Sie sind auf Seite 1von 2

Flame detector Comparison

Item Spectrex Net safety Talentum


Spectral Response UV: 0.185 - 0.260 UV Radiation UV : 185 to
um; 185 to 260 260nm
IR: 4.4-4.6 um nanometres
IR Radiation in
IR : 1.0 to
the 4.4 micron
range 2.7m

Power consumption 150mA 130mA 14mA


Detecting range (0.1m2) 15m 20m 25m
Response time (high 150ms 6s (typical) <1s
sense)
View Horizontal 100; Horizontal 90
Vertical 95 100; Vertical
95
Operating Temperature -55C to +75C -50C to - 10C to
range +75C +55C

Output Relay , 4-20mA , Relay , 4-20mA Relay , 4-


HART , MODBUS , HART , 20mA ,
MODBUS
optional
Weight 1.2kg 2.1kg 2.5kg
Approval ATEX and IECEx CSA - Class I, Approval
Ex II 2 GD, Ex de Division 1, Groups Category
IIB+H2 T5 (-55C to + B, C and D - II 2 G D -
75C) Ex de IIB+H2 T4 Temperature code Category 2 or 3
(-55C to + 85C) T5 - CANADA: Class CENELEC / IEC
Ex tD A21 IP66/X7 T 1, Zone 1, Ex d IIB Marking
95C Ex tD A21 IP66/X7 + H2 T5 EEx d IIC T6
T 105C ANSI/UL - Class I, (85C)
FM / CSA Division 1, Groups - Zone 1, 21, 2
Class I Div. 1, Groups B, B, C and D - and 22
C & D , Class II/III Div. Temperature code ISSeP Notified
1, Groups E, F & G T5 - UNITED body No. 492
EN54-10 (LPCB) STATES: Class 1, Apparatus
FM-3260 (FM) Zone 1, AEx d IIB + Certificate No.
IEC61508 - SIL2 (TUV) H2 T5 ISSeP 03ATEX012
ATEX - II 2 G Ex d II LPCB & CPD
B+H2 T5 GOST-R -
1Ex d II BT5/H2
INMETRO - BR-Ex d
II B+H2 T5
Factory Mutual
(FM) 3260
Performance
Certification SIL2
by exida ABS
Marine NEMA
Type 4X IP66 -
Enclosure ratings
Accessories Fire Simulator Tester Tester
Weather Bracket Sunshield
Protector bracket
Laser Pointer
Tilt Mount
Air Shield

Das könnte Ihnen auch gefallen