Introduction
Therelaysistheelementthatsensesanabnormalconditioninthecircuitandcommandstheoperationofthebreaker.Theycanbeclassifiedinanumberofways:
Accordingtothequantitysensed:current,voltage,activepower,reactivepower,impedancerelays
Accordingtothetripping:instantaneoustrip,delayedtrip,inversetimecurrentresponse
Accordingtotheoperatingprinciple:electromagneticrelays,inductionrelays,thermalrelays,staticordigitalrelays
Moregeneralclassificationdistinguishtwotypesofrelays:
1.Electromechanicalrelays
2.Digitalrelays
Currently,electromechanicalrelayinallitsformsisbeingreplacedbystatic,digitalandnumericalrelays,eachchangebringingwithitreductionsandsizeand
improvementsinfunctionality.
Inmosttypes(exceptdigitalrelays)therelayscontactsareclosedbyamovingpartwhichsensesaforceproportionaltothecurrent(orothersensedquantity)inthecircuit.
Arestrainingforceproducedbyaspringorothermeanssetsthethresholdabovewhichtherelayoperates.
Inaprotectionrelay,theterm"static"referstotheabsenceofmovingpartstocreatetherelaycharacteristic.Comparedtostaticrelays,digitalrelaysintroducedA/D
conversionofallmeasuredanaloguequantitiesanduseamicroprocessortoimplementprotectionalgorithm.Thedistinctionbetweendigitalandnumericalrelaysrestson
pointsoffinetechnicaldetail,andisrearlyfoundinareasotherthanprotection.Theycanbeviewedasnaturaldevelopmentsofdigitalrelaysasaresultofadvancesin
technology.
Overcurrentrelays
IECdefinitionstatesthatovercurrentrelayisameasuringrelaywhich
operateswhenthevalueofthecurrentexceedsthesetting(operatingvalue)
oftherelay.Therearegenerally3typesoftheserelays:instantaneous,
inverseandinduction.
Relaysareadaptabletotransmissionlines,buses,feedercircuits,
transformersandmotors.
Overcurrentrelaysinstantaneous Relaytimingmechanisms:a)Instantaneous,b)Inversetime,c)Timed
Overcurrentrelaysareelectromagneticrelays.Theyarebasedon
electrodynamicforceproducedonamovingpartbythecurrentflowingthroughacoil.Instantaneousrelaysoperatewithoutintentionaltimedelay.Theyareusedforfaults
closetothesourcewhenthefaultcurrentisveryhigh.Theoperatingtimeisapproximately10ms.Theconstructionofinstantaneousrelaysisusuallymovingarmature,
plunger,orinductiondisk.
Animportantcharacteristicofaninstantaneousrelayisadropoutratio.
dropoutratio=(dropoutcurrent)/(pickupcurrent)
Dropoutratioisusuallylessthan1.
Instantaneousovercurrentrelay
Instantaneousovercurrentprotection
MCTIinstantaneousovercurrentrelay
Overcurrentrelaysinversetime
Timeovercurrentrelaysoperatewithatimedelay,whichisadjustable.Forgivensetting,theactualtimedelaydependsonthecurrentthroughtherelaycoil.Highercurrent
willcauseafasteroperationoftherelay.Theminimumrelayoperationcurrent(pickupcurrent)isalsoadjustable.
Themostcommonlyusedovercurrentrelayhasboththeinstantaneousresponseforverylargecurrentsandtheinversetimeresponseforlowercurrents.
Timeovercurrentrelayscomeinfivedifferentversionsthataredefinedbythesteepnessofthetimeovercurrentcharacteristic:
http://wiki.openelectrical.org/index.php?title=Relays 1/4
5/1/2017 RelaysOpenElectrical
definitetime
moderatelyinverse
inverse
veryinverse
extremelyinverse
Inversetimeovercurrentrelaycharacteristics,
Timeovercurrentrelaycharacteristics,allversions
differentdelaysettings
Inversetimeovercurrentrelay
Overcurrentrelaysinductiondisk
Theinversetimeresponsecanbeprovidedbyaninductiondiskunit.
Intheinductiondiskunit,ametaldiskismountedonashaftthatcanfreelyrotate.Thecurrentcoilsarefixedandcreatemagneticfieldthatinduceseddycurrentsinthe
metaldisk.Themagneticfieldoftheeddycurrentsinteractswiththemagneticfieldofthestationarycoilsandproducetorqueonthedisk.Thediskanditsshaftrotateand
bringthemovingcontacttowardsthefixedcontactintoaclosedposition.
Themotionoftheshaftisopposedbyaspringthatreturnsthediskandthemovingcontactintotheopenpositionwhenthecurrentdropsbelowapresetvalue.Thetimeto
closethecontactdependsonthecontacttraveldistancewhichissetbyatimedial.Thepickupcurrentisadjustablebyselectingcurrenttapsonthecurrentcoil.Therelays
arenormallyavailablewiththreerangesofcurrenttaps:0.5to2.0A,1.5to6.0A,and4to16A.Thetimedialhasusuallypositionsmarkedfrom0to10,wherefor0
settingthecontactispermanentlyclosed.
Inductiondiskovercurrentrelay
Inductiondisktyperelay
Recommendedsettingsforovercurrentprotection
Moreonrecommendedsettingsforovercurrentdevices:OvercurrentProtection
Smallairbreakersforlowvoltagedomesticcircuits
CircuitbreakersthatareusedatthedistributionboardinhousesarecalledMCBs(minaturecircuitbreakers).Thedistributionboardisalsocalledtheconsumerunit.
Thermal
Theloadcurrentispassedthroughasmallheater,thetemperatureofwhichdependsuponthecurrentitcarries.Theheaterwillwarmupabimetalstrip.Whenexcessive
currentflowsthebimetalstripwillwarptotripthelatchmechanism.
Somedelayoccursowingtothetransferofheatproducedbytheloadcurrenttothebimetalstrip.Thermaltripsaresuitableonlyforsmalloverloadsoflongduration.
Excessiveheatcausedbyheavyoverloadcanbuckleanddistortthebimetalstrip.
Magnetic
Theprincipleusedinthistypeisthemagneticforceofattractionsetupbythemagneticfieldofacoilcarryingtheloadcurrent.Atnormalcurrentsthemagneticfieldisnot
strongenoughtoattractthelatch.Overloadcurrentswillincreasetheforceofattractionandoperatethelatchtotripthemaincontacts.
Insidea10ampthermalmagneticcircuitbreaker.Thesecircuitbreakersarestandardinmoderndomesticandcommercialelectricaldistributionboards.
http://wiki.openelectrical.org/index.php?title=Relays 2/4
5/1/2017 RelaysOpenElectrical
SimpleMCB
Crosssectionofthethermalmagneticcircuit
Thermalmagneticcircuitbreaker(1Ph+N)2A250VAC
breaker
Typicalmagneticcircuitbreaker
Numberdescription:
1.Actuatorleverusedtomanuallytripandresetthecircuitbreaker.Alsoindicatesthestatusofthecircuitbreaker(On/Off/tripped).
2.Actuatormechanismforcesthecontactstogetherorapart.
3.ContactsAllowcurrenttoflowwhentouchingandbreaktheflowofcurrentwhenmovedapart.
4.Terminals
5.Bimetallicstrip
6.Calibrationscrewallowstoadjustthetripcurrentofthedeviceafterassembly.
7.Solenoid
8.Arcdivider/extinguisher
Differential(unit)protection
Differentialprotectionisaveryreliablemethodofprotectinggenerators,transformers,buses,andtransmissionlinesfromtheeffectsofinternalfaults.Innormaloperating
conditions,thecurrentthroughtheCTsisthesamesotherelayseesnodifferentialcurrent.Thisisalsothecaseforexternalfaults.Differentialprotectioncanbeusedfor
protectinggeneratorsfromfaultstoground.DifferentialprotectionofbusbarsinsubstationsusesoneCTforeachincomingline.Allincomingcurrentsareaddedupand
comparedtothesumofalloutgoingcurrents.
MicroprocessorbasedSEL387Llinecurrentrelay
Generalschematicsofthedifferentialrelay
Differential(unit)protectionfortransformers
Inapplyingtheprinciplesofdifferentialprotectiontotransformers,avarietyofconsiderationshavetobetakenintoaccount.Theseinclude:
a)correctionforpossiblephaseshiftacrossthetransformerwindings(phasecorrection)
b)theeffectsofthevarietyofearthingandwindingarrangements(filteringofzerosequencecurrents)
c)correctionforpossibleunbalanceofsignalsfromcurrenttransformersoneithersideofthewindings(ratiocorrection)
d)theeffectofmagnetisinginrushduringinitialenergisation
e)thepossibleoccurrenceofoverfluxing
Theprimaryandsecondarycurrentshavedifferentmagnitudesandphases,sothemagnitudeandthephaseshiftmustbebalancedbyappropriateratiooftheCTs.Ifthe
transformerisY,thecurrentsalsohave30phaseshift.ThephaseshiftiscorrectedbyconnectingtheCTsonthesideinY,andontheYsidein.
CooperPowerSystemsiXP420differentialrelay,suitablefortransformers
Differentialprotectionintransformers
Whenusedontheoverheadlines,thedifferentialprotectionhasthepracticallengthlimitationof40kmforproblemswiththepilotwire(wireusedtotransferstatedataof
theprotectedline,i.e.tosendinformationifthefaulthasoccured).
Distancerelays
Theimpedanceofatransmissionlineisproportionaltoitslength,fordistancemeasurementitisappropriatetousearelaycapableofmeasuringtheimpedanceofalineup
toapredeterminedpoint(thereachpoint).Sucharelayisdescribedasadistancerelayandisdesignedtooperateonlyforfaultsoccurringbetweentherelaylocationandthe
selectedreachpoint,thusgivingdiscriminationforfaultsthatmayoccurindifferentlinesections.
Thebasicprincipleofdistanceprotectioninvolvesthedivisionofthevoltageattherelayingpointbythemeasuredcurrent.Theapparentimpedancesocalculatedis
comparedwiththereachpointimpedance.Ifthemeasuredimpedanceislessthanthereachpointimpedance,itisassumedthatafaultexistsonthelinebetweentherelay
andthereachpoint.Thereachpointofarelayisthepointalongthelineimpedancelocus(setofpoints)thatisintersectedbytheboundarycharacteristicoftherelay.Since
thisisdependentontheratioofvoltageandcurrentandthephaseanglebetweenthem,itmaybeplottedonanR/Xdiagram.Thelociofpowersystemimpedancesasseen
bytherelayduringfaults,powerswingsandloadvariationsmaybeplottedonthesamediagramandinthismannertheperformanceoftherelayinthepresenceofsystem
faultsanddisturbancesmaybestudied.
http://wiki.openelectrical.org/index.php?title=Relays 3/4
5/1/2017 RelaysOpenElectrical
Generalsettingofthedistanceprotection
Threezonestepdistancerelayingtoprotect100%ofalineand
backuptheneighbourline TecQuipmentPS250distancerelay
Asthepowersystemsbecomemorecomplexandthefaultcurrentvarieswithchangesingenerationandsystemconfiguration,directionalovercurrentrelaysbecome
difficulttoapplyandtosetforallcontingencies,whereasthedistancerelaysettingisconstantforawidevarietyofchangesexternaltotheprotectedline.
Followingtopicsgivethemainoverviewoverthedifferentdistancerelaytypes:
Impedancerelays
Impedancerelaysareusedwheneverovercurrentrelaysdonotprovideadequateprotection.Theyfunctioneveniftheshortcircuitcurrentisrelativelylow.Thespeedof
operationisindependentofcurrentmagnitude.
Therelayconsistsofabalancedbeam.Ateachendofthebalancedbeamisacoilthatexertsaforceonthebeamatthatend.Onecoilisconnectedtoacurrenttransformer,
theothercoiltoapotentialtransformer.Undernormalconditions,thecontactoftherelayiskeptopen.Duringafault,thevoltagedrops,andthecurrentrises.Thetorque
duetothecurrentcoiloverpowersthetorqueduetothevoltagecoil,andtherelayclosesitscontact.
TheimpedancerelayhasacircularcharacteristiccenteredattheoriginoftheRXdiagram.Itisnondirectionalandisusedprimarilyasafaultdetector.
Admittancerelays
Theadmittancerelayisthemostcommonlyuseddistancerelay.Itisthetrippingrelayinpilotschemesandasthebackuprelayinstepdistanceschemes.Itscharacteristic
passesthroughtheoriginoftheRXdiagramandisthereforedirectional.Intheelectromechanicaldesignitiscircular,andinthesolidstatedesign,itcanbeshapedto
correspondtothetransmissionlineimpedance.
Reactancerelays
Thereactancerelayisastraightlinecharacteristicthatrespondsonlytothereactance(XL)oftheprotectedline.Itisnondirectionalandisusedtosupplementthe
admittancerelayasatrippingrelaytomaketheoverallprotectionindependentofresistance.Itisparticularlyusefulonshortlineswherethefaultarcresistanceisthesame
orderofmagnitudeasthelinelength.
Trivia