Figure 1
2.

Figure 2
3. An interconnected generator-reactor system is shown in Fig. 3. The base values
for the given percent reactance are the ratings of the individual pieces of equipment.
A three-phase short-circuit occurs at point F. Determine the fault current and the
fault kVA if the bus bar line-to-line voltage is 11kV. Assume 50MVA as the base
MVA

15MVA 30MVA 30MVA


10% 15% 15%
G1 G2 G3

X1 X2
10MVA 8MVA
F× 10% 5%

Figure 3

4. The system shown in Fig. 4 is initially on no load. Calculate the sub-transient fault
current that results when a three-phase fault occurs at F, given that the transformer
voltage on the high-voltage side is 66kV.

60MVA
13.8kVA
Xd" = 0.25pu
G1
30MVA F
13.8kV ×
Xd" = 0.25pu ∆Y
G2
Figure 4