GLOBAL STANDARD Page 1 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

RGDAT

This document has the objective to specify the functions and provide for construction and
testing instruction of Directional Fault Passage Indicator (DFPI/RGDAT).

Countries
Elaborated by Verified by Approved by
I&N NT/RCP

Argentina Head of Local RCP

Brasil Victor Manuel Galvao Macedo Cost

Chile Hans Christian Rother Salazar

Colombia Cesar Augusto Rincon Alvarez

Iberia Maria Avery Fernandez

Italy Lilia Consiglio

Peru Roberto Leonidas Sanchez Vargas

Romania Marius Mihai Domnicu

Elaborated by Verified by Approved by


Maria Avery
Giorgio Di Lembo/
Global I&N NT/RCP Fernandez/Carmen Giorgio Di Lembo
Roberto Calone
Ranea/Jaume Badia

This document is intellectual property of Enel Spa; reproduction or distribution of its contents in any way or by any means whatsoever is
subject to the prior approval of the above mentioned company which will safeguard its rights under the civil and penal codes.
It is for internal Use. Each Country can provide a translation in local language but the official reference document is this GS English
version.

Revision Data List of modifications


00 15.12.2015 First version
Par. 6.3 and 6.4: reduction to 10A and to 2A the steps in the setting of phase overcurrent
01 10.02.2016
and residual overcurrent respectively. Editorial amendments.
GLOBAL STANDARD Page 2 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

INDEX

0 ACRONYMS ........................................................................................................................................... 5
1 SCOPE ................................................................................................................................................... 6
2 REFERENCE STANDARDS .................................................................................................................. 6
3 COMPONENTS IDENTIFICATION ........................................................................................................ 8
3.1 INFORMATION FOR PURCHASING ............................................................................................................. 9
3.2 COMPONENTS TRACKING ....................................................................................................................... 9
4 FUNCTIONS ......................................................................................................................................... 10
4.1 CHARACTERISTICS OF THE REFERENCE NETWORK ................................................................................. 10
4.2 ANALOGICAL INPUTS ............................................................................................................................ 11
4.3 EVENTS TO BE DETECTED..................................................................................................................... 11
5 TYPE OF DEVICES .............................................................................................................................. 12
6 FUNCTIONS ......................................................................................................................................... 13
6.1 INSTALLATION LAYOUTS ....................................................................................................................... 13
6.2 DETECTION OF PHASE TO GROUND FAULT: FUNCTIONAL REQUIREMENTS ................................................. 14
6.3 PHASE OVERCURRENT FUNCTION: FUNCTIONAL REQUIREMENTS ............................................................. 17
6.4 RESIDUAL OVERCURRENT FUNCTION: FUNCTIONAL REQUIREMENTS ........................................................ 17
6.5 OPTIONAL TIMERS FOR PROTECTION FUNCTIONS ................................................................................... 18
6.6 OPTIONAL TIMERS SIGNALLING ............................................................................................................. 19
6.7 PROTECTION FUNCTIONS: 59VO, 59VI AND 59VD ................................................................................. 20
6.8 VSS FUNCTION .................................................................................................................................... 20
6.9 VOLTAGE PRESENCE: FUNCTIONAL REQUIREMENTS ............................................................................... 20
6.10 LOGICAL OUTPUTS ........................................................................................................................... 21
6.11 LOGICAL INPUTS .............................................................................................................................. 22
6.12 LOCAL LED SIGNALS ........................................................................................................................ 23
6.13 VOLTAGE MONITORING PROCEDURE................................................................................................. 23
6.14 EVENT RECORDER ........................................................................................................................... 25
7 ENVIRONMENTAL OPERATING CONDITIONS ................................................................................. 25
8 CONSTRUCTIVE CHARACTERISTICS .............................................................................................. 25
9 ELECTRICAL CHARACTERISTICS..................................................................................................... 25
10 RGDAT-A70 .......................................................................................................................................... 26
10.1 CONNECTIONS FOR COLLECTING VOLTAGE SIGNALS ........................................................................... 26
GLOBAL STANDARD Page 3 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

10.2 MEASUREMENT CIRCUITS ................................................................................................................. 26


10.2.1 CAPACITIVE PLUG CHARACTERISTICS OF SECONDARY SUBSTATION PANELS ..................................... 26
11 RGDAT-A70/C ...................................................................................................................................... 27
11.1 CURRENT TRANSDUCERS CONNECTIONS ........................................................................................... 27
11.2 CONNECTIONS FOR COLLECTING VOLTAGE SIGNALS ........................................................................... 28
11.3 MEASUREMENT CIRCUITS ................................................................................................................. 28
11.3.1 CAPACITIVE PLUG CHARACTERISTICS OF SECONDARY SUBSTATION PANELS ..................................... 28
11.3.2 CURRENT TRANSDUCER CHARACTERISTICS ................................................................................... 28
12 RGDAT-A70/M ...................................................................................................................................... 31
12.1 CONNECTIONS TOWARD CURRENT TRANSDUCERS ............................................................................. 31
12.2 CONNECTIONS FOR COLLECTING VOLTAGE SIGNALS ........................................................................... 31
12.3 MEASUREMENT CIRCUITS ................................................................................................................. 32
12.3.1 CAPACITIVE DIVIDER CHARACTERISTICS ......................................................................................... 32
12.3.2 CURRENT TRANSDUCER CHARACTERISTICS ................................................................................... 32
13 RGDAT/A .............................................................................................................................................. 32
13.1 CONNECTIONS TOWARD CURRENT TRANSDUCERS ............................................................................. 32
13.2 CONNECTIONS FOR COLLECTING VOLTAGE SIGNALS ........................................................................... 32
13.3 MEASUREMENT CIRCUITS ................................................................................................................. 33
13.3.1 CAPACITIVE DIVIDER CHARACTERISTICS ......................................................................................... 33
13.3.2 CURRENT TRANSDUCER CHARACTERISTICS ................................................................................... 33
14 RGDAT-A70/O ...................................................................................................................................... 33
14.1 RGDAT-A70/O: INSTALLATION ON POLE .......................................................................................... 34
14.2 RGDAT-A70/O: INSTALLATION ON RAISED MV/LV SUBSTATION ........................................................ 36
14.3 COMBINED SENSORS TYPE-1 (24KV) ............................................................................................... 37
14.4 COMBINED SENSORS TYPE-2 (36KV) ............................................................................................... 38
14.5 RESIDUAL CURRENT CALCULATION .................................................................................................... 39
14.6 VOLTAGE INPUTS ............................................................................................................................. 39
15 CONNECTION TO REMOTE MONITORING PERIPHERAL UNIT ..................................................... 40
15.1 SIGNAL RELAY CONTACTS ................................................................................................................. 41
15.2 MEASUREMENT CONVERTERS ........................................................................................................... 41
15.3 SELF DIAGNOSIS .............................................................................................................................. 42
15.4 DEVICE CONFIGURATION AND PROGRAMMING .................................................................................... 42
16 TEST ..................................................................................................................................................... 42
16.1 TEST LIST ........................................................................................................................................ 42
GLOBAL STANDARD Page 4 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

16.2 TYPE TESTS ..................................................................................................................................... 43


16.3 ACCEPTANCE TESTS ........................................................................................................................ 45
16.4 VISUAL INSPECTION.......................................................................................................................... 45
16.5 INSULATION AND DIELECTRIC STRENGTH TESTS ................................................................................. 45
16.6 VERIFICATION OF ALL FUNCTIONS...................................................................................................... 46
16.7 OUT OF RANGE SUPPLY TESTS .......................................................................................................... 47
16.8 IMMUNITY TESTS (ELECTROMAGNETIC INTERFERENCES) .................................................................... 47
16.9 THERMAL BEHAVIOUR TESTS............................................................................................................. 47
16.10 MECHANICS COMPATIBILITY TESTS .................................................................................................... 47
16.11 CLIMATIC TESTS............................................................................................................................... 48
16.12 FUNCTIONAL FINAL TEST................................................................................................................... 48
17 COMPONENTS AND ACCESSORIES FOR RGDAT-A70/A ............................................................... 57
18 COMPONENTS AND ACCESSORIES FOR RGDAT-A70/M .............................................................. 58
19 COMPONENTS AND ACCESSORIES FOR RGDAT-A70/O .............................................................. 59
19.1 QUANTITY........................................................................................................................................ 68
APPENDIX 1 EXAMPLE OF INSTALLATION LAYOUT RGDAT-A70/O (UP OUTDOOR) ......................... 69
APPENDIX 2 ADDITIONAL ENVIRONMENTAL TESTS FOR COMBINED SENSORS ............................. 70
APPENDIX 3 DESCRIPTION OF TEST CASES FOR RGDAT-A70 DEVICE FUNCTIONAL TEST ........ 72
APPENDIX 4 SOME EXAMPLES FOR DETECTION OF VOLTAGE PRESENCE/ABSENCE .................. 84
APPENDIX 5 CHECKING TESTS FOR CURRENT SENSORS .................................................................. 85
GLOBAL STANDARD Page 5 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

0 Acronyms
RGDAT directional fault passage and voltage indicator
UP Remote Terminal Unit for the remote control of the secondary substations
GLOBAL STANDARD Page 6 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

1 Scope
This document intends to specify the functions and provides the requirements for the construction
and testing of the Directional Fault Passage Indicator and voltage detector (RGDAT) for remote
controlled MV/LV substations.

2 Reference standards
Measuring relays and protection equipment - Part 27: Product
IEC 60255-27:2013 (former IEC 60255-5)
safety requirements
Electromagnetic compatibility (EMC) - Part 4-2: Testing and
IEC 61000-4-2:2008 measurement techniques - Electrostatic discharge immunity
test
Electromagnetic compatibility (EMC) - Part 4-12: Testing and
IEC 61000-4-12:2006
measurement techniques - Ring wave immunity test
Electromagnetic compatibility (EMC) - Part 4-18: Testing and
IEC 61000-4-18:2006+AMD1:2010 CSV measurement techniques - Damped oscillatory wave immunity
test
Electromagnetic compatibility (EMC) Part 4-4: Testing and
IEC 61000-4-4:2012 RLV measurement techniques Electrical fast transient/burst
immunity test
Electromagnetic compatibility (EMC) - Part 4-5: Testing and
IEC 61000-4-5:2014
measurement techniques - Surge immunity test
Electromagnetic compatibility (EMC) Part 4-8: Testing and
IEC 61000-4-8:2009 RLV measurement techniques Power frequency magnetic field
immunity test
Electromagnetic compatibility (EMC) - Part 4-10: Testing and
IEC 61000-4-10:1993+AMD1:2000 CSV measurement techniques - Damped oscillatory magnetic field
immunity test
Electromagnetic compatibility (EMC) - Part 4-3: Testing and
IEC 61000-4-3:2006+A1:2007+A2:2010 measurement techniques - Radiated, radio-frequency,
electromagnetic field immunity test
Electromagnetic compatibility (EMC) - Part 4-29: Testing and
IEC 61000-4-29:2000 measurement techniques - Voltage dips, short interruptions and
voltage variations on d.c. input power port immunity tests
Electromagnetic compatibility (EMC) Part 4-16: Testing and
measurement techniques Test for immunity to conducted,
IEC 61000-4-16:2015 PRV
common mode disturbances in the frequency range 0 Hz to 150
kHz
Electromagnetic compatibility (EMC) - Part 4-6: Testing and
IEC 61000-4-6:2013 measurement techniques - Immunity to conducted
disturbances, induced by radio-frequency fields
IEC 60068-2-2:2007 Environmental testing - Part 2-2: Tests - Test B: Dry heat
Environmental testing Part 2-78: Tests Test Cab: Damp
IEC 60068-2-78:2012 RLV
heat, steady state
IEC 60068-2-1:2007 Environmental testing - Part 2-1: Tests - Test A: Cold
Environmental testing - Part 2-14: Tests - Test N: Change of
IEC 60068-2-14:2009
temperature
GLOBAL STANDARD Page 7 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

IEC 60068-2-6:2007 Environmental testing - Part 2-6: Tests - Test Fc: Vibration (sinusoidal)
Environmental testing - Part 2-64: Tests - Test Fh: Vibration,
IEC 60068-2-64:2008
broadband random and guidance
IEC 60529:1989+AMD1:1999+AMD2:2013 CSV Degrees of protection provided by enclosures (IP Code)
Tests on electric and optical fibre cables under fire conditions - Part 3-
IEC 60332-3-10:2000+AMD1:2008 CSV 10: Test for vertical flame spread of vertically-mounted bunched wires
or cables - Apparatus
Artificial pollution tests on high-voltage ceramic and glass insulators to
IEC 60507:2013
be used on a.c. systems
Insulators for overhead lines with a nominal voltage above 1000 V -
IEC 60383-2:1993 Part 2: Insulator strings and insulator sets for a.c. systems -
Definitions, test methods and acceptance criteria
Fire hazard testing - Part 11-10: Test flames - 50 W horizontal and
IEC 60695-11-10:2013
vertical flame test methods
Insulators for overhead lines - Composite insulator for a.c. overhead
IEC 1109:1992+AMD:1995 lines with a nominal voltage greater than 1 000 V - Definitions, test
methods and acceptance criteria
GLOBAL STANDARD Page 8 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

3 Components Identification

SERIAL
TYPE DEVICE
NUMBER

Multifunction Directional Fault Passage


DY1059-A70 Indicator electronic control unit and 160000
accessories for voltage collection-

DY 1059-A70/C Multifunction Directional Fault Passage


160001
Indicator for cable lines

DY 1059-A70/M Multifunction Directional Fault Passage


160002
Indicator for mixed lines

DY 1059-A70/A Multifunction Directional Fault Passage


160003
Indicator for overhead lines

Multifunction Directional Fault Passage for


DY 1059-A70/O-TYPE1 160004
OUTDOOR installations (24kV max)

Multifunction Directional Fault Passage for


DY 1059-A70/O-TYPE2 160005
OUTDOOR installations (36kV max)

Example of short description:

RGDA T A7 0 F AU L T DE T E C TOR MV - O T Y P E - 1

RGDA T A7 0 F AU L T DE T E C TOR MV - O T Y P E - 2

RGDA T A7 0 F AU L T DE T E C TOR MV - C

RGDA T A7 0 F AU L T DE T E C TOR MV - M

RGDA T A7 0 F AU L T DE T E C TOR MV - A

RGDA T A7 0 CONT RO L UN I T
GLOBAL STANDARD Page 9 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

3.1 Information for purchasing


The following tables provide a help in order to choose the correct serial number.

Voltage Level Pole Height SERIAL


TYPE
[VL] [PH] NUMBER
VL<24kV PH<16m DY 1059-A70/O-TYPE1 160004
VL<24kV 16m<PH<26m DY 1059-A70/O-TYPE2 160005
24kV<VL<36kV PH>16m DY 1059-A70/O-TYPE2 160005
Table 1 -Outdoor installation-

Voltage Level SERIAL


TYPE
[VL] NUMBER
VL<36kV DY 1059-A70/C 160001
1
VL<36kV DY 1059-A70/M 160002
2
VL<36kV DY 1059-A70/A 160003
Table 2 -Indoor and mixed installation-

3.2 Components tracking


All the RGDAT-A70 samples shall be provided with rating plate as specified in the ENEL standard
PVR06.

1
For application see paragraph 12.
2
For application see paragraph 13.
GLOBAL STANDARD Page 10 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

4 Functions
RGDAT-A70 is a device provided to be installed in correspondence of MV line bays of remote
controlled MV/LV substations, to locate the presence of faults and the absence of voltage signal on
the line.

4.1 Characteristics of the reference network


The networks where RGDAT-A70 will be installed can be operated with:
insulated neutral;
neutral earthed through an inductance with in parallel a resistor;
neutral earthed through an resistor;
neutral directly earthed.
The characteristics of the reference networks are:
- Rated voltage: from 6kV to 25kV 10%
- Maximum current of three-phase short circuit: 20kA
- Maximum value of time constant of the phase unidirectional
component decay: 20ms
- Maximum single phase ground fault current (insulated neutral earth): 500A
- Maximum single phase ground fault current (neutral earthed through a
resistor): 1000A
- Maximum single phase ground fault current (neutral earthed through an
inductance): 1000A
- Maximum single phase ground fault current (neutral directly earthed): 20kA
- Peak value of the unidirectional component of the current added to single-
phase ground fault current (neutral compensated ): 707A
- Maximum value of time constant of the residual unidirectional
component decay: 150ms
- Zero sequence Voltage in healthy network condition: (0-5)% of Ph-E Voltage
- Harmonic content in current: within prescribed limits by EN50160
- network rated frequency 50Hz or 60Hz
- frequency range fn=50Hz 47,5Hz51,5Hz
- frequency range fn=60Hz 57,5Hz61,5Hz
GLOBAL STANDARD Page 11 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

4.2 Analogical Inputs


RGDAT-A70 shall measure:
- phase current and residual current, through current transducer installed in correspondence of
MV line bays;
- line voltage, using voltage signals supplied by capacitor divider that, usually are installed on
panel to detect the voltage presence.
Regarding the current measurement, RGDAT-A70 can use:
2 Current sensors for measuring two-phase current and 1 current sensor for measuring residual
current or alternately:
3 Current sensors for measuring three-phase current, from which obtain also the residual current.
The sensors must be Rogoswki coils with rated ratio 1000A/100mV.

4.3 Events to be detected


RGDAT-A70 shall detect, through the measurements on the previous paragraph, the following
events:
- passage of phase over-currents exceeding a settable threshold, whose default value is 500A
(overcurrent function);
- passage of residual currents in the presence of zero sequence voltage due to a ground single-
phase fault (function of directional measurement of ground fault);
- passage of residual current in the presence of zero sequence voltage due to double-phase to
ground fault (over zero sequence current function);
- voltage presence/absence on MV line;
- presence of generic ground fault (zero sequence overvoltage Vo);
- presence of two-phase fault (positive undervoltage Vd, negative overvoltage Vi).

In paragraphs 6.2, 6.3, 6.4, 6.6, 6.8, 6.9 are specified the requirements relating to the detection
functions of the aforementioned events.
GLOBAL STANDARD Page 12 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

5 Type of devices
There are different versions of the device depending on the system type on which they should be
installed. Particularly, it should refer to the following 4 versions:

RGDAT-A70
It is formed by a single electronic control part, along with the accessories for UP connection and
the collection of the single voltage signals. It will be installed near the MV cells on panels endowed
with capacitor divider voltage transducer DJ1054 (approved by ENEL). In this case, the supplied
device is constituted by:
RGDAT-A70;
wiring and accessories for installation.

RGDAT-A70/C
Suitable to install on MV cable lines connected with panels endowed with capacitor divider voltage
transducer DJ1054 (approved by ENEL). In this case, the supplied device is constituted by:
RGDAT-A70;
opening current transducer for cables;
wiring and accessories for installation.

RGDAT-A70/M
Suitable to install on MV cable lines connected with connected with busbar systems with bare
conductors. In this case, the supplied device is constituted by:
RGDAT-A70;
mounting plate and assembling accessories;
DJ1054 current transducer assembled on a crossbeam;
Transducer crossbar to secure on a station case shelf (Figure 22);
opening current transducer for cables;
wiring and accessories for installation.

RGDAT-A70/A
Suitable to install on bare conductor MV lines connected with busbar systems with bare
conductors. In this case, the supplied device is constituted by:
RGDAT-A70;
mounting plate and assembling accessories;
DJ1054 voltage transducer assembled on a crossbeam;
Crossbeam transducer for fixing on the wall (Figure 20);
Closed type current transducer to install on the cross-wall insulators present in the upper part
of the substation (Figure 21);
wiring and accessories for installation.
GLOBAL STANDARD Page 13 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

RGDAT-A70 /O
Suitable for OUTDOOR. In this case, the supplied device is constituted by:
RGDAT-A70;
crossbeam for fixing and mounting accessories;
current/voltage transducers mounted on crossbar;
wiring and accessories for installation.
RGDAT-A70 is the control system electronic part, shall be the same for each of the four versions.
Therefore it shall allow the right configuration in case of presence of 2 phase current sensors + 1
residual current sensor or 3 phase current sensors (RGDAT-A70/ O).

6 Functions

6.1 Installation layouts


The installation layouts of RGDAT-A70 device are illustrated in the following figures:

normal power
direction

MV line

bar

RGDAT
Secondary
substation

Figure 1 -RGDAT-A70 installed on output backbone line.

normal power
direction

MV line

bar
RGDAT
Secondary
substation

Figure 2 RGDAT-A70 installed on input backbone line.


GLOBAL STANDARD Page 14 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

MV line

bar

Secondary
substation

RGDAT

Figure 3 -RGDAT-A70 installed on shunt line.


With reference to the line power source direction, RGDAT-A70 device shall detect fault conditions
on the downstream sector of the installation point. In order to satisfy this requirement in any case
listed in the previous figures and in any power source condition of the MV line, is required a specific
feature, following called inversion. Direction inversion is remotely controlled through the remote
control unit device.

6.2 Detection of phase to ground fault: functional requirements3


The device shall detect downstream ground faults both on isolated neutral grid and on
compensated neutral grid, without requiring changes to the arrangements in the passage from one
network type to another.
Furthermore the device shall detect downstream ground faults occurring during the circuit breaker
closing. The above-mentioned fault condition shall be recognised even in the absence of voltage in
capacitive plug before the fault closure (energization of the grips resulting from the closure of the
control device).
The detection of the ground fault shall be guaranteed for fault resistance values able to generate:
- a zero sequence voltage equal to a settable value at least in the phase voltage range of 1-
40%, with a step of 1% (15% accuracy on the set value);
- a residual current equal to a settable value from 1A to 40A (primary values) with a step of
0,5 (15% accuracy on the set value) default 1A;
- a related phase shift between zero sequence voltage and residual current that falls within
the following intervention area.
The intervention condition shall correspond to the contemporary presence of the three previous
conditions (logical AND).

3
If the neutral is earthed just through an inductance, the directional functions cant work properly.
In this case the functions 67NS1 and 67NS2 have to be off, and 51N should be used.
GLOBAL STANDARD Page 15 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

For ground faults that dont need the intervention condition, the device should not emit any signal.
The tripping times connected with this function are the following:
- insensitivity (fault duration to not detect) 40ms
- fault duration to detect starting from energised capacitive
plug (both operated with isolated neutral networks and
neutral solidly earthed) 80ms
- tripping time in case of fault starting from energised capacitive plug. 150ms
- fault duration to detect starting from non-energised
capacitive plug (both with isolated neutral operated
networks and neutral solidly earthed) 150ms
- tripping time in case of fault starting from non-
energised capacitive plug (closure on fault) 170ms
- release time 100ms
- time error 3%20ms
Tripping time shall be measured from the starting fault time to the emission time of the output
signal. The fault starting time is defined as the time in which the three conditions above-mentioned
are verified.
RGDAT-A70 shall have two earth directional protection thresholds, 67NS1 and 67NS2, each one
excludable through the configuration SW. The default for the device shall consider the 67NS2
threshold as excluded.
Considering the lagging angle of the residual voltage respect to zero sequence voltage, with the
insertion modes specified in the paragraph 6.1, the tripping area sectors shall be the following:
DEFAULT
67NS1 60255;
67NS2 60120;
The inverted sectors for this threshold (UD input=TRUE)
INVERTED SECTORS
67NS1 24075;
67NS2 240300;
Faults in 67NS2 sector shall cause the contemporaneous closure of the output contacts 51 and 67.
Faults in 67NS1 sector shall cause only the closure of the output contact 67.
- accuracy zero sequence voltages in the range
1-120% and residual currents in the range 1150A 2;
- hysteresis in leaving the sector 3
As example reports the inversion effect for the threshold 67NS1, this effect shall be that of rotating
the intervention sector by an angle equal to 180 (cf. Fig.).
GLOBAL STANDARD Page 16 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

DEFAULT Vo INVERTED
Vo

60
75

255

240

RGDAT-A70 shall be able to recognize intermittent type faults. The function shall be able to detect
the presence of an earth voltage arc with intermittent characteristics, activating a suitable
integrator, and, in this case, it have to render the output signal on relay 67, permanent during the
fault duration.
The measurement function of the single phase ground fault current is not mandatory for faults with
intermittent arc characteristics. In any case, the device shall not give wrong signals.
RGDAT-A70 shall permit, through a SW flag, to choose instead of the zero sequence Voltage Vo,
the negative sequence Voltage Vi as reference for intervention sectors.
The detection of the ground fault shall be guaranteed for fault resistance values able to generate:
- a negative sequence voltage equal to a settable value at least in the phase voltage range
of 1-40%, with a step of 1% (15% accuracy on the set value);
- a residual current equal to a settable value from 1A to 200A (primary values) with a step of
0,5 (15% accuracy on the set value) default 1A;
a related phase shift between negative sequence voltage and residual current that falls within the
following intervention area:
GLOBAL STANDARD Page 17 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

6.3 Phase overcurrent function: functional requirements


The device shall detect over-current that exceed the tripping threshold set, even in case of closure
on fault (current and voltage absent in the RGDAT-A70 installation point before closing).
Such function shall satisfies the following requirements:
- tripping threshold (Iint) (100900)A step 10A
default 500A 10%
- fault duration to not detect 40 ms
- fault duration to detect
(both starting from energized MV line, and in
case of closure on fault starting from
no-energized MV line) 80ms
- maximum tripping time (Imis = 1,2 Iint) 120 ms
- maximum tripping time (Imis = 2Iint) 80 ms
- closure on fault, tripping time: no change compared with above-mentioned.
- release time 80 ms
- time error 3%20ms
- starting time (with no intentional delay) 45 ms 10ms

6.4 Residual overcurrent function: functional requirements


The device shall detect over-current that exceed the tripping threshold set, even in case of closure
on fault (current and voltage absent in the RGDAT-A70 installation point before closing).
Such function, typical of cross-country fault, shall satisfies the following requirements:
- no-directional tripping threshold on residual current (Iint) (10 200)A step 2A
default 150A 10%
- fault duration to not detect 40 ms
- fault duration to detect
(both starting from energized MV line, and in
case of closure on fault starting from
no-energized MV line) 80 ms
- maximum tripping time (Imis= 1,2Iint) 120 ms
- maximum tripping time (Imis=2Iint) 100 ms
- closure on fault, tripping time no change compared with above-mentioned
- release time 80ms
- time error 3%20ms
- starting time (with no intentional delay) 45 ms 10 ms
The settings default for phase overcurrent and residual overcurrent functions shall be such that
functions are operative at the same time with the earth directional fault function (67N). Furthermore
RGDAT-A70 shall allow the exclusion of 67N function, leaving operative the two no-directional
overcurrent functions (even the calibration possibility of voltage inputs is disabled). In that case
RGDAT-A70 will operate without the protection function 67N. To evidence this mode, the indication
LED 67 located on front to the device will flash.
GLOBAL STANDARD Page 18 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

6.5 Optional timers for protection functions


Normally the timers for the functions: 51, 51N and 67N shall be set on the default values.
RGDAT-A70 shall permit, through a flag (see red circle in Figure 4), the setting on others timer
values as showed in the Figure 4.
Farther RGDAT-A70 shall permit the changing of the current full-scale associated (see yellow circle
in Figure 4) with remote measurement.

Figure 4 -Example of setting window for timers.


GLOBAL STANDARD Page 19 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

6.6 Optional timers signalling


Normally the behaviour of the signalling TS67 and TS51 is as above described.
RGDAT-A70 shall permit, through a flag (see red circle in Figure 5), the switch on other behaviour.
In detail:
- The command of relay 51 must be issued only when, after tripping of thresholds 51, 51N or
67NS2, the condition of "Voltage Absent" is detected within a certain time (T1,
programmable, default setting: 0.5 s).
- The command of relay 67 must be issued only when, after tripping of thresholds 67NS1 or
67NS2, the condition of "Voltage Absence" is detected within a certain time (T1,
programmable, default setting: 0.5 s).
- The return to quiescent status of relays 51 and 67 must occur when "Voltage Presence"
condition is detected and that condition holds for a certain time
time (T2, programmable, default
setting: 10 s).
- If there is no return of power within a certain time (T3, programmable, default setting: 4
hours), output contacts 51 and 67 return to quiescent status anyway.
According to the previous points:
- LEDs 51 and 67 must follow the state of respective relay.
- Event logging must also records the issuance of commands to relays 51 and 67, in addition
to tripping of various thresholds.

Figure 5 -Example of timers signalling.

Figure 6 -Behaviour of the signalling.


GLOBAL STANDARD Page 20 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

6.7 Protection functions: 59Vo, 59Vi and 59Vd


RGDAT-A70 device shall have 59Vo functions (zero sequence overvoltage function), 59Vi (over
negative sequence voltage function) and 27Vd (under positive sequence voltage function), with the
following characteristics:
- Setting ranges shall be the ones expressed in Table 3,
- The functions shall be excluded through configuration SW, the default configuration is
EXCLUDED for all the three thresholds,
- Each of the function of protections 59Vo, 59Vi e 27Vd shall have a intentional time delay
configurable with a setting range 060s with a step 0,1s and with a tripping time with no
intentional delay equal to 45ms,
- The exceeding of one of the 59Vo or 59Vi threshold (when the measured value exceed the
set threshold) or the when positive sequence voltage is under then the setting threshold
(27Vd) shall act on the closing/opening mode of relay contact used for the function 67N,
- Through the SW, it shall be possible change the normal status of the 67 output relay:
closed, when there are no faults, or opened when there are no faults. The contact shall be
always opened when the RGDAT-A70 is not powered.
- The equations for quantity calculus to sequences are given below:
r r r r rr r r r r r rr
V 4 + V8 + V12 V4 + V8 + 2V12 V 4 + 2V8 + V12
Vo = Vd = Vi =
3 3 3
Where alpha is = cos(120 ) + jsen (120 ) = 0,5 + j 0,866

Protection function Regulation ranges Step


59Vo 1%En40%En 1%
59Vi 1%En40%En 1%
27Vd 110%En20%En 1%
Table 3

6.8 Vss function


RGDAT shall include a maximum zero sequence voltage function that can be activated via SW.
In case a Vss adjustable threshold is exceeded the RGDAT locks the 67N function leaving
activated those 51 and 51N for a adjustable time TVss. The contact RVL shall be opened. When
the zero sequence voltage becomes lower than the threshold Vss, the functions 67N and RVL shall
be restored to the normal operation.

Protection function Regulation ranges Step


Vss 1%En40%En 1%
TVss (1600)s 1s

6.9 Voltage presence: functional requirements


RGDAT-A70 device shall be able to detect the presence of voltage on the line considering the
following threshold:
GLOBAL STANDARD Page 21 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

- 20% of rated voltage (accuracy 4%);


- 80% of rated voltage (accuracy 4%).
Such threshold distinguish the passages between presence/absence voltage conditions as
specified below:
- starting from voltage absence condition on the line, the logical state of Voltage Presence is
recognised if, for at least 250 ms, the following condition applies:
(VR > 80%Vn) OR (VS > 80%Vn) OR (VT > 80%Vn)
- starting from the condition of Voltage Presence ON, the logical state is no longer
recognised, if, the condition applies:
(VR < 20%Vn) AND (VS < 20%Vn) AND (VT < 20%Vn)
without intentional delays.
In case of drop and rise of 24 Vdc of power supply, the variable starts from voltage absence state.
In case the below condition is TRUE the variable starts from voltage presence.
(VR > 80%Vn) OR (VS > 80%Vn) OR (VT > 80%Vn)
In APPENDIX 4 are reported some diagrams that describe the function mode above described.
The signal of voltage presence, can become OFF state even if is verified the condition of voltage
presence when internal logical diagnostic of the device detect an internal fault (see 6.10 and 15.3).

6.10 Logical Outputs


The identification of fault events shall be remotely reported through the temporary closure of the
two different electrical contacts:
- A contact for the overcurrents due to faults between phases or ground double-phases
(functions of phase overcurrent or residual overcurrent) as in following TS51A described;
- A contact for the downstream single-phase fault from the point of installation (directional
earth fault function) as in following TS67AV described.
The remote signal shall endure for a time equal to that of fault condition and, in any case not less
than 150ms.
Voltage presence shall be remotely reported by closing an additional electric contact, following
indicated as TS PRES V.
The lack of power supply of the device (+24Vdc) shall not cause the emission of the signal.
TS PRES V signal shall be forced in OFF state in case of internal fault of the device (see 6.9 and
15.3).
The signals are sent to the Remote Control Peripheral Unit (DX 1215) that elaborates them in order
to select (locally) the fault section, records them chronologically and sends to the center for
searching and isolating the fault section or for direct the maintenance action on MV network.
The three output relays shall be in normally opened contact with RGDAT-A70 unpowered from
auxiliary voltage.
Through three appropriate presetting devices SW, it shall be possible to set them:
- Each single relay normally opened when monitored function is in a FALSE state, the relay
is closed when function becomes TRUE,
GLOBAL STANDARD Page 22 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

- Each single relay normally closed when monitored function is in a FALSE state, the relay
is opened when function becomes TRUE.

6.11 Logical inputs


It shall be provided a logical input that, if active (from an external signal level), inverts the
intervention sector in the sense specified in par. 6.2. with the absence of activation signal,
hereinafter indicated with UD, the intervention sector is that of default.
UD signal is transmitted through Remote Control Peripheral Unit (DX1215) according to the model
in Figure 18.
GLOBAL STANDARD Page 23 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

6.12 Local LED signals


It shall be locally signalled,
signalled, through the lighting of the LED on the front of the device, the conditions
of:
- recognition of fault events,
- inversion activated
- presence of voltage on the single phases
- internal fault
according with what below specified:
- an orange LED to signalize the phase overcurrent or residual overcurrent intervention;
- a red LED to signal the directional earth fault intervention;
- a white LED to signalize the active inversion;
- three green LEDs to identify the presence of voltage on the three phases of MV line;
- a red LED (flashing) to identify internal malfunction.
The first two LEDs (orange and red), that identify the fault of overcurrent and/or directional earth
fault shall memorize the last occurred intervention.
The later intervention of one of the two thresholds (TS (TS6767 or TS51A) resets the precedent
memorized if it is of a different type. In case of turning off the device each memorizations will be
cancelled.
Each of any three green LEDs is associated with the presence of voltage on the corresponding
phase, according to what is described in the following figure.

ON
OFF

6.13 Voltage Monitoring Procedure


Through the setting of a configuration flag, RGDAT-A70 shall commute its mode of function from
the standard one (RGDAT-A70) to that of Voltage Monitoring. In such mode all protection functions
defined beforehand shall be disabled and, furthermore, shall be redefined the meanings of logical
inputs and outputs as specified below:
RGDAT-A70 shall monitoring voltage presence following an external trigger, the trigger signal will
act on input used in inversion standard mode for the protection function 67N (UD). Therefore, when
input is high UD, RGDAT-A70 shall check the voltage, verifying the voltage presence and signaling
through the contacts of auxiliary relays (V PRESENCE).
GLOBAL STANDARD Page 24 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

In particular, with trigger present if is verified voltage presence, RGDAT-A70 shall close the relay
contact V PRESENCE with a pulse (pulse duration time settable between 0 and 5000ms with a
step of 10ms). V PRESENCE contact shall be normally opened during voltage absence.
The line voltage presence is a boolean variable and shall be a logic OR between the voltage
presence of the three phases, whereas the voltage absence is a logic AND between the voltage
absence of the three phases, as described in 6.9.
In parallel with the command of the V PRESENCE relay and with the same modes to actualize
(pulse mode) shall be also controlled the output that in normal configuration of RGDAT-A70 is
named TS51.
Lastly the output that in normal mode is named as TS67 shall be bistable, that is: the output
contact shall be opened if there is "voltage absence" and shall be closed if there is "voltage
presence".
In the absence of enabling signal (low signal on UD) the Monitoring function, RGDAT-A70 shall
command the instantaneous opening of V PRESENCE relay contact.
All the signals V PRESENCE, TS67 and TS51 shall be able to be filtered by a timer that will
add a delay that shall be settable in a range from 0 to 5000ms with a step of 10ms.
Applying three voltage signals starting from voltage absence, with zero time delay set, the
maximum delay of the voltage presence signal shall be less than 50ms.
The voltage measurement shall be anyway active, even when the digital monitoring signal is
absent, in this case only the signal functions are inhibited.

Timers Time ranges Step


Delay filter (only for outputs TS51 and V PRESENCE) 05000ms 10ms
Pulse duration closing contacts TS51 and V PRESENCE 05000ms 10ms
Table 4 V presence: timer settings.
GLOBAL STANDARD Page 25 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

6.14 Event Recorder


RGDAT-A70 shall be able to record at least 20 events including time references with the following
characteristics:
- the memory for data capture shall be circular type;
- each event shall include date and time;
- each record concerning the single event shall containing the information concerning the
fault characteristics.

7 Environmental Operating Conditions


The device shall operate accurately in the following conditions:
- operating temperature -10+55C
- relative humidity (without condensation nor ice) 93%
- atmospheric pressure 70106kPa

8 Constructive Characteristics
RGDAT-A70 device shall be placed in a case made of steel or another metal/metal alloy equivalent
in terms of electromagnetic compatibility.
The size of RGDAT-A70 shall be less than 250x200mm and the chassis shall be realised for
protruding mounting. RGDAT-A70 shall be mounted perpendicular with 4 screws M5 according to
the fixing template shown in Figure 11. RGDAT-A70 shall be equipped with a lid easily removable.
RGDAT-A70 shall be equipped with 4 fixing screws M5, made of stainless steel, with a suitable
length to protrude between 5 and 10mm from the bottom of the container; it shall have a suitable
earth bolt M10 located on corner bottom right side of the device.
In correspondence of each LED shall be printed with permanent ink the relative function.
On the bottom side of RGDAT-A70 shall be provided the terminal block for the analogue inputs with
a suitable cable guide for the connections toward the current transducer and the connections
toward the capacitive dividers (plug of the voltage presence lights).
The enclosure of RGDAT-A70 shall satisfy the protection level IP31 code (IEC 60529).

9 Electrical Characteristics
RGDAT-A70 shall be assembled according to the principle diagram illustrated in Figure 1, Figure 2
and Figure 3. It can use two phase current transducers plus an residual current sensor or three
phase current transducers.
The two configurations shall be selected by a suitable HW/SW selector (easily accessible from
outside), which makes them perfectly equivalent from a functional point of view.
The firmware of the device shall be located on an non-volatile memory that can be totally update
through the serial port whose device shall be equipped.
RGDAT-A70, with no fault condition present (ground to phase or short circuit fault) shall have a
consumption <3W.
GLOBAL STANDARD Page 26 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

The rated power supply voltage is 24 VDC with positive pole connected to the earth.
The correct operation shall be guarantee inside the range 20% of the rated voltage, even in
presence of alternating current component 10% on the voltage supply.
For values of the voltage supply that do not ensure the correct functioning, RGDAT-A70 device
shall not emit any unwanted signal, local or remote.
RGDAT-A70 shall be protected against polarity inversion.

10 RGDAT-A70

10.1 Connections for collecting voltage signals


The voltage signals are derived from capacitors already arranged on MV panels using the plug of
the fixed part of the voltage presence/absence device ENEL standard DY 1811.
The connections for this extraction shall be organised using six pins pursuant to the unification
table DY 1811 and three shielded wires of a section 0,5mm and a length equal to 3m.
2

The abovementioned connections shall be attested on the terminal board MA as shown in Figure
12.
In order to ensure safety, in case of direct contacts from an operator in occurrence of insulation
failure of the capacitors, shall be provided from the manufacturer an appropriate solution that will
be subject to approval by Enel.

10.2 Measurement circuits

10.2.1 Capacitive plug characteristics of secondary substation panels


The device derives network voltages from three capacitive dividers (one for each phase with the
same characteristics) with the following parameters (see Figure 16):
- Equivalent capacitive reactance XC1 included between 100 M and 700 M (impedance a
50 Hz)
- Partial voltage V2 (detectable to the plug through an impedance of a measure of 1 M)
included between 25 V and 250 V
- Voltage variation (V2) to the plug, due to differences of capacitive values and/or to parasitic
coupling between the three dividers:
amplitude <30%
displacement angle <15
During the commissioning the device must be able to actuate a calibration of the measurements
gained to the inputs of the 3 capacitive dividers to compensate voltage variations V2 above
mentioned. Such calibration shall be performed on demand through a SW automatic procedure
from the configuration terminal. It is not foreseen the possibility that such procedure becomes
active periodically in an automatic mode.
GLOBAL STANDARD Page 27 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

11 RGDAT-A70/C

11.1 Current transducers connections


Inside RGDAT-A70 shall be provided a terminal block, called MA on Figure 12, suitable for
2
collecting section conductors until 2,5 mm , in which will be applied the connections with current
transducers.
For the electric connection of current transducers with RGDAT-A70 shall be provided a cabling
(Figure 14), realised in unipolar conductors with a section 1 mm , including:
2

- n1 unipolar cable, for ground connection between the current node (ground bolt on the
RGDAT-A70 chassis) and the earth of the substation (length 3 m);
- n1 jumper in unipolar cable for the connection between the ground bolt on the RGDAT-
A70 chassis and the ground terminal on the terminal block MA;
- n2 conductors for each current transducer signals. A conductor will be connected to the
RGDAT-A70 terminal board MA (live conductor) the other conductors will be connected to ,
the ground by the bolt on the RGDAT-A70 enclosure.
Such conductors shall have at least a length of 3,5m (suitable for installation of the current
transducer on the bottom of the MV panel) and be all six gathered and inserted, at least for
a length of 3,0m starting from the chassis of RGDAT-A70, within a flexible protective
device (rilsan braided sleeves or similar).
All the used cables shall have a nominal voltage 450/750V and fire retardant characteristics
according to IEC 60332 standards.
Conductors shall be provided of pre-insulated terminals suited to the type of expected connection
(faston, cylindrical, ring, etc.) and also identification marks and references to the realized wiring
diagram.
The insulation of conductors shall be black and on the terminations of the terminal board shall be
provided a white numbering indicating the caption of the terminal board and the terminal number
(ex. MA 1).
2
For the ground circuit part shall use a conductor of 1 mm with a yellow-green insulator and a ring
termination to the ground for bolts 10.
The connections on the current transducers shall be encapsulated in resin if fixed, otherwise shall
be provided a polarized connector, with golden contacts, and provided with a protection against
accidentally disconnections.
To render uniform the installation conditions and release them from the direction of energy from the
time of installation of the device, it is agreed that the residual current Sensor is always installed
with the identification point of the Primary (P1) upwards the side of the bars of the MV panel of
the secondary substation. With such sensor positioning and in absence of inversion (Default),
lRGDAT-A70 shall present a direction of output intervention from MV bars.
The remote control operator will provide for invert remotely the intervention verse according to the
conditions of the substation alimentation.
GLOBAL STANDARD Page 28 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

11.2 Connections for collecting voltage signals


Voltage signals are derived from capacitors already arranged on MV panels using the plug of the
fixed part of the voltage presence/absence device ENEL Standard DY 1811.
The connections for this extraction shall be organised using six pins pursuant to the ENEL
Standard DY 1811 and three shielded wires of a section 0,5mm and a length equal to 3 m.
2

The abovementioned connections shall be attested on the terminal board MA as shown in Figure
12.
In order to ensure safety, in case of direct contacts from an operator in occurrence of insulation
failure of the capacitors , shall be provided from the manufacturer an appropriate solution that will
be subject to approval by Enel.

11.3 Measurement circuits

11.3.1 Capacitive plug characteristics of secondary substation panels


The device derives network voltages from three capacitive dividers (one for each phase with the
same characteristics) with the following parameters (see Figure 16):
- Equivalent capacitive reactance XC1 included between 100 M and 700 M (impedance a
50 Hz)
- Partial voltage V2 (detectable to the plug through an impedance of a measure of 1M)
included between 25V and 250V
- Voltage variation (V2) to the plug, due to differences of capacitive values and/or to parasitic
coupling between the three dividers:
amplitude <30%
displacement angle <15
During the commissioning the device must be able to actuate a calibration of the measurements
gained to the inputs of the 3 capacitive dividers to compensate voltage variations V2 above
mentioned. Such calibration shall be performed on demand through a SW automatic procedure
from the configuration terminal. It is not foreseen the possibility that such procedure becomes
active periodically in an automatic mode.

11.3.2 Current transducer characteristics


Current transducers and accessories for their correct installation are integral part of the supply. The
type of transducer (Rogowski coil) shall be to permit an easy assembling also on cables already
installed.
The transducer shall be in corrosion- resistant material compatible with the provided opening
system.
11.3.2.1 Phase current transducers
Current transducers for detection of phase current shall be installed on MV cables that have a
diameter between 25mm and 52mm and to each of them, during installation, will be joined a
2
unipolar cable of 25 mm (for the grounding of the MV cable shield).
The diameter of the transducer shall be equal to 90mm10%.
GLOBAL STANDARD Page 29 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

For their size, it shall be taken into account the stresses resulting the following functioning
conditions:
- Permanent current on each cable 630A
- Short circuit thermal current (for 1s) 20kA
- Dynamic current (peak) 50kA
11.3.2.2 Residual current transducers
Residual current transducer should be installed on set of three MV cables with a diameter of the
circumscribed circle between 75 and 170 mm.
The diameter of the transducer shall be equal to 240mm10%.
The characteristics of the residual current transducer (or the phase ones if used for measuring
residual current) shall be able to detect the failure even with residual current having the following
characteristics:
- Unidirectional component amplitude 707A
- Unidirectional component time constant 150ms
- Symmetrical component 50A
residual current transducer could produce output error current, for null residual current, due to:

a) Centring and balancing errors of the 3 passing cables respect to the toroid axis
With a single conductor that enters and exits from the Rogoswsky coil applying a current of 200 A,
the output signal from the sensor shall correspond to a primary current not higher to 0.6A,
(maximum error) independently from the distance d between the torus centre and the centre of
symmetry of the 2 conductors and independently from the angular position () of the air gap on coil
closure.
GLOBAL STANDARD Page 30 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

b) Angular position of air gap on the orthogonal plane to the passing cables
With single conductor that enters and exits from the Rogoswsky coil and positioned to the centre of
the same sensor with an applied current of 200 A, the output signal from the sensor shall
correspond to a primary current not higher to 0.2A, (maximum error), independently from the
angular position () of the air gap.

c) Induced currents from parallel cables of the adjacent lines to the outer sensors
With a conductor carrying a current of 200 A, external to the sensor and parallel to its axis, the
output signal from the sensor shall correspond to a primary current not higher to 0.3A, (maximum
error), at a distance of 5 cm between the outer edge of the sensor and the axis of the conductor,
independently from the angular position () of the air gap on the sensor plane.
GLOBAL STANDARD Page 31 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

12 RGDAT-A70/M
It has to be installed on MV cable lines connected to bus-bar systems in bare conductors.
The RGDAT-A70 device is identical to C model and it is fixed to the wall through a plate provided
with threaded holes according to the fixing template (Figure 11). The plate shall be installed
through expanding rawlplug and shaped so as to remain enough distant from the wall. RG-DAT
plate, the attachment screws and the expanding rawlplug shall be included in the supply.

12.1 Connections toward current transducers


The connections with current transducers, that are integral part of the supply, shall have the same
characteristics shown in fig. 8.1 The encumbrance and the installation methods are shown in Fig.
10.
In particular, the 2 conductors from each current transducer shall have a length of 3,5 m and head
to a suitable wall socket equipped with a ground bolt.
In the socket is grafted a 6 pin male connector connected to the terminal board MA of RGDAT-A70
through 6 shield conductors of section 1 mm and with a length of 0,5 meters as shown in the
2

detail 11 of Figure 19.


As in RG-DAT/C, the ground node of the three transducers shall be realized on the ground bolt of
RGDAT-A70 and not on the socket.
However, the female socket, when is not connected to the male one, shall provide automatically for
ground short circuiting (through its bolt) the currents from transducers.

12.2 Connections for collecting voltage signals


The voltage signals are derived from phase voltage transducers assembled on a suitable crossbar
(Figure 22). The encumbrance and the installation modality are shown in Figure 19; transducer
characteristics are listed below.
For transducer connections shall be arranged three shield conductors with section 0,5 mm and
2

with a length of 3,5 meters, headed to a wall socket equipped with a ground bolt.
In the socket is grafted a 4 pin male connector connected to the terminal board MA of RGDAT-A70
through 4 shield conductors of section 1mm and with a length of 0,5 meters as shown in fig. 10.
2

The female socket, when is not connected to the male one, shall provide automatically for ground
short circuiting (through its bolt) the voltages of the transducers.
The proper RGDAT-A70, voltage transducers, the crossbar, current transducers, sockets and male
connectors, cables and accessories for the installation are included in the supply.
To ensure the safety (direct contacts by an operator on the equipment, in case of failure of
the insulation of capacitors) shall be provided by manufacturer an appropriate device,
placed at the bottom of the same capacitive detectors (surge arresters, ) that prevent the
transfer of dangerous voltages on RGDAT-A70 circuits; such device will be subject for
approval by Enel Distribuzione.
GLOBAL STANDARD Page 32 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

12.3 Measurement circuits

12.3.1 Capacitive divider characteristics


See par. 11.3.1 (RGDAT-A70).

12.3.2 Current transducer characteristics


See par. 11.3.2 (RG-DAT-A70 /C).

13 RGDAT/A
It has to be installed on MV cable lines in bare conductors connected to bus-bar systems also in
bare conductors.
The RGDAT-A70 device is the same of C model and shall be fixed to the wall through a plate
provided with threaded holes according to the fixing template (Figure 11). The plate shall be
installed through expanding rawplug and shaped so as to remain enough distant from the wall. RG-
DAT plate, the attachment screws and the expanding rawplug shall be included in the supply.

13.1 Connections toward current transducers


The connections with current transducers, that are integral part of the supply, shall have the same
characteristics shown in par. 11.1 The encumbrance and the installation modality are shown in
Figure 19.
The two conductors from each current transducer shall have a length of 6,5m and head to a
suitable wall socket equipped with a ground bolt.
In the socket is grafted a 6 pin male connector connected in turn to the terminal board MA of
RGDAT-A70 through 6 shield conductors of section 1mm and with a length of 0,5 meters as
2

shown in the detail 11 of Figure 19.


As in RGDAT/C, the ground node of the three transducers shall be on the ground bolt of RGDAT-
A70 and not on the socket.
The female socket, when is not connected to the male one, shall provide automatically for ground
short circuiting (through its bolt) the currents from transducer.

13.2 Connections for collecting voltage signals


The voltage signals are derived from phase voltage transducers assembled on a suitable crossbar
(Figure 20). The encumbrance and the installation modality are shown in Figure 19; transducer
characteristics are listed below.
For transducer connections shall be arranged three shield conductors with section 0,5mm and
2

with a length of 6,5 meters, headed to a wall socket equipped with a ground bolt.
In the socket is grafted a 4 pin male connector connected in turn to the terminal board MA of
RGDAT-A70 through 4 shield conductors of section 1mm and with a length of 0,5 meters as
2

shown in Figure 19.


GLOBAL STANDARD Page 33 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

The female socket, when is not connected to the male one, shall provide automatically for ground
short circuiting (through its bolt) the voltages of the transducers.
The RGDAT-A70, voltage transducers, the crossbar, current transducers, sockets and male
connectors, cables and accessories for the installation shall be included in the supply.
To ensure the safety (direct contacts by an operator on the equipment, in case of failure of
the insulation of capacitors) shall be provided by manufacturer an appropriate device,
placed at the bottom of the same capacitive detectors (surge arresters, ) that prevent the
transfer of dangerous voltages on RGDAT-A70 circuits; such device will be subject for
approval by Enel.

13.3 Measurement circuits

13.3.1 Capacitive divider characteristics


See par. 11.3.1 (RG-DAT/C).

13.3.2 Current transducer characteristics


Current transducers for the collection of phase and residual current (integral part of the supply)
should be installed in correspondence with wall-bushing insulator (ENEL standard DJ 1055 July
1989), according to what shown in Figure 19 and Figure 21.
The Rogowski coil shall have a point openable in order to permit an easy assembling also on
cables already installed. The assembling system of transducers and all the required accessories
are integral part of the supply.
For other functional characteristics and performances worth as expressed in par. 11.3.2.1 and
11.3.2 (RG-DAT/C).
To render uniform the installation conditions and release them from the direction of energy from the
time of installation of the device, it is agreed that the current sensors are always installed with the
identification point of the Primary (P1) toward the bars of the MV panel of the secondary substation.
With such sensor positioning and in absence of inversion (Default), lRGDAT shall present a
direction of output intervention from MV bars.
The remote control operator will provide for invert remotely the intervention direction according to
the conditions of the substation alimentation.

14 RGDAT-A70/O
It has to be installed on pole where are installed driven switch or recloser. The sensors shall be
suitable for Outdoor installation.
RGDAT-A70/O shall measure:
- The phase currents and the residual current, by means of three suitable phase current
transducers for installation on overhead bare conductors;
- The phase voltages and the zero sequence voltage, by means of three suitable phase
voltage transducers for installation on overhead bare conductors.
All the measurements shall be carried out with reference to r.m.s.
GLOBAL STANDARD Page 34 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

For each phase the current and voltage sensors, shall be integrated in one piece combined
component. The sensor can be active, but the power supply shall be supplied only from RGDAT-
A70.
RGDAT-A70 shall be the same RGDAT-A70/C type and shall be installed inside the box containing
the UP for pole installation.
The combined sensor shall provide a proportional voltage signal to the primary voltage such that
with a 9kV primary voltage, the output signal shall be at least of 1V.

14.1 RGDAT-A70/O: Installation on pole


The following figure shows a example of installation layout for 20kV network (the forbidden area
and all the distances depend from the network rated voltage).

POLE TYPE 12/D-14/D POLYGONAL


Surge arresters MINIMUM INSTALLATION HEIGHT

Combined
sensors

Forbidden
area

Forbidden
area
VT for
power supply

Switch

Figure 7 -Example of RGDAT-A70/O installation.


GLOBAL STANDARD Page 35 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Post Insulator

Combined sensors

Figure 8 -Example of RGDAT-A70/O installation on pole.


GLOBAL STANDARD Page 36 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

14.2 RGDAT-A70/O: Installation on raised MV/LV substation

Forbidden area

Sensors
crossbar

Derivation box

Forbidden area Derivation box

Spiral sheath
GLOBAL STANDARD Page 37 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Insulating bushing

Combined sensor

Surge arresters

Figure 9 --Example of RGDAT-A70/O installation on raised MV/LV substation.

14.3 Combined sensors TYPE-1 (24kV)


The combined current/voltage sensor shall be resistant to the severe environmental conditions.
With reference to the CEI EN 60529 standard, the sensors shall have a IP65 level protection.
The creepage distance between the live conductor and the part connec ted to the earth shall be at
connected
least 700mm.
Between the earth and the sensor shall be installed a suitable insulator (included in the package)
with the following mechanical features:
- Specified mechanical load (STL): 10kN
- Specified bending load (SCL): 2kN
- Specified bending load designed (MDCL): 2,5kN
Dimensional requirements:
- Maximum diameter of external covering: 120mm
GLOBAL STANDARD Page 38 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

- Minimum rated creepage distance: 700mm


- Minimum distance between metallic parts: 210mm
Electrical requirements:
- Rated Voltage 24kV
- Dielectric insulation level in the rain (50Hz and 60Hz): 70kV
- Dielectric insulation level to atmospheric pulse (dry environment): 150kV
3
- Dielectric voltage level (salt spray): Up=18kV 224kg/m
In case that the combined sensors perform also outdoor post insulator functions, the mechanical
features of the insulator shall be as above listed and, if is present a junction between the post
insulator and combined sensor its mechanical features shall be as listed below:
- Bending load between on the junction: 0,95kN
Considering a maximum combined sensor weight of 3,5kg and its maximum encumbrance less
than 400X400mm.
For the design, it shall be taken into account the stresses resulting the following functioning
conditions:
- Permanent current on each phase 500A
- Short circuit thermal current (for 1s) 16kA
- Dynamic current (peak) 31,5kA
For each sensor a 8 meters connection cable (for RGDAT-A70 wiring) shall be included in the
supplied package.

14.4 Combined sensors TYPE-2 (36kV)


The combined current/voltage sensor shall be resistant to the severe environmental conditions.
With reference to the CEI EN 60529 standard, the sensors shall have a IP65 level protection.
The creepage distance between the live conductor and the part connected to the earth shall be at
least 1000mm.
Between the earth and the sensor shall be installed a suitable insulator (included in the package)
with the following mechanical features:
- Specified mechanical load (STL): 10kN
- Specified bending load (SCL): 2kN
- Specified bending load designed (MDCL): 2,5kN
Dimensional requirements:
- Maximum diameter of external covering: 120mm
- Minimum rated creepage distance: 1000mm
- Minimum distance between metallic parts: 400mm
Electrical requirements:
- Rated Voltage 36kV
- Dielectric insulation level in the rain (50Hz and 60Hz): 70kV
- Dielectric insulation level to atmospheric pulse (dry environment): 170kV
3
- Dielectric voltage level (salt spray): Up=18kV 224kg/m
GLOBAL STANDARD Page 39 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

In case that the combined sensors perform also outdoor post insulator functions, the mechanical
features of the insulator shall be as above listed and, if is present a junction between the post
insulator and combined sensor its mechanical features shall be as listed below:
- Bending load between on the junction: 0,95kN
Considering a maximum combined sensor weight of 3,5kg and its maximum encumbrance less
than 400X400mm.
For the design, it shall be taken into account the stresses resulting the following functioning
conditions:
- Permanent current on each phase 630A
- Short circuit thermal current (for 1s) 20kA
- Dynamic current (peak) 50kA
For each sensor a 20 meters connection cable (for RGDAT-A70 wiring) shall be included in the
supplied package.

14.5 Residual current calculation


The RGDAT-A70/O type shall calculate the residual current by the sum of the three phase currents.
In order to compensate the error due the composition of the three phase errors, RGDAT-A70 shall
valuate continually the residual current offset (IOPRE), in healthy network conditions. During a fault
RGDAT-A70 shall subtract the vector IOPRE from the vector IO measured (continually current
compensation).
In details:
- the above mentioned IOPRE shall be calculated using a mobile window, with 100ms of width
and with 10ms of update time. This functionality shall be activated via SW;
4
- in case that the setting zero sequence voltage threshold is exceeded , the calculation of
IOPRE shall be frozen and subtracted to the IO measured, this compensation shall be active
during the period in which the setting zero sequence voltage threshold is exceeded;
- the calculation of IOPRE restarts after 30s while the zero sequence voltage is less than the
setting threshold.

14.6 Voltage inputs


In order to avoid unwanted starts of the protection in case of disconnection of a single voltage plug,
RGDAT-A70/O shall be able to detect this occurrence and block the protection functions.
In order to reduce the zero sequence voltage error due to the differences between the three
voltage sensors, RGDAT-A70/O shall permit a individual compensation of the sensors via three

4
Minimum Vo threshold set between 67.S1 and 67.S2.
GLOBAL STANDARD Page 40 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

compensation coefficients. This compensation shall acts only on the voltage amplitude. This
5
compensation coefficients shall be provided by the manufacturer.
In order to compensate zero sequence voltage presence in healthy network conditions, RGDAT-
A70 shall valuate continually the zero sequence voltage (VOPRE), this value (amplitude and phase)
shall be subtracted to VO during a fault (continually compensation).
In details:
- the above mentioned VOPRE shall be calculated using a mobile window, with 100ms of width
and with 10ms of update time. This functionality shall be activated via SW;
6
- in case that the setting zero sequence voltage threshold is exceeded , the calculation of
VOPRE shall be frozen and subtracted to the VO measured, this compensation shall be
active during the period in which the setting zero sequence voltage threshold is exceeded;
- the calculation of VOPRE restarts after 30s while the zero sequence voltage VO is less than
the setting threshold.
- The compensation shall be activated until VOPRE is less than 3V, at exceeding of this
threshold RGDAT-A70/O shall stop the updating of VOPRE.

15 Connection to remote monitoring peripheral unit


Inside RGDAT-A70 shall be provided a terminal block, in addition to that one mentioned in par.
2
11.1, called MB (Figure 12) suitable for collecting section conductors until 2,5 mm , in which will be
applied the connecting cable with the remote control peripheral unit.
For the electrical connection between RGDAT-A70 and the remote monitoring unit (power of device
and transfer of messages) shall be provided a cable (Figure 13), with a length of 8m and structure
2
9x1mm ; one end of the cable shall be equipped with the flying part of the rectangular connector
shown in Figure 15; the other one shall be prepared for the connection to the terminal block MB of
the RGDAT-A70; each cable conductor shall be equipped with tip terminations and also
identification marks and references to the cabling diagram realised by the manufacturer.
The connector shall be realised with insulating material with adequate electric and mechanical
characteristics; it shall be complete with strain relief and equipped with the contacts described in
Figure 15 required to perform the functions specified on the wiring diagram of Figure 10.
The contacts, male type (the female type fitted to the installed fixed part on the UP not included in
2
the supply), shall be able to receive the section conductors until 2 mm and assure the
characteristics indicated below:
- rated voltage: 24V
- current carrying capacity (ampacity): 13A
- Voltage drop on male-female pair
traversed by a current of 5A: 50mV

5
In case of replacement of a single sensor, a new coefficient shall be settable in RGDAT-A70.
6
Minimum Vo threshold set between 67.S1 and 67.S2.
GLOBAL STANDARD Page 41 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

- Insertion-extraction power: 0,4010N/contact


Cable characteristics shall be the following:
- rated voltage: 300/500V
2
- composition: 9x1mm
- flexible cable conductor in untinned annealed copper
- PVC insulator with R2 quality
- external diameter (on the insulator) of the cores: 3mm
7
- distinction of cores, through colours , according to CEI-UNEL00725
- PVC sheath of Rz quality
- characteristics of fire retardant according to CEI 20-22
On both the end of the cable shall be attached a mark strap device, in PVC, on which will be
placed, during the commissioning, the indication of the number and the denomination of the
compartment to which it relates.
All the connection component described above shall be dimensioned and realised to ensure the
passing of the tests contained in paragraph 16.

15.1 Signal relay contacts


The relay contacts for remote signaling of the exceeding of the thresholds shall be able to commute
the small currents and have the following characteristics:
- nominal capacity 2A
- breaking capacity at 24Vcc (con L/R = 40ms) 0,1A
10
5
- number of electrical cycles ensured
10
6
- number of mechanical cycles ensured

15.2 Measurement converters


The measurement of current sent to the Remote Control Peripheral Unit (UP) shall be derived from
one of phase current transducer and converted in a current analog value between one of the two
ranges listed below:
- output level (terminals 4 and 7 in Figure 10) 5mA (overload 20%);
- output level (terminals 4 and 7 in Figure 10) 6-20mA (overload+20%);
- accuracy: 10%.
Both of the two output poles toward the UP shall be insulated from the earth and from the power
supply. (24 VDC).

7
Cores of the same colour are accepted on the condition that the numbers that indicate the reference to
the terminal board MB are imprinted on the core itself.
GLOBAL STANDARD Page 42 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

15.3 Self diagnosis


RGDAT-A70 shall include a self diagnosis that at start-up and cyclically, according to
the requirements of operation, checks the correctness of data and program, and also
of its hardware. In case of anomaly RGDAT-A70 shall produce:
- The opening of all outputs, including that relating to the signal of Voltage Presence (TS
PRES V) that, in that case, is forced to OFF condition;
- The local signal of fault through the lighting of the specific flashing red LED.

15.4 Device configuration and programming


RGDAT-A70 shall provide a serial interface RS232 on DB9 connector that allow the connection to
a PC for configuration, monitoring and diagnosis of the device.
The programming SW includes in the supply (with an no limited number of user licenses) shall be
compatible with the operating systems WINDOWS 7, XP.
In particular, it shall be verified all the SW functionality using an USB/RS232 converter interface.
Configuration functionality
The programming SW shall allow:
- the launch of the calibration procedure of voltage inputs. In the event that the calibration
procedure is not successful, the program shall supply the information about the type of
error identified;
- display the voltage measurements before and after the calibration procedure;
- the setting of current threshold value in field 14A with a step of 0.5A (default value: 2A);
- the setting of zero sequence voltage value in the range 116% of phase voltage with a
step 1% (default value: 6%).
Monitoring and diagnosis functionality
The programming SW shall allow:
- the monitoring of zero sequence voltage measured before and after the calibration
procedure;
- the monitoring of phase current and residual current in amplitude and phase;
- the launch of a diagnostic test of the device;
- the simulation of intervention of each expected device signals toward the Remote Control
Peripheral Unit;
- firmware upgrade.

16 TEST

16.1 Test list


1) Visual inspection
2) Insulation and dielectric strength tests
3) Functional tests
4) Out of range power supply tests
GLOBAL STANDARD Page 43 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

5) Immunity test to electromagnetic interferences


6) Thermal performance test
7) Mechanical compatibility tests
8) Climatic tests
9) Final check of functioning

16.2 Type tests


The type tests are all those mentioned in the previous paragraph.
The supplier must keep and provide ENEL access to the documentation which attests to the
success of the execution of the type tests.
At the discretion of ENEL such tests may be repeated all or in part during the supplies, as evidence
of type conformity.
GLOBAL STANDARD Page 44 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

ENVIRONMENTAL COMPATIBILITY TESTS

TYPE DETAIL NOTES/TEST LEVELS STANDARD


Impulse test Overvoltage category IV IEC 60255-27:2013
Dielectric test AC test voltage 2 kV IEC 60255-27:2013
Insulation resistance 100 M to 500 VDC IEC 60255-27:2013
Contact discharg level 3
Electrostatic discharges IEC 61000-4-2:2008
Air discharge level 3
Ring Wave level 3 IEC 61000-4-12:2006
IEC 61000-4-
Damped oscillatory waves level 2
18:2006+AMD1:2010
Fast transient/burst level 4 IEC 61000-4-4:2012
Surge 1,2-50/8-20 level 3 IEC 61000-4-5:2014

Power frequency magnetic field level 5 IEC 61000-4-8:2009

IEC 61000-4-
Insulation and Damped oscillatory magnetic field level 4
10:1993+AMD1:2000
EMC test
Radiated, radio-frequency, electromagnetic field level 3 IEC 61000-4-
Radiated, radio-frequency, electromagnetic field 3:2006+A1:2007+A2:
level 3 2010
(digital radio telephones)
Short interruptions on d.c. input power ports level 0% t = 0,05 s
Voltage dips level 50% t = 0,1 s IEC 61000-4-29:2000
Voltage variations on d.c. input power ports Un 20%; t = 10 s
Test voltage level at main frequency level 3
Conducted common mode disturbances in the IEC 61000-4-16:2015
level 3
frequency range 0 Hz to 150 kHz
Conducted disturbances induced by radio-
level 3 IEC 61000-4-6:2013
frequency fields

Dry heat +70 C 2 C (16 hours) IEC 60068-2-2:2007


+40 C 2 C,
Damp heat IEC 60068-2-78:2012
RH = 93% 3% (4 days)
No-powered equipment
Cold (-25 3)C (16 hours) IEC 60068-2-1:2007
Change of TA = -25C; TB =70C;
IEC 60068-2-14:2009
Climatic test temperature (3 hours+3 hours)
Dry heat +70 C 2 C (16 hours) IEC 60068-2-2:2007
+40 C 2 C,
Damp heat IEC 60068-2-78:2012
RH = 93% 3% (4 days)
Powered equipment
Cold (-25 3)C (16 hours) IEC 60068-2-1:2007
Change of TA = -25C; TB =70C; (3
IEC 60068-2-14:2009
temperature hours+3 hours)
lower frequency 10 Hz
upper frequency 500 Hz
acceleration amplitude 10
Vibration (sinusoidal) IEC 60068-2-6:2007
Mechanical m/s2
test displacement amplitude
0,075 mm
Vibration, broad-band random (digital control)
IEC 60068-2-64:2008
and guidance

Table 5 Test levels for environmental tests.


GLOBAL STANDARD Page 45 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

16.3 Acceptance tests


Acceptance tests are that indicated in par. 16.1, points 1), 2) (except for the impulse voltage
withstanding test) and 3), limited to a significant set of tests including those prescribed in
APPENDIX 2. In case of solutions that adopt 3 phase sensors for the detection of residual current,
acceptance test shall also include sensor phase tests described in APPENDIX 5, test 2c (for
Holmgreen connection) or an equivalent test to be agreed, according to APPENDIX 3.
Acceptance tests shall be realised through a specific device for automatic test (SCA).
A report attesting the overcoming of SCA tests shall be attached on each device.
The procedures for preparation and certification of SCA device are included in the document ENEL
Distribuzione SQ/P/0101 August 2001.
Any test relating phase current sensor shall be performed also outside of the SCA, attaching on
each set of three current sensors the related test report.

16.4 Visual inspection


It is mandatory to verify the absence of visible manufacturing defects, the accuracy of construction,
the compliance of the dimensions of the cabinet container with those indicated in the present
specification, as well as the prescribed IP degree of protection.

16.5 Insulation and dielectric strength tests


The objective of tests is that to verify dielectric strength between the three independent circuits of
RGDAT-A70 described below; each test shall be performed by applying the voltage (with the
corresponding value to the level specified for each circuit) between each of the three circuits and
the two connected to ground:
a) Voltage inputs
b) Current inputs (applied to the primary side of the current sensors)
c) Signalization outputs and power supply (24 Vdc port).
IEC 60255-27:2013
Impulse test (Overvoltage category IV);
Dielectric test (AC test voltage 2 kV);
Insulation resistance (100 M to 500 Vdc).
GLOBAL STANDARD Page 46 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

16.6 Verification of all functions


All the functions shall be checked with three different conditions of power supply: 80%, 100% and
120% of the power supply voltage.
The tests to perform concern:
Tests on current transducers. Measurement of offset current induced due the assembling
conditions of residual current transducer (see cap. 11.3.2.2 and APPENDIX 5).
Tests on the detection of voltage presence/absence. Tests on the detection of voltage
presence/absence. Variation of the voltage on both directions near of the threshold voltages. It
shall be tested the behaviour in all possible case in the changing of voltage on three phases.
Check of the angular sector of intervention concerning the detecting function of the phase
to ground fault. Such check shall be performed considering both senses of rotation of the vector
in steps of 1, and shall be performed with and without inversion.
Verification of the intervention thresholds. In static conditions (that is steady sinusoidal wave)
shall be verified all the thresholds (voltage and current) previously specified. In particular:
- Verification of thresholds of maximum current and maximum zero sequence current, both
at the tripping and the release;
- Verification of thresholds (from 1% to 16%) of zero sequence voltage both at the tripping
and the release;
- Verification of thresholds (from 1A to 4 A) of zero sequence current both at the tripping and
the release.
Transient tests. Feeding RGDAT-A70 device with voltage and current waveforms obtained from
fault simulations or default field recordings, it is possible to make a functional test of the device in
transient conditions. In particular transients refer to the following conditions:
Fault tests between phases. Multi-phase faults with current equal to 1.2 Iint, 2 Iint, 10 Iint, (3 cases)
Fault tests for phase to ground fault. Faults for isolated neutral earth networks and neutral current
compensation networks with variable compensation, with a network extension from 100 A to 500 A,
with zero fault resistances with a value of 15% inferior and higher to the limit corresponding to the
calibration reported in Appendix. (24 cases)
Fault tests for country cross fault. Faults for a network with a compensation of 100%, with an
extension of 300 A and with fault resistances corresponding to residual current (on the two lines
with the fault) from 120 A to 180 A respectively (4 cases). Holding stable the threshold value of
intervention for the maximum zero sequence current (value specified 150 A) RGDAT-A70s of the
lines affected by the faults, it is required to intervene with trip 51 for currents over the above-
mentioned threshold; it could intervene with trip 67 (according to the active angular sector) for
currents below the same threshold.
Test closure on fault . Closure transients (and rapid reclosing) on faulty line for isolated neutral
earth and neutral current compensation networks in the conditions of existing line voltages
(RGDAT-A70 upstream of the operating organ) and absent (RGDAT-A70 downstream of the
operating organ) (12 cases).
Evolutionary fault tests. Transients of evolutionary fault (closure on single-phase fault and reclosing
on double-phase and vice versa) (2 cases).
Re-striking faults. Simulation of re-striking faults on network with 100% compensation and
extension 300A (4 cases). In case of faults as shown in Figure 17 is expected a behaviour as
shown in the same figure.
GLOBAL STANDARD Page 47 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Fault recordings (only in type tests): Transients obtained by field oscilloperturbographyc recordings,
related to single-phase fault events with an intervention of SHUNT switch and re-striking faults for
isolated neutral earth networks (6 cases) and neutral current compensation networks (6 cases)
A detailed description of the test cases and of the expected results is presented in
Appendix to the present specification. It will be made available from ENEL the file in
COMTRADE format needed to verify the above-mentioned functional test.
In case of type tests, the tests shall be repeated five times.

16.7 Out of range supply tests


It shall be verified that all functions of RGDAT-A70 are inhibited by feeding the device with the
values of the supply voltage that dont provide the proper function.

16.8 Immunity tests (Electromagnetic interferences)


The objective of the tests is to verify the correct functioning of RGDAT-A70 subject to the
application of various electromagnetic disturbance.
- the function of RGDAT-A70 is intended as "protection";
- the environment installation is intended as "MV/LV station";
- the signal port is intended as "local connections".
The interferences shall be applied on the terminal board MA, with reference to voltage inputs, and
to current transducers (primary signals) for what concerns the current inputs.
The procedure for verifying the correct functioning of RGDAT-A70 during this tests shall be agreed
with ENEL.

16.9 Thermal behaviour tests


It shall be revealed the thermal map of the RGDAT-A70 feeding with maximum values
of the nominal range; the test shall be performed under the following normal environmental
conditions:
- temperature: 1535 C
- atmospheric pressure: 86106 kPa
- relative humidity: 4575%
The values of overtemperature, collected near the individual components, shall be used for
verifying that, at the higher temperature of the expected operating , the maximum permissible
temperature of functioning for the same components is not exceeded.
Moreover, the thermal map shall be used for the definition of thermal time constant in view of the
temperature variation test.

16.10 Mechanics compatibility tests


The tests and are divided in:
- immunity tests to sinusoidal type vibrations (working device)
GLOBAL STANDARD Page 48 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

- resistance tests to transport and handling stresses (non working device)


The requirements to apply are the following:
- immunity to sinusoidal vibrations V.H.3
- resistance to transport and handling stresses test type broadband random vibrations
The procedures for verifying the correct operation of RGDAT-A70 during this tests shall be agreed
with ENEL.

16.11 Climatic tests


The referring levels of the single group of tests are indicated in the Table 5.
The procedures for verifying the correct operation of RGDAT-A70 during this tests shall be agreed
with ENEL

16.12 Functional final test


In order to check that RGDAT-A70 operates regularly after the execution of all the prescribed type
tests, they shall be repeated, with the characteristics of the acceptance tests, those indicated in
sections 1), 2) and 3) of par. 16.1.
GLOBAL STANDARD Page 49 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

+24 Vcc/ com TS

TS PRESV

TS 67 AV

COM UD

- 24 Vcc
Terminal Board

TS 51 A

N.C.
MB

UD
M1

M2

10
5
1

9
6
7
8

8
2

7
Terminal Board
MA DY 1811

Panel
MV
TA TA TA TA
phase4 Phase8(*) phase12
homopolar (*)

(*) OPTIONAL

Figure 10 -Circuit diagram of Directional Fault Passage Indicator (RGDAT-A70)

-24 Vcc Power supply (-24 Vcc)


+24 Vcc/Com TS Power supply (+24Vcc) e Common remote signals
TS 51 A Multiphase or ground double phase fault signal
TS PRES V Voltage presence MV signal (level)
TS 67AV Single-phase ground fault signal downstream of the device
M1 Measurement of line current (pole 1)
M2 Measurement of line current (pole 2)
UD Reverse direction command 67AV
com UD Common reverse direction command 67AV
GLOBAL STANDARD Page 50 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Figure 11 -Maximum dimensions and installation template of RGDAT-A70 for using on MV


cells.

MA MB
5 6 7 8 6 7 8 9 10

TA TA TA V4 V8 V12 screen + TS TS
TS M 1 M2 UD Com -
phase phase phase com 51A 67AV
PRES UD
4 8/ homo 12 TS V

Figure 12 -Terminal blocks for input voltages and currents (MA) and output signals (MB).

RGDAT 9x1

L 8m

Figure 13 -Remote control unit connecting cable.


GLOBAL STANDARD Page 51 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Earth conductor
2
16mm from
Earth bolt.

jumper conductor
Earth node to
Terminal block MA.

yellow/green conductors
from secondary sensors

Figure 14 -Cabling scheme RGDAT/C.


GLOBAL STANDARD Page 52 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

1 Com TS Power supply (+24Vcc) and Common remote


signals

2 TS 51 A Multiphase or double-phase fault

3 TS PRES V Voltage presence MV (level)

4 M1 Measurement - pole 1

5 TS 67AV Ground to phase fault (downstream)

6 M2 Measurement - pole 2

7 COM UD Reverse direction command 67 AV (common)

8 UD Reverse direction command 67 AV

9 - Power supply (-24 Vcc)

Figure 15 -Rectangular connector (UP side).


GLOBAL STANDARD Page 53 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Figure 16 -Single phase equivalent diagram of a capacitive divider.


GLOBAL STANDARD Page 54 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

150 ms
fault
monofase
to ground

RESIDUAL CURRENT
CORRENTE OMOPOLARE
guasto

150 ms
< 80 ms 85 ms
phase

TS67AV
0 100 200 300 400 500 t [ms] 600
150 ms
fault
arco int.

RESIDUAL CURRENT
CORRENTE OMOPOLARE
re-striking

150 ms
< 80 ms 85 ms

TS67AV
0 100 200 300 400 500 t [ms] 600
re-striking fault
arco int.

RESIDUAL CURRENT
CORRENTE OMOPOLARE

< 80 ms 85 ms
TS67AV

0 100 200 300 400 500 600


t [ms]
Figure 17 -Examples of a correct functioning following a ground-phase fault and intermittent
arc (both with resistance within specification limits). It's showed a waveform of residual
current and of fault detection signal at the output of the device.
Upper diagram: phase to ground fault in case of isolated neutral network. The first fault remains
less than 80ms, then is not detected by the device; the second fault remains more than 80ms and it
is detected. The output signal changes the state after no more than 150 ms from the beginning of
the fault and it has a duration not less than 150ms.
Following diagrams: intermittent arc for isolated neutral network. With presence of intermittent fault
that remains for the same times of the previous example, the device shall give a correct signal
(middle diagram, same signal of single-phase fault) or, at most, give no signal (lower diagram).
GLOBAL STANDARD Page 55 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

RG_DAT UP

I_Max =50mA UD (8)


Reversing
circuit

COM_UD (7)
+24Vcc

+24Vcc

Reversal = OFF => TR1 = OFF

Reversal = ON => TR1 = ON

Figure 18 -Diagram of reversal of the direction command single phase to ground fault
detection.
GLOBAL STANDARD Page 56 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

SEE FIG. 20

SEE FIG. 21

MOTOR DRIVED IMS DY515/1

BARE COPPER TIE BAR H=4900 mm

MOTOR DRIVED IMS DY515/2

SEE DY 515 PAG. 8/11

OPEN ABLE CURRENT SENSOR

DETAIL 11

Figure 19 -Front view of a substation for overhead lines.


GLOBAL STANDARD Page 57 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

17 Components and accessories for RGDAT-A70/A

WIRING INPUT CAPACITIVE DIVIDERS

WIRING INPUT CURRENT SENSORS

Figure 20 -High crossbar for insulators with capacitive dividers.

Figure 21 -Feed through insulator with current sensor.


GLOBAL STANDARD Page 58 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

18 Components and accessories for RGDAT-A70/M

LIST OF THE MATERIALS

POST INSULATORS CROSSBAR

Figure 22 -Low crossbar for insulators with capacitive dividers.


GLOBAL STANDARD Page 59 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

19 Components and accessories for RGDAT-A70/O

combined
sensor

spiral sheath joint for spiral sheath


ring and gasket

junction plastic box

plate for box fixing

Figure 23 -Combined sensors installation kit.


Components:
spiral sheath: 17mm
junction plastic box
plate for box fixing
joint for spiral sheath
ring and gasket for mounting fitting
screws, washers, nuts for medium voltage connections
The following document will describe all the parts. Other solutions may be allowed only if
equivalent in terms of resistance to solar radiation, the functionality and waterproofness.
GLOBAL STANDARD Page 60 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Junction plastic box


Technical requirements:
- Height: 128mm
- Effective height: 94mm
- IP level protection: 54 (EN 60529, IK09 EN 50102)
- Base width: 128mm
- Effective base width: 94mm
- Depth: 63mm
- Effective depth: 50mm
- Material: reinforced polyamide resin
- Color: RAL 7035 (gray)
- Box type: empty
- Mounting type: on wall

A [mm] H [mm] G [mm] A [mm] H [mm]


128 63 26,5 94 50
GLOBAL STANDARD Page 61 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Plate for box fixing


The plate is used only in case of mounting on pole.
Profiled anodized aluminium, thickness 3mm
GLOBAL STANDARD Page 62 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Spiral sheath
Technical requirements:
- Material: polyamide
- Resistance to bending: good
- Resistance to crushing: 400N/100mm
- Impact test: 6J
- Temperature: -40C/+105C
- Class self-extinguishing: V2
- Colour: grey

Nominal diameter (mm) d2 (mm) d1 (mm) Bending radius


17 21,5 15,5 40
GLOBAL STANDARD Page 63 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Joint for spiral sheath


Technical requirements:
- Material: composite polyamide
- IP level protection: 67
- Colour: grey
- metric thread: metric

Nominal diameter (mm) M (mm) g (mm) D (mm) L (mm) SW (mm)


17 20x1,5 13 33 43 27
GLOBAL STANDARD Page 64 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Ring and gasket


Gasket for isometric thread, PG and Gas.
Technical requirements:
- Max temperature: +150C
- Thread: M20X1,5 e PG13,5 e G

Di (mm) De (mm) S (mm)


21 27 2

Ring for fitting


Ring for fitting with isometric thread, colour gray RAL7001 and thread M20X1,5.

CH (mm) D (mm) S (mm)


26 28 6
GLOBAL STANDARD Page 65 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Screws, washers, nuts for medium voltage connections

1 Hexagonal screw INOX M12X40 UNI/DIN 5739


2 Screw TCB M5X10 Steel INOX DIN 7985 ZB
3 Nut steel INOX M12 UNI/DIN 5588
4 Flat washer INOX M12 UNI/DIN 6592
5 Washer grower INOX M12 UNI/DIN 1751
GLOBAL STANDARD Page 66 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Support Bracket

The round profiles (or tubes) must be soldered to the support in galvanized sheet metal as shown
in the figures herein, and each of the 4 round profiles must be subjected to tensile test.

The test consists of applying a horizontal force F of 100 daN to each individual round profile (not
simultaneously) for one minute and verify that they are not subsequently occurred chipping,
breakage or cracks of all the welding bead
Test Requirements:
Type tests and construction:
ENEL Standard DS 3850 for bracket metallic parts
ENEL Standard DJ 3955 for insulators
Acceptance tests:
Visual inspection and The supplier upon delivery must ensure, with a declaration of
conformity, the full compliance of the
the product to the technical requirements above.
On each item will be marked the following data:
GLOBAL STANDARD Page 67 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

On the metal support:


Identification number of support, trademark of the manufacturer, year of manufacture.
On the insulators:
In a suitable position to be agreed with ENEL must be marked the Specified Mechanical
Load insulator in kN, the term constructive assigned by the manufacturer to the type of
insulator, the name or trademark of the manufacturer, year and month of manufacture.
GLOBAL STANDARD Page 68 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

19.1 Quantity

Combined sensors for RGDAT-A70/O installation on pole/substation

Quantity Description
9 Pcs Hexagonal screw INOX M12X40 UNI/DIN 5739
9 Pcs Flat washer INOX M12 UNI/DIN 6592
9 Pcs Washer grower INOX M12 UNI/DIN 1751
9 Pcs Nut steel INOX M12 UNI/DIN 5588
5 Pcs Ring nylon M20 gray
2 Pcs Screw TCB M5X10 Steel INOX DIN 7985 ZB
4 Pcs Gasket 1/2" - PG13,5 - M20
8 Pcs Joint for spiral sheath
1 Pcs Junction plastic box
1 Pcs Plate for box fixing
10 m Spiral sheath

Assembly support (crossbar+insulators) for combined sensors

Quantity Description
1 Pcs. Support bracket
6 Pcs. Hexagonal screw INOX M12X40 UNI/DIN 5739
6 Pcs. Flat washer INOX M12 UNI/DIN 6592
6 Pcs. Washer grower INOX M12 UNI/DIN 1751
6 Pcs. Nut steel INOX M12 UNI/DIN 5588
3 Pcs. Post insulators (only in case not integrated in the combined sensors)
GLOBAL STANDARD Page 69 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

APPENDIX 1 Example of installation layout RGDAT-A70/O (UP outdoor)

POLE: LEVELS OF MINIMUM INSTALLATION

Forbidden area

Post insulators
crossbar

Forbidden area

Derivation box Derivation box

spiral sheath

spiral sheath

Figure 24 -Minimum distances for pole installation polygonal type 12/D and 14/D.
GLOBAL STANDARD Page 70 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

APPENDIX 2 Additional environmental tests for combined sensors


AGING: the sensor must withstand environmental stresses, electrical and the combination
thereof, under normal operating conditions, without giving rise to processes of degradation
(tracking, drilling, etc.) that could affect the functionality of the insulator. For this purpose
the combined sensor will stand the test of accelerated aging electrical environment than
5,000 hours as specified in Annex C of IEC 1109. In case the sensor contains electronic
board, shall be performed some functional tests with RGDAT-A70/O connected to three
sensors before and after the test cycle, with the expected results of the tests virtually
equal. The electronics that uses the sensors not will be tested;
LIQUID TIGHTNESS: It needs the check of liquid tightness of the interface between the
conductor sensor output and the insulation as required by section 7.4 of the Amendment
1 of IEC 1109. Instead of applying a tensile load it is possible apply a bending moment to
be agreed after the examination of the final prototype for 1 minute. The test will be
considered passed if, after the release of the load, the liquid in the area of the interface will
not be entered for more than 10mm along the conductor. At the same test he will have to
be subjected compass hollow in which is housed the tube mounting, at both ends, with the
hose inserted inside the bush;
SALINITY TIGHTNESS: the combined sensor must have a profile of the fins and a
creepage such as to ensure the sealing surface in conditions of pollution, the salinity
values and voltage given in the tables of unification (to be defined after the examination of
the prototype). The aim must be realized a test salinity sealing. The verification test salinity
sealing must be carried out properly after washing the insulators in the manner indicated in
the Standard IEC 60507, taking into account the following details and indications:
The cleaning of the insulator must be carried out by wiping the entire surface with a
soft sponge soaked in a solution, at a temperature of 50 C, water and trisodium
phosphate. The isolator must therefore be thoroughly rinsed with tap water;
The process of pre-conditioning as indicated in the standard mentioned above
should not be done; in its stead the insulator must be subjected, for a period of 3
hours, to a preconditioning consisting in the application of a voltage equal to 80% of
18 kV, simultaneously with the salinity of 224 kg/m;
The isolator must therefore be subjected to the series of tests of one hour. The
number of tests of the series is equal to 12, carried out at the voltage of 18 kV and
to salinity of 224 kg/m;
The time interval between the end of the pre-conditioning and the start of the tests of
the series must not be greater than 30min. Said interval must also be respected
between the end of a single test and the beginning of the next. At the end of each
test, the insulator must be rinsed with a simple jet of tap water;
The test is positive if there is tight during preconditioning and in at least 8 of the Test
Series.
In case the sensor contains electronic board, shall be performed some functional tests with
RGDAT-A70/O connected to three sensors before and after the test cycle, with the expected
results of the tests virtually equal. The electronics that uses the sensors not will be tested.
LEAK TEST IMPULSE ATMOSPHERIC DRY - IEC 60383-2; par. 6, 9, 12.1 (as
applicable): the test will carried out on 3 sensors connected to the electronic part powered
and active. The test will be considered passed if the three sensors are not damaged and
are not emitted tripping signals;
LEAK TEST FREQUENCY INDUSTRIAL UNDER RAIN - IEC 60383-2; par. 6, 7, 10.1,
12.1 (as applicable): the test will carried out on 3 sensors connected to the electronic part
GLOBAL STANDARD Page 71 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

powered and active. The test will be considered passed if the three sensors are not
damaged and are not emitted tripping signals;
INFLAMMABILITY: the material used for the coating of the sensors must pass the
flammability test scheduled in IEC 60695- 11-10 (former IEC 60707), and be in class V0,
using method B (formerly FV).
GLOBAL STANDARD Page 72 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

APPENDIX 3 Description of test cases for RGDAT-A70 device Functional test


The objective of the following functional tests is to check through additional tests the RGDAT-A70
conformity to functional requirements enclosed in this specification.
The tests will verify the ability to recognize electrical faults and the presence/absence of line
voltage.
The tests to perform concern the recognizing of fault events (phase to ground fault, cross-country
fault, and phase to phase fault) and reclosing on fault, and also the detection of voltage presence,
during opening and closing of line switch and/or IMSs in Substation.
In order to check the detection of fault transients shall be applied the following sequence of
events:
- Pre-fault healthy voltage signal (duration about 5 seconds);
- Electrical fault;
- Opening of the line with fault (after an appropriate period of time, higher than the time of
recognition specified for RGDAT-A70 device);
- Removal of the fault;
- Reclosing of the line (with voltage return to the value previous to the fault itself);
- Post-fault healthy voltage signal (duration about 2 seconds).
For closing cases (and rapid reclosing) on fault the sequence is, on the other hand the
following:
- Pre-fault healthy voltage signal (duration about 3 seconds);
- Closing on fault;
- Opening of the line with fault (after an appropriate period of time, higher than the time of
recognition specified for RGDAT-A70 device);
- Rapid reclosing of the line (while remains the fault condition).
Concerning the cases of re-striking fault, have assumed some cases with a duration of less than
80 ms and other ones with a higher duration, to verify the possible detection capacity and
insensitivity towards intermittent faults.
Finally, the fault recordings concern single-phase faults and arc events, as described in detail
hereinafter.
The network structure supposed for the tests acquired from simulations is shown in Figure A-1 and
represents a simplified network diagram, but adequate for the purposes of the same tests.
It is a MV network to 20 kV composed of three equivalent lines; the network extension in terms of
fault single-phase current changes, according to the cases, from 100A to 500A. Unless otherwise
specified, the line shown in fig. as L1 is supposed of a length that represents about the 40 % of the
entire network (maximum value allowed), while the remaining two lines are supposed of a length
corresponding respectively to 10% and to 50% of the entire network.
In cases of compensated network has supposed the diagram with the coil connected to the neutral
point of transformer.
The three-phase short-circuit current to MV bus-bars is approximately 10kA.
The faults (ground single-phase) are supposed around the zero crossing of the phase voltage; this
condition, although unlikely, represents, in general, a more critical condition for RGDAT-A70 device
(in case of compensated network the fault current - then residual measured on the line with the
fault - displays the maximum unidirectional component).
GLOBAL STANDARD Page 73 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

The cases of single-phase fault supposed a different fault resistances according to what specified
hereinafter.
The output values of RGDAT-A70 to control for the evaluation of the result of the described tests
are the signals TS67AV, TS51A, TSPRESV.
All the cases described represent the type tests for RGDAT-A70 device; the acceptance tests are
represented, on the other hand, by a little subset of the above-mentioned type tests, identified in
the column test with the symbol T+A (Type+Acceptance).
Multiphase fault tests
20 kV network isolated neutral earth, extension 200A. These are ground bi-phase fault with an
appropriate fault resistance supposed in point p1 of line L1 (about 25% of the length)
Referring to Figure A-1, for these fault transients are provided:
- Phase voltage in point 1;
- Phase current in point 1;
for each transient, the functional test consists in the test obtained feeding the device with phase
voltage and, respectively, phase current R+S, R+T, S+T. Then, each test shall be repeated
launching in the device the direction reversal (the test result shall be independent from the
presence of reversal signal).

event name fault current test

1 gupol1 4 kA (8 In) T
2 gupol2 800 A (1.6 In) T+A
3 gupol3 550 A (1.1 In) T

Fault tests for ground single-phase.


Referring to Figure A-1, for these transients of single-phase fault are provided:
- Phase voltage and zero sequence current8 in point 1 (faulty line);
- Phase voltage and zero sequence current in point 29 (healthy line);
For each transient, the test consists in two tests, obtained feeding the device, respectively, with
quantities in point 1 and with quantities in point 2. Then, each test shall be repeated launching in
the device the direction reversal.

8
Intended as the sum of three phase current (so it is the primary residual current of the current
sensor of the RGDAT-A70).
9
In case of RGDAT-A70 assembled with three phase sensors will be supplied, as an alternative to
residual current, the three phase currents.
GLOBAL STANDARD Page 74 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Tests with 20 kV network, isolated neutral

event name network extension calibration ] (Lfault) Test


Rfault [
1 gm01ni 100 A Vo=9% Io=1 A 0. 90 T+A
2 gm02ni 100 A Vo=9% Io=1 A 1250. 90 T
3 gm03ni 100 A Vo=9% Io=1 A 1060. 90 T
4 gm04ni 100 A Vo=9% Io=1 A 1450. 90 T
5 gm05ni 200 A Vo=1% Io=1 A 0. 90 T
6 gm06ni 200 A Vo=1% Io=1 A* 5000. 90 T
7 gm07ni 200 A Vo=1% Io=1 A* 4000. 90 T
8 gm08ni 200 A Vo=1% Io=1 A* 6000. 90 T

* Additional test Verify the NON-intervention of RGDAT-A70 for adjustment of Io=2A.

EXPECTED RESULTS

without reversal with reversal


event name faulty line healthy line faulty line healthy line
1 gm01ni trip 67 no trip no trip trip 67
2 gm02ni trip 67 (possible) no trip no trip trip 67 (possible)
3 gm03ni trip 67 no trip no trip trip 67
4 gm04ni no trip no trip no trip no trip
5 gm05ni trip 67 no trip no trip trip 67
6 gm06ni trip 67 (possible)* no trip no trip trip 67 (possible)*
7 gm07ni trip 67* no trip no trip trip 67*
8 gm08ni no trip no trip no trip no trip

* Additional test Verify the NON-intervention of RGDAT-A70 for adjustment of Io=2A.


GLOBAL STANDARD Page 75 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Tests with 20 kV network, compensated neutral

event name network extension Compensation degree Set calibration ] (Lfault) Test
Rg [
1 gm01nc 300 A 50 % Vo=6% Io=1 A 0 130,5 T+A
2 gm02nc 300 A 50 % Vo=6% Io=1 A 1000. 130,5 T
3 gm03nc 300 A 75 % Vo=7% Io=1 A 1500. 210,5 T
4 gm04nc 300 A 75 % Vo=7% Io=1 A 1800. 210,5 T
5 gm05nc 500 A 95 % Vo=1% Io=1 A 0 184 T
6 gm06nc 500 A 100 % Vo=1% Io=1 A* 17 k 251 T
7 gm07nc 500 A 100 % Vo=1% Io=1 A* 14 k 251 T
8 gm08nc 500 A 100 % Vo=1% Io=1 A* 20 k 251 T
9 gm09nc 300 A 135 % Vo=12% Io=1 A 0 252 T
10 gm10nc 300 A 135 % Vo=12% Io=1 A 790 252 T
11 gm11nc 300 A 135 % Vo=12% Io=1 A 670 252 T
12 gm12nc 300 A 135 % Vo=12% Io=1 A 910 252 T
13 gm13nc 500 A 150 % Vo=15% Io=1 A 0 255,5 T
14 gm14nc 500 A 150 % Vo=15% Io=1 A 280 255,5 T
15 gm15nc 500 A 150 % Vo=15% Io=1 A 230 255,5 T
16 gm16nc 500 A 150 % Vo=15% Io=1 A 330 255,5 T

* Additional test Verify the NON-intervention of RGDAT-A70 for adjustment of Io=3A.


GLOBAL STANDARD Page 76 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

EXPECTED RESULTS

without reversal with reversal without reversal with reversal


event name faulty line healthy line faulty line healthy line
1 gm01nc trip 67 no trip no trip trip 67
2 gm02nc trip 67 no trip no trip trip 67
3 gm03nc trip 67 (possible) no trip no trip trip 67 (possible)
4 gm04nc no trip no trip no trip no trip
5 gm05nc trip 67 trip 51 no trip trip 51
6 gm06nc trip 67 (possible) no trip trip 67 (possible) trip 67 (possible)
7 gm07nc trip 67 no trip trip 67 * trip 67
8 gm08nc no trip no trip no trip no trip
9 gm09nc trip 67 o 51 trip 51 trip 51 (possible) trip 51
10 gm10nc trip 67 (possible) no trip trip 67 (possible) trip 67 (possible)
11 gm11nc trip 67 no trip trip 67 trip 67
12 gm12nc no trip no trip no trip no trip
13 gm13nc trip 51 trip 51 trip 51 trip 51
14 gm14nc trip 67 (possible) no trip trip 67 (possible) trip 67 (possible)
15 gm15nc trip 67 (possible) no trip trip 67 trip 67
16 gm16nc no trip no trip no trip no trip

* Additional test Verify the NON-intervention of RGDAT-A70 for adjustment of Io=3A.


GLOBAL STANDARD Page 77 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Fault tests for cross-country fault


Referring to Figure A-1, for these transients of double-phase fault are provided:
10
- Phase voltages, phase currents and residual current in point 1 (fault on first line);
- Phase voltages, phase currents and residual current in point 3 (fault on second line);
For each transient, the test consists in two tests, obtained feeding the device, respectively, with
quantities in point 1 and with quantities in point 3. Then, each test shall be repeated launching in
the device the direction reversal.
Tests with 20 kV network, 300 A, compensated neutral with a compensation degree of 100%
The faults are supposed (on different phases) in points p1 and p2, Figure A-1.

event denomination Iomo line 1 1 Iomo line 2 2 test


1 gdomo1 250 A 101 350 A 275 T
2 gdomo2 150 A 99.5 265 A 272 T
3 gdomo3 37 A 107 135 A 268 T
4 gdomo4 63 A 103 165 A 270 T
E
XPECTED RESULTS

without reversal with reversal


event name faulty line 1 faulty line 3 faulty line 1 faulty line 3
1 gdomo1 trip 51 trip 51 trip 51 trip 51
2 gdomo2 trip 51 or trip 67 trip 51 trip 51 (possible) trip 51
3 gdomo3 trip 67 no trip no trip trip 67
4 gdomo4 trip 67 trip 51 no trip trip 51

10
Intended as the sum of three phase current (so it is the primary residual current of the sensor of
the RGDAT-A70).
GLOBAL STANDARD Page 78 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Closed tests (and rapid re-closure) on permanent fault


Referring to Figure A- 2 for transients of fault closure and re-closure are provided:
- Phase voltages Va (quantities 1,2,3 of comtrade file)
- Phase voltages Vb (quantities 4,5,6 of comtrade file)
- Residual current Iomo1 (quantity 7 of comtrade file)
- Residual current Iomo3 (quantity 8 of comtrade file)
For each transient, the functional test consists in four tests, obtained feeding the device
respectively:
- With Va voltages and Iomo1 current (with these quantities is reproduced a condition of
closure on the downstream fault, with presence of voltages before the closure (capacitive
panels already fed);
- with Vb voltages and Iomo1 current (with these quantities is reproduced a condition of
closure on the downstream fault, with absence of voltages before the closure (capacitive
panels not fed);
- With Va voltages and Iomo3 current (with these quantities is reproduced a condition of
closure on the upstream fault, with presence of voltages before the closure (capacitive
panels already fed);
- with Vb voltages and Iomo3 current (with these quantities is reproduced a condition of
closure on the upstream fault, with absence of voltages before the closure (capacitive
panels not fed);
the tests shall be conducted setting up for lRGDAT-A70 a voltage calibration equal to 6% and a
value of minimal current equal to 1A (except as further specified), and without reversal signal.
6 events with isolated neutral network
rich_01ni zero resistive fault with synchronous closure of IMS poles;
rich_01nibis as previous, but the fault lasts only 150ms (time limit of fault duration to
recognize);
rich_02ni zero resistive fault with IMS poles discrepancy equal to 2ms.
rich_03ni resistive fault (Vomop about 7%: shall intervene) with IMS poles discrepancy equal
to 2ms.
rich_04ni resistive fault (Vomop about 5%: shall not intervene) with IMS poles discrepancy
equal to 2ms.
rich_05ni resistive fault (Vomop about 7%: shall intervene) with IMS poles discrepancy equal
to 5ms.
rich_05nibis as previous, but the fault lasts only 150ms (time limit of fault duration to
recognize);
rich_06ni zero resistive fault with IMS poles discrepancy equal to 10ms.
GLOBAL STANDARD Page 79 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

EXPECTED RESULTS

event Name Va Iomo1 Va Iomo3 Vb Iomo1 Vb Iomo3


1 rich_01ni trip 67 trip 51 trip 67 trip 51
2 rich_01nibis trip 67 trip 51 trip 67 trip 51
3 rich_02ni trip 67 trip 51 trip 67 trip 51
4 rich_03ni trip 67 no trip trip 67 no trip
5 rich_04ni no trip no trip no trip no trip
6 rich_05ni trip 67 no trip trip 67 no trip
7 rich_05nibis trip 67 no trip trip 67 no trip
8 rich_06ni trip 67 trip 51 trip 67 trip 51

The event rich_04ni shall be repeated for downstream cases (line 1) setting up a voltage
adjustment equal to 2% and in current equal to 4A : trip shall not occur because Iomo is inferior to
4A.
6 events with Compensated Neutral network
rich_01nc zero resistive fault with synchronous closure of IMS poles;
rich_01ncbis as previous, but the fault lasts only 150ms (time limit of fault duration to
recognize);
rich_02nc zero resistive fault with IMS poles discrepancy equal to 2ms.
rich_03nc resistive fault (Vomop about 7%: shall intervene) with IMS poles discrepancy equal
to 2ms.
rich_04nc resistive fault (Vomop about 5%: shall not intervene) with IMS poles discrepancy
equal to 2ms.
rich_05nc resistive fault (Vomop about 7%: shall intervene) with IMS poles discrepancy equal
to 5ms.
rich_05ncbis as previous, but the fault lasts only 150 ms (time limit of fault duration to
recognize);
rich_06nc zero resistive fault with IMS poles discrepancy equal to 10 ms.

EXPECTED RESULTS

event name Va Iomo1 Va Iomo3 Vb Iomo1 Vb Iomo3


1 rich_01nc trip 67 trip 51 trip 67 trip 51
2 rich_01ncbis trip 67 trip 51 trip 67 trip 51
3 rich_02nc trip 67 trip 51 trip 67 trip 51
4 rich_03nc trip 67 no trip trip 67 no trip
5 rich_04nc no trip no trip no trip no trip
6 rich_05nc trip 67 no trip trip 67 no trip
7 rich_05ncbis trip 67 no trip trip 67 no trip
8 rich_06nc trip 67 trip 51 trip 67 trip 51
GLOBAL STANDARD Page 80 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

The event rich_04nc shall be repeated for downstream cases (line 1) setting up a voltage
adjustment equal to 2% and in current equal to 4A: trip shall not occur because Iomo is inferior to
4A.
Tests of closure (and rapid reclosure) on evolutionary fault
- with the same test procedures of the fault closing and reclosure tests above described will
have:
2 events (with Compensated Neutral network) of evolutionary fault
evol_01nc single-phase fault (Iomo<150A) that at the second reclosure returns as double-
phase (Iomo>150A);
evol_02nc double-phase fault (Iomo>150 A) that at the second reclosure returns as simple
single-phase (Iomo<150A);

EXPECTED RESULTS

event name Va Iomo1 Va Iomo3 Vb Iomo1 Vb Iomo3


1 evol_01nc trip 67+ trip 51 no trip trip 67+ trip 51 no trip
2 evol_02nc trip 51+ trip 67 trips 51 (possible) trip 51+ trip 67 trips 51 (possible)

Tests relating to intermittent arc simulations.


Referring to Figure A-1 for transients of fault closure are provided:
11
- phase voltages and residual current in point 1;
- phase voltages and residual current in point 2;
For each transient, the functional test consists in two tests, obtained feeding the device
respectively with quantities in point 1 and quantities in point 2. Each test shall be then repeated by
activating in the device the directional reversal. The adjustments to set for the RGDAT-A70 will be
Vomo=2%, Iomo=1A for all the tests.
The tests in question refer only to the directional detection function of the single-phase fault, in the
event that fault current is not continuous but, for further arc extinctions and restriking, indeed
intermittent.
The used arc modeling, relatively simple, consists in a fault that, activated for an appropriate
ground-phase voltage, it keeps a certain resistance for a part of the cycle; such resistance is later
increased very rapidly, leading to about 1 millisecond to extinction of the same fault.

11
Intended as the sum of three phase current (so it is the primary residual current of the sensor TA
of the RGDAT-A70).
GLOBAL STANDARD Page 81 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

The simulations differ in the duration of the event and in the hypothesis of the arc priming.

Tests refer to a network of 20 kV, 300 A.

event denomination Network type Event duration test


1 arc1 NI <40 ms T
2 arc2 NI >80 ms T
3 arc3 NI 1s T
4 arc4 NI 1s T
5 arc5 NC <40 ms T
6 arc6 NC >80 ms T
7 arc7 NC 1s T
8 arc8 NC 1s T

EXPECTED RESULTS
With device without reversal
- For tests with quantities in point 1 (faulty line): trip 67 or no trip;
- For tests with quantities in point 2 (healthy line): no trip.
With device with active reversal
- For tests with quantities in point 1 (faulty line): no trip;
- For tests with quantities in point 2 (healthy line): trip 67 or no trip.
GLOBAL STANDARD Page 82 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Fault recordings (only for type tests)


Transients obtained by field oscilloperturbographyc recordings, related to single-phase and/or
intermittent fault events.
For these cases are available wave forms of secondary phase voltages, of zero sequence voltage
(not necessary for the test) and residual currents of two secondary lines (one of which with the
fault): so it will possible to feed RGDAT-A70 directly with these quantities on MB terminal board or
through current transducers and capacitor dividers after a recalculation of the values on the primary
side.
For each transient, the functional test consists in two tests, obtained feeding the device with bar
voltages and, respectively, with the residual current of the faulty line and of the healthy line. Then
each test shall be repeated activating in the device the direction reversal.
Isolated neutral network
Recordings of single-phase fault with the intervention of SHUNT switch (3 cases) and intermittent
arc events (3 cases).
Compensated neutral network
Recordings of single-phase fault (3 cases) and intermittent arc (3 cases).
At last, there are two field recordings, concerning an intermittent arc event on compensated neutral
network.

Figure A-1 Reference network for TEST events of RGDAT-A70


GLOBAL STANDARD Page 83 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

Figure A- 2: Events for fault closure.


Impulse response of integrator Rogowski
RGDAT-A70 shall have some output measurement points of the Rogowski integrated signal.
With the Rogowski coils connected to the RGDAT-A70, will injected a primary positive impulse of
current (duration 20ms; amplitude 20A).
The time constant () of the impulse response shall be less than 4ms (Figure 25).
Its allowed a time constant less than 60ms but in that case the amplitude of the impulse response
must be less than 1/20 of the injection.

Figure 25 -Example of impulse response.


During a simulation of a re-striking fault RGDAT-A70 shall record the intervention measurement
values on a log file.
GLOBAL STANDARD Page 84 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

APPENDIX 4 Some examples for detection of voltage PRESENCE/ABSENCE

VR

0.8

0.2

VS

0.8

0.2

VT

0.8

0.2

LEDR

LEDS

LEDT

TS

1
250 ms
0

PRESENCE/ABSENCE
Modalit VOLTAGE MODE
: PRESENZA TENSIONE
GLOBAL STANDARD Page 85 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

APPENDIX 5 Checking tests for current sensors


We assume that sensors present a linear characteristic, in the contrary case the manufacturer shall
supply the characteristic curve.
The supplier shall specify the input impedance of the inputs used to acquire the quantities
concerning currents of RGDAT-A70, and indicate the magnitude that used by the device for its
algorithm (voltage and/or current).
The tests that should be performed are of two types: a first sequence planned for the sensor of
residual currents for the case of RGDAT-A70 that uses two sensors for phase currents and one
sensor for residual currents, a second sequence for evaluate the behaviour of RGDAT-A70 that
uses three sensors of phase current.
Tests for the sensor of residual current
1a. Determination of the characteristic
The residual sensor is charged with the impedance provided by the manufacturer is determined the
typical primary current/output signal (voltage) up to 200A.
1b. Test to highlight the behaviour of the sensor of residual current to centering and
symmetry mismatch of the three passing cable.
Instead of considering a set of three currents, to simplify, it is used a coil at least of 1500mm with
axes of conductors distant each other 45mm.
The coil is inserted in the centre of residual current sensor, applying a current of about 200A. The
coil is moved along a specific direction from the centre to touch the inner side of the sensor,
recording the value of the quantity transduced and bringing back to primary current.
Such measurement shall be repeated for the eight directions placed at 45 relative to each other,
that cover the entire round angle. At least two directions shall correspond with the axis of air gaps.
The test is considered passed if in all conditions the detected residual current does not exceed (in
terms of primary current) 0,6A (and 0,2A in the case of a coil perfectly centred).
1c. Test to highlight the behaviour of residual current sensor in presence of an external
current.
This test has the objective to evaluate the influence over the residual current sensor to residual
current that flows on a set of three placed near the same sensor.
To simplify, the test is performed with a coil of, at least, 1500mm high and, at least, with a width of
1000mm, based a current equal to 200A.
Placing the coil outside of the sensor of the residual current, starting from the contact position
between the sensor and the coil, the latter is progressively separated measuring the translated
magnitude and obtaining the equivalent primary current.
The test shall be repeated for the same eight directions considered in point 1b.
The test is considered passed if, in all conditions, the detected residual current for distance
between the coil and the transducer >= 5cm does not exceed (in terms of primary current) 0,3A.
Tests for phase current sensors (configuration that consists on 3 phase current sensors)
2a. Determination of feature
A sensor is charged with the impedance provided by the manufacturer is determined the typical
primary current / output signal (voltage) up to 750A.
GLOBAL STANDARD Page 86 of 86

GSTP001
RGDAT-A70 Rev. 01
10/02/2016

2b. Test to highlight the behaviour to centering and symmetry faults of the three passing
cable.
The three current sensors shall be connected to detect a single secondary magnitude sum of the
three translated quantities.
Instead of considering a set of three currents, to simplify, it is used only a conductor with a current
equal to 600A that flows two sensors in order to invalidate the residual current.
The conductor shall remain perfectly centred inside the first sensor and for what concern the
second sensor it shall be moved along the eight directions as required in the similar test set for the
point 1b.
The test is considered passed if, in all conditions, the detected residual current does not exceed (in
terms of primary current) 0,6A (and 0,2A in case of both conductors perfectly centred).
2c. Test to verify the correct translation of zero sequence current.
Considering the three sensors connected as in point 2b. two of them are crossed by a centred
conductor with a current of 600 A; inside the third transducer is passed another conductor with a
current of 4 A. The conductor is moved along the eight positions as required in point 1b. and the
secondary magnitude is measured to obtain the equivalent primary current.
The test is considered passed if, in all conditions, the error of the detected residual current does
not exceed (in terms of primary current) 0,6 A.
Remark:
The tests 2b and 2c evaluate the behaviour of RGDAT-A70 that employs three phase-current
sensors in Holmgreen configuration.
In the event of adopting three phase current sensors, but with detection of residual current through
mathematical calculations, the tests to perform on sensor shall be agreed with ENEL according to
the planned modality.