Beruflich Dokumente
Kultur Dokumente
Entrytype:Productnote,EntryID:101096918,Entrydate:09/09/2014 (0)
Rate
FunctionexpansionsforET200SPinterfaceandI/Omodules
Entry Associatedproduct(s)
New firmw areversionsorfunctionexpansionsarenow availablefordifferentinterfaceandI/Omodules.
ET200SPinterfacem odules
New functionsfortheIM1556PNHighFeature(PROFINET)
ConnectionofET200AL
SingularsystemredundancyNAP:S2
DarkBaseUnitsarenow alsopermissibleinSlot1ofthestation(forexample,fortheAIenergymeter)
LinkstotheIM1556PNHF
Manual:73184046
GSDML:57138621
ConnectionofET200AL
Fromfirmw areV3.0.0,anIM1556canbeexpandedviatheBaseUnitBUSendandtheBusAdapterBASend
w ithupto16modulesofthenew IP67I/OlineET200AL.Formoredetailedinformation:SeeSalesreleaseET
200AL,entryID:92345524
Module ArticleNo.
BaseUnitBUSend 6ES71936BN000NE0
BusadapterBASend 6ES71936AS000AA0
Singularsystem redundancy:NAP:S2
Fromfirmw areversionV3.0,theET200SPinterfacemoduleIM1556PNHFcanbeconnectedviaNAPS2system
redundancytoanS7400Hsystem(fromfirmw areversionV6.0.4).Thefollow ingstationsetuprulesapplyhere:
https://support.industry.siemens.com/cs/document/101096918/functionexpansionsforet200spinterfaceandiomodules?dti=0&lc=enAR 1/3
6/6/2017 FunctionexpansionsforET200SPinterfaceandI/OmodulesID:101096918IndustrySupportSiemens
1.Themaximumdatalengthperstationw ithactiveS2redundancyis990byteseachforinputdataandoutput
data.Thelengthiscomposedof:
I/Odata,includinguserdataqualifiersthatmayhavebeenconfigured
NumberofI/Omodulesw ithexclusivelyinputoroutputdata(inbytes)
2xnumberofI/Omodulesw ithinputandoutputdata(inbytes)
2.ThecombinationofS2redundancyw iththeConfigurationcontrollerfunction(optionhandling)isnotsupported
w ithfirmw areV3.0.
3.PossibleI/Omodulesw ithactiveS2Systemredundanz
Withfirmw areversionV3.0,allI/Omodulescanbeusedw iththeexceptionofPROFIsafemodulesandthestation
expansionw ithETconnectionforconnectingtheET200AL
New functionsfortheIM1556DPHighFeature(PROFIBUS)
ConnectionofET200AL
DarkBaseUnitsarenow alsopermissibleinSlot1ofthestation(forexample,fortheAIenergymeter)
LinkstotheIM1556DPHF
Manual:73098660
GSD:73016883
I/Om odules
Supportforvaluestatus(QI,qualityinformation)
Supportforupdatew ithsignedfirmw are
Functionexpansionfortheanaloginputm oduleAIEnergyMeter400VACST
Parameterizablelow ermeasuringlimitofthecurrentvalues(zeropointsuppression):From20to250mA,
defaultvalue:50mA
Ifthesuppliedcurrentislessthantheparameterizedlow ercurrentlimit,thecurrentmeasuredvalueandall
https://support.industry.siemens.com/cs/document/101096918/functionexpansionsforet200spinterfaceandiomodules?dti=0&lc=enAR 2/3
dependentvariablesw illbesuppressedorsetto"0".
6/6/2017 FunctionexpansionsforET200SPinterfaceandI/OmodulesID:101096918IndustrySupportSiemens
Alluserdatavariantsalsoreceivequalifierinformationinthesecondbyte
Introductionofanadditionaluserdatavariant:BasicquantitiesofthreephasemeasurementL1,L2,L3(see
tablebelow )
Byte Assignment
0 Userdatavariant=245(F5H)
1 Qualityinformation=ObQQI3U3I2U2I1U1
2...5 Totalactivepow erL1L2L3
6...9 TotalactiveenergyL1L2L3export
10...13 TotalactiveenergyL1L2L3import
14...17 CurrentL1
18...21 CurrentL2
22...25 CurrentL3
26...27 VoltageUL1N
28...29 VoltageUL2N
30...31 VoltageUL3N
LinkstotheAIEnergyMeter400VACST
Manual:73098696
Additionalinform ation
ET200SPManualCollection
Thisfilecontains:
ET200SPSystemManual
Productinformation(importantinformationinadditiontothemanuals)
Functionmanualsonthetopics
Diagnostics
Communication
Analogvalueprocessing
Counting,measuringandpositiondetection
Highprecisioninput/outputw ithtimebasedIO
Interferenceproofdesignofthecontrollers
Cycletimesandresponsetimes
ET200SPCPU
S71510SP1PN
S71512SP1PN
PROFINETandPROFIBUSinterfacemodules
I/Omodules
FailsafeI/Omodules
BaseUnits
https://support.industry.siemens.com/cs/document/101096918/functionexpansionsforet200spinterfaceandiomodules?dti=0&lc=enAR 3/3