Sie sind auf Seite 1von 2

Copyright 2013 National Fire Protection Association (NFPA).

Licensed, by agreement, for individual use and single download on April 29, 2013 to GEIC for designated user HABEEB MECHERY. No other
reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact licensing@nfpa.org.

FEATURES OF FIRE PROTECTION 10195

compromising the fire resistance rating of the assembly or the (3) Existing enclosures in existing buildings 12-hour fire
structural integrity of the assembly. barriers
(4) Enclosures for lodging and rooming houses as speci-
8.6 Vertical Openings.
fied in Chapter 26
8.6.1 Floor Smoke Barriers. Every floor that separates stories (5) Enclosures for new hotels as specified in Chapter 28
in a building shall meet the following criteria: (6) Enclosures for new apartment buildings as specified in
Chapter 30
(1) It shall be constructed as a smoke barrier in accordance
with Section 8.5. 8.6.6 Communicating Space. Unless prohibited by Chapters 11
(2) It shall be permitted to have openings as described by through 43, unenclosed floor openings forming a communicat-
8.6.6, 8.6.7, 8.6.8, 8.6.9, or Chapters 11 through 43. ing space between floor levels shall be permitted, provided that
the following conditions are met:
8.6.2* Continuity. Openings through floors shall be enclosed
with fire barrier walls, shall be continuous from floor to floor, (1) The communicating space does not connect more than
or floor to roof, and shall be protected as appropriate for the three contiguous stories.
fire resistance rating of the barrier. (2) The lowest or next-to-lowest story within the communicat-
8.6.3 Continuity Exemptions. The requirements of 8.6.2 shall ing space is a street floor.
not apply where otherwise permitted by any of the following: (3) The entire floor area of the communicating space is open
and unobstructed, such that a fire in any part of the space
(1) Where penetrations for cables, cable trays, conduits, pipes, will be readily obvious to the occupants of the space prior
tubes, combustion vents and exhaust vents, wires, pneumatic to the time it becomes an occupant hazard.
tube conveyors, and similar items to accommodate electri- (4) The communicating space is separated from the remainder
cal, mechanical, plumbing, and communications systems of the building by fire barriers with not less than a 1-hour fire
are protected in accordance with 8.3.5.1 and 8.5.6 resistance rating, unless one of the following is met:
(2) Where specified by 8.6.6, 8.6.7, 8.6.8, 8.6.9.1, 8.6.9.2,
8.6.9.3, or Chapters 11 through 43 (a) In buildings protected throughout by an approved
(3) Where escalators and moving walks are protected in ac- automatic sprinkler system in accordance with Sec-
cordance with 8.6.9.6 or 8.6.9.7 tion 9.7, a smoke barrier in accordance with Sec-
(4) Where expansion or seismic joints are designed to pre- tion 8.5 shall be permitted to serve as the separa-
vent the penetration of fire and are shown to have a fire tion required by 8.6.6(4).
resistance rating of not less than that required for the (b) The requirement of 8.6.6(4) shall not apply to fully
floor when tested in accordance with ANSI/UL 2079, sprinklered residential housing units of detention
Standard for Tests for Fire Resistance of Building Joint Systems and correctional occupancies in accordance with
(5) Where existing mail chutes meet one of the following 22.3.1(2) and 23.3.1.1(2).
criteria: (5) The communicating space has ordinary hazard contents
(a) The cross-sectional area does not exceed 0.1 ft2 protected throughout by an approved automatic sprin-
(0.01 m2). kler system in accordance with Section 9.7 or has only low
(b) The building is protected throughout by an approved hazard contents. (See 6.2.2.)
automatic sprinkler system in accordance with Sec- (6) Egress capacity is sufficient to allow all the occupants of
tion 9.7. all levels within the communicating space to simulta-
8.6.4 Shafts. Shafts that do not extend to the bottom or the top neously egress the communicating space by consider-
of the building or structure shall comply with either 8.6.4.1, ing it as a single floor area in determining the required
8.6.4.2, or 8.6.4.3. egress capacity.
(7)*Each occupant within the communicating space has ac-
8.6.4.1 Shafts shall be enclosed at the lowest or highest level of cess to not less than one exit without having to traverse
the shaft, respectively, with construction in accordance with 8.6.5. another story within the communicating space.
8.6.4.2 Shafts shall be permitted to terminate in a room or (8) Each occupant not in the communicating space has ac-
space having a use related to the purpose of the shaft, pro- cess to not less than one exit without having to enter the
vided that the room or space is separated from the remainder communicating space.
of the building by construction having a fire resistance rating
8.6.7* Atriums. Unless prohibited by Chapters 11 through 43,
and opening protectives in accordance with 8.6.5 and 8.3.4.
an atrium shall be permitted, provided that the following con-
8.6.4.3 Shafts that do not extend to the bottom or top of the ditions are met:
building or structure shall be permitted to be protected by
approved fire dampers installed in accordance with their list- (1) The atrium is separated from the adjacent spaces by fire
ing at the lowest or highest floor level, as applicable, within the barriers with not less than a 1-hour fire resistance rating,
shaft enclosure. with opening protectives for corridor walls, unless one of
the following is met:
8.6.5* Required Fire Resistance Rating. The minimum fire (a) The requirement of 8.6.7(1) shall not apply to exist-
resistance rating for the enclosure of floor openings shall be as
ing, previously approved atriums.
follows (see 7.1.3.2.1 for enclosure of exits):
(b) Any number of levels of the building shall be permit-
(1) Enclosures connecting four or more stories in new con- ted to open directly to the atrium without enclosure,
struction 2-hour fire barriers based on the results of the engineering analysis re-
(2) Other enclosures in new construction 1-hour fire barriers quired in 8.6.7(5).

2012 Edition
Copyright 2013 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on April 29, 2013 to GEIC for designated user HABEEB MECHERY. No other
reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact licensing@nfpa.org.

10196 LIFE SAFETY CODE

(c)*Glass walls and inoperable windows shall be permit- (2) Such openings shall be separated from unprotected verti-
ted in lieu of the fire barriers where all the following cal openings serving other floors by a barrier complying
are met: with 8.6.5.
i. Automatic sprinklers are spaced along both (3) Such openings shall be separated from corridors.
sides of the glass wall and the inoperable win- (4)*In other than approved, existing convenience openings,
dows at intervals not to exceed 6 ft (1830 mm). such openings shall be separated from other fire or
ii. The automatic sprinklers specified in smoke compartments on the same floor.
8.6.7(1)(c)(i) are located at a distance from the (5) In new construction, the convenience opening shall be
glass wall not to exceed 12 in. (305 mm) and separated from the corridor referenced in 8.6.9.1(3) by a
arranged so that the entire surface of the glass is smoke partition, unless Chapters 11 through 43 require
wet upon operation of the sprinklers. the corridor to have a fire resistance rating.
iii. The glass wall is of tempered, wired, or lami- (6)*Such openings shall not serve as a required means of egress.
nated glass held in place by a gasket system that 8.6.9.2 Where permitted by Chapters 11 through 43, unen-
allows the glass framing system to deflect with- closed vertical openings created by convenience stairways
out breaking (loading) the glass before the shall be permitted as follows:
sprinklers operate. (1) The convenience stair openings shall not serve as re-
iv. The automatic sprinklers required by quired means of egress.
8.6.7(1)(c)(i) are not required on the atrium (2) The building shall be protected throughout by an ap-
side of the glass wall and the inoperable window proved, supervised automatic sprinkler system in accor-
where there is no walkway or other floor area on dance with Section 9.7.
the atrium side above the main floor level. (3) The convenience stair openings shall be protected in ac-
v. Doors in the glass walls are of glass or other ma- cordance with the method detailed for the protection of
terial that resists the passage of smoke. vertical openings in NFPA 13, Standard for the Installation of
vi. Doors in the glass walls are self-closing or Sprinkler Systems.
automatic-closing upon detection of smoke. 8.6.9.3 Convenience stairs shall be permitted to be unen-
vii. The glass is continuous vertically, without hori- closed in large open areas such as atriums and shopping malls.
zontal mullions, window treatments, or other
obstructions that would interfere with the wet- 8.6.9.4 For other than existing hoistways in existing build-
ting of the entire glass surface. ings, elevator cars located within a building shall be enclosed
as follows:
(2) Access to exits is permitted to be within the atrium, and
exit discharge in accordance with 7.7.2 is permitted to be (1) Where there are three or fewer elevator cars in the build-
within the atrium. ing, they shall be permitted to be located within the same
(3) The occupancy within the atrium meets the specifications hoistway enclosure.
for classification as low or ordinary hazard contents. (See (2) Where there are four elevator cars in the building, they
6.2.2.) shall be divided in such a manner that not less than two
(4) The entire building is protected throughout by an ap- separate hoistway enclosures are provided.
proved, supervised automatic sprinkler system in accor- (3) Where there are more than four elevator cars in the build-
dance with Section 9.7. ing, the number of elevator cars located within a single
(5)*For other than existing, previously approved atriums, an en- hoistway enclosure shall not exceed four.
gineering analysis is performed that demonstrates that the 8.6.9.5 Service openings for conveyors, elevators, and dumb-
building is designed to keep the smoke layer interface above waiters, where required to be open on more than one story at
the highest unprotected opening to adjoining spaces, or 6 ft the same time for purposes of operation, shall be provided
(1830 mm) above the highest floor level of exit access open with closing devices in accordance with 7.2.1.8.
to the atrium, for a period equal to 1.5 times the calculated 8.6.9.6 Any escalators and moving walks serving as a required
egress time or 20 minutes, whichever is greater. exit in existing buildings shall be enclosed in the same man-
(6)*In other than existing, previously approved atriums, ner as exit stairways. (See 7.1.3.2.)
where an engineered smoke control system is installed to
8.6.9.7 Any escalators and moving walks not constituting an
meet the requirements of 8.6.7(5), the system is indepen-
exit shall have their floor openings enclosed or protected as
dently activated by each of the following:
required for other vertical openings, unless otherwise permit-
(a) Required automatic sprinkler system ted by one of the following:
(b) Manual controls that are readily accessible to the fire
department (1) The requirement of 8.6.9.7 shall not apply to escalators in
large open areas, such as atriums and enclosed shopping
8.6.8 Two-Story Openings with Partial Enclosure. A vertical malls.
opening serving as other than an exit enclosure, connecting (2)*In buildings protected throughout by an approved auto-
only two adjacent stories and piercing only one floor, shall be matic sprinkler system in accordance with Section 9.7, es-
permitted to be open to one of the two stories. calator and moving walk openings shall be permitted to
be protected in accordance with the method detailed in
8.6.9 Convenience Openings. NFPA 13, Standard for the Installation of Sprinkler Systems, or
8.6.9.1 Where permitted by Chapters 11 through 43, unen- in accordance with a method approved by the authority
closed vertical openings not concealed within the building having jurisdiction.
construction shall be permitted as follows: (3) In buildings protected throughout by an approved auto-
matic sprinkler system in accordance with Section 9.7, es-
(1) Such openings shall connect not more than two adjacent calator and moving walk openings shall be permitted to
stories (one floor pierced only). be protected by rolling steel shutters appropriate for the

2012 Edition

Das könnte Ihnen auch gefallen