Section 5

Part Section 5 5
Page 562
Pat of 567 5
Application Manual for NEMA Motors Page 05/08 1
Date 09/07
Application Manual for NEMA Motors
External Connection Diagrams - Single Speed

T1

DWG. #51-676-394 3 PHASE 9 LEAD WYE

T4
T7
LINES CONNECTED
VOLTS CONN.
L1 L2 L3 TOGETHER
LOW T1 T7 T2 T8 T3 T9 T4T5T6 YY
T9 T8 HIGH T1 T2 T3 T4 T7 - T5 T8- T6 T9 Y
T6 T5

T3 T2

DWG. #51-676-397 3 PHASE 9 LEAD DELTA


T1

LINES CONNECTED
VOLTS CONN.
L1 L2 L3 TOGETHER
T9 T4
T6 T7 LOW T1T6T7 T2T4T8 T3T5T9
HIGH T1 T2 T3 T4 T7 - T5 T8- T6 T9

T8 T5
T3 T2

T1

DWG. #51-688-280 PART WINDING START


3 PHASE 9 LEAD WYE
T4
T7
LINES CONNECTED CONN.
L1 L2 L3 TOGETHER
RUN T1 T7 T2 T8 T3 T9 T4T5T6 YY
T9 T8 START T1 T2 T3 T4T5T6 Y
T6 T5

T3 T2
Section 5
Part Section 5 5
Page 563
Part of 567 5
Application Manual for NEMA Motors Page 05/08 2
Date 09/07
Application Manual for NEMA Motors
External Connection Diagrams - Single Speed

DWG. #51-406-529 PART WINDING START


3 PHASE 6 LEAD WYE
T7 T1

LINES L1 L2 L3
START T1 T2 T3 T7T8T9 OPEN
RUN T1 T7 T2 T8 T3 T9
T3 T8
T9 T2

DWG. #51-697-465 6 LEAD WYE DELTA START

T6 T1

T3 T4

T5 T2

LINES CONNECTED CONN.


L1 L2 L3 TOGETHER
START T1 T2 T3 T4T5T6 Y
RUN T1 T6 T2 T4 T3 T5
Section 5
Part Section 5 5
Page 564
Part of 567 5
Application Manual for NEMA Motors Page 05/08 3
Date 09/07
Application Manual for NEMA Motors
External Connection Diagrams - 2 Speeds

CLASS OF SERVICE
AND DWG. NUMBER
SINGLE WINDING

LINES
SPEEDS CONN.
L1 L2 L3
LOW SPEED T1 T2 T3 T4 T5 T6 OPEN Y
#51-110-063 HIGH SPEED T6 T4 T5 T1 T2 T3 TOGETHER YY
T4

VARIABLE T1
TORQUE
T3

T2 T6
T5

#51-110-060 LINES
SPEEDS CONN.
T4 L1 L2 L3
LOW SPEED T1 T2 T3 T4 T5 T6 OPEN
CONSTANT HIGH SPEED T6 T4 T5 T1 T2 T3 TOGETHER YY
TORQUE T3 T1

T2
T5 T6

#51-110-069
LINES
SPEEDS CONN.
L1 L2 L3
T4
LOW SPEED T1 T2 T3 T4 T5 T6 OPEN YY
CONSTANT HIGH SPEED T6 T4 T5 T1 T2 T3 TOGETHER
HORSE-POWER
T3 T1

T5 T6
T2
Section 5
Part Section 5 5
Page 565
Part of 567 5
Application Manual for NEMA Motors Page 05/08 4
Date 09/07
Application Manual for NEMA Motors
External Connection Diagrams - 2 Speeds

CLASS OF SERVICE
AND DWG. NUMBER DOUBLE WINDING

3 PHASE 6 LEAD WYE


LINES
#51-110-062 SPEEDS OPEN CONN.
L1 L2 L3
1) Variable Torque LOW SPEED T1 T2 T3 T11T12T13 Y
HIGH SPEED T11 T12 T13 T1 T2 T3 Y
OR
2) Constant Torque T1 T11
OR
3) Constant
Horse-power

T3 T2 T13 T12