The characteristic curve of an equal percentage valve shifts towards linear as the Distortion
Coefficient (Dc) drops. This drop also reduces the rangeabillity of the valve.
Similarly, under these same conditions, the characteristics of a linear valve would shift towards quick
opening (QO, not shown in Figure 2). In addition, as the Dc coefficient drops, the controllable
minimum flow increases, and therefore the rangeability of the valve also drops.
Rangeability
The conventional definition of rangeability is the ratio between the maximum and minimum
controllable flows through the valve. Minimum controllable flow (Fmin) is not the leakage flow
(which occurs when the valve is closed), but the minimum flow that is still controllable, and can be
changed up or down as the valve is throttled.
Using this definition, manufacturers usually claim a 50:1 rangeability for equal-percentage valves,
33:1 for linear valves, and about 20:1 for quick-opening valves. These claims suggest that the flow
through these valves can be controlled down to 2%, 3%, and 5% of maximum. However, these
figures are often exaggerated. In addition, as can be seen in Figure 2, the minimum controllable flow
(Fmin) rises as the distortion coefficient (Dc) drops. Therefore, at a Dc of 0.1, the 50:1 rangeability of
an equal-percentage valve drops to about 10:1.
Consequently, the rangeability should be defined as the flow range over which the actual installed
valve gain stays within 25% of the theoretical (inherent) valve gain (in the units of GPM per %
stroke). To illustrate the importance of this limitation, Figure 3 shows the actual gain of an equal
percentage valve starts to deviate from its theoretical gain by more than 25%, when the flow reaches
about 65%.
Therefore, in determining the rangeability of such a valve, the maximum allowable flow should be
65%. Actually, if one uses this definition, the rangeability of an =% valve is seldom more than 10:1.
In such cases, the rangeability of a linear valve can be greater than that of an =% valve. Also, the
rangeability of some rotary valves can be higher because their clearance flow tends to be lower, and
their body losses near the wide open position also tend to be lower than those of other valve
designs.
To stay within 25% of the theoretical valves gain, the maximum flow should not exceed 60% of
maximum in a linear valve or 70% in an =% valve. In terms of valve lift, these flow limits correspond
to 85% of maximum lift for =% and 70% for linear valves.