency: 50 and 60 Hz (settable)
Isolation to ELV level. Operating range: 45 to 65Hz
Phase rotation: ABC

P14x Technical Data Sheet 9 P141/2/3/4/5 Software Version 46J


AC Current Battery Backup
Nominal current (In): 1 and 5 A dual rated. Front panel mounted
(1A and 5A inputs use different transformer tap Type AA, 3.6V (SAFT advanced battery
Connections, check correct terminals are reference LS14250) Battery life (assuming
wired). relay energized for 90% time) >10 years
Nominal burden per phase: < 0.15 VA at In
Thermal withstand: Field Voltage Output
continuous 4 In Regulated 48Vdc
for 10s: 30 In Current limited at 112mA maximum output
for 1s; 100 In
Linear to 64 In (non-offset AC current).
Digital (Opto) Inputs
Universal opto inputs with programmable
AC Voltage voltage thresholds (24/27, 30/34, 48/54,
Nominal voltage (Vn): 100 to 120 V or 380 to 110/125, 220/250V). May be energized from
480V phase-phase (min. 196 Vac, max. 560 the 48V field voltage, or the external battery
Vac). supply.
Nominal burden per phase: < 0.02 VA at Vn. Rated nominal voltage: 24 to 250Vdc
Thermal withstand: Operating range: 19 to 265Vdc
continuous 2 Vn Withstand: 300Vdc, 300Vrms.
for 10s: 2.6 Vn Peak current of opto input when energized is
3.5mA (0-300V)
Power Supply Nominal pick-up and reset thresholds:
Nominal battery 24/27: 60 - 80% DO/PU
(logic 0) <16.2 (logic 1) >19.2
Auxiliary Voltage (Vx) Nominal battery 24/27: 50 - 70% DO/PU
Three ordering options: (logic 0) <12.0 (logic 1) >16.8
(i) Vx: 24 to 48 Vdc Nominal battery 30/34: 60 - 80% DO/PU
(ii) Vx: 48 to 110 Vdc, and 40 to (logic 0) <20.4 (logic 1) >24.0
100Vac (rms) Nominal battery 30/34: 50 - 70% DO/PU
(iii) Vx: 110 to 250 Vdc, and 100 to (logic 0) <15.0 (logic 1) >21.0
240Vac (rms) Nominal battery 48/54: 60 - 80% DO/PU
(logic 0) <32.4 (logic 1) >38.4
Operating Range Nominal battery 48/54: 50 - 70% DO/PU
(i) 19 to 65V (dc only for this variant) (logic 0) <24.0 (logic 1) >33.6
(ii) 37 to 150V (dc), 32 to 110V (ac) Nominal battery 110/125: 60 - 80% DO/PU
(iii) 87 to 300V (dc), 80 to 265V (ac) (logic 0) <75.0 (logic 1) >88.0
With a tolerable ac ripple of up to 12% for a dc Nominal battery 110/125: 50 - 70% DO/PU
supply, per IEC 60255-11: 1979. (logic 0) <55.0 (logic 1) >77.0
Nominal battery 220/250: 60 - 80% DO/PU
Nominal Burden (logic 0) <150.0 (logic 1) >176.0
Quiescent burden: 11W. (Extra 1.25W when Nominal battery 220/250: 50 - 70% DO/PU
fitted with second rear Courier) (logic 0) <110 (logic 1) >154
Additions for energized binary inputs/outputs: Recognition time:
Per opto input: <2ms with long filter removed,
0.09W (24 to 54V), <12ms with half cycle ac immunity filter on
0.12W (110/125V),
0.19W (220/120V). Output Contacts
Per energized output relay: 0.13W
Standard Contacts
Power-up Time General purpose relay outputs for signaling,
Time to power up < 11s. tripping and alarming:
Continuous Carry Ratings (Not Switched):
Power Supply Interruption Maximum continuous current: 10A (UL: 8A)
Per IEC 60255-11: 1979 Short duration withstand carry: 30A for 3s
The relay will withstand a 20ms interruption 250A for 30ms
in the DC auxiliary supply, without Rated voltage: 300 V
de-energizing.
Per IEC 61000-4-11: 1994
The relay will withstand a 20ms interruption
in an AC auxiliary supply, without
de-energizing.
P14x Technical Data Sheet 10 P141/2/3/4/5 Software Version 46J
Make & Break Capacity: 30A for 200 ms, dc resistive, 10,000
DC: 50W resistive operations (subject to the above limits of
DC: 62.5W inductive (L/R = 50ms) make/break capacity & rated voltage)
AC: 2500VA resistive (cos = unity) 10A (*), dc inductive, 10,000 operations
AC: 2500VA inductive (cos = 0.7) (subject to the above limits of make/break
capacity & rated voltage)
Make, Carry:
30A for 3 secs, dc resistive, 10,000 *Typical for repetitive shots - 2 minutes idle
operations (subject to the above limits of for thermal dissipation
make/break capacity and rated voltage)
No. of Shots
Voltage Current L/R
in 1 sec
Make, Carry & Break:
30A for 200ms, ac resistive, 2,000 65V 10A 40ms 5
operations (subject to the above limits of 150V 10A 40ms 4
make/break capacity & rated voltage) 4A for
1.5 secs, dc resistive, 10,000 operations 250V 10A 40ms 2
(subject to the above limits of make/break 250V 10A 20ms 4
capacity & rated voltage)
MOV protection: Max Voltage 330V dc
0.5A for 1 sec, dc inductive, 10,000 Durability:
operations (subject to the above limits of Loaded contact: 10 000 operations
make/break capacity & rated voltage) minimum
Unloaded contact: 100 000 operations
10A for 1.5 secs, ac resistive/inductive, minimum
10,000 operations (subject to the above
limits of make/break capacity & rated Operate Time:
voltage) Less than 0.2ms
Reset Time:
Durability: Less than 8ms
Loaded contact: 10 000 operations
minimum Watchdog Contacts
Unloaded contact: 100 000 operations Non-programmable contacts for relay
minimum healthy/relay fail indication:
Breaking capacity:
Operate Time DC: 30W resistive
Less than 5ms DC: 15W inductive (L/R = 40ms)
Reset Time AC: 375VA inductive (cos = 0.7)
Less than 5ms
IRIG-B 12X Interface (Modulated)
High Break Contacts (Model D Only) External clock synchronization per IRIG
Continuous Carry Ratings (Not Switched): standard 200-98, format B12X.
Maximum continuous current: 10A Input impedance 6k at 1000Hz
Short duration withstand carry: 30A for 3s Modulation ratio: 3:1 to 6:1
250A for 30ms Input signal, peak-peak: 200mV to 20V
Rated voltage: 300 V
IRIG-B 00X Interface (Un-modulated)
Make & Break Capacity: External clock synchronization per IRIG
DC: 7500W resistive standard 200-98, format B00X.
DC: 2500W inductive (L/R = 50ms) Input signal TTL level
Input impedance at dc 10k
Make, Carry:
30A for 3 secs, dc resistive, 10,000
operations (subject to the above limits of
make/break capacity & rated voltage)

Make, Carry & Break:


30A for 3 secs, dc resistive, 5,000
operations (subject to the above limits of
make/break capacity & rated voltage)
P14x Technical Data Sheet 11 P141/2/3/4/5 Software Version 46J
Environmental Conditions 1kV rms AC for 1 minute, across open
contacts of changeover output relays.
(ii) Per ANSI/IEEE C37.90-1989 (reaffirmed
Ambient Temperature Range 1994):
Per IEC 60255-6: 1988 1.5 kV rms AC for 1 minute, across open
Operating temperature range: contacts of changeover output relays.
-25C to +55C (or -13F to +131F).
Storage and transit:
-25C to +70C (or -13F to +158F). Impulse Voltage Withstand Test
Tested as per Per IEC 60255-27: 2005
IEC 60068-2-1: 2007 Front time: 1.2 s, Time to half-value: 50 s,
-25C storage (96 hours) Peak value: 5 kV, 0.5J
-40C operation (96 hours) Between all terminals, and all terminals and
IEC 60068-2-2: 2007 case earth.
+85C storage (96 hours)
Electromagnetic Compatibility
Ambient Humidity Range (EMC)
Per IEC 60068-2-3: 1969:
56 days at 93% relative humidity and +40C
Per IEC 60068-2-30: 1980: 1 MHz Burst High Frequency Disturbance
Damp heat cyclic, six (12 + 12) hour cycles, Test
93% RH, +25 to +55C Per IEC 60255-22-1: 1988, Class III,
Common-mode test voltage: 2.5 kV,
Corrosive Environments Differential test voltage: 1.0 kV,
(For relays with harsh environment coating Test duration: 2s, Source impedance: 200
of PCBs) EIA(RS)232 ports excepted.
Per IEC 60068-2-60: 1995, Part 2, Test Ke,
Method (class) 3 100kHz Damped Oscillatory Test
Industrial corrosive environment/poor Per EN61000-4-18: 2007: Level 3
environmental control, mixed gas flow test. Common mode test voltage: 2.5kV
21 days at 75% relative humidity and +30oC Differential mode test voltage: 1kV
exposure to elevated concentrations of H2S,
(100 ppb) NO2, (200 ppb) Cl2 (20 ppb).
Per IEC 60068-2-52 Salt mist (7 days) Immunity to Electrostatic Discharge
Per IEC 60068-2-43 for H2S (21 days), 15 ppm Per IEC 60255-22-2: 1996, Class 4,
Per IEC 60068-2-42 for SO2 (21 days), 25 ppm 15kV discharge in air to user interface,
display, and exposed metalwork.
Per IEC 60255-22-2: 1996, Class 3,
Type Tests 8kV discharge in air to all communication
ports.
Insulation 6kV point contact discharge to any part of
Per IEC 60255-27: 2005 the front of the product.
Insulation resistance > 100M at 500Vdc
(Using only electronic/brushless insulation Electrical Fast Transient or Burst
tester). Requirements
Per IEC 60255-22-4: 2002. Test severity
Creepage Distances and Clearances Class III and IV:
Per EN 61010-1: 2001 Amplitude: 2 kV, burst frequency 5kHz
Pollution degree 2, (Class III),
Overvoltage category III, Amplitude: 4 kV, burst frequency 2.5kHz
Impulse test voltage 5 kV. (Class IV).
Applied directly to auxiliary supply, and
applied to all other inputs. EIA(RS)232
High Voltage (Dielectric) Withstand ports excepted.
EIA(RS)232 ports excepted.
(i) Per IEC 60255-27: 2005, 2 kV rms
AC, 1 minute: Surge Withstand Capability
Between all case terminals connected IEEE/ANSI C37.90.1:2002:
together, and the case earth. 4kV fast transient and 2.5kV oscillatory applied
Also, between all terminals of independent common mode and differential mode to opto
circuits. inputs (filtered), output relays, CTs, VTs,
1kV rms AC for 1 minute, across open power supply, field voltage.
watchdog contacts. 4kV fast transient and 2.5kV oscillatory applied
common mode to communications, IRIG- B.
P14x Technical Data Sheet 12 P141/2/3/4/5 Software Version 46J
Surge Immunity Test Radiated Emissions
EIA(RS)232 ports excepted. Per EN 55022: 1998: Class A:
Per IEC 61000-4-5: 2005 Level 4, 30 - 230MHz, 40dBV/m at 10m
Time to half-value: 1.2/50 s, measurement distance
Amplitude: 4kV between all groups and case 230 - 1GHz, 47dBV/m at 10m
earth, measurement distance.
Amplitude: 2kV between terminals of each
group.
EU Directives
Immunity to Radiated Electromagnetic
Energy EMC Compliance
Per IEC 60255-22-3: 2000, Class III: Per 89/336/EEC:
Test field strength, frequency band 80 to 1000 Compliance to the European Commission
MHz: Directive on EMC is claimed via the Technical
10 V/m, Construction File route. Product Specific
Test using AM: 1 kHz / 80%, Standards were used to establish conformity:
Spot tests at 80, 160, 450, 900 MHz EN50263: 2000
Per IEEE/ANSI C37.90.2: 1995:
25MHz to 1000MHz, zero and 100% square Product Safety
wave modulated. Per 2006/95/EC:
Field strength of 35V/m. Compliance to the European Commission Low
Voltage Directive. (LVD) is
Radiated Immunity from Digital demonstrated using a Technical File.
Communications A product specific standard was used to
Per EN61000-4-3: 2002, Level 4: establish conformity.
Test field strength, frequency band 800 to 960 EN 60255-27: 2005
MHz, and 1.4 to 2.0 GHz:
30 V/m,
Test using AM: 1 kHz / 80%.
R&TTE Compliance
Radiated Immunity from Digital Radio Radio and Telecommunications Terminal
Telephones Equipment (R&TTE) directive 99/5/EC.
Per ENV 50204: 1995 Compliance demonstrated by compliance to
10 V/m, 900MHz and 1.89GHz. both the EMC directive and the Low voltage
directive, down to zero volts.
Immunity to Conducted Disturbances Applicable to rear communications ports.
Induced by Radio Frequency Fields
Per IEC 61000-4-6: 1996, Level 3, ATEX Compliance
Disturbing test voltage: 10 V ATEX Potentially Explosive Atmospheres
directive 94/9/EC, for equipment.
Power Frequency Magnetic Field Immunity The equipment is compliant with Article 1(2) of
Per IEC 61000-4-8: 1994, Level 5, European directive 94/9/EC.
100A/m applied continuously, It is approved for operation outside an ATEX
1000A/m applied for 3s. hazardous area. It is however approved for
Per IEC 61000-4-9: 1993, Level 5, connection to Increased Safety, Ex e, motors
1000A/m applied in all planes. with rated ATEX protection, Equipment
Per IEC 61000-4-10: 1993, Level 5, Category 2, to ensure their safe operation in
100A/m applied in all planes at gas Zones 1 and 2 hazardous areas.
100kHz/1MHz with a burst duration of 2s.
CAUTION - Equipment with this marking is not
itself suitable for operation within a potentially
Conducted Emissions explosive atmosphere.
Per EN 55022: 1998: Class A:
0.15 - 0.5MHz, 79dBV (quasi peak) Compliance demonstrated by Notified Body
66dBV (average) certificates of compliance.
0.5 - 30MHz, 73dBV (quasi peak) 60dBV
(average).

II (2) G

P14x Technical Data Sheet 13 P141/2/3/4/5 Software Version 46J


Mechanical Robustness

Vibration Test
Per IEC 60255-21-1: 1996
Response Class 2
Endurance Class 2

Shock and Bump


Per IEC 60255-21-2: 1995
Shock response Class 2
Shock withstand Class 1
Bump Class 1

Seismic Test
Per IEC 60255-21-3: 1995
Class 2
Transit Packaging Performance
Product testing to simulate protection offered
by primary packaging carton, to ISTA 1C
specification

Vibration and Drop Release Tests:

Vibration tests in 3 orientations, vibratory


movement 7 Hz, amplitude 5.3 mm,
acceleration 1.05g

Drop tests - 10 drops from 61 cm height on


multiple carton faces, edges and corners

P14x Third Party Compliances


Underwriters Laboratory (UL)

File Number: E202519


Issue Date: 21-04-2005
(Complies with Canadian and US
requirements).

Energy Networks Association (ENA)

Certificate Number: 101 Issue 3


Assessment Date: 10-12-2004

Type (s): P141, P142, P143 & P145

P14x Technical Data Sheet 14 P141/2/3/4/5 Software Version 46J


Protection Functions DT reset:
2% or 50ms whichever is greater
Repeatability: 5%
Three Phase Overcurrent Protection * Reference conditions TMS = 1, TD = 1 and
IN > setting of 1A, operating range 2-20In
Accuracy
Additional tolerance X/R ratios: SEF
5% over X/R 190 DT Pick-up: Setting 5%
Overshoot: <30ms Minimum IDMT Trip level: 1.05 x Setting 5%
Drop-off: 0.95 x Setting 5%
Inverse Time Characteristic IDMT shape:
5% or 40ms whichever is greater *
IEEE reset:
Accuracy 7.5% or 60ms whichever is greater
DT Pick-up: Setting 5% DT operation:
Minimum IDMT trip level: 2% or 50ms whichever is greater
1.05 x setting 5% DT reset: 5%
Drop-off: 0.95 x setting 5% Repeatability: 5%
IDMT shape: 5% or 40ms whichever * Reference conditions TMS = 1, TD = 1 and
is greater IN > setting of 100mA, operating range 2-0In
IEEE reset: 5% or 50ms whichever
is greater
DT operation: 2% or 50ms, whichever is REF
greater Pick-up: Setting formula 5%
DT reset: 5% Drop-off: 0.80 x setting formula 5%
Directional boundary (RCA 90%): Operating time: <60ms
2% hysteresis 2o High pick up: Setting 5%
Characteristic: UK curves High operating time: <30ms
IEC 60255-3 1998 Repeatability: <15%
US curves:
IEEEC37.1121996 Wattmetric SEF
Pick-up For P=0W
ISEF> 5% or P> 5%
Earth/Sensitive Fault Protection Drop off: For P>0W
(0.95 x ISEF>) 5% or 0.9 x P> 5%
Earth Fault 1 Boundary accuracy:
DT Pick-up: Setting 5% 5% with 1o hysteresis
Minimum IDMT trip level: 1.05 x Setting 5% Repeatability: 5%
Drop-off: 0.95 x Setting 5%
IDMT shape: SEF Cos(PHI)/
5% or 40ms whichever is greater * Pick-up: Setting 5% for angles RCA60o
IEEE reset: Drop-off: 0.90 x Setting
5% or 50ms whichever is greater IDMT shape:
DT operation: 5% or 50ms whichever is greater *
2% or 50ms whichever is greater IEEE reset:
DT reset: 5% 7.5% or 60ms whichever is greater
Repeatability: 2.5% DT operation:
* Reference conditions TMS = 1, TD = 1 and 2% or 50ms whichever is greater
IN> setting of 1A operating range 2-20In DT reset: 5%
Repeatability:2%
Earth Fault 2
DT Pick-up: Setting 5% * Reference conditions TMS = 1, TD = 1 and
Minimum IDMT Trip level: 1.05 x Setting 5% IN > setting of 100mA, operating range 2-0In
Drop-off: 0.95 x Setting 5%
IDMT shape: SEF Sin(PHI)
5% or 40ms whichever is greater * Pick-up: Setting 5% for angles from RCA60o
IEEE reset: to RCA90o
10% or 40ms whichever is greater Drop-off: 0.90 x Setting
DT operation: IDMT shape:
2% or 50ms whichever is greater 5% or 50ms whichever is greater *

P14x Technical Data Sheet 15 P141/2/3/4/5 Software Version 46J


IEEE reset: is greater
7.5% or 60ms whichever is greater Repeatability: <5%
DT operation: Disengagement time: <50ms
2% or 50ms whichever is greater tRESET: 5%
DT reset: 5% Instantaneous operating time: < 50ms
Repeatability: 2%
Reference conditions TMS = 1, TD = 1 and Sensitive Reverse/Low Forward/
IN > setting of 100mA, operating range 2-0In Over Power (1 Phase)

Zero Polarizing Accuracy


Operating pick-up: 2%o of RCA 90% Pick-up: Setting 10%
Hysteresis: <3o Reverse/Over power Drop-off:
VN > Pick-up: Setting 10% 0.9 of setting 10%
VN > Drop-off: 0.9 x Setting 10% Low forward power Drop-off:
1.1 of Setting 10%
Angle variation Pick-up:
Negative Polarizing Expected pick-up angle 2 degree
Operating Pick-up: 2%o of RCA 90% Angle variation Drop-off:
Hysteresis: <3o Expected drop-off angle 2.5% degree
VN 2 > Pick-up: Setting 10% Operating time: 2% or 50ms whichever is
VN 2 > Drop-off: 0.9 x Setting 10% greater
I2 > Pick up: Setting 10% Repeatability: <5%
I2 > Drop-off: 0.9 x Setting 10% Disengagement time: <50ms
tRESET: 5%
Instantaneous operating time: <50ms
Negative Sequence Overcurrent

Accuracy Under Voltage Protection


DT Pick-up: Setting 5%
Minimum IDMT trip level: 1.05 x Setting 5% Accuracy
Drop-off: 0.95 x Setting 5% DT Pick-up: Setting 5%
IDMT shape: 5% or 40ms whichever IDMT Pick-up: Setting 5%
is greater Drop-off: 1.02 x Setting 5%
IEEE reset: 5% or 50ms whichever IDMT shape: 2% or 50ms whichever is
is greater greater
DT operation: 2% or 50ms, whichever is DT operation: 2% or 50ms whichever is
greater greater
DT reset: 5% Reset: <75ms
Directional boundary (RCA 90%): Repeatability: <1%
2% hysteresis 2o
Characteristic: UK curves Over Voltage Protection
IEC 60255-3 1998
US curves:
IEEEC37.1121996 Accuracy
DT Pick-up: Setting 5%
IDMT Pick-up: Setting 5%
Reverse/Low Forward/Over Power Drop-off: 0.98 x Setting 5%
Protection IDMT shape: 2% or 50ms whichever is
greater
Accuracy DT operation: 2% or 50ms whichever is
Pick-up: Setting 10% greater
Reverse/Over Power drop off: 0.95 x Setting Reset: <75ms
10% Repeatability: <1%
Low forward Power drop off:
1.05xSetting+10% Rate of Change of Voltage dv/dt
Angle variation pick-up: Expected pick-up
angle 2 degree
Protection
Angle variation drop-off: Expected drop-off
angle 2.5 degree Accuracy for 110V VT
Operating time: 2% or 50ms whichever Tolerance: 1% or 0.07, whichever is greater
Pick-up: Setting tolerance
P14x Technical Data Sheet 16 P141/2/3/4/5 Software Version 46J
Drop-off: (Setting - 0.07) tolerance for Operating time* (overfrequency):
positive direction <125ms for Fs/Ff ratios less than 2
Drop-off: (Setting + 0.07) tolerance for <150ms for Fs/Ff ratios less than 30
negative direction <200ms otherwise
Operating time@50Hz: [(Avg.cycle*20)+60]ms Reset time*: <200ms
Reset time@50Hz: 40ms * Reference conditions: Tested using step
changes in frequency with Freq.Av.Cycles
setting = 0 and no intentional time delay.
Neutral Displacement/Residual Fs/Ff ratios as stated, where:
Voltage Fs = start frequency - frequency setting
Ff = frequency setting - end frequency
Accuracy
Pick-up: Setting 5% or 1.05 x Setting 5% Advanced Frequency Supervised
Drop-off: 0.95 x Setting 5%
Rate of Change of Frequency
IDMT shape: 5% or 65ms whichever is
greater f+df/dt Protection [81RF]
DT operation: 2% or 20ms whichever is
greater <55ms Accuracy
Reset: <35ms Pick-up:
Repeatability: <10% Setting10mHz (frequency threshold)
Setting 3% or 10mHz/s, whichever is
greater (df/dt threshold)
Under-frequency Protection Drop-off (frequency threshold):
Setting +20mHz, 10mHz (underfrequency)
Accuracy Setting -20mHz, 10mHz (overfrequency)
Pick-up: Setting 0.025Hz Drop-off (df/dt threshold, falling frequency):
Drop-off: 1.05 x Setting 0.025Hz Setting +0.005Hz/s, 10mHz/s
DT operation: 2% or 50ms whichever is (for settings between 0.01Hz/s and 0.1Hz/s)
greater * Setting +0.05Hz/s, 5% or 55mHz/s,
* The operating time will also include a time whichever is greater
for the relay to frequency track (for settings greater than 0.1Hz/s)
(20Hz/second) Drop-off (df/dt threshold, rising frequency):
Setting -0.005Hz/s, 10mHz/s
(for settings between 0.01Hz/s and 0.1Hz/s)
Over-frequency Protection Setting -0.05Hz/s, 5% or 55mHz/s,
whichever is greater
Accuracy (for settings greater than 0.1Hz/s)
Pick-up: Setting 0.025Hz
Drop-off: 0.95 x Setting 0.025Hz Operating & Reset Time
DT operation: 2% or 50ms whichever is Instantaneous operating time:
greater * <125ms for Freq.Av.Cycles setting = 0
* The operating will also include a time for Reset time:
the relay to frequency track (20Hz/ second) <400ms for df/dt.Av.Cycles setting = 0

Advanced Over/Under Frequency Advanced Independent Rate of


f+t Protection [81U/81O] Change of Frequency df/dt+t
Protection [81R]
Accuracy
Pick-up: Setting10mHz Accuracy
Drop-off: Pick-up:
Setting +20mHz, 10mHz (underfrequency) Setting 3% or 10mHz/s, whichever is
Setting -20mHz, 10mHz (overfrequency) greater
Operating timer: Drop-off (falling frequency):
2% or 50ms whichever is greater Setting +0.005Hz/s, 10mHz/s
(for settings between 0.01Hz/s and 0.1Hz/s)
Operating & Reset Time Setting +0.05Hz/s, 5% or 55mHz/s,
Operating time* (underfrequency): whichever is greater
<100ms for Fs/Ff ratios less than 2 (for settings greater than 0.1Hz/s)
<160ms for Fs/Ff ratios less than 6 Drop-off (rising frequency):
<230ms otherwise Setting -0.005Hz/s, 10mHz/s
(for settings between 0.01Hz/s and 0.1Hz/s)
P14x Technical Data Sheet 17 P141/2/3/4/5 Software Version 46J
Setting -0.05Hz/s, 5% or 55mHz/s, Thermal Overload
whichever is greater
(for settings greater than 0.1Hz/s)
Operating timer: Accuracy
2% or 50ms whichever is greater Thermal alarm pick-up:
Calculated trip time 10%
Operating & Reset Time Thermal overload pick-up:
Operating time*: Calculated trip time 10%
<200ms for ramps 2x setting or greater Cooling time accuracy:
<300ms for ramps 1.3x setting or greater 15% of theoretical
Reset time*: <250ms Repeatability: <5%
* Reference conditions: Tested with * Operating time measured with applied
df/dt.Av.Cycles setting = 0, for df/dt current of 20% above thermal setting.
settings greater than 0.1Hz/s (positive or
negative, as relevant) and no intentional
time delay. Voltage Dependent Overcurrent

Accuracy
Advanced Average Rate of Change VCO / VRO threshold Pick-up:
of Frequency f+Df/Dt Protection Setting 5%
[81RAV] Overcurrent Pick-up:
(K factor x Setting) 5%
Accuracy VCO / VRO threshold Drop-off:
Pick-up: 1.05 x Setting 5%
Setting10mHz (frequency threshold) Overcurrent Drop-off:
Setting 0.1Hz/s (Df/Dt threshold)* 0.95 x (K factor x Setting) 5%
Drop-off: Operating time:
Setting +20mHz, 10mHz (falling frequency) 5% or 60 ms whichever is greater
Setting -20mHz, 10mHz (rising frequency) Repeatability: <5%
Operating timer:
2% or 30ms whichever is greater
* Reference conditions: To maintain Cold Load Pick-up Setting
accuracy the minimum time delay setting,
Dt, should be: Accuracy
Dt > 0.375 x Df + 0.23 (for Df setting < 1Hz) I> Pick-up: Setting 1.5%
Dt > 0.156 x Df + 0.47 (for Df setting 1Hz) I> Pick-up: Setting 2.5%
IN> Pick-up: Setting 1.5%
Operating Time I> Drop-off: 0.95 x Setting 1.5%
Typically <125ms with Freq.Av.Cycles = 0 I> Drop-off: 0.95 x Setting 2.5%
IN> Drop-off: 0.95 x Setting 1.5%
DT operation:
Advanced Load Restoration 0.5% or 40ms whichever is greater
Accuracy
Repeatability: <1%
Pick-up: Setting10mHz
Drop-off: Setting -20mHz, 10mHz
Restoration timer: Negative Sequence Overvoltage
2% or 50ms whichever is greater Protection
Holding timer:
2% or 50ms whichever is greater
Accuracy
Pick-up: Setting 5%
Broken Conductor Logic Drop-off: 0.95 x Setting 5%
DT operation: 2% or 50ms whichever is
Accuracy greater
Pick-up: Setting 2.5% Repeatability: <5%
Drop-off: 0.95 x Setting 2.5%
DT operation: 2% or 40ms whichever is
greater

P14x Technical Data Sheet 18 P141/2/3/4/5 Software Version 46J


Admittance, Conductance and Programmable Scheme Logic
Susceptance
Accuracy
Accuracy Output conditioner timer: Setting 2% or 50ms
YN, BN and BN measurements: whichever is greater
5% Dwell conditioner timer: Setting 2% or 50ms
YN, BN, BN Pick-up: Setting 5% whichever is greater
YN, BN, BN Drop-off: Pulse conditioner timer: Setting 2% or 50ms
>0.85 x Setting whichever is greater
Operating time:
Start <100ms Trip Setting 2% or 50 ms Measurements and Recording
Operating boundary: 2
Facilities
VN: Setting 5%

Measurements
Selective Overcurrent Protection Current: 0.05 3In
Accuracy: 1.0% of reading
Accuracy Voltage: 0.052Vn
Fast block operation: <25ms Accuracy: 1.0% of reading
Fast block reset: <30ms Power (W): 0.22Vn 0.053In
Time delay: Setting 2% or 20ms whichever is Accuracy: 5.0% of reading at unity power
greater factor
Reactive Power (Vars):
0.22Vn, 0.053In
Voltage Transformer Supervision Accuracy: 5.0% of reading at zero power
factor
Accuracy Apparent Power (VA): 0.22Vn 0.053In
Fast block operation: <25ms Accuracy: 5% of reading
Fast block reset: <30ms Energy (Wh): 0.22Vn 0.23In
Time delay: Setting 2% or 20ms whichever is Accuracy: 5% of reading at zero power factor
greater Energy (Varh): 0.22Vn 0.23In
Accuracy: 5% of reading at zero power factor
Current Transformer Supervision Phase accuracy: 036
Accuracy: 0.5%
Frequency: 4565Hz
Accuracy Accuracy: 0.025Hz
In> Pick-up: Setting 5%
VN< Pick-up: Setting 5%
In> Drop-off: 0.9 x Setting 5% Performance
Year 2000: Compliant
VN< Drop-off: (1.05 x Setting 5% or 1V
whichever is greater Real time clock accuracy: <2% seconds/day
Modulation ratio: 1/3 or 1/6
Time delay operation: Setting 2% or 20ms
Input signal peak-peak amplitude:
whichever is greater
200mV20V
CTS block operation: <1 cycle
Input impedance at 1000Hz:
CTS reset: <35ms
6000
External clock synchronization:
CB fail Conforms to IRIG standard 200-98, format B

Accuracy IRIG-B and Real Time Clock


I > Pick-up: Setting 5% or 20 mA whichever is
greater Accuracy (for modulated and un-modulated
I > Drop-off: 100% of setting 5% or 20 mA versions)
whichever is greater Real time clock accuracy: < 2 seconds/day
Timers: 2% or 50 ms whichever is greater
Reset time: <25 ms without DC offset
<35 ms with DC offset

P14x Technical Data Sheet 19 P141/2/3/4/5 Software Version 46J


Disturbance Records Receiver Optical Characteristics

Accuracy (TA = 0C to 70C, VCC = 4.75 V to 5.25 V)


Magnitude and relative phases: Parameter Sym Min. Typ. Max. Unit
5% of applied quantities
Input Optical PIN
Duration: 2% Power Minimum Min. -33.5 -31
dBm
avg.
Trigger position: 2% (minimum Trigger at Window Edge (W)
100ms) Input Optical PIN
Bm
Line length: 0.011000kn ** Power Minimum Min. -34.5 -31.8
avg.
at Eye Center (C)
Line impedance (100/110V): 0.1/In250/In
Input Optical PIN dBm
Line impedance (380/480V): 0.4/In1000/In Power Maximum Max.
-14 -11.8
avg.
Line angle: 2085
KZN residual: 07.00 Note: The 10BaseFL connection will no
KZN res. angle: -90+90 longer be supported as IEC 61850
does not specify this interface
Plant Supervision

Accuracy
Timers: 2% or 20ms whichever is greater
Broken current accuracy: 5%

Timer Accuracy
Timers: 2% or 40ms whichever is greater
Reset time: <30ms

Undercurrent Accuracy
Pick-up: 10% or 25mA whichever is greater
Operating time: <20ms
Reset: <25ms

IEC 61850 Ethernet Data


100 Base FX Interface
Transmitter Optical Characteristics
(TA = 0C to 70C, VCC = 4.75 V to 5.25 V)

Parameter Sym Min. Typ. Max Unit

Output Optical
Power BOL -19 - dBm
PO -14
62.5/125 m, NA -20 16.8 avg.
= 0.275 Fiber EOL

Output Optical -
Power BOL 22.5 - dBm
PO -14
50/125 m, NA = - 20.3 avg.
0.20 Fiber EOL 23.5

Optical Extinction 10
% dB
Ratio -10

Output Optical
PO dBm
Power at -45
(0) avg
Logic 0 State

BOL - Beginning of life


EOL - End of life

P14x Technical Data Sheet 20 P141/2/3/4/5 Software Version 46J


Settings, Measurements and Oct/Nov/Dec
DST End Mins: 0min1425min
Records List RP1 Time Zone: UTC/Local
RP2 Time Zone: UTC/Local
Settings List Tunnel Time Zone: UTC/Local

Global Settings (System Data) Configuration


Language: English/French/German/Spanish Setting Group:
Frequency: 50/60Hz Select via Menu
Select via Opto
Active Settings: Group 1/2/3/4
Circuit Breaker Control Setting Group 1: Disabled/Enabled
(CB Control) Setting Group 2: Disabled/Enabled
CB Control by: Setting Group 3: Disabled/Enabled
Disabled Setting Group 4: Disabled/Enabled
Local System Config: Invisible/Visible
Remote Overcurrent: Disabled/Enabled
Local+Remote Negative Sequence O/C: Disabled/Enabled
Opto Broken Conductor: Disabled/Enabled
Opto+local Earth Fault 1: Disabled/Enabled
Opto+Remote Earth Fault 2: Disabled/Enabled
Opto+Rem+local SEF/REF1 Prot: Disabled/Enabled
Close Pulse Time: 0.1050.00s Residual O/V NVD: Disabled/Enabled
Trip Pulse Time: 0.105.00s Thermal Overload: Disabled/Enabled
Man Close t max: 0.019999.00s Neg. Sequence O/V: Disabled/Enabled
Man Close Delay: 0.01600.00s Cold Load Pick-up: Disabled/Enabled
CB Healthy Time: 0.019999.00s Selective Logic: Disabled/Enabled
Check Sync. Time: 0.019999.00s Admit. Protection: Disabled/Enabled
Reset Lockout by: User Interface/CB Close Power Protection: Disabled/Enabled
Man Close RstDly: 0.10600.00s Volt Protection: Disabled/Enabled
CB Status Input: Freq. Protection: Disabled/Enabled
None CB Fail: Disabled/Enabled
52A Supervision: Disabled/Enabled
52B Fault Locator: Disabled/Enabled
52A & 52B System Checks2: Disabled/Enabled
Auto-Reclose3: Disabled/Enabled
Input Labels: Invisible/Visible
Date and Time Output Labels: Invisible/Visible
IRIG-B Sync: Disabled/Enabled Adv. Freq. Protn: Disabled/Enabled
Battery Alarm: Disabled/Enabled CT & VT Ratios: Invisible/Visible
LocalTime Enable: Disabled/Fixed/Flexible Record Control: Invisible/Visible
LocalTime Offset: -720 min720min Disturb Recorder: Invisible/Visible
DST Enable: Disabled/Enabled Measuret Setup: Invisible/Visible
DST Offset: 30min60min Comms Settings: Invisible/Visible
DST Start: First/Second/Third/ Commission Tests: Invisible/Visible
Fourth/Last Setting Values: Primary/Secondary
DST Start Day: Sun/Mon/Tues/Wed/ Control Inputs: Invisible/Visible
Thurs/Fri/Sat Ctrl I/P Config: Invisible/Visible
DST Start Month: Jan/Feb/Mar/Apr/May/ Ctrl I/P Labels: Invisible/Visible
Jun/Jul/Aug/Sept/Oct/ Direct Access: Disabled/Enabled
Nov/Dec DST Start InterMiCOM: Disabled/Enabled
Mins: 0min1425min Function Key4: Invisible/Visible
DST End: First/Second/Third/ RP1 Read Only: Disabled/Enabled
Fourth/Last RP2 Read Only: Disabled/Enabled
DST End Day: Sun/Mon/Tues/Wed/ NIC Read Only: Disabled/Enabled
Thurs/Fri/Sat LCD Contrast: (Factory pre-set)
DST End Month: Jan/Feb/Mar/Apr/
May/Jun/Jul/Aug/Sept/

P14x Technical Data Sheet 21 P141/2/3/4/5 Software Version 46J


CT and VT Ratios Input 32 Trigger: No Trigger/Trigger L/H/
Main VT Primary: 100V...1MV Trigger H/L
Main VT Sec'y: 80...140V
C/S VT Primary2: 100V...1MV Measured Operating Data
C/S VT Secondary: 80...140V
NVD VT Primary5: 100V...1MV
(Measure't. Setup)
NVD VT Secondary: 80...140V Default Display:
Phase CT Primary: 1A30kA 3Ph + N Current
Phase CT Sec'y: 1A/5A 3Ph Voltage
E/F CT Primary: 1A30kA Power
E/F CT Sec'y: 1A/5A Date and Time
SEF CT Primary: 1A30kA Description
SEF CT Sec'y: 1A/5A Plant Reference
I Derived Phase5: Frequency
IA Access Level
IB Local Values: Primary/Secondary
IC Remote Values: Primary/Secondary
None Measurement Ref: VA/VB/VC/IA/IB/IC
C/S Input2: Measurement Mode: 0/1/2/3
A-N Fix Dem. Period: 199mins
B-N Roll Sub Period: 199mins
C-N Num. Sub Periods: 115
A-B Distance Unit: Miles/Kilometers
B-C Fault Location:
C-A Distance
Main VT Location2: Line/Bus Ohms
% of Line
Remote2 Values: Primary/Secondary
Sequence of Event Recorder
(Record Control) Communications
Alarm Event: Disabled/Enabled RP1 Protocol:
Relay O/P Event: Disabled/Enabled Courier
Opto Input Event: Disabled/Enabled IEC870-5-103
General Event: Disabled/Enabled DNP 3.0
Fault Rec. Event: Disabled/Enabled RP1 Address: (Courier or IEC870-5-103):
Maint. Rec. Event: Disabled/Enabled 0255
Protection Event: Disabled/Enabled RP1 Address: (DNP3.0):
DDB 31 - 0: (up to): 065519
DDB 1279 - 1248: RP1 InactivTimer: 130mins
Binary function link strings, selecting which RP1 Baud Rate: (IEC870-5-103):
DDB signals will be stored as events, and 9600/19200 bits/s
which will be filtered out RP1 Baud Rate: (DNP3.0):
1200 bits/s
Oscillography (Disturb. Recorder) 2400 bits/s
Duration: 0.1010.50s 4800 bits/s
Trigger Position: 0.0100.0% 9600 bits/s
Trigger Mode: Single/Extended 19200 bits/s
Analog Channel 1: (up to): 38400 bits/s
Analog Channel 8: RP1 Parity:
Disturbance channels selected from: Odd/Even/None
VA/VB/VC/Vchecksync./IA/IB/IC/IN/IN RP1 Meas Period: 160s
Sensitive RP1 PhysicalLink:
Digital Input 1: (up to): Copper
Digital Input 32: Fiber Optic (IEC870-5-103, DNP3.0, Courier,
Selected binary channel assignment from MODBUS)
any DDB status point within the relay (opto K-Bus (Courier only)
input, output contact, alarms, starts, trips, RP1 Time Sync: Disabled/Enabled
controls, logic). DNP Need Time: 130m
Input 1 Trigger: No Trigger/Trigger L/H/Trigger DNP App Fragment: 1002048
H/L DNP App Timeout: 1120
(up to): DNP SBO Timeout: 110
DNP Link Timeout: 0120

P14x Technical Data Sheet 22 P141/2/3/4/5 Software Version 46J


RP1 CS103 Blocking: No. CB Ops Lock: 110000
Disabled CB Time Maint: Alarm Disabled/Enabled
Monitor Blocking CB Time Maint: 0.0050.500s
Command Blocking CB Time Lockout: Alarm Disabled/Enabled
CB Time Lockout: 0.0050.500s
RP1 Port Config. (Courier): Fault Freq. Lock: Alarm Disabled/Enabled
K Bus Fault Freq. Count: 19999
EIA(RS)485 Fault Freq. Time: 09999s
RP1 Comms. Mode:
IEC60870 FT1.2 Frame 10-Bit No Parity
Optocoupled Binary Inputs
(Opto Config.)
Optional Additional Second Rear Global threshold:
Communication (Rear Port2 (RP2)) 24 - 27V
RP2 Protocol: Courier (fixed) 30 - 34V
RP2 Port Config: 48 - 54V
Courier over EIA(RS)232 110 - 125V
Courier over EIA(RS)485 220 - 250V
K-Bus Custom
RP2 Comms. Mode: Opto Input 1:
IEC60870 FT1.2 Frame (up to):
10-Bit NoParity Opto Input #. (# = max. opto no. fitted):
RP2 Address: 0255 Custom options allow independent
RP2 InactivTimer: 130mins thresholds to be set per opto, from the same
RP2 Baud Rate: range as above.
9600 bits/s Filter Control:
19200 bits/s Binary function link string, selecting which
38400 bits/s optos will have an extra 1/2 cycle noise filter,
and which will not.
Characteristics:
Optional Ethernet Port Standard 60% - 80%
NIC Tunl Timeout: 1...30mins 50% - 70%
NIC Link Report: Alarm/Event/None Time stamping accuracy: + 1 msec
NIC Link Timeout: 0.1...60s

Control Inputs into PSL


Commission Tests
Monitor Bit 1: (Ctrl. I/P Config.)
(up to): Hotkey Enabled:
Monitor Bit 8: Binary function link string, selecting which of
Binary function link strings, selecting which the control inputs will be driven from
DDB signals have their status visible in the Hotkeys.
Commissioning menu, for test purposes Control Input 1: Latched/Pulsed
Test Mode: (up to):
Disabled Control Input 32: Latched/Pulsed
Test Mode Ctrl Command 1:
Blocked Contacts (up to):
Test Pattern: Ctrl Command 32:
Configuration of which output contacts are to ON/OFF
be energized when the contact test is SET/RESET
applied. IN/OUT
Static Test Mode: Disabled/Enabled ENABLED/DISABLED

Circuit Breaker Condition EIA(RS)232 Teleprotection


Monitoring (CB Monitor Setup) (InterMiCOM Comms.)
Broken I^: 1.02.0 Source Address: 110
I^ Maintenance: Alarm Disabled/Enabled Received Address: 110
I^ Maintenance: 125000 Data Rate:
I^ Lockout: Alarm Disabled/Enabled 600 Baud
I^ Lockout: 125000 1200 Baud
No. CB Ops Maint: Alarm Disabled/Enabled 2400 Baud
No. CB Ops Maint: 110000 4800 Baud
No. CB Ops Lock: Alarm Disabled/Enabled 9600 Baud

P14x Technical Data Sheet 23 P141/2/3/4/5 Software Version 46J


19200 Baud Settings in Multiple Groups
Loopback Mode: Note: All settings here onwards apply for
Disabled/Internal/External setting groups # = 1 to 4.

Test Pattern:
Configuration of which InterMiCOM signals Protection Functions
are to be energized when the loopback test
is applied.
System Config.
Phase Sequence:
InterMiCOM Conf. Standard ABC
IM Msg Alarm Lvl: 0100.0% Reverse ACB
IM1 Cmd Type: Disabled/Direct/Blocking 2NDHARM BLOCKING:
(up to): Disabled
IM4 Cmd Type: Disabled/Direct/Blocking Enabled
IM5 Cmd Type: Disabled/Permissive/Direct 2ndHarm Thresh: 570
(up to): I>lift 2H: 432
IM8 Cmd Type: Disabled/Permissive/Direct
IM1 FallBackMode: Default/Latched
(up to):
Phase Overcurrent (Overcurrent)
IM8 FallBackMode: Default/Latched I>1 Function:
IM1 DefaultValue: 0/1 Disabled
(up to): DT
IM8 DefaultValue: 0/1 IEC S Inverse
IM1 FrameSyncTim: 10ms1.50s IEC V Inverse
(up to): IEC E Inverse
IM8 FrameSyncTim: 10ms1.50s UK LT Inverse
UK Rectifier
RI
Function Keys4 IEEE M Inverse
Fn. Key Status 1: IEEE V Inverse
(up to): IEEE E Inverse
Fn. Key Status 10 US Inverse
Disable US ST Inverse
Lock Def User Curve 1
Unlock/Enable Def User Curve 2
Fn. Key 1 Mode: Toggled/Normal Def User Curve 3
(up to): Def User Curve 4
Fn. Key 10 Mode: Toggled/Normal I>1 Direction:
Fn. Key 1 Label: Non-Directional
(up to): Directional Fwd
Fn. Key 10 Label: Directional Rev
User defined text string to describe the I>1 Current Set: 0.084.00 In
function of the particular function key I>1 Time Delay: 0.00100.00s
I>1 TMS: 0.0251.200
I>1 Time Dial: 0.01100.00
IED CONFIGURATOR I>1 K (RI): 0.1010.00
Switch Conf. Bank: No Action/Switch Banks I>1 DT Adder: 0.00100.00
I>1 Reset Char.: DT/Inverse
IEC61850 GOOSE I>1 tRESET: 0.00100.00s
GoEna: Disabled/Enabled I>2 Status
Test Mode: Disabled/Pass Through/Forced (up to):
VOP Test Pattern: 0x00000000... I>2 tRESET
0xFFFFFFFF All settings and options chosen from the
Ignore Test Flag: No/Yes same ranges as per the first stage
overcurrent, I>1.
I>3 Status:
Control Input User Labels Disabled
(Ctrl. I/P Labels) Enabled
Control Input 1: I>3 Direction:
(up to): Non-Directional
Control Input 32: Directional Fwd
User defined text string to describe the Directional Rev
function of the particular control input
P14x Technical Data Sheet 24 P141/2/3/4/5 Software Version 46J
I>3 Current Set: 0.0832.00 In Load Blinder
I>3 Time Delay: 0.00100.00s Blinder Status:
I>4 Status Disabled
(up to): Enabled
I>4 Time Delay Blinder Function:
All settings and options chosen from the 3Ph
same ranges as per the third stage 1Ph
overcurrent, I>3. Blinder Mode:
I> Char Angle: -9595 Both
I>5 Status Forward
(up to): Reverse
I>5 tRESET FWD Z Impedance: 0.1100 ohm
All settings and options chosen from the FWD Z Angle: 585 deg
same ranges as per the first stage REV Z Impedance: 0.1100 ohm
overcurrent, I>1. REV Z Angle: 585 deg
I>6 Status Binder V<Block: 10120 V
(up to): Binder I2>Block: 0.84 A
I>6 Time Delay PU cycles: 050
All settings and options chosen from the DO cycles: 050
same ranges as per the third stage
overcurrent, I>3.
I> Blocking: Negative Sequence Overcurrent
Binary function link string, selecting which I2>1 Function:
overcurrent elements (stages 1 to 4) will be Disabled
blocked if VTS detection of fuse failure DT
occurs. IEC S Inverse
IEC V Inverse
Binary function link string, selecting which IEC E Inverse
overcurrent elements (stages 1 to 4) will be UK LT Inverse
blocked if 2nd Harmonic Block is enabled with IEEE M Inverse
an option of choosing 1PH block. IEEE V Inverse
IEEE E Inverse
US Inverse
Voltage Dependent Overcurrent
US ST Inverse
V DEPENDANT O/C
I2>1 Direction:
V Dep OC Status
Non-Directional
VCO Disabled
Directional Fwd
VCO >1 Directional Rev
VCO >2 I2>1 Current Set: 0.084.00 In
VCO >1 & >2 I2>1 Time Delay: 0.00100.00s
VCO >5 I2>1 TMS: 0.0251.200
VCO >1 & >2 & >5 I2>1 Time Dial: 0.01100.00
VCO >1 & >5 I2>1 DT Adder: 0.00100.00
VC0 >2 & >5 I2>1 Reset Char.: DT/Inverse
VRO I>1 I2>1 tRESET: 0.00100.00s
VRO I>2 I2>2 Status
VRO I>5 (up to):
VRO >1 & >2 I2>2 tRESET
VRO >1 & >5 All settings and options chosen from the
VRO >2 & >5 same ranges as per the first stage
VRO >1 & >2 & I>5 overcurrent, I2>1.
V Dep OC V<1 Set I2>3 Status:
10120 V (100/120 V) Disabled
40480 V (380/440 V) Enabled
V Dep OC V<2 Set I2>3 Direction:
10120 V (100/120 V) Non-Directional
40480 V (380/440 V) Directional Fwd
Directional Rev
I2>3 Current Set: 0.0832.00 In
I2>3 Time Delay: 0.00100.00s
I2>4 Status

P14x Technical Data Sheet 25 P141/2/3/4/5 Software Version 46J


(up to): (up to):
I2>4 Time Delay IN1>2 tRESET
All settings and options chosen from the All settings and options chosen from the
same ranges as per the third stage same ranges as per the first stage ground
overcurrent, I2>3. overcurrent, IN>1.
IN1>3 Status:
I2> VTS Blocking: Disabled
Binary function link string, selecting which Enabled
Neg. Seq. O/C elements (stages 1 to 4) will IN1>3 Directional:
be blocked if VTS detection of fuse failure Non-Directional
occurs. Directional Fwd
Directional Rev
Binary function link string, selecting which IN1>3 Current Set: 0.0832.00 In
Neg. Seq. O/C elements (stages 1 to 4) will IN1>3 Time Delay: 0.00200.00s
be blocked if 2nd Harmonic Block is enabled. IN1>4 Status
(up to):
I2> Char Angle: -9595 IN1>4 Time Delay
I2> V2pol Set: All settings and options chosen from the
0.525.0 (100 - 110V): same ranges as per the third stage ground
2100 (380 - 480V): overcurrent, IN>3.
IN1> Blocking:
Broken Conductor Binary function link string, selecting which
Broken Conductor: Disabled/Enabled ground overcurrent elements (stages 1 to 4)
I2/I1 Setting: 0.201.00 will be blocked if VTS detection of fuse
I2/I1 Time Delay: 0.0100.0s failure occurs.
Binary function link string, selecting which
Ground Overcurrent ground overcurrent elements (stages 1 to 4)
(Earth Fault 1 & 2) will be blocked if 2nd Harmonic Block is
IN1>1 Function enabled.
Disabled IN1> Char Angle: -9595
DT IN1> Polarization:
IEC S Inverse Zero Sequence
IEC V Inverse Neg. Sequence
IEC E Inverse IN1> VNpol Set:
UK LT Inverse 0.580.0V (100 - 110V)
RI 2320V (380 - 480V)
IEEE M Inverse IN1> V2pol Set:
IEEE V Inverse 0.525.0V (100 - 110V)
IEEE E Inverse 2100V (380 - 480V)
US Inverse IN1> I2pol Set: 0.081.00 In
US ST Inverse
IDG Sensitive Earth Fault Protection/
Def User Curve 1 Restricted Earth Fault Protection
Def User Curve 2 SEF/REF Options:
Def User Curve 3 SEF
Def User Curve 4 SEF cos (PHI)
IN1>1 Directional SEF sin (PHI)
Non-Directional Wattmetric
Directional Fwd Hi Z REF
Directional Rev Lo Z REF
IN1>1 Current Set: 0.084.00 In Lo Z REF + SEF
IN1>1 IDG Is: 1.04.0 In Lo Z REF + Wattmetric
IN1>1 Time Delay: 0.00200.00s ISEF>1 Function:
IN1>1 TMS: 0.0251.200 Disabled
IN1>1 Time Dial: 0.01100.00 DT
IN1>1 K(RI): 0.10..10.00 IEC S Inverse
IN1>1 IDG Time: 1.00..2.00 IEC V Inverse
IN1>1 DT Adder: 0.00100.00 IEC E Inverse
IN1>1 Reset Char.: DT/Inverse UK LT Inverse
IN1>1 tRESET: 0.00100.00s RI
IN1>2 Status IEEE M Inverse

P14x Technical Data Sheet 26 P141/2/3/4/5 Software Version 46J


IEEE V Inverse: RESTRICTED EARTH-FAULT
IEEE E Inverse (Low Impedance)
US Inverse IREF > K1: 0 20%
US ST Inverse IREF > K2: 0 150%
IDG IREF > Is1: 0.081.00 In
Def User Curve 1 IREF > Is2: 0.11.50 In
Def User Curve 2 (High Impedance)
Def User Curve 3 IREF > K1: 0.051.00 In
Def User Curve 4
ISEF>1 Directional:
Non-Directional
Neutral Voltage Displacement
Directional Fwd (Residual O/V NVD)
Directional Rev. VN>1 Function:
ISEF>1 Current Set: 0.0050.01 In Disabled
ISEF>1 IDG Is: 1.04.0 In DT
ISEF>1 Time Delay: 0.00200.00s IDMT
ISEF>1 TMS: 0.0251.200 VN>1 Voltage Set: 150V
ISEF>1 Time Dial: 0.5100.0 VN>1 Time Delay: 0.00100.00s
IN1>1 K(RI): 0.10..10.00 VN>1 TMS: 0.5100.0
ISEF>1 IDG Time: 1.00..2.00 VN>1 tReset: 0.00100.00s
ISEF>1 DT Adder: 0.00100.00 VN>2 Status: Disabled/Enabled
ISEF>1 Reset Char: DT/Inverse VN>2 Voltage Set:
ISEF>1 tRESET: 0.00100.00s 180V (100/110V)
ISEF>2 Status 4320V (380/440V)
(up to): VN>2 Time Delay: 0.00100.00s
ISEF>2 tRESET
All settings and options chosen from the Thermal Overload
same ranges as per the first stage ground Characteristic:
overcurrent, IN>1. Disabled
ISEF>3 Status: Single
Disabled Dual
Enabled Thermal Trip: 0.084.00 In
ISEF>3 Directional: Thermal Alarm: 50100%
Non-Directional Time Constant 1: 1200mins
Directional Fwd Time Constant 2: 1200mins
Directional Rev
ISEF>3 Current Set: 0.005.2.000 In
ISEF>3 Time Delay: 0.00200.00s Negative Sequence Overvoltage
ISEF>4 Status Protection
(up to): V2> Status: Disabled/Enabled
ISEF>4 Time Delay V2> Voltage Set:
All settings and options chosen from the 1V110V (100/120V)
same ranges as per the third stage ground 4V - 440V (380/440V)
overcurrent, IN>3. V2> Time Delay: 0.00100.00s
ISEF> Blocking:
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4) Cold Load Pick-up Setting
will be blocked if VTS detection of fuse tcold Time Delay: 014 400s
failure occurs. tclp Time Delay: 014 400s
Overcurrent
Binary function link string, selecting which I>1 Status: Block/Enabled
ground overcurrent elements (stages 1 to 4) I>1 Current Set: 0.084.00 In
will be blocked if 2nd Harmonic Block is I>1 Time delay: 0.00100.00s
enabled. I>1 TMS: 0.025.2.000
ISEF> Char. Angle: -9595 I>1 Time Dial: 0.515.0
ISEF> VNpol Set: I>2 Status
0.580.0V (100 - 110V) (up to):
2320V (380 - 480V) I>2 Time Dial
WATTMETRIC SEF: All settings and options chosen from the
PN> Setting: 020W (1A, 100/120V) same ranges as per the 1st stage.
PN> Setting: 0100W (5A, 100/120V) I>3 Status: Block/Enabled
PN> Setting: 0 80W (1A, 380/440V) I>3 Current Set: 0.0832.00 In
PN> Setting: 0400W (5A, 380/440V) 3 Time delay: 0.00100.00s
P14x Technical Data Sheet 27 P141/2/3/4/5 Software Version 46J
I>4 Status GN Status: Disabled/Enabled
(up to): GN>Direction
I>4 Time Delay Non-Directional
All settings and options chosen from the Directional Fwd
same ranges as per the 1st stage. Directional Rev.
E/F1 GN> Set (SEF):
IN1>1 Status: Block/Enabled 0.15mS (100/110V)
IN1>1 Current Set: 0.084.00 In 0.251.25mS (380/440V)
IN1>1 IDG Is: 1.04.0 In GN> Set (E/F):
IN1>1 Time Delay: 0.00200.00s 150mS (100/110V)
IN1>1 TMS: 0.025.2.000 0.2512.5mS (380/440V)
IN1>1 Time Dial: 0.515.0 GN> Time Delay: 0.05s100s
IN1>1 K(RI): 0.10..10.00 GN>tRESET: 0s100s
IN1>2 Status Over Susceptance
(up to): BN Status: Disabled/Enabled
IN2> 1 K(RI) GN>Direction
All settings and options chosen from the Non-Directional
same ranges as per the E/F1 stage. Directional Fwd
I>5 Status Directional Rev.
(up to): BN> Set (SEF)
I>5 Time Dial 0.15mS (100/110V)
All settings and options chosen from the 0.0251.25mS (380/440V))
same ranges as per the 1st stage. BN> Set (E/F):
I>6 Status 150mS (100/110V)
(up to): 0.2512.5mS (380/440V)
I>6 Time Delay BN> Time Delay: 0.05100s
All settings and options chosen from the BN> tRESET: 0s100s
same ranges as per the 3rd stage.
Undervoltage Protection
Selective Overcurrent Logic V< Measur't. Mode:
Overcurrent Phase-Phase
I>3 Time Delay: 0.00100.00s Phase-Neutral
I>4 Time Delay: 0.00100.00s V< Operate Mode:
Earth Fault1 Any Phase
IN1>3 Time Delay: 0.00200.00s Three Phase
IN1>4 Time Delay: 0.00200.00s V<1 Function:
Earth Fault2 Disabled
IN2>3 Time Delay: 0.00200.00s DT
IN2>4 Time Delay: 0.00200.00s IDMT
Sensitive E/F V<1 Voltage Set:
ISEF>3 Time Delay: 0.00200.00s 10120V (100/110V)
ISEF>4 Time Delay: 0.00200.00s 40480V (380/440V)
Overcurrent V<1 Time Delay: 0.00100.00s
I>6 Time Delay: 0.00100.00s V<1 TMS: 0.5100.0
V<1 Poledead Inh: Disabled/Enabled
V<2 Status: Disabled/Enabled
Neutral Admittance Protection V<2 Voltage Set:
VN Threshold: 10120V (100/110V)
140V (100/120V) 40480V (380/440V)
4160V (380/440V) V<2 Time Delay: 0.00100.00s
CT Input Type: SEF CT/E/F CT V<2 Poledead Inh: Disabled/Enabled
Correction angle: 3030o
Overadmittance
YN Status: Disabled/Enabled Overvoltage Protection
YN> Set (SEF): V> Measur't. Mode:
0.110mS (100/110V) Phase-Phase
0.0252.5mS (380/440V) Phase-Neutral
YN> Set (EF): V> Operate Mode:
1100mS (100/110V) Any Phase
0.2525mS (380/440V) Three Phase
YN> Time Delay: 0.05s100.00s V>1 Function:
YN> tRESET: 0.00100.00s Disabled
Over Conductance DT
P14x Technical Data Sheet 28 P141/2/3/4/5 Software Version 46J
IDMT (up to):
V>1 Voltage Set: F<2 Time Delay
60185V (100/110V) All settings and options chosen from the
240740V (380/440V) same ranges as per the 1st stage.
V>1 Time Delay: 0.00100.00s
V>1 TMS: 0.5100.0
V>2 Status: Disabled/Enabled
Advanced Over/Under Frequency
V>2 Voltage Set: Protection (f+t [81U/81O])
60185V (100/110V) Stage 1 f+t Status:
240740V (380/440V) Disabled
V>2 Time Delay: 0.00100.00s Enabled
1 (f+t) f: 40.1069.90Hz
1 (f+t) t: 0.00100.00s
dv/dt Protection Stage 2 f+t Status
dv/dt Meas. Mode: (up to):
Phase-Phase 9 (f+t)t
Phase-Neutral All settings and options chosen from the
dv/dt1 Function: same ranges as per the first stage
Disabled over/underfrequency, Stage 1 f+t.
Negative
Positive
Both Advanced Frequency Supervised
dv/dt1 Oper Mode: Rate of Change of Frequency
Any Phase Protection
Three Phase (f+df/dt [81RF]
dv/dt1 AvgCycles: 550 Stage 1 f+df/dt Status:
dv/dt1 Threshold: 0.5200 Disabled
dv/dt1 TimeDelay: 0100s Enabled
dv/dt1 tRESET: 0100s 1 (f+df/dt) f: 40.1069.90Hz
dv/dt2 Function: 1 (f+df/dt) df/dt:
Disabled 0.0110.0Hz/s
Negative Stage 2 f+df/dt Status
Positive (up to):
Both 9 (f+df/dt) df/dt
dv/dt2 Oper Mode: All settings and options chosen from the
Any Phase same ranges as per the first stage
Three Phase frequency supervized rate of change of
dv/dt2 AvgCycles: 550 frequency, Stage 1 f+df/dt.
dv/dt2 Threshold: 0.5200
dv/dt2 TimeDelay: 0100s
dv/dt2 tRESET: 0100s Advanced Independent Rate of
Change of Frequency Protection
Under-Frequency Protection (df/dt+t [81R])
F<1 Status: Disabled/Enabled Stage 1 df/dt+t Status:
F<1 Setting: 45.0065.00Hz Disabled
F<1 Time Delay: 0.00100.00s Negative
F<2 Status Positive
(up to): 1 (df/dt+t) df/dt: 0.0110.00Hz/s
F<4 Time Delay 1 (df/dt+t) t: 0.00100.00 s
All settings and options chosen from the Stage 2 df/dt+t Status
same ranges as per the 1st stage. (up to):
F> Blocking: 9 (df/dt+t) t
Binary function link string, selecting which All settings and options chosen from the
frequency elements (stages 1 to 4) will be same ranges as per the first stage
blocked by the pole-dead logic. independent rate of change of
frequency, Stage 1 df/dt+t.

Over-Frequency Protection
F>1 Status: Disabled/Enabled
F>1 Setting: 45.0065.00Hz
F>1 Time Delay: 0.00100.00s
F<2 Status

P14x Technical Data Sheet 29 P141/2/3/4/5 Software Version 46J


Advanced Average Rate of Change CT Supervision
of Frequency Protection CTS Status: Disabled/Enabled
(f+Df/Dt [81RAV]) CTS VN< Inhibit:
Stage 1 f+Df/Dt Status: 0.522.0V (100/110V)
Disabled 288V (380/440V)
Enabled CTS IN> Set: 0.084.00 In
1 (f+Df/Dt) f: 40.1069.90Hz CTS Time Delay: 010s
1 (f+Df/Dt) Df: 0.210.0Hz VTS PickupThresh: 20120V
1 (f+Df/Dt) Dt: 0.022.00 s
Stage 2 f+Df/Dt Status Fault Locator
(up to): Line Length (km): 0.0011000.000km
9 (f+Df/Dt) Dt Line Length (mi): 0.20625.00mi
All settings and options chosen from the Line Impedance: 0.10250.00
same ranges as per the first stage average Line Angle: 2085
rate of change of frequency, Stage 1 f+Df/Dt. KZN Residual: 0.007.00
KZN Res. Angle: -9090
Advanced Load Restoration
Restore1 Status: Bus-Line Synchronizm and Voltage
Disabled Checks (System Checks)
Enabled
VOLTAGE MONITORS
Restore1 Freq.: 40.1069.90Hz
Live Voltage:
Restore1 Time: 07200s
1.0132.0V (100/110V)
Restore2 Status
22528V (380/440V)
(up to):
Dead Voltage:
Restore9 Time
1.0132.0V (100/110V)
All settings and options chosen from the
22528V (380/440V)
same ranges as per the first stage load
restoration, Restore1.
Synchrocheck (Check Sync.)
CS1 Status: Disabled/Enabled
Circuit Breaker Fail CS1 Phase Angle: 590 o
CB Fail 1 Status: Disabled/Enabled
CS1 Slip Control:
CB Fail 1 Timer: 0.0010.00s
None
CB Fail 2 Status: Disabled/Enabled
Timer
CB Fail 2 Timer: 0.0010.00s
Frequency
Volt Prot. Reset:
Both
I< Only
CS1 Slip Freq.: 0.011.00Hz
CB Open & I<
CS1 Slip Timer: 0.099.0s
Prot. Reset & I<
CS2 Status
Ext Prot. Reset:
(up to):
I< Only
CS2 Slip Timer
CB Open & I<
All settings and options chosen from the
Prot. Reset & I<
same ranges as per the first stage CS1
element.
Undercurrent CS Undervoltage:
I< Current Set: 0.023.20 In 10.0132.0V (100/110V)
IN< Current Set: 0.023.20 In 40528V (380/440V)
ISEF< Current Set: 0.0010.800 In CS Overvoltage:
BLOCKED O/C 40.0185.0V (100/110V)
Remove I> Start: Disabled/Enabled 160740V (380/440V)
Remove IN> Start: Disabled/Enabled CS Diff Voltage:
1.0132.0V (100/110V)
4528V (380/440V)
Fuse Failure (VT Supervision) CS Voltage Block:
VTS Status: None
Blocking/Indication Undervoltage
VTS Reset Mode: Manual/Auto Overvoltage
VTS Time Delay: 1.010.0s Differential
VTS I> Inhibit: 0.0832.00 In UV & OV
VTS I2> Inhibit: 0.050.50 In UV & DiffV
OV & DiffV
UV, OV & DiffV
P14x Technical Data Sheet 30 P141/2/3/4/5 Software Version 46J
System Split I>3 and I>4:
SS Status: Disabled/Enabled No Action/Initiate Main AR/Block AR
SS Phase Angle: 90175 IN1>1 and IN1>2: No Action/Main AR
SS Under V Block: Disabled/Enabled IN1>3 and IN1>4:
SS Undervoltage: No Action/Initiate Main AR/Block AR
10.0132.0V (100/110V) IN2>1, IN2>2: No Action/Initiate Main AR
40528V (380/440V) IN2>3 and IN2>4:
SS Timer: 0.099.0s No Action/Initiate Main AR/Block AR
CB Close Time: 0.0000.500s ISEF>1, ISEF>2, ISEF>3 and ISEF>4:
No Action/Initiate Main AR/Initiate SEF AR/
Block AR
Auto-reclose YN/GN/ BN>: No Action/Initiate Main AR
AR Mode Select: Ext. Prot.: No Action/Initiate Main AR
Command Mode SYSTEM CHECKS
Opto Set Mode AR with ChkSync.: Disabled/Enabled
User Set Mode AR with SysSync.: Disabled/ Enabled
Pulse Set Mode Live/Dead Ccts: Disabled/Enabled
Number of Shots: 14 No System Checks:
Number of SEF Shots: 04 Enabled/Disabled
Sequence Co-ord.: Disabled/Enabled SysChk on Shot 1: Disabled/ Enabled
CS AR Immediate: Disabled/Enabled I>5: No Action/Initiate Main AR
Dead Time 1: 0.01300.00s I>6: No Action/Initiate Main AR/Block AR
Dead Time 2: 0.01300.00s
Dead Time 3: 0.019999.00s
Dead Time 4: 0.019999.00s Opto Input Labels
CB Healthy Time: 0.01s9999.00s Opto Input 1:
Start Dead q on: (up to):
Protection Resets/CB Trips Opto Input 24:
qReclaim Extend: User defined text string to describe the
No Operation/On Prot. Start function of the particular opto input.
Reclaim Time 1: 1.00600.00s
Reclaim Time 2: 1.00600.00s Output Labels
Reclaim Time 3: 1.00600.00s Relay 1:
Reclaim Time 4: 1.00600.00s (up to):
AR Inhibit Time: 0.01600.00s Relay 32:
AR Lockout: No Block/Block Inst. Prot. User defined text string to describe the
EFF Maint. Lock: function of the particular relay output contact.
No Block/Block Inst. Prot.
AR Deselected:
No Block/Block Inst. Prot.
Manual close:
No Block/Block Inst. Prot.
Trip 1 Main: No Block/Block Inst. Prot.
Trip 2 Main: No Block/Block Inst. Prot.
Trip 3 Main: No Block/Block Inst. Prot.
Trip 4 Main: No Block/Block Inst. Prot.
Trip 5 Main: No Block/Block Inst. Prot.
Trip 1 SEF: No Block/Block Inst. Prot.
Trip 2 SEF: No Block/Block Inst. Prot.
Trip 3 SEF: No Block/Block Inst. Prot.
Trip 4 SEF: No Block/Block Inst. Prot.
Trip 5 SEF: No Block/Block Inst. Prot.
Man. Close on Flt.:
No Lockout/Lockout
Trip AR Inactive:
No Lockout/Lockout
Reset Lockout by:
User Interface/Select Non-Auto
AR on Man. Close: Enabled/Inhibited
Sys. Check Time: 0.019999.00s
AR Skip Shot 1: Enabled/disabled
AR INITIATION
I>1, I>2: No Action/Initiate Main AR
P14x Technical Data Sheet 31 P141/2/3/4/5 Software Version 46J
Measurements List 3 Phase Watts
3 Phase VArs
3 Phase VA
Measurements 1 Zero Seq. Power
I Magnitude 3Ph Power Factor
I Phase Angle Ph Power Factor
Per phase ( = A, B, C) current Independent power factor measurements
measurements for all three phases ( = A, B, C).
IN Measured Mag. 3Ph WHours Fwd
IN Measured Ang. 3Ph WHours Rev.
IN Derived Mag. 3Ph VArHours Fwd
IN Derived Angle 3Ph VArHours Rev.
ISEF Magnitude 3Ph W Fix Demand
ISEF Angle 3Ph VArs Fix Dem.
I1 Magnitude I Fixed Demand
I2 Magnitude Maximum demand currents measured on a
I0 Magnitude per phase basis ( = A, B, C).
I RMS 3Ph W Roll Dem.
Per phase ( = A, B, C) RMS current 3Ph VArs Roll Dem.
measurements I Roll Demand
V- Magnitude Maximum demand currents measured on a
V- Phase Angle per phase basis ( = A, B, C).
V Magnitude 3Ph W Peak Dem.
V Phase Angle 3Ph VAr Peak Dem.
All phase-phase and phase-neutral voltages I Peak Demand
( = A, B. C) Maximum demand currents measured on a
VN Derived Mag. per phase basis ( = A, B, C).
VN Derived Ang. Reset Demand: Yes/No
V1 Magnitude.
V2 Magnitude
Measurements 3
V0 Magnitude
Highest Phase I
V RMS Thermal State
All phase-neutral voltages ( = A, B, C) Reset Thermal
Frequency IREF Diff.
C/S Voltage Mag. IREF Bias
C/S Voltage Ang. Admittance
C/S Bus-line Ang. Conductance
Slip Frequency Susceptance
IM Magnitude Admittance
IM Phase Angle Conductance
I1 Magnitude Susceptance
I1 Phase Angle I2/I1 Ratio
I2 Magnitude SEF Power
I2 Phase Angle IA 2nd Harmonic
I0 Magnitude IB 2nd Harmonic
I0 Phase Angle IC 2nd Harmonic
V1 Magnitude APh Sen Watts
V1 Phase Angle APh Sen Vars
V2 Magnitude APh Power Angle
V2 Phase Angle Z1 Imp Mag
V0 Magnitude Z1 Imp Ang
V0 Phase Angle Phase A Imp Mag
Phase A Imp Ang
Measurements 2 Phase B Imp Mag
Phase Watts Phase B Imp Ang
Phase VArs Phase C Imp Mag
Phase C Imp Ang
Phase VA
All phase segregated power
measurements, real, reactive and apparent
( = A, B, C)

P14x Technical Data Sheet 32 P141/2/3/4/5 Software Version 46J


Stage Statistics (Advanced) O/Voltage Start
StgX f+t Sta V> 1 2 AB BC CA
StgX f+t Trip O/Voltage Trip
StgX f+df/dt Trp V> 1 2 AB BC CA
StgX df/dt+t Sta Underfrequency
StgX df/dt+t Trp Start F< 1234
StgX f+Df/Dt Sta Trip F< 1234
StgX f+Df/Dt Trp Overfrequency
StgX Revn Date Start F> 1 2
(X = 1, 2, 3, 4, 5, 6, 7, 8, 9) Trip F> 1 2
Overadmittance
YN> Start Trip
Circuit Breaker Monitoring Statistics Overconductance
CB Operations GN> Start Trip
CB Operations Oversusceptance
Circuit breaker operation counters on a per BN> Start Trip
phase basis ( = A, B, C). Breaker Fail:
Total I Broken CB Fail 1 2
Cumulative breaker interruption duty on a Supervision
per phase basis ( = A, B, C). VTS/CTS/VCO/CLP
CB Operate Time A/R State: Trip 1/2/3/4/5
CB CONTROL Advanced Freq. Protection
Total Re-closures Start >123456789
Advanced Freq. Protection
Trip >123456789
Fault Record Proforma Adv. F+df/dt Protection
The following data is recorded for any Trip >123456789
relevant elements that operated during a Adv. df/dt Protection
fault, and can be viewed in each fault record. Start >123456789
Time & Date Adv. df/dt Protection
Event Text Trip >123456789
Event Value Adv. DelF/DelT Protection
Select Fault: [0...n] Start >123456789
Started Phase: A/B/C Adv. DelF/DelT Protection
Tripped Phase: A/B/C Trip >123456789
Overcurrent Faulted Phase: A/B/C
Start I> 123456 Start Elements:
Trip I> 123456 Trip Elements:
Neg. Seq. O/C Binary data strings for fast polling of which
Start I2> 1234 protection elements started or tripped for the
Trip I2> 1234 fault recorded.
Broken ConductorTrip Fault Alarms:
Earth Fault 1 Binary data strings for fast polling of alarms
Start IN1> 1234 for the fault recorded.
Trip IN1> 1234 Fault Time:
Earth Fault 2 Active Group: 1/2/3/4
Start IN2> 1234 System Frequency: Hz
Trip IN2> 1234 Fault Duration: s
Sensitive E/F CB Operate Time: s
Start ISEF> 1234 Relay Trip Time: s
Trip ISEF> 1234 Fault Location: km/miles//%
Restricted E/F The current magnitudes and phase angles
Trip IREF> stored before the fault inception.
Residual O/V NVD
I
Start VN> 1 2
V:
Trip VN> 1 2
Per phase record of the current and voltage
Thermal Overload: Alarm/Trip
magnitudes during the fault.
Neg. Seq. O/V
IN Measured
V2> Start Trip
IN Derived
U/Voltage Start
IN Sensitive
V< 1 2 AB BC CA
IREF Diff.
U/Voltage Trip
IREF Bias
V< 1 2 AB BC CA
VAN
P14x Technical Data Sheet 33 P141/2/3/4/5 Software Version 46J
VBN
VCN
VN Derived
Admittance
Conductance
Susceptance

P14x Technical Data Sheet 34 P141/2/3/4/5 Software Version 46J


P14x CASE DIMENSIONS

Figure 1: P141/P142 Case dimensions

P14x Technical Data Sheet 35 P141/2/3/4/5 Software Version 46J


P1616ENi

Figure 2: P143/P145 Case dimensions

Figure 3: P143 with 32I + 32O Case dimensions

P14x Technical Data Sheet 36 P141/2/3/4/5 Software Version 46J


P14x 2nd Rear Communication Board Connection Diagram

P1727ENb

Figure 4: P14x second rear port connection

P14x Technical Data Sheet 37 P141/2/3/4/5 Software Version 46J


External Connection Diagrams

P2140ena

Figure 5: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
(8 I/P & 7 O/P)
P14x Technical Data Sheet 38 P141/2/3/4/5 Software Version 46J
P2141ena

Figure 6: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with High Impedance Restricted Earth Fault (8 I/P & 7 O/P)
P14x Technical Data Sheet 39 P141/2/3/4/5 Software Version 46J
P2142ena

Figure 7: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Low Impedance Restricted Earth Fault (8 I/P & 7 O/P)
P14x Technical Data Sheet 40 P141/2/3/4/5 Software Version 46J
P2143ena

Figure 8: P141 Feeder Management Relay - Directional and Directional Earth Fault with VEE
Connected VT (8 I/P & 7 O/P)
P14x Technical Data Sheet 41 P141/2/3/4/5 Software Version 46J
P4609ENa

Figure 9: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
(8 I/P & 8 O/P)

P14x Technical Data Sheet 42 P141/2/3/4/5 Software Version 46J


P2144ena

Figure 10: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (8 I/P & 7 O/P)
P14x Technical Data Sheet 43 P141/2/3/4/5 Software Version 46J
Figure 11: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (8 I/P & 11 O/P with 4 High Break Contacts)
P14x Technical Data Sheet 44 P141/2/3/4/5 Software Version 46J
P2145ena

Figure 12: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (12 I/P & 11 O/P)
P14x Technical Data Sheet 45 P141/2/3/4/5 Software Version 46J
P2146ena

Figure 13: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (16 I/P & 7 O/P)
P14x Technical Data Sheet 46 P141/2/3/4/5 Software Version 46J
P2147ena

Figure 14: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (8 I/P & 15 O/P)
P14x Technical Data Sheet 47 P141/2/3/4/5 Software Version 46J
P2148ena

Figure 15: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 14 O/P)
P14x Technical Data Sheet 48 P141/2/3/4/5 Software Version 46J
P2270ENa

Figure 16: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 18 O/P with 4 High Break
Outputs)
P14x Technical Data Sheet 49 P141/2/3/4/5 Software Version 46J
P2151ena

Figure 17: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 22 O/P)
P14x Technical Data Sheet 50 P141/2/3/4/5 Software Version 46J
P2271ENa

Figure 18: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 22 O/P with 8 High Break
Contacts)
P14x Technical Data Sheet 51 P141/2/3/4/5 Software Version 46J
P2272ENa

Figure 19: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 26 O/P with 4 High Break
Contacts)
P14x Technical Data Sheet 52 P141/2/3/4/5 Software Version 46J
P2154ena

Figure 20: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 30 O/P)
P14x Technical Data Sheet 53 P141/2/3/4/5 Software Version 46J
P2149ena

Figure 21: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 14 O/P)
P14x Technical Data Sheet 54 P141/2/3/4/5 Software Version 46J
P2273ENa

Figure 22: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 22 O/P)

P14x Technical Data Sheet 55 P141/2/3/4/5 Software Version 46J


Figure 23: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-Reclose and Check Synchronizing (32 I/P & 32 O/P)

P14x Technical Data Sheet 56 P141/2/3/4/5 Software Version 46J


P2153ena

Figure 24: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (32 I/P & 14 O/P)
P14x Technical Data Sheet 57 P141/2/3/4/5 Software Version 46J
Figure 25: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (8 I/P & 7 O/P)
P14x Technical Data Sheet 58 P141/2/3/4/5 Software Version 46J
Figure 26: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (8 I/P & 11 O/P with 4 High
Break Contacts)
P14x Technical Data Sheet 59 P141/2/3/4/5 Software Version 46J
Figure 27: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (8 I/P & 15 O/P)
P14x Technical Data Sheet 60 P141/2/3/4/5 Software Version 46J
Figure 28: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (12 I/P & 11 O/P)
P14x Technical Data Sheet 61 P141/2/3/4/5 Software Version 46J
Figure 29: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (16 I/P & 7 O/P)
P14x Technical Data Sheet 62 P141/2/3/4/5 Software Version 46J
DIRECTION OF FORWARD CURRENT FLOW
A
P2 P1 P2 P1
X A
S2 S1
X B

X C C B
S2 S1 A B C PHASE ROTATION
MiCOM P145 (PART)
C1 5A MiCOM P145 (PART)
N
A J11
WATCHDOG

P14x Technical Data Sheet


A B C n J12 CONTACT
F1
1A J13
NOTE 2. C3 OPTO 9 F2 WATCHDOG
C4 5A C23 a b c J14 CONTACT
N F3
B H1
V CHECK OPTO 10 F4 H2 RELAY 1
n SYNC
1A C24 F5 H3
C6
OPTO 11 H4 RELAY 2
C7 5A F6
a b c H5
F7
C H6 RELAY 3 ANY TRIP
OPTO 12 F8 NOTE 3.
D1 H7
1A -
C9 OPTO 1 H8 RELAY 4
D2
+ H9
C10 5A
D3 NOTE 4. RELAY 5
- H10
N OPTO 2
D4 H11
+
H12 RELAY 6
1A D5
C12 -
OPTO 3 COMMS H13
D6 NOTE 5.
C13 5A + H14
N RELAY 7
D7 H15
SENSITIVE -

63
D8 OPTO 4 H16
+
1A J17 H17
C15 D9 - RELAY 8
-
OPTO 5 SEE DRAWING H18
A D10 EIA485/
C19 + 10Px4001.
KBUS F9
D11 J18
- PORT +
F10 RELAY 9
D12 OPTO 6 J16
+ SCN F11
D13 F12 RELAY 10
-
B C20 D14 OPTO 7 F13
+ J1 *
- F14
AC OR DC RELAY 11
D15 J2
- x AUX SUPPLY
+ F15
D16 OPTO 8
+ F16
J7

Auto-reclose and Check Synchronizing (12 I/P & 12 O/P)


D17 + F17 RELAY 12
C C21 COMMON
D18 J8 F18
CONNECTION +
48V DC FIELD
VOLTAGE OUT J9
-
N C22 J10
-

CASE
EARTH
NOTES 1.

(a) C.T. SHORTING LINKS 2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY.

3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
ENSURE CORRECT OPERATION OF THE PROTECTIVE RELAY.
(b) PIN TERMINAL (P.C.B. TYPE) 4. OPTO INPUTS 1 AND 2 MUST BE USED FOR SETTING GROUP
CHANGES IF THIS OPTION IS SELECTED IN THE RELAY MENU.

5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

P1608ENa

Figure 30: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with

P141/2/3/4/5 Software Version 46J


DIRECTION OF FORWARD CURRENT FLOW
A
P2 P1 P2 P1
X A
S2 S1
X B

X C C B
S2 S1 A B C PHASE ROTATION
MiCOM P145 (PART) MiCOM P145 (PART)
C1 5A N F1 J11
WATCHDOG
A OPTO 9 J12 CONTACT
F2
A B C C2 n J13

P14x Technical Data Sheet


F3 WATCHDOG
1A J14 CONTACT
NOTE 2. C3 OPTO 10 F4 H1
C4 5A C23 a b c RELAY 1
N F5 H2
B H3
V CHECK OPTO 11 F6
C5 H4 RELAY 2
n SYNC
1A C24 F7 H5
C6
OPTO 12 F8 H6 RELAY 3 ANY TRIP
a b c C7 5A NOTE 3.
F9 H7
C RELAY 4
H8
C8 OPTO 13 F10
D1 H9
-
C9 1A F11 RELAY 5
D2 OPTO 1 H10
+ OPTO 14
C10 5A F12 H11
D3 NOTE 4.
- H12 RELAY 6
N OPTO 2 F13
D4 H13
C11 + OPTO 15 F14
1A D5 H14 RELAY 7
C12 -
D6 OPTO 3 F15 H15
C13 5A +
N OPTO 16 F16 H16
D7
SENSITIVE - H17
OPTO 4 F17 RELAY 8
D8

64
+ H18
COMMON
1A D9 CONNECTION F18
C15 - G1
D10 OPTO 5 G2 RELAY 9
A C19 +
D11 COMMS G3
- RELAY 10
OPTO 6 NOTE 5. G4
D12
+ G5
D13 G6 RELAY 11
-
B OPTO 7 J17
C20 D14 - G7
+
SEE DRAWING G8 RELAY 12
D15 EIA485/
- KBUS 10Px4001. G9
OPTO 8 J18
D16 PORT + RELAY 13
+ G10
D17 J16 G11
SCN

Auto-reclose and Check Synchronizing (16 I/P & 16 O/P)


C C21 COMMON RELAY 14
D18 CONNECTION G12
G13
J1 *
- G14
AC OR DC RELAY 15
N C22 x AUX SUPPLY J2 G15
+
G16
J7 G17
+ RELAY 16
J8 G18
+
48V DC FIELD
VOLTAGE OUT - J9
NOTES 1.
2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY. J10
C.T. SHORTING LINKS - CASE
(a) 3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO ENSURE EARTH
CORRECT OPERATION OF THE PROTECTIVE RELAY.
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
4. OPTO INPUTS 1 AND 2 MUST BE USED FOR SETTING GROUP
(b) PIN TERMINAL (P.C.B. TYPE) CHANGES IF THIS OPTION IS SELECTED IN THE RELAY MENU.

5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.

P1607ENa

Figure 31: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with

P141/2/3/4/5 Software Version 46J


P2275ENa

Figure 32: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 20 O/P with 4 High Break
Contacts)
P14x Technical Data Sheet 65 P141/2/3/4/5 Software Version 46J
MiCOM P145 (PART) J11
WATCHDOG
DIRECTION OF FORWARD CURRENT FLOW J12 CONTACT
A J13
P2 P1 P2 P1 F1 WATCHDOG
X A J14 CONTACT
OPTO 9 F2
S2 S1 H1
X B
F3 H2 RELAY 1
X C C B OPTO 10 F4 H3
S2 S1 A B C PHASE ROTATION
H4 RELAY 2
MiCOM P145 (PART) F5
H5
C1 5A OPTO 11 F6 RELAY 3 ANY TRIP
N H6
NOTE 3.
A F7 H7

P14x Technical Data Sheet


n OPTO 12 H8 RELAY 4
A B C F8
1A H9
NOTE 2. C3 F9
H10 RELAY 5
C4 5A C23 a b c OPTO 13
N F10 H11
B H12 RELAY 6
V CHECK F11
n SYNC OPTO 14 H13
F12
1A C24 H14
C6 RELAY 7
F13 H15
a b c C7 5A
OPTO 15 F14 H16
C
F15 H17 RELAY 8
D1 - H18
1A OPTO 16 F16
C9 D2 OPTO 1
+ G1
C10 5A F17
D3 NOTE 4. G2 RELAY 9
- COMMON
N OPTO 2 CONNECTION F18 G3
D4
+ RELAY 10
G4
1A D5 -
C12 G5
D6 OPTO 3 RELAY 11
C13 5A + G6
N D7 G7
SENSITIVE - COMMS
OPTO 4 G8 RELAY 12
D8 + NOTE 5.
G9
1A

66
C15 D9 - RELAY 13
G10
D10 OPTO 5
A C19 + G11
D11 G12 RELAY 14
- J17
OPTO 6 - G13
D12 +
EIA485/ SEE DRAWING G14 RELAY 15
D13 - KBUS 10Px4001.
J18 G15
B C20 D14 OPTO 7 PORT +
+ G16
J16 G17
D15 - SCN RELAY 16
OPTO 8 G18
D16 +
E1
D17 RELAY 17
C C21 COMMON E2
D18 CONNECTION E3
J1 *
- E4 RELAY 18
AC OR DC

Auto-reclose and Check Synchronizing (16 I/P & 24 O/P)


x AUX SUPPLY J2 E5
N C22 +
E6 RELAY 19

+ J7 E7
E8 RELAY 20
J8
+
48V DC FIELD E9
VOLTAGE OUT - J9 RELAY 21
E10
- J10 E11
NOTES 1. E12 RELAY 22
2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY.
C.T. SHORTING LINKS E13
(a) 3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO E14
ENSURE CORRECT OPERATION OF THE PROTECTIVE RELAY. RELAY 23
CASE E15
4. OPTO INPUTS 1 AND 2 MUST BE USED FOR SETTING GROUP EARTH E16
(b) PIN TERMINAL (P.C.B. TYPE) CHANGES IF THIS OPTION IS SELECTED IN THE RELAY MENU. E17 RELAY 24
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001. E18

* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

P1611ENa

Figure 33: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with

P141/2/3/4/5 Software Version 46J


P2276ENa

Figure 34: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 24 O/P with 8 High Break
Contacts)
P14x Technical Data Sheet 67 P141/2/3/4/5 Software Version 46J
P2277ENa

Figure 35: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 28 O/P with 4 High Break
Contacts)
P14x Technical Data Sheet 68 P141/2/3/4/5 Software Version 46J
DIRECTION OF FORWARD CURRENT FLOW

P2 P1 P2 P1 A
X A
S2 S1
X B MiCOM P145 (PART)
X C
C B J11 E1
S2 S1 A B C WATCHDOG
PHASE ROTATION CONTACT J12 E2 RELAY 17
J13 E3
MiCOM P145 (PART) WATCHDOG
N CONTACT J14 E4 RELAY 18
C1 5A C23 H1 E5
A
n RELAY 1 H2 E6 RELAY 19
V CHECK
H3 E7

P14x Technical Data Sheet


A B C SYNC
1A C24 a b c RELAY 2 H4 E8 RELAY 20
NOTE 2. C3
H5 E9
C4 5A
N ANY TRIP RELAY 3 H6 E10 RELAY 21
B D1 NOTE 3.
- H7 E11
D2 OPTO 1 RELAY 4 RELAY 22
n + H8 E12
C6 1A D3 NOTE 4. H9 E13
-
C7 5A OPTO 2 RELAY 5 H10 E14
a b c D4 RELAY 23
+ H11 E15
C D5
- RELAY 6 H12 E16
D6 OPTO 3 H13 E17
1A + RELAY 24
C9 H14 E18
D7 RELAY 7
C10 5A -
D8 OPTO 4 H15
B1
N + H16
B2 RELAY 25
D9
- RELAY 8 H17 B3
1A D10 OPTO 5 H18
C12 + B4 RELAY 26
C13 5A D11 G1 B5
-
N D12 OPTO 6 RELAY 9 G2 B6 RELAY 27
SENSITIVE +
D13 G3 B7
- RELAY 10 G4 B8 RELAY 28
1A

69
C15 D14 OPTO 7
+ G5 B9
A C19 D15 RELAY 11 G6 B10 RELAY 29
-
D16 OPTO 8 G7 B11
+ RELAY 12 G8 B12 RELAY 30
D17
COMMON G9 B13
D18 CONNECTION RELAY 13 G10 B14
B RELAY 31
C20 G11 B15
F1
-
OPTO 9 RELAY 14 G12 B16
F2
+ G13 B17
F3 RELAY 32
- G14 B18
RELAY 15
F4 OPTO 10 G15
C C21 +
F5 G16
-
G17

Auto-reclose and Check Synchronizing (16 I/P & 32 O/P)


F6 OPTO 11 RELAY 16
+ G18 *
N C22 F7 J1 -
- AC OR DC
F8 OPTO 12 J2 x AUX SUPPLY
+
+
F9
- COMMS J7
NOTE 5. +
F10 OPTO 13
+ J8
2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED F11 +
48V DC FIELD
NOTES: - J9
AND ARE TYPICAL ONLY. J17 - VOLTAGE OUT
1. F12 OPTO 14 -
+ J10
3. THIS RELAY SHOULD BE ASSIGNED TO ANY F13 SEE DRAWING -
C.T. SHORTING LINKS EIA485/
(a) TRIP TO ENSURE CORRECT OPERATION OF - 10Px4001.
KBUS J18
THE PROTECTIVE RELAY. F14 OPTO 15 +
+ PORT
4. OPTO INPUTS 1 AND 2 MUST BE USED FOR F15 J16
(b) - SCN
PIN TERMINAL (P.C.B. TYPE) SETTING GROUP CHANGES IF THIS OPTION IS CASE
F16 OPTO 16 EARTH
SELECTED IN THE RELAY MENU. +
F17
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001. COMMON
F18 CONNECTION POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
*

P1614ENa

Figure 36: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with

P141/2/3/4/5 Software Version 46J


DIRECTION OF FORWARD CURRENT FLOW MiCOM P145 (PART)
F1
A
P2 P1 P2 P1 OPTO 9 F2
X A
S2 S1 F3 J11
X B WATCHDOG
OPTO 10 J12 CONTACT
F4
X C C B J13
S2 S1 A B C PHASE ROTATION F5 WATCHDOG
J14 CONTACT
OPTO 11 F6
MiCOM P145 (PART) H1
C1 5A H2 RELAY 1
N F7
OPTO 12 H3
A F8
H4 RELAY 2
A B C C2 n
F9

P14x Technical Data Sheet


H5
NOTE 2. C3 1A
OPTO 13 F10 H6 RELAY 3 ANY TRIP
C4 5A C23 a b c NOTE 3.
F11 H7
N
B H8 RELAY 4
OPTO 14 F12
V CHECK
C5 H9
n SYNC
1A C24 F13 H10 RELAY 5
C6
OPTO 15 F14 H11
a b c C7 5A
H12 RELAY 6
C F15
H13
C8 OPTO 16 F16
D1 H14 RELAY 7
1A -
C9 OPTO 1 F17 H15
D2 COMMON
+
C10 5A CONNECTION F18 H16
D3 NOTE 4.
- H17
N OPTO 2 E1 RELAY 8
D4 + H18
C11 OPTO 17 E2
1A D5 - G1
C12 E3
D6 OPTO 3 G2 RELAY 9
C13 5A + OPTO 18
N E4 G3
D7 -
SENSITIVE G4 RELAY 10
OPTO 4 E5
C14 D8
+ OPTO 19 G5
1A E6

70
C15 D9 G6 RELAY 11
-
OPTO 5 E7 G7
A C19 D10 + OPTO 20 E8 G8 RELAY 12
D11 -
E9 G9
D12 OPTO 6
+ G10 RELAY 13
OPTO 21 E10
D13 - G11
B C20 OPTO 7 E11 G12 RELAY 14
D14 + OPTO 22 E12 G13
D15 -
E13 G14 RELAY 15
D16 OPTO 8
+ OPTO 23 G15
E14
D17 G16
C C21 COMMON E15 G17 RELAY 16
D18 CONNECTION
OPTO 24 E16 G18

Auto-reclose and Check Synchronizing (24 I/P & 16 O/P)


E17
N C22 COMMON
CONNECTION E18 * J1
-
AC OR DC
J2 x AUX SUPPLY
+
COMMS
NOTE 5. J7
+
J8 +
48V DC FIELD
NOTES 1. J9
2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY. - J17 - VOLTAGE OUT
(a) C.T. SHORTING LINKS SEE DRAWING J10
3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO EIA485/ -
KBUS 10Px4001.
ENSURE CORRECT OPERATION OF THE PROTECTIVE RELAY.
PORT + J18
4. OPTO INPUTS 1 AND 2 MUST BE USED FOR SETTING GROUP J16 CASE
(b) PIN TERMINAL (P.C.B. TYPE) CHANGES IF THIS OPTION IS SELECTED IN THE RELAY MENU. SCN EARTH

5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.


* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

P1610ENa

Figure 37: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with

P141/2/3/4/5 Software Version 46J


P2278ENa

Figure 38: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 20 O/P with 4 High Break
Contacts)
P14x Technical Data Sheet 71 P141/2/3/4/5 Software Version 46J
DIRECTION OF FORWARD CURRENT FLOW
MiCOM P145 (PART) J11
A WATCHDOG
P2 P1 P2 P1 J12
X A CONTACT
S2 S1 J13
X B F9 WATCHDOG
J14 CONTACT
OPTO 13 F10
X C C B H1
S2 S1 A B C PHASE ROTATION F11 H2 RELAY 1

MiCOM P145 (PART) OPTO 14 F12 H3


H4 RELAY 2
C1 5A N F13
H5
A OPTO 15 F14 H6 RELAY 3 ANY TRIP
A B C n NOTE 3.
F15 H7
1A RELAY 4

P14x Technical Data Sheet


NOTE 2. C3 OPTO 16 H8
F16
C4 5A C23 a b c H9
N F17 RELAY 5
B COMMON H10
V CHECK CONNECTION F18 H11
n SYNC RELAY 6
1A C24 H12
C6
E1 H13
a b c C7 5A
OPTO 17 E2 H14 RELAY 7
C D1 H15
- E3
D2 OPTO 1 H16
1A + OPTO 18 E4
C9 NOTE 4.
H17 RELAY 8
D3 -
C10 5A E5 H18
D4 OPTO 2
+ OPTO 19 E6 G1
N
D5 - G2 RELAY 9
E7
D6 OPTO 3 G3
C12 1A + OPTO 20 E8 RELAY 10
D7 G4
C13 5A - E9
N OPTO 4 G5
D8 + OPTO 21 RELAY 11
SENSITIVE E10 G6
D9 - G7
E11
1A D10 OPTO 5 G8 RELAY 12
C15 + OPTO 22 E12
G9
A C19 D11

72
- E13 RELAY 13
OPTO 6 G10
D12 + OPTO 23 E14 G11
D13 G12 RELAY 14
-
OPTO 7 E15
D14 G13
+ OPTO 24 E16
B C20 G14 RELAY 15
D15 - E17 G15
D16 OPTO 8 COMMON
+ E18 G16
CONNECTION
D17 G17 RELAY 16
COMMON
D18 CONNECTION G18
C C21
COMMS B1
F1 NOTE 5. B2 RELAY 17
-
F2 OPTO 9 B3
N C22 + J17 RELAY 18
- B4

Auto-reclose and Check Synchronizing (24 I/P & 24 O/P)


F3
- SEE DRAWING B5
OPTO 10 EIA485/
F4 10Px4001. B6 RELAY 19
+ KBUS
J18
NOTES 1. F5 PORT + B7
-
C.T. SHORTING LINKS OPTO 11 J16 B8 RELAY 20
(a) F6 SCN
+
B9
F7 RELAY 21
- J1 * B10
F8 OPTO 12 -
+ AC OR DC B11
(b) PIN TERMINAL (P.C.B. TYPE) x AUX SUPPLY J2
+ B12 RELAY 22
B13
2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY. J7
+ B14 RELAY 23
CASE J8 B15
3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO EARTH +
ENSURE CORRECT OPERATION OF THE PROTECTIVE RELAY. 48V DC FIELD
J9 B16
VOLTAGE OUT -
4. OPTO INPUTS 1 AND 2 MUST BE USED FOR SETTING GROUP B17 RELAY 24
- J10
CHANGES IF THIS OPTION IS SELECTED IN THE RELAY MENU. B18

5. FOR COMMS OPTIONS SEE DRAWING 10Px4001.


* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

P1612ENa

Figure 39: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with

P141/2/3/4/5 Software Version 46J


DIRECTION OF FORWARD CURRENT FLOW

P2 P1 P2 P1 A
X A
S2 S1 E1 MiCOM P145 (PART)
X B
OPTO 17 E2
X C
C C B E3 J11
S2 S1 A B WATCHDOG
PHASE ROTATION OPTO 18 J12
E4 CONTACT
J13
MiCOM P145 (PART) E5 WATCHDOG
N J14 CONTACT
C1 5A C23 OPTO 19 E6 H1
A
n H2 RELAY 1
E7
V CHECK
A B C OPTO 20 H3

P14x Technical Data Sheet


SYNC E8
1A C24 a b c H4 RELAY 2
NOTE 2. C3
E9 H5
C4 5A
N OPTO 21 E10 H6 RELAY 3 ANY TRIP
B D1 NOTE 3.
- H7
E11
D2 OPTO 1 RELAY 4
n + OPTO 22 H8
1A E12
C6 D3 NOTE 4. H9
-
C7 5A OPTO 2 E13 H10 RELAY 5
a b c D4
+ OPTO 23 H11
C E14
D5
- H12 RELAY 6
OPTO 3 E15
D6 H13
1A + OPTO 24
C9 E16 H14
D7 RELAY 7
C10 5A -
OPTO 4 E17 H15
D8 COMMON
N + H16
CONNECTION E18
D9
- H17 RELAY 8
OPTO 5 B1
1A D10 H18
C12 + OPTO 25 B2
C13 5A D11 G1
-
N OPTO 6 B3 RELAY 9
D12 G2
SENSITIVE + OPTO 26 B4 G3
D13
- G4 RELAY 10
1A OPTO 7 B5
C15 D14

73
+ OPTO 27 G5
B6
A C19 D15 G6 RELAY 11
- B7
D16 OPTO 8 G7
+ OPTO 28 B8 G8 RELAY 12
D17
COMMON B9 G9
D18 CONNECTION G10 RELAY 13
OPTO 29 B10
B C20
F1 G11
- B11 G12 RELAY 14
F2 OPTO 9
+ OPTO 30 B12 G13
F3
- B13 G14
RELAY 15
F4 OPTO 10 G15
C C21 + OPTO 31 B14
F5 G16
-
B15 G17
F6 OPTO 11 RELAY 16

Auto-reclose and Check Synchronizing (32 I/P & 16 O/P)


+ OPTO 32 B16 G18
N C22 F7
-
B17
F8 OPTO 12 COMMON
+ B18 *
CONNECTION J1
F9 - AC OR DC
-
OPTO 13 J2 x AUX SUPPLY
F10 +
+
2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED F11 COMMS
NOTES: - NOTE 5. J7
AND ARE TYPICAL ONLY. +
F12 OPTO 14
1. + J8
3. THIS RELAY SHOULD BE ASSIGNED TO ANY +
F13 48V DC FIELD
(a) C.T. SHORTING LINKS TRIP TO ENSURE CORRECT OPERATION OF - J9
J17 - VOLTAGE OUT
F14 OPTO 15 -
THE PROTECTIVE RELAY.
+ SEE DRAWING J10
EIA485/ -
4. OPTO INPUTS 1 AND 2 MUST BE USED FOR F15 10Px4001.
- KBUS
(b) PIN TERMINAL (P.C.B. TYPE) SETTING GROUP CHANGES IF THIS OPTION IS J18
F16 OPTO 16 PORT +
SELECTED IN THE RELAY MENU. + CASE
J16 EARTH
F17
SCN
5. FOR COMMS OPTIONS SEE DRAWING 10Px4001. COMMON
F18 CONNECTION
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY

P1613ENa

Figure 40: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with

P141/2/3/4/5 Software Version 46J


Ordering Options
Information Required with Order

Relay Type (Feeder Management Relay) P141/2/3/4


Auxiliary Voltage Rating
24 - 48V dc only 1
48 - 125V dc (30 - 110V ac) 2
110 - 250V dc (100 - 240V ac) 3
Vn rating
100 - 120V ac 1
380 - 480V ac (Min. 196Vac, Max. 560Vac) 2
Hardware options
Nothing 1
IRIG-B modulated only 2
Fiber optic converter (ST) only (except IEC 61850) 3
IRIG-B (modulated) & fiber optic converter (ST) 4
(except IEC 61850)
Second rear Courier 7
Second rear Courier port + InterMiCOM E
Second rear Courier port + InterMiCOM + IRIG-B (modulated) F
IRIG-B (modulated) + second rear comms. 8
IRIG-B (de-modulated) C
Ethernet (100Mbps) 6
Ethernet (100Mbps) + IRIG-B (modulated) A
Ethernet (100Mbps) + IRIG-B (de-modulated) B
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports + G
Modulated IRIG-B
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports + H
Un-modulated IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports + Modulated J
IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports + K
Un-modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fiber ports + L
Modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + M
Un-Modulated IRIG-B
Product Specific
P141 P142/4 P143

No additional hardware A
4 inputs + 4 relays B
Additional 8 optos C
Additional 8 relays D
Additional 8 optos and 8 relays E
Additional 16 optos F
Additional 16 relays G
Additional 4 high break relays H
Additional 8 inputs + 4 high break relays J
Additional 8 relays + 4 high break relays K
Additional 8 high break relays L
32 inputs and 32 relays configuration (P143 only) M
8 inputs and 8 relays configuration (P141 only) N

Protocol Options
K-Bus/Courier 1
MODBUS 2
IEC 60870-5-103 3
DNP3.0 4
DNP3.0 over Ethernet + Courier over RS485 8
IEC 61850 + Courier over RS485 6
IEC 61850 + CS103 over RS485 7

Mounting

Panel Mounting M

P14x Technical Data Sheet 74 P141/2/3/4/5 Software Version 46J


Language
Multilingual - English, French, German, Spanish 0
Multilingual - English, French, German, Russian 5
Multilingual - English, French, Chinese C
Software Version

Unless specified the latest version will be delivered 4 6

Settings File
Default 0
Customer Specific 1
Hardware Suffix

Original J

P14x Technical Data Sheet 75 P141/2/3/4/5 Software Version 46J


Relay Type (Feeder Management Relay) P145
Auxiliary Voltage Rating
24 - 48V dc only 1
48 - 125V dc (30 - 110V ac) 2
110 - 250V dc (100 - 240V ac) 3
Vn rating
100 - 120V ac 1
380 - 480V ac (Min. 196Vac, Max. 560Vac) 2
Hardware options
Nothing 1
IRIG-B modulated only 2
Fiber optic converter (ST) only (except IEC 61850) 3
IRIG-B (modulated) & fiber optic converter (ST) 4
(except IEC 61850)
Second rear Courier 7
Second rear Courier port + InterMiCOM E
Second rear Courier port + InterMiCOM + IRIG-B (modulated) F
IRIG-B (modulated) + second rear comms. 8
IRIG-B (de-modulated) C
Ethernet (100Mbps) 6
Ethernet (100Mbps) + IRIG-B (modulated) A
Ethernet (100Mbps) + IRIG-B (de-modulated) B
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports + G
Modulated IRIG-B
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports + H
Un-modulated IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports + Modulated J
IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports + K
Un-Modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fiber ports + L
Modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fiber ports + M
Un-Modulated IRIG-B
Product Specific
Version with 16 output contacts & 16 digital inputs A
Version with 12 output contacts & 12 digital inputs B
Version with 16 output contacts & 24 digital inputs C
Version with 24 output contacts & 16 digital inputs D
Version with 24 output contacts & 24 digital inputs E
Version with 16 output contacts & 32 digital inputs F
Version with 32 output contacts & 16 digital inputs G
Additional 4 high break relays H
Additional 8 inputs + 4 high break relays J
Additional 8 relays + 4 high break relays K
Additional 8 high break relays L
Protocol Options
K-Bus/Courier 1
MODBUS 2
IEC 60870-5-103 3
DNP3.0 4
DNP3.0 over Ethernet + Courier over RS485 8
IEC 61850 + Courier over RS485 6
IEC 61850 + CS103 over RS485 7
Mounting

Panel Mounting M

Language
Multilingual - English, French, German, Spanish 0
Multilingual - English, French, German, Russian 5
Multilingual - English, French, Chinese C
Software Version

Unless specified the latest version will be delivered 4 6

P14x Technical Data Sheet 76 P141/2/3/4/5 Software Version 46J


Settings File
Default 0
Customer Specific 1
Hardware Suffix

Original J

P14x Technical Data Sheet 77 P141/2/3/4/5 Software Version 46J


PXXX
Product Description

Alstom Grid

- ALSTOM 2011. ALSTOM, the ALSTOM


logo and any alternative version thereof are
trademarks and service marks of ALSTOM.
The other names mentioned, registered or
not, are the property of their respective
companies. The technical and other data
contained in this document is provided for
information only. Neither ALSTOM, its officers
or employees accept responsibility for, or
should be taken as making any representation
or warranty (whether express or implied), as
to the accuracy or completeness of such data
or the achievement of any projected
performance criteria where these are
indicated. ALSTOM reserves the right to
revise or change this data at any time without
further notice.