Split Air Conditioner

Thank
you for choosing our
product. .

For proper operation, please


,
read
and keep this manual
carefully.

If you have lost the Owners Manual, please contact the local agent
. , or
visit
,
www.gree.com or sent email to global@gree.com.cn for electronic version.
www.gree.com e-mail
global@gree.com.mk .
GWH09TA-S3DNA1D
GWH09TA-S3DNA2D
GWH09TB-S3DNA1D
GWH12TB-S3DNA1D
GWH12TB-S3DBA3E
GWH12TB-S3DBA1E
GWH18TC-S3DBA1E
GWH18TC-S3DNA1D
GWH18TC-S3DBA3E
GWH24TD-S3DNA1D
GWH24TD-S3DBA3E
GWH24TD-S3DBA1E
Content

Operation Notices

Precautions............................................................................................................ 1

Parts
Name............................................................................................................
6
Screen Operation Guide

Buttons on remote
controller..................................................................................
7
Introduction for icons
on display
screen.................................................................
7
Introduction for
buttons on remote
controller.........................................................
8
Introduction for special
function............................................................................13

Operation guide...................................................................................................
15
Replacement
of batteries
in remote controller......................................................
15
Emergency
operation
.......................................................................................... 16
Maintenance

Clean and Maintenance........................................................................................16



Malfunction

Malfunction
analysis
............................................................................................ 19
Installation
Notice

Installation
dimension diagram ............................................................................
23
Tools
for
installation
............................................................................................. 24
Selection of installation
location .......................................................................... 24

Requirements
for electric
connection .................................................................. 25

Installation

Installation ofindoor
unit......................................................................................
26
Installation
ofoutdoor unit ...................................................................................
31
Vacuum pumping................................................................................................. 34

Leakage detection
............................................................................................... 34

Check after
installation ........................................................................................ 35

Testand
operation

Test operation
.......................................... ............................................................35
Install snow guard
(Optional)
...............................................................................36

Attachment

Configuration of
connection
pipe ......................................................................... 37
Pipe expanding
method
.......................................................................................
39
Wired
Controller ()
(Optional).................................................................................. 40
This
appliance isnot intended
for
use(
by persons (including
) children)
with reduced physical,
sensory
or mental capabilities,
, or
lack of experience
and knowledge,
unless they have been
given
supervision

or instructionconcerning
.use of the
appliance by a person
responsible
for
their safety.

Children
should be supervised to ensure that they do not play with the appliance.
.
This marking
indicates
that
this product
should
not be
disposed
withother household
wastes

throughout the EU.
To
.prevent
possible harm
to the
environment
or human health
from
un-
controlled waste
disposal,
recycle it responsibly
to promote
, the sustainable
reuse of mate-

rial resources.
To return
your used device,
. please use
the return
and collection
systems or

contact the
retailer where
the product was
purchased. They can take this product for envi-
.
ronmental safe recycling.
R410A(R32/125: 50/50): 2087.5
Explanation of Symbols

Indicates a hazardous situation that, if not avoided, will


DANGER result in death or serious injury.

Indicates a hazardous situation that, if not avoided, could


WARNING result in death or serious injury.

Indicates a hazardous situation that, if not avoided, may


CAUTION result in minor or moderate injury.
Indicates important but not hazard-related information,
NOTICE used to indicate risk of property damage.

Indicates a hazard that would be assigned a signal word


WARNING or CAUTION.
Precautions

WARNING

Operation and Maintenance


This appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe
way and understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by
children without supervision.
Do not connect air conditioner to multi-purpose socket.
Otherwise, it may cause fire hazard.
Do disconnect power supply when cleaning air
conditioner. Otherwise, it may cause electric shock. .
If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Do not wash the air conditioner with water to avoid
electric shock.
Do not spray water on indoor unit. It may cause electric
shock or malfunction.
After removing the filter, do not touch fins to avoid injury.
Do not use fire or hair dryer to dry the filter to avoid
deformation or fire hazard.

1
Precautions

WARNING

Maintenance must be performed by qualified


professionals. Otherwise, it may cause personal injury
or damage.
Do not repair air conditioner by yourself. It may cause
electric shock or damage. Please contact dealer when
you need to repair air conditioner.
Do not extend fingers or objects into air inlet or air
outlet. It may cause personal injury or damage.
Do not block air outlet or air inlet. It may cause
malfunction.
Do not spill water on the remote controller, otherwise the
remote controller may be broken.
When below phenomenon occurs, please turn off air
conditioner and disconnect power immediately, and then
contact the dealer or qualified professionals for service.
Power cord is overheating or damaged.
Theres abnormal sound during operation.
Circuit break trips off frequently.
Air conditioner gives off burning smell.
Indoor unit is leaking.

If the air conditioner operates under abnormal conditions,


it may cause malfunction, electric shock or fire hazard.
When turning on or turning off the unit by emergency
operation switch, please press this switch with an insulating
object other than metal.
Do not step on top panel of outdoor unit, or put heavy
objects. It may cause damage or personal injury.

2
Precautions

WARNING

Attachment
Installation must be performed by qualified professionals.
Otherwise, it may cause personal injury or damage.
Must follow the electric safety regulations when installing
the unit.
According to the local safety regulations, use qualified
power supply circuit and circuit break.
Do install the circuit break. If not, it may cause malfunction.
An all-pole disconnection switch having a contact separation
of at least 3mm in all poles should be connected in fixed
wiring.
Including an circuit break with suitable capacity, please
note the following table. Air switch should be included
magnet buckle and heating buckle function, it can protect
the circuit-short and overload.
Air Conditioner should be properly grounded. Incorrect
grounding may cause electric shock.
Don't use unqualified power cord.
Make sure the power supply matches with the
requirement of air conditioner. Unstable power supply or
incorrect wiring or malfunction. Please install proper power
supply cables before using the air conditioner.
Properly connect the live wire, neutral wire and
grounding wire of power socket.
Be sure to cut off the power supply before proceeding
any work related to electricity and safety.

3
Precautions

WARNING

Do not put through the power before finishing installation.


If the supply cord is damaged, it must be replaced by
the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper
tube.
The appliance shall be installed in accordance with
national wiring regulations.
Installation must be performed in accordance with the
requirement of NEC and CEC by authorized personnel
only
The air conditioner is the first class electric appliance. It
must be properly grounding with specialized grounding
device by a professional. Please make sure it is always
grounded effectively, otherwise it may cause electric shock.
The yellow-green wire in air conditioner is grounding
wire, which can't be used for other purposes.
The grounding resistance should comply with national
electric safety regulations.
The appliance must be positioned so that the plug is
accessible.
All wires of indoor unit and outdoor unit should be
connected by a professional.
If the length of power connection wire is insufficient, please
contact the supplier for a new one. Avoid extending the
wire by yourself.

4
Precautions

WARNING

For the air conditioner with plug, the plug should be


reachable after finishing installation.
For the air conditioner without plug, an circuit break
must be installed in the line.
If you need to relocate the air conditioner to another
place, only the qualified person can perform the work.
Otherwise, it may cause personal injury or damage.
Select a location which is out of reach for children and
far away from animals or plants.If it is unavoidable,
please add the fence for safety purpose.
The indoor unit should be installed close to the wall.
Instructions for installation and use of this product are
provided by the manufacturer.

Working temperature range

Indoor side
DB/WB( ) Outdoor side DB/WB( )

Maximum cooling
32/23 43/26
Maximum heating
27/- 24/18

NOTICE:
:
The operating temperature
range
(outdoor temperature)
( for cooling
) only unit
is
-15
-15 ~
4343 ; for
; heat pump unit is -20
~ 43 . -20 43 .

5
Parts Name
Indoor Unit
air inlet

aux.button

horizontal louver
air outlet

cooling power receiver


indicator indicator window
display

heating temp. drying


indicator indicator indicator

(Display content or position may be different from above remote controller


graphics, please refer to actual products)

Outdoor Unit
air inlet

handle

air outlet

NOTICE:
Actual product may be different from above graphics, please refer to actual
products.

6
Buttons on remote controller
1 ON/OFF button
2 FAN button
3 MODE button
4 +/- button
5 TURBO button
2
2 6 button
5 6
4 7 button
4 11
7
3
3 9
8 8 CLOCK button
10 12
1 13 1 9 TIMER ON/
14 16
15 TIMER OFF button
10 TEMP button
11 / button
(before opening cover (after opening cover
12 I FEEL button
1 ON/OFF button 13 LIGHT button
2 FAN button 14 X-FAN button
3 MODE button 15 QUIET button
4 +/- button 16 SLEEP button

Introduction for icons


on display
screen

I feel Set fan speed



Quiet
Turbo mode
Turbo
Send signal

Operation mode
Healthy mode

Auto mode
Scavenging functions

8
heating function

Cool mode
Set temperature

Dry mode
This
is a general
remote
controller.
. Some

models have
this
function while
some do
.
Fan mode
not. Please refer to the actual models.
.

Heat mode
X-FAN function

Set time

TIMER ON /TIMER OFF
/
Clock

Sleep mode
Child lock

Up & down
swing

Light

Left & right
swing

Temp.
display type

:
Set temp. . : Indoor ambient
temp.
.
:
Outdoor ambient temp.
.

7
Introduction
for buttons
on remote
controller

Note:
:
This
is
a general use remote
controller,
it
could
be used for
the air conditioners

with multifunction; For
some.function,
which
the
model
don't have,
if press the

corresponding button onthe
remotecontroller
that the unit will
keep.
the original
running status.
After putting through
the power,
, the air
conditioner will give out a sound.
.
Operation
indictor
" "is
ON (red indicator).
( ).After that,
, you can operate
the air
conditioner
by using
remote
controller.
.
Under on status,
pressing
, the button
on
the remote controller,
the signal
, icon " "

on the display
of remote
controllerwill blink
once and the
air conditioner
will
""give
,
.
out a de sound, which means the signal has been sent to the air conditioner.

Under off status,
set temperature
, and clock icon
will be
displayedon
the display

of remote controller (If timer on, timer off and light functions are set,
( , / the corre-
,
);
sponding icons
will
be displayed on the display of remote controller at the same
.
time); Under on status, the display will show the corresponding set function icons.
1 ON/OFFbutton
/ (on/off button)
Press this button,
the
unit
will be turned
on, press
, it once more,
the unit will
, be turn-

. .
ed off. Sleep function will be canceled, while unit off.
2 FAN button
(fan button)
Press
this button,
Auto,
Low,
Medium-low, Medium, Medium-high,
, High
, -, speed can
be circularly selected. After powered on, Auto fan speed is default. Under DRY
-, .
.
mode, Low
.
fan speed only can be set up.
ATUO Low fan Medium-low fan Medium fan :
Note: Its Low fan speed
.
Medium-high fan High fan under Dry mode.
3 MODE button
(mode button)
Press
this button,
Auto,
Cool,
Dry,
Fan, Heat
mode
can be
selected circularly. Auto
.
. .
mode is default while power on. Under Auto mode, the temperature will not be dis-
28 . 25.
played; Under Heat mode, the initial value is 28(82); Under other modes, the
initial value is 25(77). AUTO COOL DRY

FAN HEAT
( .
(only for cooling and heating unit. As for cooling only unit, it wont have any action
,
when it receives the signal of heating operation.)
).

4 +/- button
+/- (+/- button)
Presetting temperature
can be increased.
Press this button,
. the temperature
can be

set up, continuously
press
this
button
and hold
, fortwo
seconds,
the relative
contents

can quickly
change, until unhold
this button
and send
. the order
that the () signal

, .
will be displayed
16-30,all the
time. The temperature
61-86. adjustment is unavailable under the
Auto mode, but the order can be sent if pressing this button. Temperature of Celsius
degree setting: 16-30; for Fahrenheit degree setting: 61-86.
8
Introduction
for buttons
on remote
controller

Presetting temperature
can be decreased.
Press
this button,
. the temperature
can

be
set up,
continuously
press this
button
and
, holdfor
two seconds,
the relative co-

.
ntents
can quicklychange,
, until
unhold
this button and send the order that the
.
() signal will be displayed all the time. The temperature adjustment is unavailable
under the Auto mode, but the order can be sent by if pressing this button.

5 TURBO
button (turbo button)
Under
Cool or Heat
mode,
press this button
can
turn onor/
turn off the Turbo function.

After the Turbo function turned on, the signal of Turbo will display. The signalwill
. , .
.
be automatically cancelled if changing the mode or fan speed.
6 button

Press this
button to set
left&
right swing angle
cycling
as below:

:.

OFF

7 button

Press this
button to set
swing
angle,
which
circularly changes
as below: .

OFF
This
remote controller
is.
universal. If
it receives threes
kinds of
following
status, the

swing
angle
will remain original.
.

If guide
louveris
stopped when it is swinging
up
and down,
it will remian
- , its
present

position.
.

indicates
guide louver swings back and forth in the five places, as shown in the figure.

8 CLOCK button
(clock button)
Press
this button,
the clock
canbeset
up, signal
,blink and display.
Within5 .
seconds, 5
+ - 2
the value can be adjusted by pressing + or - button, if continuously press this
, . ,
button for 2
seconds above, in every 0.5 seconds, the value on ten
. place ofMinutewill be increased
1.
During blinking,
repress
. theClock button
or Confirm
, 12:00button, signal
will be
constantly

displayed
and it denotes
the setting
. succeeded.
After
poweredon, 12:00is
defaulted
to
.
display and signal will be displayed. If there is signal be displayed that denotes
the current time value is Clock value, otherwise is Timer value.
9 TIMER ON/TIMER
OFF button
/ (timer on/off button)
Timer On setting:
Sign al
ON will blink
: and display,
signal
will
ON,conceal,
the num-

erical
section will become
the timer on
setting
status. During
5 seconds
blink, by
.
pressing + or
- button to adjust the
+time
-value of numerical
section,
every press
of
.
+ - , .
that button, the value will be increased or decreased 1 minute. Hold pressing + or -
9
Introduction
for
buttons
on remote
controller
button,
2 seconds
later,
it quickly
change,
the way
2 of change
is: During
the
. initial
2.5 seconds,
ten numbers
change inthe
, one place
TIMERof
minute, then the one
place

is constant, ten numbers change in the tens place of minu te at 2.5 seconds speed
.
.
and carry. During 5s blink, press the Timer button, the timer setting succeeds. The
.
Timer On has been set up, repress the timer button, the Timer On will be canceled.
Before sett ing the Timer, please adjust the Clock to the current actual time.
,
One press
TIMERthis
OFFkey to enter
- into TIMER
. OFF setup, in which
case
the TIMER OFF

icon will
. blink. The method of setting is the sameas for TIMER ON.

10 TEMP button
(temp button)
Press this button,
you can
see indoor
set temperature,
indoor ambient
temperature
,
or outdoor ambient temperature on indoor units display. The setting on remote co-
.
ntroller is selected circularly as below:
:
no display

When selecting
" " with remote
controller
or no display, temperature
indicator on
,
indoor unit
displays
set
temperature; When
selecting.
" " with remote controller,
temperature
indicatoron indoor unit,
displays
indoor ambient temperature;
When

selecting " " with
remote controller,
temperature
. indicator on indoor
unit displays

outdoor ambient
, temperature.
3s
later it will return
to the setting
temprature
or .
it
depends
3 onthe
other received
signal
within 3s.
.
Attention:
: When displaying
the outdoor
ambient,
the displaying
, range is
0-60

When
0-60 it goes
C. beyond
the
range,
it keeps
the threshold
data (the
smallest0
(
- 0 , 60 .
and the largest 60).
Warm tips: When
: operating buttons
on the
cover please
make
sure
the cover
is
.
closed completely.
11 / button

Press this
button to achieve
the on and
off of healthy
and
scavenging
functions in
,
operation status.
Press
. this button
for the
first time
to start scavenging
function;

LCD displays
" " . Press
the button
for
the second
time to start
healthy
and sc-
avenging functions simultaneously; LCD displays " " and " ". Press this button
,

for the thirdtime


to quit
healthy
and scavenging
functions simultaneously.
. Press
the

button for the fourth time to start healthy function; LCD display " " . Press this bu-
,
.
tton again to repeat the operation above.
NOTE: This function is applicable to partial of models.
12 I FEEL button

Press thisbutton
once,
toturn
on the
I FEEL
I FELL function,
, then Ithe
figure
FELL of "I FEEL"

will
be displayed,
after every
, press of otherfunction
button,
every200ms to send
200
I FELL ;
I FEEL once, after this function started, the remote controller will send temperature
10 .
to the main
I FELLun it in every 10 minutes. When repress this button, this function will be
.
turned off.
10
Introduction
for buttons
on remote
controller
13 LIGHT
button
( light button)
Press
this button
at
unit
On
or Off status, Light
On and LightOff
. can be set
up.
After powered on, Light On is defaulted.
.

14 X-FAN button
X - FAN (X-FAN button)
Pressing X-FAN
button
"X-FAN" in
COOL or DRY
mode, the
icon
is displayed and the
" "
indoor fan
, will continue
operation
for 2 minutes in order
to dry2 the
indoor
unit even

. "X-FAN"
though you have turned off the unit. After energization, X-FAN OFF is defaulted.
. X-FAN ,
X-FAN
is
not available in AUTO,
FAN or HEAT mode.
.
15 QUIET button
(quiet button)
Press
this button, the
Quiet status
is,
under(the Auto Quiet mode
(display
Avto "
); "
and "Auto" signal) and Quiet mode (display " " singal) and Quiet OFF (there
( ) ( .
is no
signal of "
" displayed), after
powered on, the
QuietOFF is defaulted.
.

Under the Quiet mode (Display " " signal).


The Quiet function is only available for some models.

16 SLEEP button
(sleep button)
Press
this button,
, can select
Sleep 11 ( ), Sleep
22( ), Sleep
33( )
and
cancel
the
Sleep, circulate
.between these, after
electrified,
Sleep Cancel
, is de-

faulted. .

Sleep
1is Sleep
mode 1,
1 - in Cool, Dehumidify
modes: sleep
status
: after run
for,

1 ,
one hour, the main unit setting temperature will increase 1, 2 hours, setting te-
2 , ;
mperature
increased 2, the unit
, will run atthis
setting
temperature; In Heat
mode:
1 ,
sleep status
after run
forone hour,
the setting
2 , temperature
will decrease
1, 2

hours, setting temperature will decrease 2, then the unit will run at this setting
.
temperature.
Sleep
2 is sleep
mode 2, that
2 - is airconditioner
will
run according to the
presetting
a
group of sleeptemperature
. curve.
In
Cool
mode:
:
(1) When setting
the initial
temperature 16-23,
16-23 ,after turned on Sleep
function,

1 ,
the temperature will be increased 1 in every hour, after 3 the temperature
, 7 1 ,
will be
maintained, after 7hours, the temperature will be decreased 1, after
.
that the unit will keep on running under this temperature;
(2)
When setting
the initial
temperature 24-27,
24-27 , after turned on
Sleep function,

1 ,
the temperature will be increased 1 in every hour, after 2 the temperature
, 7 1 ,
will be
maintained, after 7hours, the temperature will be decreased 1, after
.
that the unit will keep on running under this temperature;
(3)
When setting
the initial
temperature 28-29,
28-29 , after turned on
Sleep function,

1 ,
the temperature will be increased 1 in every hour, after 1 the temperature
, 7 1 ,
will be
maintained, after 7hours, the temperature will be decreased 1, after
.
that the unit will keep on running under this temperature;
11
Introduction
for buttons
on remote
controller

(4)
When setting
the initial
temperature
3030, under
, this
7 temperature setting, after

7hours,
1 ,thetemperature
will be decreased
1, after that the unit will keep on
.
running under this temperature;
In Heat
mode:
:
(1) Under the initial
presetting
temperature
16,
16 , it will run
under
thissetting tem-

.
perature all along.
(2)
Under the initial
presetting
temperature17-20,
after Sleep
17-20 , function started

1 , 1
up, the temperature will decrease 1 in every hour, after 1 decreased, this
.
temperature will be maintained.
(3)
Under the initial
presetting
temperature
21-27,
21-27 , after Sleep
function started

1 , 2
up, the temperature will decrease 1 in every hour, after 2 decreased, this
.
temperature will be maintained.
(4) Under the initial
presetting
temperature
28-30,
28-30 , after Sleep
function started

up, the temperature will decrease 1 in every hour, after 3 decreased, this
1 , 3
.
temperature will be maintained.
Sleep
3 -
the sleep curve setting under
3 - Sleepmode
by DIY:

(1) Under
Sleep
3 mode,
,press "Turbo" button
for
a
long time, remote
,controller en-

ters into user
individuation
sleep settingstatus,
at this
time,
thetime of remote
,
,
controller will display "1hour", the setting temperature "88" will display the corr-

esponding
( temperature
of last setting
sleep curve
and
blink (The first);
entering
will display according to the initial curve setting value of original factory);
(2) Adjust "+" and
+ "-" button,
- could change the
corresponding
setting temperature,

after adjusted, press "Trubo" button for confirmation;
;
(3) At this
, time, 1hour
will beautomatically
increased
at the timer
postion
on the(
1
"remote controller, (that are "2hours" or "3hours" or "8hours"), the place of se-
2 " "3" "8 "),
.
tting temperature "88" will display the corresponding temperature of last setting
sleep curve and blink;
(4)
Repeat the above
step (2)~(3)(2)
operation,
(3), until
8hours
temperature
setting
finished,
8 , ;
sleep curve setting finished, at this time, the remote controller will resume the
.
original timer display; temperature display will resume to original setting tem-
perature.
Sleep3- the
sleep
curve setting under
3 - Sleep
mode
by
DIY
could be inquired:

:
The user could accord to sleep curve setting method to inquire the presetting sleep

curve,
enter intouser
, individuation
sleep setting
status, but
do not change
, thetem-

perature, press,
"Turbo" button directly
for
confirmation.
, .
Note: In theabove
: presetting
or enquiry
procedure,
if continuously
within10s,
there
is no button
, pressed,
the sleep
10 curve setting
status
will
be automatically quit

.
on/off mode timer sleep pr-
and resume to display the original displaying. In the presetting or enquiry
ocedure, press "ON/OFF" button, "Mode" button, "Timer" button or "Sleep"
.
button, the sleep curve setting or enquiry status will quit similarly.
12
Introduction
for special
function

AboutX-FAN
X-FAN function

This
function indicates
that moisture
on evaporator
of indoor
unit will be
blowed
after

the unit is stopped to avoid mould.
.
1.
Having set X-FAN
X-FANfunction on: After
: turning offthe
unit
by
pressing ON/OFF
ON/OFFbutton

2 .
indoor fan will continue running for about 2 min. at low speed. In this period, press
X-FAN .
X-FAN button to stop indoor fan directly.
2.
Having set X-FAN
X-FNfunction off: After
: turning offthe
unit
by
pressing ON/OFF
ON/OFFbutton,

the complete
unit
will be off
directly.
.

About
AUTO AUTO
RUN RUN

When
AUTO
AUTO RUNRUN modeis,
selected, the setting
temperature
will
not
be displayed
on
LCD
the LCD,
, the unit
will
be in
accordance
with the
room temp.automatically
to select
the

.
suitable running method and to make ambient comfortable.

About
TURBO turbo function
If
start this function,
the unit will
, run at
super-high fan speed
to
cool or heat quickly
so
that
the
ambient
temp. approachs
the preset temp.
as soon
as possible.
.

About
LOCK lock

Press + and
+- buttons simultaneously
- to
lock or unlock
the
keyboard. If the remote
. co-
ntroller is locked,
the icon
, will
bedisplayed
, on it, in which
case, press
any
button,

3 . .
the mark will flicker for three times. If the keyboard is unlocked, the mark will disappear.
About swing up and down

1.
Press swing up and down
button continuously
morethan
2s, the
2 m ain unit will
swing

backand
forth from
up to down , and
- , then
loosen
the,
button,
the unit will stop swing

.
and present position of guide louver will be kept immediately.
2. Under swing
up and
, down mode,when
the
status is switched
from
, off to
, if press
this
button again 2s
later,
2 . status will
, switchtooff
status.
directly;
If press this button
2
,
again within
2s, the change
. of swing status will also depend on the circulation seque-
nce stated above.
About swing left and right

1. Press swing
left and right
button continuously
more
than 2s, themain
2 unit willswing

back and
forth from
left to right,
- , and
then loosen the
button,
, the unit will
stop swing

.
and present position of guide louver will be kept immediately.
2. Under swing
left and
, right mode,when
the status is switched
from
off to
,
if press
this button
again
2 2s later, status
will switch
to
off;
status directly;
if press
this button

again within
2s,,
the change
of swing status will
also depend
on the
circulation
sequ-
.
ence stated above.

13
Introduction
for special
function
About switch
between
Fahrenheit
and
Centigrade

Under
status ofunit
off, press
, MODE and
- buttons
MODE simultaneously
- to switch
and
.F.
C

Combination of "TEMP"
TEMPand "CLOCK"
CLOCK buttons:
:

About Energy - saving Function
Press
TEMP
and CLOCK
simultaneously
in COOL
TEMP CLOCK mode to start
energy-saving
fun-

ction. Nixie tube on the remote controller displays SE. Repeat the operation to
. quit

the
SE. function. .
Combination of "TEMP"
TEMPand "CLOCK"
CLOCK buttons:

About 8 Heating Function
8C

Press
TEMP
and CLOCK
, simultaneously
"TEMP" in HEAT mode
"CLOCK" to start 8
Heating Function

Nixie tube
8on the remotecontroller
. displays and
a selected
temperature
of 8.
8 C. .
(46 if Fahrenheit is adopted). Repeat the operation to quit the function.
About Quiet function
Quiet

When
quiet function
is selected:
:
1. Under
1. cooling
mode: indoor
: fan operates
at notch 4 speed.
10
minuteslater or when
4 . 10
indoor
ambient
temperature28,
indoor
fan will operateat
notch 2 speed
or
28quiet
,
2
mode according to the comparison between indoor ambinet temperature and set tem-
.
perature.
2. : 3
2.
heating
Under mode: indoor fan operates
at notch 3 speed
or quiet .
mode according
to the
3. comparison
,between indoor ambient
: temperature
and set temperature.

3. Under dry, fan mode: indoor fan operates at quiet mode.
.
4.
4. Under auto mode:
the
: indoor fan operates at the auto
quiet mode according
to actual

cooling,
heating
orfan,
mode. .
About Sleep function
Sleep
Under
theFan
and Auto mode,
the Sleep,
function
cannot beset up, under
Dehumidify

mode, only Sleep 1 can be selected. Select and enter into any kind of Sleep mode,
, Sleep 1. the

,
Quiet function will be attached and stared, different Quiet status could be optional and
.
turned off.
WIFI Function

Press "MODE"
MODEand "TURBO"
TURBO button
simultaneously
to
turn on wi-fi
or turn off WIFI
.
function. When
wi-fi WIFI
function
is turned
WI-FI on, the " .
" iconwill
be displayed
10on
.
TURBO MODE . Wi-fi
remote controller; Long press "MODE" and "TURBO" buttons simultaneously
. (
for
10s, remote
) controller will send WIFI reset code and then the WIFI function will be
turned on. WIFI function is defaulted ON after energization of the remote controller.
(This function only applicable for some models. )
14
Operation guide

General operation
4

1. After
1. poweredon,
press ON/OFF
button,
, the unitwill
start
"ON/OFF"
3
to run.
(Note:When
it is
powered on, the guide
(: louver of
, 5
).
main unit will close automatically.) 2
2. "MODE" .
2. Press MODE button, select desired running mode.
3. + -
3. Pressing
(+AUTO
or - button,
toset the desired
temperature (It is
).
1

unnecessary
4. to set
FAN the
temp.
at AUTO mode.)

4. Pressing FAN
, button, set fan
: speed, can
, select AUTO
-, -FAN,
LOW, MEDIUM-LOW, MEDIUM, MEDIUM-HIGH and HIGH.
.
5. .
5. Pressing and button, to select the swing.
Optional operation

4
1.
Press SLEEP button,
SLEEP to setsleep.
, .
2. Press TIMER ON and TIMER OFF
TIMER ON TIMERbutton,
OFF, can
set the

2
.
scheduled timer on or timer off.
3.
Press LIGHT button,
to control
LIGHT the onand
off of the

3 1

displaying part of the unit (This function may be not
( )
available for some units).
4.
Press TURBO button,
can ,
TURBO realize
theON and OFF
of
.
TURBO function.
Replacement of batteries
in remote
controller

1. Press the
1. back side
of remote controller
marked battery
reinstall
the cover
of battery
box along
the arrowdirection.

2. Replace two
7# (AAA 1.5V) dry batteries, and
. remove
2. make sure
the
position of
1.5 V "+" polar and "-" polar

are
correct. + - .
3. Reinstall
3. the cover of
battery
box.
. Cover of battery box

NOTICE

During
operation, point theremote
, control
signal
sender at the
receiving

window
on
indoor unit.
.

The distance between
signalsender
and receiving
windowshould be
no
more than
8 8m,
and
there should
be no obstacles
. between them.
Signal
may
beinterfered
easily in the
room where
there is fluorescent
lamp
or wireless
telephone;
; remote
controller should
be
close to indoor unit during

operation.
.
Replace
new batteries
of the
same model
, when replacement is required.
.
When
you dont use
remote controller
for a long,
time,please
take out the

batteries.
.
If
the displayon
remote controller is fuzzy
or
theres no display,
, please

replace
batteries.
.

15
Emergency operation

If remote
controller is
lost or damaged,
please use auxiliary
, button
to turn


on or turn conditioner.
off the air
The
operation in
details.
are as
below:
( ). ,
.
air conditioner. When the air conditioner is turned on, it will operate under
AUTO .
auto mode.
panel


aux. button

WARNING:Use
:insulated
object

to press
theauto button .

Clean and
Maintenance

WARNING


Turn off the
air conditioner
and
disconnect
the power
before cleaning
the
air

conditioner to avoid electric shock.
.

Do not
wash
the air conditioner
with water
to avoid
electric shock.
.

Do not use volatile


liquid
to clean
theair
conditioner.
.

Clean surface of indoor unit


When the surfaceof


indoor unit
is dirty, it is recommended
, to use
a soft dry cloth

or wet
cloth to
wipe it. .

NOTICE:
:
Do not remove
the panel
when cleaning it.
.

16
Clean and
Maintenance

Open panel

1 Pull out the
panel
to
a certain

3 Use dust
catcher
or water
to
.
. ,
the water
(below
(45
45 C))
toclean

,
it, and then put it in a shady
, .
and cool place to dry.


2

.
4
panel
cover tightly.
.

WARNING

. ,
.
operation environment,
, clean
frequency
can be increased.
, .
,
.

17
Clean and Maintenance

Checking
NOTICE:
: before
use-season

1.
1. Check whether
air inlets and air outlets are blocked.
.
2. Check whether
2. air switch, plug
and socket
are in .
good condition.
3. .
4. Check whether
4. mounting
bracket for outdoor
unit is damaged
or corroded.
.
If yes,
please
contact dealer.
.
5. Check whether
5. drainage
pipe .
is damaged.

Checkingafter
NOTICE:
: use-season

1.
Disconnect powersupply.
.

3.
Check whether mounting
bracket for outdoor
unit is damaged
or corroded.
.
If yes,
please contact
dealer.
.

Notice for recovery


:
1.
Many
packing materials
arerecyclable
materials.
.
Please
dispose
them inappropriate
recycling unit.
.
2. If you want
to
dispose the
air conditioner, please
, contact localdealer or

consultant
service center forthe
correct
disposal method.
.

18
Malfunction analysis

General phenomenon
analysis

Please check below items before asking for maintenance. If the malfunction still
.

.

Phenomenon
Check items
Solution


Whether it's interfered
severely
( .
Pull out the plug. Reinsert
.
(such as
static electricity,
, ? stable
the plug after about
.
3min, and
3

voltage)? then turn on the unit again.



Whether remote
controller is


within
the signal
receiving
? Signal receiving
8m. range is 8m.
range?
Indoor unit
Whether there are obstacles?
?
Remove obstacles.
.
cant receive

Whether remote
controller
is
Select
proper angle and point

remote

pointing at the receiving
the remote controller at the re-

controllers
?
window?
.
ceiving window on indoor unit.

signal or

Is sensitivity of remote
contro-
Check the batteries.
. If the
remote

ller low; fuzzy display and no

powerof
batteries
, is too low,

controller
? .
display? please replace them.
has no

.
action. Check whether
remote cont-

No
display when operating
roller appears
to be
. damaged.
e,
remote controller? .
?
If yes, replace it.
1.
Take the
remote controller

.
?
Fluorescent lamp in room? close to indoor unit.
2.
.
and then try it again.


Air inlet
or
air
outlet of
indoor

Eliminateobstacles.
.
unit is blocked?
?

Under
heating
,mode, indoor
After reaching toset
temper-

No air temperature
is reached
to set ature, indoor
, unit will
stop bl-

emitted

temperature?
? .
owing out air.

from

indoor
Heating
mode
is
turned on
just In
order to
prevent blowing

unit now?
? out cold air, indoor unit will be

,
started after
delaying
for sev-

eral minutes,
which
isa nor-

mal phenomenon.
.

19
Malfunction analysis

Phenomenon
Check items
Solution

Power
failure?
?
Wait until power
recovery.
.

Is plug
loose? ?

Reinsert the plug.
.


Air switch trips off or fuse
is
Ask professional to replace


burnt out?
?
air switch
. or fuse.
Air condit-

Wiring
has malfunction?
?
Ask professional toreplace
.it.
ioner cant

operate Unit hasrestarted
immediately
3

Wait for 3min, and.
then turn
after stopping
operation?
?
on the unit again.

Whether
the
function setting

? .
for remote controller is Reset the function.
correct?

Because
indoor
air is cooled

Mist is em-

rapidly.
After a ,
while, indoor

itted from
Indoor
temperature
and hum-

temperature and humidity will
indoorunits
idity is high?
?
be decrease and mist will
.
air outlet
disappear.


Temperaturecant
be adju-

sted under
auto mode.

Unit
is operating under
auto .
?
mode? Please
switch the
operation
Set temper-

adjust
mode if you need to

ature cant
temperature.
.
be adjusted


Yourrequired temperature


Set temperature
range:
:
exceeds the set temperature

? 16 ~30 .
range?


Wait until the voltage


Voltage is too
low? ?

.
resumes normal.

Cooling

Filter is dirty?
? .
(heating)
()
effect is


Set
temperature is
in proper Adjust temperature
to proper

range?
? range.
.
not good.


Door and window are open?
?
Close door and window.
.

20
Malfunction analysis

Phenomenon
Check items
Solution


Whether theres
odour
, source,


1. Eliminate theodour
source.

Odours are , .
such as furniture and cigarette, .
emitted

etc. 2. .


Air conditioner
Whether theres interference,
, .

Disconnect power, put back
,
, .
operates
such as thunder, wireless power, and then turn
on the
abnormally devices, etc. unit again.
.

During
defrosting under
he-
Outdoor

? ating mode, it may generate
,
unit has
Heating mode is turned on? ,
vapor, which is a normal
vapor

phenomenon.

The
noise
is the
sound of

Water

"
Air conditioner
is turned on or

?
" turned off just now? the unit,
, which
is a normal
.
noise
phenomenon.

This
is the sound offriction


Air conditioner is turned on or caused by expansion and/or

Cracking
?
turned off just now? contraction.
of panel or other
noise
parts due to the change of
temperature.

21
Malfunction analysis

Error
Code

When
air conditioner
status is abnormal,
, temperature
indicator
on indoor
unit will

.
.
ation of error code.
Above indicator
diagram isonly

Indoor
for
reference. Please
. refer to


display

actual product for the actual

indicator and position.
Error
code
.

Error code Troubleshooting


Heating indicator
ON 10s OFF 0.5s
Means defrosting status. Its the normal phenomenon.

F1 Please contact qualified professionals for service.


F2 Please contact qualified professionals for service.
C5 Please contact qualified professionals for service.
It can be eliminated after restarting the unit. If not, please
H6 contact qualified professionals for service.

Note: If there're
: other error
codes,
please
contact
qualified
professionals
for
,
service.
.

WARNING
When below phenomenon occurs, please turn off air conditioner and discon-

for service.
Power cord is overheating or damaged.
Theres abnormal sound during operation.
Air switch trips off frequently.
Air conditioner gives off burning smell.
Indoor unit is leaking.

If the air conditioner operates under abnormal conditions, it may cause

22
Installation dimension
diagram

Space to the ceiling

At least 15cm

Space to
the wall

At least 15cm
At least 15cm
Space to
the
wall

m
0c
30
At least 250cm
t
as n
At
le ctio
s tru
ob
he
ot
cet
S pa
Space to the obstruction

the
to n
At least 50cm

e
ac ctio
Sp stru
ob st
t lea
A cm
30

Drainage pipe
At least 30cm
Space to th
e wall

n
tio cm
At least 50cm
tr uc 00
bs st
2
theo lea Space to the
e to At obstruction
ac
Sp

23
Tools for installation
1 Level meter 2 Screw driver 3 Impact drill
4 Drill head 5 Pipe expander 6 Torque wrench
7 Open-end wrench 8 Pipe cutter 9 Leakage detector
10 Vacuum pump 11 Pressure meter 12 Universal meter
13 Inner hexagon spanner 14 Measuring tape
Note:
Please contact the local agent for installation.

Selection of installation location


Basic requirement Indoor unit
Installing the unit in the following pla- 1. There should be no obstruction near air
ces maycause malfunction. If it is un- inlet and air outlet.
avoidable, please consult the local 2. Select a location where the condensat-
dealer: ion water can be dispersed easily and
1.The place with strong heat sources, won't affect other people.
, 3. Select a location which is convenient to
connect the outdoor unit and near the
or volatile objects spread in the air.
power socket.
2.The place with high-frequency 4. Select a location which is out of reach
devices (such as welding machine, for children.
medical equipment). 5. The location should be able to withstand
3.The place near coast area. the weight of indoor unit and won't incr-
4.The place with oil or fumes in the air. ease noise and vibration.
5.The place with sulfureted gas. 6. The appliance must be installed 2.5m
6.Other places with special circums-
tances. 7. Don't install the indoor unit right above
7.The appliance shall not be install- the electric appliance.
ed in the laundry. 8. Please try your best to keep way from
fluorescent lamp.
Outdoor unit

will not affect neighborhood.


2. The location should be well ventilated and dry, in which the outdoor unit
won't be exposed directly to sunlight or strong wind.
3. The location should be able to withstand the weight of outdoor unit.
4. Make sure that the installation follows the requirement of installation
dimension diagram.
5. Select a location which is out of reach for children and far away from animals
or plants.If it is unavoidable, please add the fence for safety purpose.
24
Requirements for electric connection
Safety precaution
1. Must follow the electric safety regulations when installing the unit.

air switch.
3. Make sure the power supply matches with the requirement of air conditioner.
Unstable power supply or incorrect wiring or malfunction. Please install proper
power supply cables before using the air conditioner.
4. Properly connect the live wire, neutral wire and grounding wire of power socket.
5. Be sure to cut off the power supply before proceeding any work related to
electricity and safety.

7. If the supply cord is damaged, it must be replaced by the manufacturer, its

8. The temperature of refrigerant circuit will be high, please keep the interconnec-
tion cable away from the copper tube.
9. The appliance shall be installed in accordance with national wiring regulations.

Grounding requirement

grounding with specialized grounding device by a professional. Please make


sure it is always grounded effectively, otherwise it may cause electric shock.
2. The yellow-green wire in air conditioner is grounding wire, which can't be used
for other purposes.
3. The grounding resistance should comply with national electric safety regulations.
4. The appliance must be positioned so that the plug is accessible.
5. An all-pole disconnection switch having a contact separation of at least 3mm in

6. Including an air switch with suitable capacity, please note the following table. Air
switch should be included magnet buckle and heating buckle function, it can
protect the circuit-short and overload. (Caution: please do not use the fuse only
for protect the circuit)

Air-conditioner Air switch capacity


091218K 16A
24K 25A

25
Installation of indoor unit
Step one: choosing installation location
rm it with the client.

Step two: install wall-mounting frame


1. Hang the wall-mounting frame on the wall; adjust it in horizontal position with the

plastic expansion particles in the holes.


3. Fix the wall-mounting frame on the wall with tapping screws (ST4.2X25TA) and

Step three: open piping hole


1. Choose the position of piping hole according to the direction of outlet pipe. The
position of piping hole should be a little lower than the wall-mounted frame,
shown as below.
0912K 18K
Wall Wall Wall Wall
Mark in the middle of it Level meter Mark in the middle of it Level meter
Space Space Space Space
to the to the to the to the
wall wall wall wall
above above above above
150mm 150mm 150mm 150mm

Left Right Left Right


55mm 55mm 70mm 70mm
Rear piping hole Rear piping hole Rear piping hole Rear piping hole

24K
Wall Wall
Mark in the middle of it Level meter
Space Space
to the to the
wall wall
above above
150mm 150mm

Left Right
70mm 70mm
Rear piping hole Rear piping hole

Note: Please select the corresponding installation dimensional drawing ac-


cording to actual wall-mounted plate.
2. Open a piping hole with the diameter of 55/70 on the selected outlet pipe
position. In order to drain smoothly, slant the piping hole on the wall slightly
downward to the outdoor side with the gradient of 5-10.

26
Installation of indoor unit

Indoor outdoor
Note:
Pay attention to dust prevention and
take relevant safety measures when
opening the hole.
The plastic expansion particles are 55/
5-10 70
not provided and should be bought
locally.

Step four: outlet pipe


1. The pipe can be led out in the 2. When select leading out the pipe
direction of right, rear right, left or from left or right, please cut off the
rear left. corresponding hole on the bottom
case.
left right

left rear left cut off


rear right the hole
right

1. Aim the pipe joint at the corresponding


bellmouth.
pipe joint union nut pipe

2. Pretightening the union nut with hand.

3. Adjust the torque force by referring to the following sheet. Place the open-end
wrench on the pipe joint and place the torque wrench on the union nut. Tighten
the union nut with torque wrench.

27
Installation of indoor unit
open-end Hex nut diameter Tightening torque (N.m)
wrench 6 15~20
union nut 9.52 30~40
12 45~55
torque wrench pipe 16 60~65
19 70~75
indoor pipe
4. Wrap the indoor pipe and joint of con-
nection pipe with insulating pipe, and
then wrap it with tape. insulating pipe

Step six: install drain hose


1. Connect the drain hose to the outlet pipe of
indoor unit.
drain hose
outlet pipe
2. Bind the joint with tape.
outlet drain hose
tape pipe

Note: drain hose


Add insulating pipe in the indoor
drain hose in order to prevent
condensation.
The plastic expansion particles are
insulating pipe
not provided.

Step seven: connect wire of indoor unit

panel screw
1. Open the panel, remove the screw
on the wiring cover and then take
down the cover.

wiring cover
28
Installation of indoor
unit

2. Make the power connection wire go cable-cross


through the cable-cross hole at the back hole
of indoor unit and then pull it out from
the front side.
power connection
wire

3. Remove the wire clip; connect the power connection wire to the wiring terminal
according to the color; tighten the screw and then fix the power connection wire
with wire clip.

N(1) 2 3
yellow-green
blue black brown
(green)

outdoor unit connection

4.
Put wiring cover back
, and
then tighten
the screw.
.
5. Close thepanel.
.

Note:
:
All
wires of
indoor unit and
outdoor unit
should be connected
by
a professional.

.
for a new one. Avoid extending the wire by yourself.
,
installation.
. .
For the air conditioner without plug, an air switch must be installed in the line.
The air switch should be all-pole parting and the contact parting distance should
be more than 3mm.

29
Installation
of indoor
unit

Step eight: bind up pipe


1. Bind up the connection pipe, power connection
pipe drain
hose
band

cord and drain hose with the band.
indoor unit
indoor and
outdoor power cord
gas
pipe

indoor power
cord

band
liquid pipe 3. Bind
them evenly.
.
drain hose 4. The liquid
pipe and
gas pipe
should

be
bound separately
at the end.
.
2. Reserve a certain length of drain
hose and power cord for installation Note:
when binding them. When binding to The power cord and control wire
a certain degree, separate the indoor can't be crossed or winding.
power and then separate the drain The drain hose should be bound
hose. at the bottom.

Step nine: hang the indoor unit


1. Put the bound pipes in the wall pipe and then make them pass through the wall
hole.
2. Hang the indoor unit on the wall-mounting frame.
3. Stuff the gap between pipes and wall hole with sealing gum.
4. Fix the wall pipe.
5. Check if the indoor unit is installed firmly and closed to the wall.
indoor outdoor upper hook

wall pipe
sealing gum

lower hook of
wall-mounting frame

Note:
Do not bend the drain hose too excessively in order to prevent blocking.

30
Installation of outdoor
unit

:
(select
( it
according
to the actual
installation
situation)
)

1.
Select installation location
according
to the house
structure.
.
2. Fix the support
of outdoor
unit on the
selected
location
with expansion
screws.
.

Note:

installing the outdoor unit.


Make sure the support can withstand at least
four times of the unit weight.
The outdoor unit should be installed at least

joint.
For the unit with cooling capacity of 2300W
~5000W, 6 expansion screws are needed;
for the unit with cooling capacity of 6000W
~8000W, 8 expansion screws are needed;
for the unit with cooling capacity of 10000W
at
least 3cm3cm
above the floor

~16000W, 10 expansion screws are needed.

Step two: install drain joint


(Only for cooling and heating 1. Place the outdoor unit on the
unit) support.
1. Connect the outdoor drain joint into 2. Fix the foot holes of outdoor unit
the hole on the chassis, as shown in with bolts.
the picture below. foot holes
2. Connect the drain hose into the drain
vent.

drain vent chassis foot holes


outdoor drain joint
Drain hose

31
Installation
of outdoor
unit

Step :
four:
connect indoor and outdoor
pipes

1.
Remove the screw onthe
right
han- 3. Pretightening the union
nut with
.
,
dle of outdoor unit
.
and then remove hand.
the handle.
pipe joint
screw
handle
yellow-
green
union nut

2. Remove
the screw cap
of
valve and
4.
Tighten the union nut
with torque
,
aim the pipe
joint at the
bellmouth of
.
wrench by referring to the sheet
.
pipe. below.
liquid pipe Hex nutdiameter Tightening torque

(N.m)

liquid gas pipe 6 15~20


valve 9.52 30~40
12 45~55
gas valve 16 60~65
19 70~75

:
1. Remove
the wire clip;
connect
, the power
connection
wire to
the wiring terminal

according to the color; fix them with screws.
( )
.

0912K: 1824K:
N(1) 2 3
N(1) 2 3 L N
N L
yellow- yellow-
blue black brown brown blue
green green
yellow-
yellow- blue brown green
blue black brown green L N
N L POWER
Indoor unit connection
POWER
Indoor unit connection

32
Installation of outdoor unit

2.
Fix the power connection
wire and
signal
control wire
with
wire clip
((only for

cooling
and heating unit).
.)

Note:
:
, .
Never
cut
the
power connection
wire
to prolong or
shorten the distance.
.

Step
six:
:neaten
the pipes

1.
The pipes should
be
placed along the wall,

,
bent reasonably and hidden possibly. Min.
. .
semidiameter of bending the pipe is 10cm.
10cm.
wall

2. If
the outdoor unit
is higher than the
wall

, U
hole, you must set a U-shaped curve in the
,
pipe before pipe goes
into the room,
in .

order to prevent rain from getting into the U-shaped
curve
room.
drain
hose

Note:
:

The through-wal height of drain hose
Slant the drain hose
slightly dow-

.
shouldn't be higher
than
the outlet
, be
nwards. The drain hose can't
pipe hole of indoor unit.
. .
the drain hose

can't
raise

upwards.


The can't
drain hose
be .
fluctuant


The water outletcan't
, be placed

in water in order
. to drain smoothly.

The drain hose




can't be fluctuant
. The water

outlet can't be


fluctuant
outlet
The water
can't be
placed

in water

33
Vacuum pumping
Use vacuum pump

1. Remove the valve caps on


the liquid valve and gas liquid valve piezometer Lo Hi
valve and the nut of refri-
gerant charging vent. gas valve
2. Connect the charging hose refrigerant charging valve cap
of piezometer to the refri- vent
gerant charging vent of gas nut of refrigerant
valve and then connect the charging vent
other charging hose to the
vacuum pump. vacuum pump
3. Open the piezometer com-
pletely and operate for inner hexagon
spanner
10-15min to check if the
pressure of piezometer re-
mains in -0.1MPa. close
4. Close the vacuum pump
open
and maintain this status for
1-2min to check if the pres-
sure of piezometer remains
in -0.1MPa. If the pressure decreases, there may be leakage.
5. Remove the piezometer, open the valve core of liquid valve and gas valve
completely with inner hexagon spanner.
6. Tighten the screw caps of valves and refrigerant charging vent.
7. Reinstall the handle.

Leakage
detection

1. With leakage
detector:
:
Check if there
is leakage
with leakage
detector.
.
2. With soap water:
:
If leakage
detector
is not
available,
, please
use soap water for
leakage detection.

.
Apply soap
3 . water at the
suspected
position and
keep the
soap,
water for
more

than 3min.
. If there are air bubbles coming out of this position, there's a leakage.

34
Check after
installation

.

Items to be checked Possible malfunction


The unit may drop, shake or emit noise.
Have you done the refrigerant leakage
test? (heating) capacity.
It may cause condensation and water
dripping.
It may cause condensation and water
Is water drained well?
dripping.
Is the voltage of power supply accord-
ing to the voltage marked on the It may cause malfunction or damaging
nameplate? the parts.

Is electric wiring and pipeline installed It may cause malfunction or damaging


correctly? the parts.
Is the unit grounded securely? It may cause electric leakage.
Does the power cord follow the speci- It may cause malfunction or damaging
the parts.
Is there any obstruction in the air inlet
and outlet? (heating) capacity.
The dust and sundries caused during It may cause malfunction or damaging
installation are removed? the parts.
The gas valve and liquid valve of
connection pipe are open completely? (heating) capacity.
Is the inlet and outlet of piping hole It may cause insufficient cooling
been covered? (heating) capacity or waster eletricity.

Test operation

1.
Preparationof test operation
:

The client
approves the airconditioner.
.
Specify the important notes for
air conditioner to the client.
.
2. Method of test
operation

Put through the power,
press
ON/OFF
button on
"ON/OFF" the remote
controller
to start

operation.
.

Press MODE button
"MODE" to select AUTO,
COOL,
DRY, FAN
and
HEAT
to check
(COOL,
whether
HEAT, the
FAN, DRYoperation is normal
) or not.
.
If
the ambient
temperature
is lower
16than 16
, , the
air conditioner cant

start cooling.
.
35
Install snow guard (Optional)
()

In consideration of snow during installation of outdoor units

:
Note: It is required to equip snow guard and a higher foundation base to

prevent
snow
from
coveringair inlet and
outlet.
.

Correct
Incorrect

Above
20cm

The snow guard shall
be
wider
than

the
air conditioner.

seasonal

wind WALL seasonal WALL
wind
100cm Above
Snow guard
(Provide at field) More than 50cm

Height
of base in
consideration
of
snow
(More than
( 50cm)
50 )


Snow guard
(
(Install
in
windward
side)
)

Windward side

50cm Above

The snow
guard
shall
be wider
than the

air conditioner.
.
Height of
base in consideration
ofsnow

(More than
( 5050cm)
)

36
Configuration
of connection
pipe

1.
Standard length of connection
pipe

5m, 7.5m, 8m.
2.Min. length of
connection
pipe is 3m. 3m.

3.Max. length of
connection
pipe and max.
high difference.
.

Max.
length Max.
length
Cooling
Max.
height Cooling
Max.
height
of connec-
of connec-

capacity difference capacity difference
tion pipe tion pipe

5000Btu/h 24000Btu/h
15 5 25 10
(1465W) (7032W)

7000Btu/h 28000Btu/h
15 5 30 10
(2051W) (8204W)

9000Btu/h 36000Btu/h
15 5 30 20
(2637W) (10548W)

12000Btu/h 42000Btu/h
20 10 30 20
(3516W) (12306W)

18000Btu/h 48000Btu/h
25 10 30 20
(5274W) (14064W)

4. The additional
refrigerant oil and refrigerant
charging required
after
prolonging

connection pipe
.
After the length
of
connection pipe is prolonged
for 10m
10at
the basis
of
, 5 ml
standard length, you should add 5ml of refrigerant oil for each additional 5m
5 .
of connection pipe.
The calculation
method of additional
refrigerant
charging
amount
( (on
the
basis

of liquid pipe): ):
=
Additional refrigerant charging amount = prolonged length of liquid pipe
x .
additional refrigerant charging amount per meter

Basing on the
length of standard
pipe,
add
refrigerant
5, according
to the


requirementas table. The
shown in the additional
refrigerant
. charging amount

per meter
is
different according
to
the diameter
of
liquid pipe. See the


following sheet. . .

37
Configuration
of connection
pipe

Additional refrigerant
charging amount
for R22, R407C, R410A and R134a

Diameterof
connection
pipe Outdoor unit
throttle

Liquid
pipe(mm)
(mm) Gas pipe(mm)
(mm) Cooling
only(g/m)
(g/m) Cooling
and heating(g/m)
(g/m)

6 9.52 or 12 15 20

6 or 9.52 16 or 19 15 50

12 19 or 22.2 30 120

16 25.4 or 31.8 60 120

19 _ 250 250

22.2 _ 350 350

38
Pipe expanding
method

Note:
:
Improper pipe
expanding is the
main cause
of refrigerant
leakage. Please
. expand

the pipe
according
to
the following steps: :

A:
Cut the pipe
E:
: Expand the port

Expand the port
with
expander.
.

the distance of indoor unit and
.
outdoor unit. hard
mold
Cut the required
pipe
with pipe
cutter.
. expander
pipe

pipe
pipe
cutter

leaning uneven
Note:
:
burr
"A"
"" iso
differentaccording to the

diameter, please refer
, to the sheet

:
below:

Outer diameter
A(mm)
:
B:
Remove the burrs (mm)
(mm)
Max Min

Remove the burrs withshaper
and

prevent the burrs from getting into
, 6 - 6.35(1/4") 1.3 0.7
.
the pipe. 9.52(3/8") 1.6 1.0
pipe

shaper
12-12.7(1/2") 1.8 1.0
15.8-16(5/8") 2.4 2.2
downwards

F: Inspection
:
Check thequality
of expanding
port.
.
If there
is
any
blemish, expand
, the

C: Put on
: suitable insulating
pipe
. .
port again according to the steps
D: Put on the
: union nut
. above.
Remove
the union nuton
the indoor

smooth
surface

connection pipe and
outdoor
valve;
.
.
install the union nut on the pipe.
improper
expanding
union pipe

leaning
damaged
crack uneven

surface thickness
pipe

the length
is equal

39
Wired Controller
(Optional)
()

If the product
you bought
is equipped
with wired
, controller, please

refer to the following introductions of wired controller.
.

11. Displaying Part


:

Fig1.1.1
1.1.1 Outline
of wired controller

1.1 LCD Display


LCD of Wired Controller

Fig.1.1.2
1.1.2 LCD
LCD display

40
Wired
Controller (Optional)
()

1.2 Instruction
toLCD
LCD Display

Table1.1
1.1
No.
Symbols
Description

1 Swing function

(
2 Air exchange function (this function is yet unavailable for this unit).

3 Sleep function
(Only sleep
1). sleep 1)
(

4 Each kind
of running
mode
of
indoor unit (auto mode) ( )

5 Cooling
mode

6 Dry mode

7 Fan mode

8 Heating
mode

9 Defrosting function
for the
outdoor unit.

(
10 Gate-control
)function (this function is yet unavailable for this unit).

11
Lock function.
Shield functions
(Button operation,
( temperature
, setting, On/Off operation,
/,
12 SHIELD
Mode setting
are disabledby
the remote
monitoring
system.) ).

13 Turbo Turbo function


state

Memory
function (The
indoor unit
( resumes the original
setting
state after

14 MEMORY
power
failure
and then power recovery).
)

15
It blinks
under
on state ofthe
, operation
unit without
of any
button. .


Energy-saving (
function
(this function
is yet unavailable
for this unit).
16 SAVE
)

17 Ambient/setting
temperature value
/

18 E-HEATER Electric auxiliary


heating
function.

19 BLOW Blow function.


20 Timing value.

Quiet
function (
(two:
types: quiet
and auto quiet)
)
21 QUIET
(this function
( is
yet unavailable
for this unit).
)

41
Wired Controller
(Optional)
()

2
Buttons
2.1
Layout
of Buttons

2.2
Functionsof
Buttons
Table2.1
2.1
No.
Name
Function

1 Enter/Cancel Function
selection and cancellation.

o
2 Running temperature
. setting of the
indoor unit, range:16~30
, C.16-30C
6 Timer setting,
. range:0.5-24
, hr. - 24 h
0,5

3 Fan Setting of the high/middle/low/auto


fan speed.
///
////
4 Mode Setting of the Cooling/Heating/Fan/Dry/Auto mode of the indoor unit.

5 Function Switchover among


the functions
of Turbo/Save/E-heater/Blow
//e-heater/ etc..
.

7 Timer Timer setting.


8 On/Off Turn on/off the indoor unit


/
Press themfor
5s
under off state of
5 the
unit to enter/cancel the/
Memory
( ,
function(If memory is set, indoor unit after power failure and then power

4+2 +Mode recovery will
. resume the original
, setting state.
If not, the
indoor unit is

defaulted to
be off after
. power
recovery. Memoryoff
is default before

delivery.). .

By pressing them at the same time under off state of the unit, will be

,
3+6 Fan+ displayed
on the
wired controller
for the cooling
. only unit, while will be
displayed on the wired controller for the cooling and heating unit.
Upon
startup of
the unit without malfunction
or under
, off state
of the

unit,press
them
at
the
same time for55s
to enter
the
lock state, in which

2+6 + , . 5
case,any other buttons wont respond the press. Repress them for 5s to quit
.
this state.

42
Wired
Controller (Optional)
()
33
Operation
Instructions

3.1 /
3.1 On/Off
Press
on
On/Off to turn the

unit
and turn by
it off .
another press. .
Note:
: The state
3.1.1shown in Fig.3.1.1
indicates
the
Off state ofthe
unit after
power on. The state
.
3.1.2 in
shown Fig.3.1.2 On
indicates the
state of the unit after power
on. .

Fig.3.1.1
3.1.1Off State
Off Fig.3.1.2
On
3.1.2 OnState

3.2 Mode Setting


3.2
Under ON state
of the unit,
, press the
Mode
Mode to switch
the operation
modes
as the
following:
sequence:
AutoCoolingDryFanHeating.
- - - -

3.3 Temperature
3.3 Setting

Press or
to increase/decrease the preset
/ temperature.
If pressing
. either of
them
continuously,
the temperature
, will be
increasedor1Cdecreased by 1C
0,5 , every
0.5s,as shown
in
3.3.1
Fig.3.3.1.
In
the Cooling, Dry, Fan
, or Heating
, mode, the
temperature setting range
is 16C~30C.
16-30 C.

In
the Auto mode, the
setting temperature is .
unadjustable.

Fig.3.3.1
3.3.1 Fig.3.4.1
3.4.1
43
Wired Controller
(Optional)
()
3.4 Fan Setting
3.4
Under the On
state of
, the unit, press
FanFan and then
, fan
speed ofthe indoor unit will
change
circularly as shown
in
Fig.3.4.1.
3.4.1
Low Middle High

3.5
3.5 Timer Setting

, Timer ,
Under on-state of the unit, Press Timer button to set timer off of the unit. Under off-state of the
. Timer
unit, press Timer
button toset
timer on of the unit in the same way.
.
Timer on setting:

Under off-state
of the
unit
without timer
setting,
,if
Timer
button
is pressed, LCD will
Timer , display
LCD xx.

Hour,with
ON blinking.
In this,
case, press
ON or button
. to adjust
timer on and
then
press
Timer to

Timer .

Timer off setting:



Under on-state
of the
unit without timer
setting,
, if
Timer button isTimer
pressed, LCD
, willLCD
display xx.

, OFF .
Hour,with OFF blinking. In this case, press or button to adjust timer on and then press Timer to
Timer .

Cancel timer:

After
setting of timer, if Timer
, button
is pressed,
LCD wont
Timer , display xx. Hour
LCD so
thattimer setting

.
is canceled.
Timer off setting
under
the On state
of the unit is shown
as Fig.3.5.1. 3.5.1

, Timer

Timer Enter/Cancel

Fig.3.5.1
3.5.1 Timer off Setting
under
the On State
of the
Unit

44
Wired Controller
(Optional)
()

Timer on setting
under
the Off state
of the
unit is
shown as Fig.3.5.2.
3.5.2

, Timer

Timer Enter/Cancel

Fig.3.5.2
3.5.2
Timer on Setting under
the
Off State
of the
Unit
Timer range: 0.5-24hr.
: Everypress
0.5 - 24 . of
or will
make
the settime increased or decreased
/ by
0.5 .If
0.5hr.
either ispressed
of them ,
continuously, the set time /
will increase/ 0.5every
decrease by 0.5hr
0.5 .
0.5s.

45
Wired Controller
(Optional)
()

3.6
3.6 Swing Setting
Swing On:
Press Function
under
: on state of the
unit to
, activate the swing
Function function. In this case,

. . Enter/Cancel .

Swing
Off: When
the Swing function
: is on,
press
, Function to enterthe
Function Swing
setting

interface,with blinking.
. After that, press
. Enter/Cancel
to cancel this
Enter/Cancel function. Swing
setting is
.
3.6.1.
shown as Fig.3.6.1.

, Function Enter/Cancel

Enter/Cancel Function

Fig.3.6.1 Swing
3.6.1 Setting

Notes:
. Sleep, Turbo
1. or Blow setting
is the
, same
as the Swing
setting.

.
. After the setting has been done, it has to press the key Enter/Cancel to back to the setting
2. , Enter/Cancel
.

46
Wired
Controller (Optional)
()

3.7 Sleep Setting


3.7

Sleep on: Press


:
Function under
the
On state of
the unit Function
till the unit enters
the Sleepsetting

. Enter/Cancel
.
Sleep off:When
the
Sleep function
: is activated,press
Function
to enter
the Sleep
Function setting


status. After that, . to
press Enter/Cancel
cancel Enter/Cancel .
this function.

In the or
Cooling Dry,
mode,
the temperature will

increaseby
1C
after
the unit
runs under
1 , .
Sleep1
for 1hr and 1C after another 1hr.After that, the unit will run at this temperature.
.
In the
Heating
,mode, the temperature
will decrease
by
1C after the
unit runs
under Sleep 1 for

1hr
and 1C 1 ,
after another 1hr.
After unit
that, the
will run.
at this
temperature.
.
Sleep setting
is shownas
Fig.3.7.1.
3.7.1.

, Enter/Cancel
Function


Enter/Cancel Function


Fig.3.7.1.
Sleep Setting
3.7.1

47
Wired Controller
(Optional)
()

3.8 Turbo Setting


3.8
Turbo
function:
: The unit
at the high
fanspeed
can realize
quick
cooling or
heating
so that
the

.
room temperature can quickly approach the setting value.

In the Cooling
or Heating
mode, Functiontill
press Function the unit
enters theTurbo
setting

status and
, Enter/Cancel .

When the Turbo


function
is activated,
press Function
Function to
enter the
Turbo setting
status and then

Enter/Cancel .
press Enter/Cancel to cancel this function.
Turbo function
setting is as shown
in Fig.3.8.1.
3.8.1.

, Function Enter/Cancel

Enter/Cancel Function


Fig.3.8.1
Turbo Setting
3.8.1

48
Wired Controller
(Optional)
()

3.9 E-heater Setting


3.9 E - heater
E-heater
E-heater (auxiliary
( electric
heating function):
):In
the
Heating mode,
E-heater is
allowedE-heater
to be
.
Once
the wired
controller
or
the remote controller
enters
the Heating
mode, this
function
will be
.
turned on automatically.
Press Function
in
Function the Heating mode
to
enter the
E-heater setting
interface and
E-heater, then press

Enter/Cancel
Enter/Cancel
to cancel this .
function.
Press Function
to
Function enter the E-heater
setting
status, if the E-heater
function
E-heater, is not activated,
E-heater
Enter/Cancel .
and then press Enter/Cancel to activate it.
The setting of this
function
is shown
as Fig.3.9.1
below:
3.9.1.

, Enter/Cancel
Function
E-hater E-hater

E-heater

Enter/Cancel Function
E-
heater
Fig.3.9.1 E-heater Setting
3.9.1 E-heater

49
Wired
Controller (Optional)
()

3.10 Blow Setting


3.10
Blow
function: After the
: unit is
turned off, the
, water
in
evaporator
of
indoor unit will be

e .
automatically evaporated to avoid mildew.
In the Cooling
or Dry
mode, press
Function Funcion
till the unit enters
the Blow
setting
status and then

press Enter/Cancel
to active
this function.
Enter/Cancel .
When the
Blow function
is activated,
, press Function
to the
Function Blow setting
status and
then press


Enter/Cancel Enter/Cancel
to cancel .
this function.
Blow function
setting is as shown
in Fig.3.10.1
3.10.1

, Function Enter/Cancel

Enter/Cancel Function


Fig.3.10.1
3.9.1 Blow Setting

Notes:
:
. When
1. the
Blow function is activated,
, if
turning off the unit
by
pressing On/Off or
On/Off by
the
, , LCD
remote controller, the indoor fan will run at the low fan speed for 2 min, with BLOW displayed on
BLOW. ,
the LCD.
While, if the Blow function is deactivated, the indoor fan will be turned off directly.
.
. Blow function is unavailable in the Fan or Heating mode.
2. .

50
Wired
Controller (Optional)
()
3.11
3.11 Other Functions

a.
A. Lock

Upon
startup of
the unit without
malfunction
or under the Off
state
of the unit, press
, and at
5
the same time for 5s till the wired controller
. LCD enters the Lock
. function. In this case, LCD displays .
After that, repress these two buttons at the same time for 5s to quit this function.
, 5 .
, .
Under the Lock state, any other button press wont get any response.
b.
. Memory

Memory
switchover: Under
: the Off state
of the unit,
press Mode
andMode
at the
same time for
5 .
5s to switch memory states between memory on and memory off. When this function is activated,
Memory .
Memory
will be
displayed.
If this function
is not set, the unit will be under the Off state after power
.
failure and then power recovery.
Memory
recovery: If
: this
function has been
set for the
wired controller,
the wired
, controller
after

.
power failure will resume its original running state upon power recovery. Memory contents: On/
/, ,
Off, Mode, set temperature,
set fan speed and Lock function.
.

4 Installation and
4 Dismantlement

4.1
4.1 Connection
of
the Signal Line of the
Wired Controller
Open the
cover of
the
electric
control box of
the indoor
unit.
.
Let the single
line of the
wired
controller
through
therubber ring..


Connectthe

signal line wired
of the
control
to the 4-pin 4
socket of the PCB.
indoor unit
.
Tighten the
signal wire with
ties.
.
The communication
distance
between
the main
board and the wired
controller can
be
up
to
20 meters
20 ( the standard
( distance is88)
meters)

4.2
4.2 Installation
of
the Wired
Controller
PVC Pipe

1 2 3 4 5

Fig.4.1
Accessories
4.1 for the Installation
of the Wired
Controller

Table 4.1
4.1

No.
1 2 3 4 5
Socket
box Soleplate
of
Front
Panel
Screw
Screw

Name
embedded
the Wired
of the Wired

M4X25 ST 2.9X6
in the wall Controller Controller

51
Wired
Controller (Optional)
()

1 2 3 4

7 6 5

8 9 10

Fig.4.2
Fig.4.24.2
shows the installation
steps
of
the wired controller,
but,
there are some
issues
that need
your attention.
:
1)
1) Prior ,
to the installation, please firstly
cut off thepower
supply of
, the
wire
buried
in the
installation
hole, that is, no operation
is allowed
with.
electricity during the whole installation.
2)
2) Pull out thefour-core
-twisted
pair line
from the installation
holes and
then let itgothrough


the rectangular hole
behind
the soleplate
of the .
wired controller.
3)

with M4X25.
screws M4X25.
4)4)
Insert the
four-core twisted pair
- line
into the slotof
the wired
controller
and then buckle
the

front panel .
and the soleplate of the wired controller together.
5) , ST2.9X6
CAUTION!

Please
pay special attention
to the followings
during
the connection to
avoid the malfunction
of

the air conditioning
unit due to electromagnetic
interference.
.
Separate the
. signal and communication
lines
of the
wired controller
from the
power cord

.
52
Wired
Controller (Optional)
()
and connection lines
between
the indoor and outdoor
unit, with
a minimum interval of
20cm,

20 , .
otherwise the communication of the unit will probably work abnormally.
If the
. air
conditioning unit is
installed where
is
vulnerable
to
electromagnetic,
.
interference,then the signal and communication lines of the wired controller must be the shielding
twisted pair lines.

4.3
4.3 Dismantlement of the Wired
Controller

1 2 3 4

5 Errors Display
5
If there
is an error
occurring
during the
operation
,of the system,
the error
code
will be
displayed
LCD
,
on the LCD,as
show in Fig.5.1. Ifmulti
5.1.occur
errors same
at the
time, their ,
codes will be displayed
.
circularly.
Note: In
: event ofany error,
please
turn off the
, unit and
contact the professionally
skilled

personnel. .

Fig.5.1
5.1

53
Wired
Controller (Optional)
()
Table5.1
5.1
Meaning
of Each
Error

Error
Error

Error
Error

Code
Code

Return
air temperature
sensor open/
/
F1 Drive board communication
error
P6
short circuited

evaporator
temperature sensor
open/
/
F2 Compressor overheating
protection
H3
short
circuited
Indoor unit
liquid
valve temperature

b5 Indoor and outdoor units unmatched LP
sensor open/short
/ circuited

Indoor gas
valve
temperature
sensor
Communication
line misconnected
or

b7 dn
open/ short/
circuited expansion
valve error

IPM temperature sensor open/short
IPM /
P7 E7
circuited
Outdoor
ambient temperature
sensor
/
F3 Pump-down
Fo
open/
short circuited
Outdoor
unit condenser
mid-tube

F4 Jumper error
Jumper C5
temperature
sensor open/short
circuited
./
Discharge
temperature
sensor open/
/
F5 Forced
defrosting
H1
short circuited


Indoor and outdoor communication error

E6 Compressor startup failure
Lc

DC bus
DC bus under-voltage protection
- PL High discharge
temperature protection
E4

DCbus
DC bus over-voltage
protection
- PH Overload
protection
E8
Compressor
phase
current
sensing

U1 Whole
unit over-current
protection
E5
circuit error

Compressor demagnetization
protection
HE Over phase
current
protection
P5

PFC
PFC protection Hc Compressor desynchronizing
H7

IPM Temperature
IPM Protection
P8 IPM Current
IPM protection H5
Compressor
phase
loss/reversal
/
Over-power protection
L9 Ld
protection

System
charge shortage
or blockage
Frequency
restricted/reduced
with whole

F0 F8
protection
unit current protection

Frequency
restricted/reduced with IPM
IPM
Capacitor charging
error
PU En
current protection
Frequency
restricted/reduced with high

High pressure
protection
E1 F9
discharge temperature

Frequency
restricted/reduced with anti-

Low pressure
protection
E3 FH
freezing protection
Frequency
restricted/reduced
with
Compressor
stalling
LE F6
overload protection

Frequency
restricted/reduced with IPM
IPM
Over-speeding
LF EU
temperature protection
Drive
board temperature
sensor error PF Indoor unit
full water
error
E9

AC contactor
protection
P9 Anti-freezing protection
E2

Temperature
drift protection
PE AC input voltage
abnormal
PP

Sensor
connection
protection
Pd Whole unit current sensing circuit error

U5

DC bus
voltage drop error DC bus
U3 44-way
valve reversing
error
U7

Outdoor
fan 1 error
protection 1
L3 Motor stalling
H6
2
Outdoor fan 2 error protection LA PG motor
zero-crossing protection
PG U8

54
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070
Tel: (+86-756) 8522218 Fax: (+86-756) 8669426
E-mail: gree@gree.com.cn www.gree.com

66160000181