WHITE PAPER:

UNDERSTANDING TRIPLEN HARMONICS

Contributed by Cowles Andrus March 2014 Figure 1 shows the relationship of the fundamen-
tal and the first triplen harmonic. Because triplen
ABSTRACT harmonics are of the zero sequence unlike the
fundamental which is positive, the magnitude
With the push for energy efficiency comes the pro- of the currents of these harmonics on a 3-phase
liferation of non-linear loads whose overall effect system is additive in the neutral circuit. This can
on the power transmission system may not always cause very large currents to f low in the neutral,
be as beneficial as originally intended. The triplen and unless the neutral is sufficiently oversized to
harmonics that are caused by nonlinear loads can handle the extra current, significant heating can
cause issues such as excessive neutral currents, occur causing a fire hazard. In the past, before the
transformer failures, excessive heating of motors, introduction of PCs, UPS, and other devices caus-
electronic device failures, failed capacitor banks, ing large nonlinear loads, the manufacturers of
breakers and fuses tripping, and communication powering strips would sometimes undersize their
issues related to RFI and noise ingression into the neutral wires to save money. For resistive linear
communication system. This paper details what loads, the neutral currents were usually quite low.
triplen harmonics are, what causes them, system This undersizing of the neutral wiring turned out
issues that result from triplen harmonics, and best to be a major factor contributing to many fires in
practice for mitigating triplen harmonics and their the past. Now it is commonplace to see the neutral
effects. wires oversized to prevent a potential fire hazard.

TRIPLEN HARMONICS Figure 2 shows how the three phases add together
to enhancing the third harmonic on the neutral
Triplen harmonics are odd multiples of the 3rd when the load becomes nonlinear. With a linear Figure 1. Relationship of
harmonic, where the name triplen is derived from. load, there is no current f low on the neutral line. the fundamental and triplen
This would be for example the 3rd, 9th, 15th, 21st harmonics
etc In other words, in a four wire system as shown

Fundamental 9th Harmonic


3rd Harmonic 15th Harmonic
21st Harmonic

+
Current or Voltage

0
Time

1 3 5 7 9

Page 1 WP152 2015 Power Monitors, Inc. Call Us: (800) 296-4120 www.powermonitors.com
WHITE PAPER:
UNDERSTANDING TRIPLEN HARMONICS

in Figure 2, where there are three phases and a


neutral, the phase currents return path is by the
neutral conductor. In a distribution system with A Phase
an ideal resistive linear load, the 120 degree phase
shift between the different phase currents allows
them to be perfectly balanced, cancelling out any
neutral currents, resulting in no current f low in
the neutral. In a real world situation, distribu-
tion systems always have some mix of linear and
non-linear loads, so the current on one phase does B Phase
not have a pulse on the other phases with which
to cancel out the other, causing current to f low at
intervals of three times the fundamental frequency
thus creating triplen harmonics. At the extremes,
currents generated in the neutral due to non-linear
loads can be as high as 173% of the phase cur-
rents.
C Phase

=1.73 x Line Current


Neutral
To compound this problem, when harmonics are
higher in frequency than the fundamental, they
use less of a conductor to carry the current. This
phenomenon is known as the skin effect. This is
clearly illustrated in Figure 2b on the Neutral. harmonics are produced as a result of nonlinear Figure 2. The three phases
This shows that the frequency of the neutral cur- loads on a power system. The rectifier is a major combine
rent when providing power to a non-linear load is offender being a nonlinear device that takes the
nearly 3 times the frequency of the fundamental alternating current and converts it to a DC pulses.
or 180 Hz on a nominal 60 Hz power distribu-
tion system. As the frequencies of the harmonics One of the most common rectifiers in use today is
become higher, they utilize less of the cross-sec- the silicon based P-N junction type. For simplicity,
tional area of the conductor and stay closer to the the waveform in Figure 3 represents a single diode
conductors surface. This raises the resistance of charging a capacitor. When the rectifier is forward
the conductor causing the I2R losses to increase. bias, it begins to conduct, allowing the capacitor
These elevated currents also put a strain on power to charge, thus loading the AC line. As demon-
transformers causing them to generate excessive strated in the in Figure 3, the amount of current
heat which may cause them to fail or fail sooner. that is drawn from the AC source is repeated
These triplen harmonics are not only problematic every cycle. In a full wave bridge configuration,
to 3 phase systems, they also affect single phase this action happens twice as often, on both the
power supplies. positive going edge and negative going edge of the
sine wave after the diode has sufficient voltage to
SOURCES OF TRIPLEN HARMONICS overcome the junction voltage drop, usually 0.7
volts for silicon. Depending on the charge of the
Triplen harmonics are not produced by the gener- capacitor, the capacitor value, and the load on the
ating station or a power generating source. Triplen capacitor determines when the diode will start

Page 2 WP152 2015 Power Monitors, Inc. Call Us: (800) 296-4120 www.powermonitors.com
WHITE PAPER:
UNDERSTANDING TRIPLEN HARMONICS

Diode Ends
Conduction
Diode Starts
Conduction

0c Capacitor
Discharge

t1 t2
Conduction
Angle

to conduct and how long the conduction cycle is. on the system. Figure 3. Waveform of a
This will also govern the conduction angle. It is typical half wave rectifiers
clear to see this is not a linear process and will Another source of triplen harmonics are electronic conductive cycle
cause harmonics. Also, on 3 phase systems, since ballasts use in f luorescent lamps. In some depart-
rectification occurs on each of the three phases, ment stores and offices, there can be hundreds or
the conduction cycle of the rectifier will occur even thousands, and with the reduction of incan-
at three times the rate as on a single phase. This descent type lighting, this trend is not likely to
along with a doubling of the line rate due to the improve. Even light dimmers for the incandescent
use of a full wave bridge raises the frequency of lighting can be a source of triplen harmonics.
the harmonic generated, but also tends to lessen
the conduction time, thus the conductive angle With the push for more efficient lighting, and the
which may lessen the severity compared to a recti- phasing out of incandescent lighting, compact f lu-
fication system with fewer poles. orescent lamps, CFL, and LED type lighting are
rapidly becoming the norm. Incandescent lamps,
Triplen harmonics are the result of devices that even though not nearly as efficient as CFL and
offer non-linear loads to the system. Any power LEDs, have one distinct advantage, they present-
supply that converts AC to DC uses a rectifier, ed a much more linear load to the power system,
which presents a non-linear load. These types of causing virtually no harmonics this is not the
power supplies are used in almost any electronic case with CFL and LEDs.
component plugged into AC. Computers, UPS,
TVs, radios, amplifiers, are just a few examples. ISSUES RESULTING FROM TRIPLEN
The more power they consume, usually the more HARMONICS
triplen harmonics are generated, even if each
device on its own does not consume much power, One of the main issues that result from triplen
the total can contribute to an overall problem. For harmonics is the overheating of transformers and
example, a single PC may not present much of an rotating equipment. If triplen harmonics con-
issue, but in a location such as an office building, taining 5th or 11th harmonics are applied to a
100 PCs could easily become a nonlinear burden 3-phase motor, it will attempt to drive the motor

Page 3 WP152 2015 Power Monitors, Inc. Call Us: (800) 296-4120 www.powermonitors.com
WHITE PAPER:
UNDERSTANDING TRIPLEN HARMONICS

in reverse. In order to compensate, the motor must When driving a nonlinear load, it is better, if
draw additional current at the fundamental, even- possible, to use a delta configuration as opposed
tually causing it to overheat. Some of the other to a wye-configuration. See Figure 5. In a del-
negative effects of triplen harmonics include in- ta configuration, the neutral line is eliminated;
creased hysteresis losses in transformers, decreased therefore the harmonics have no neutral line to
kVA capacity, neutral overloading, unacceptable travel in. Even though the triplen harmonics are
neutral-to-ground voltages, distorted voltage and trapped in the delta loads loop, there is a down-
current waveforms, failed capacitor banks, break- side, the triplen harmonics are still generated in
ers and fuses tripping, interference on phone and the non-linear load causing monetary losses in the
communications systems, unreliable operation of delta transformers efficiency. This does isolate the
electronic equipment, erroneous register of electric harmonics from line and source, but at a cost of
meters, wasted capacity and inefficient distribu- causing higher currents to f low in the secondary
tion of power, and an increased maintenance of windings of the loads delta transformer. Because
equipment and machinery. of this, the delta transformers load capacity needs
to be de-rated to keep the triplen harmonics from
WAYS TO REDUCE TRIPLEN HARMONICS causing them to overheat.

There are ways to mitigate the large voltage dis- With the use of PMIs Recorders and Provision, it
tortions caused by triplen harmonics. One of the is easy to measure and verify the triplen harmon-
most effective ways is to install an inductor on the ics contribution to the Total Harmonic Distortion
source. The inductor acts as a low pass filter, pass- of a system.
ing the fundamental 60 Hz frequency and block-
ing the higher frequency harmonics from affecting In Figure 6, it is very clear to see how Provision
the power line feeding the nonlinear load. Adding displays the measured THD, % of the Funda-
inductors to devices such as computer power sup- mental Triplens by the recorder. In this case, the
plies and UPSs can also reduce triplen harmonics. current magnitude of Channel 1 is 18.67% and
Channel 2 is 12.50%. This can be a very valuable
Another way of reducing triplen harmonics from a tool in analyzing the triplen harmonics of a system
nonlinear load is with a drive isolation transform- at different points in the distribution system. With Figure 4. An isolation
er. Figure 4 shows how an isolation transformer this knowledge of where and what is causing the transformer can improve the
improves the waveform powering single phase excessive triplen harmonics, it allows action to waveform powering single
VFD loads that can cause triplen harmonics. be taken to control the triplen harmonics before phase VFD loads, preventing
equipment damage occurs. triplen harmonics

Drive
Adjustable Isolation Adjustable
Frequency Transformer Frequency
Drive Drive
AC AC
Motor Motor

Other Loads Other Loads

Page 4 WP152 2015 Power Monitors, Inc. Call Us: (800) 296-4120 www.powermonitors.com
WHITE PAPER:
UNDERSTANDING TRIPLEN HARMONICS

Figure 5. Wye (top) versus


A Phase Line Delta (bottom) configuration

Line
B Phase

Load
Source

Neutral Neutral

C Phase Line

Line A Phase

Line
B Phase

Source Load

C Phase Line

Page 5 WP152 2015 Power Monitors, Inc. Call Us: (800) 296-4120 www.powermonitors.com
WHITE PAPER:
UNDERSTANDING TRIPLEN HARMONICS

CONCLUSION

As time progresses, new regulations and technol-


ogies will continue to introduce energy saving
devices such as the switching power supplies,
f luorescent lamps, CFL, LED lighting and other
non-linear electronics. Even though the efficiency
of each individual devices continues to increase,
its effect to the power transmission system may
not always be as positive as first thought. Some-
times improvements in one area, as in improved
efficiency, can often cause problems in another
area, such as nonlinear loads. Triplen harmonics
that are caused by nonlinear loads can cause issues
such as excessive neutral currents, transformer
failures, excessive heating of motors, electronic de-
vice failures, failed capacitor banks, breakers and
fuses tripping, and communication issues related
to RFI and noise ingression into the communica-
tion system. With the right monitoring equipment
and integrated software, and an understanding
of power quality fundamentals, it is possible to
continually and effectively assess overall system
health and prevent potential system failure. Even
though triplen harmonics may not be completely
eliminated, steps can be taken to control them,
such as filtering and designing the system to be
able to handle them by upsizing the neutral lines
and transformer capacities.

Cowles Andrus, III