Beruflich Dokumente
Kultur Dokumente
Page
Customer Letter/
Warranty . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 1 1.1
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
..................................
. . . . . 2 1.2 Operating
principle . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.3
Construction . . . . . . . . . . . . . . . . . . . . . .
..................................
. . . . . . 2 2.1 Gas
conveyed . . . . . . . . . . . . . . . . . . . . . . . . . .
..................................
. 3 2.2 Working
conditions . . . . . . . . . . . . . . . . . . . . . . . . .
...............................3
2.2.1 Speed of rotation
2.2.2 Pressure
2.2.3 Temperature
2.3 Capacity adjustment . . . . . . . . . . . . .
..................................
. . . . . . . . 4 3.1
Handling . . . . . . . . . . . . . . . . . . . . . . . . . .
..................................
. . . . . 4 3.2 Storage . . . . . . . . . . . . . . . . . .
..................................
..............4
3.2.1 Bearing storage
3.2.2 Preservation of the
compression chamber
4.1 On-site positioning of blower . . . . . .
..................................
. . . . . . . 5 4.2 Changing the inlet/outlet
arrangement . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 5 4.3
Coupling . . . . . . . . . . . . . . . . . . . . . . . . . .
..................................
. . . 5-7
4.3.1 Direct coupling
4.3.2 Belt drive coupling
4.4 Direction of rotation air flow
direction . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 8 4.5 System
piping . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.................................8
4.5.1 Inlet pipe
4.5.2 Outlet pipe
4.6 Check
valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.................................8
4.7 Safety
valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.................................8
4.8 Electrical connection . . . . . . . . . . . . .
..................................
. . . . . . . 9 5.1 Preliminary controls . . . . .
..................................
. . . . . . . . . . . . . . . . 9 5.2 Start-up . . . . . .
..................................
..........................9
5.2.1 First start-up
5.2.2 Normal start-ups
5.3 Operating
checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.3.1 Daily checks
5.3.2 Check after first 50 hours
5.3.3 Check every 500 hours
5.4 Stopping the
blower . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 10 6.1
Preventive
maintenance . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.1.1 Oil change
7.0 Troubleshooting . . . . . . . . . . . . . . . . .
...................................
. . . . . . 12 8.1 Blower
disassembly . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9.1 Blower in operation . . . . . . . . . . . . . . .
...................................
. . . . 13 9.2 Before any blower
service . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 13 9.3 During
blower
service . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 14 10.1 Oil
type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
..................................
14 10.2 Oil viscosity . . . . . . . . . . . . . . . . . .
...................................
. . . . . . . . 14 10.3 Recommended
oils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 14 10.4
Minimum working
temperature . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 14
Sectional drawings and parts
descriptions . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 15-22 Bare Shaft
Dimension Charts . . . . . . . . . . . . . .
.............................
23-24 Design Features / Tri-Lobe
Blower Performance Chart . . . . . .
. . . . . . . . . . . . . . . . . . 25
Blower merupakan peralatan mekanis yang digunakan untuk memindahkan atau mengalirkan
sejumlah udara / gas secara kontiniu dengan memberikan energi pada udara / gas tersebut melalui
suatu empeling yang berputar , sehingga mengakibatkan adanya perubahan energi kinetis menjadi
energi potensial / tekanan.
Blower merupakan peralatan yang hampir sama dengan fan, bila ditinjau dari energi potensial /
tekanan discharger yang dihasilkan, maka dengan diameter yang sama, fan dan blower dapat
dibedakan sebagai berikut :
a. FAN : Menghasilkan beda tekanan antara discharger dan suction sangat kecil atau tergantung
diameter yang digunakan
b. Blower : Menghasilkan beda tekanan antara discharger dan suction ` lebih besar dari fan.
Sedangkan untuk beda tekanan yang lebih besar blower dapat dilaksanakan dengan compressor.
Penggunaan fan dan blower sangat luas, khususnya untuk industri migas dan petrokimia banyak
digunakan sebagai :
1. Sebagai penggerak ( yang sering ) digunakan :
Electro Motor
Motor baker
Turbin gas atau turbin uap
2. Pemilihan material untuk fan dan blower tergantung dari :
Fluida yang dihandle Kondisi operasi ( tekanan dan temperature ) Kondisi lingkungan
Sistem operasi ( intermiten atau kontiniu ) Sedangkan besarnya gaya tergantung dari
kapasitas dan tekanan discharger yang diperlukan. Untuk dapat memilih yang tepat maka
dapat dilihat dari katalog yang dikeluarkan dari berbagai manufacturing.
Dalam makalah ini Akan dibahas Blower secara umum dan blower Tipe
Rotary blower seri TL (Tri-Lobe) sehingga nantinya akan tergambar jelas pengertian apa itu
blower,fungsi,prinsip kerja aplikasi diindustri dan cara perawatanya.
Manual ini berlaku untuk Rotary Blowers dari Seri TL dari ukuran 10 sampai ukuran 900, keduanya
dalam versi horisontal (H) dan vertikal (V).
1a 1b 1c 1d
Fig. 1
1.3 Konstruksi
Seri TL Blower direkayasa untuk aliran udara yang paling halus, menghasilkan lebih rendah
Denyut dan kebisingan
Bodi ditutup pada kedua ujungnya oleh pelat ujung tempat rumah untuk segel dan bantalan berada. Rotor
disinkronkan oleh sepasang roda gigi timing yang memiliki gigi heliks, mengeras dan tanah. Poros memiliki segel
labirin; Kebocoran gas dikumpulkan di ruang udara khusus di sampul dan dibuang ke atmosfer. Dua sumps
dipasang pada penutup yang berfungsi sebagai sumpit minyak untuk pelumasan splash bantalan dan roda gigi
sinkronisasi. Roda gigi diikat di poros melalui kopling kerucut di bawah tekanan minyak.
Number Description
1 Body
2 Rotor
3 Rotor
4 End Plates
5 Gears
2 1 3 5 6 4 4 6 6 Labyrinth Seals
Fig. 2
2.2.1 Tekanan - Tekanan inlet berkisar antara 3 psig (20,7 kPa) sampai 15 psig (103,4 kPa).
Tekanan diferensial maksimum ditunjukkan pada Tabel I, dan tergantung pada ukuran
blower. Rasio kompresi maksimum untuk semua ukuran blower adalah 2.
2.2.2 Suhu - Suhu masuk gas berkisar antara -13F (-25C) sampai 122F (50C). Suhu
diferensial maksimum yang diizinkan ditunjukkan pada Tabel I, dan tergantung pada ukuran
blower. Suhu maksimum gas yang diijinkan pada debit adalah 266F (130C).
Table I: Operation Limits
TL Arrangement Delta T
Size Vertical Horiz. psig Hg F C
TL10 4800 4800 13 13 190 105
TL20 4800 4800 13 13 190 105
TL30 4800 4800 15 15 200 110
TL40 4800 4800 15 15 200 110
TL41 4800 4800 11 12 165 90
TL50 4800 3000 15 15 200 110
TL60 4800 3000 15 15 200 110
TL61 4800 3000 11 12 165 90
TL70 3800 2200 15 15 200 110
TL80 3800 2200 15 15 200 110
TL81 3800 2200 11 12 165 90
TL90 3000 1900 15 15 200 110
TL100 3000 1900 15 15 200 110
TL101 3000 1900 10 12 150 83
TL110 2400 1500 15 15 200 110
TL120 2400 1500 12 13 180 100
TL900 1800 1125 12 13 180 100
3 Blower Engineering
Instructional Manual
2.3 Capacity adjustment
Capacity can only be adjusted in one of the two following ways:
Varying the speed of rotation. This can be achieved via belt drives or by varying the
electric motor supply voltage frequency or with a double polarity motor.
Bleeding off of excess capacity via a regulating valve on the outlet
Do not use the safety valve for this purpose because it will suffer excessive wear.
Do not re-circulate the excess gas into the blower inlet without cooling because it could
cause excessive heating.
WARNING: Do not adjust the gas capacity by using throttle valves placed on the
inlet or outlet piping.
3.1 Handling
To hoist the blower, use a
cable as shown in fig. 3
WARNING:
Do not use the holes in the
flanges to lift the blower. Horizontal: /H Vertical: /V
Fig. 3
3.2 Storage
Keep the blower in a dry cool closed environment. Do not remove the protective coverings
placed over the blower openings. Renew the preservation every 6 months, or more frequently
if the climate is damp.
Bearing storage Half fill the sumps with anti-rust oil. Manually rotate the blower shaft.
Dispose of the used oil in accordance with local regulations.
Preservation of the compression chamber Remove the protective coverings from the
blower openings. Apply a thin film of anti-rust oil to the internal surfaces of the body to
the covers and to the rotor surfaces.
WARNING: Use anti-rust and foam inhibiting oil with fire point over
392F (200C) only.
E E E E
A B
D
D
Fig. 4
Letter Description
A Left Foot
B Right Foot
C Oil fill plug
D Oil drain plug
E Oil level sight glass
4.3 kopling
4.3.1 Kopling langsung - Geser setengah kopling ke poros blower dan motor
menggunakan alat yang sesuai.
Letakkan blower pada jarak dari motor yang ditunjukkan oleh produsen
kopling.
Sejajarkan poros blower dan motor dan, bila diperlukan masukkan shims
di bawah kaki motor dan / atau blower.
Mount the drive belts. Belt tension is produced by using the motor thrust screws in
accordance with the values shown in Table V. During this phase, the alignment of the sheaves
must be checked using a scale resting against the sheaves as shown in figure 5.
WARNING: Excessive belt tension could damage the blower and the motor.
Secure the feet of the motor
5.3 If replacing 3V or 5V belts with the same belt length and same number of belts in 3VX or 5VX
cross section, belt tension does not need to be increased.
NOTE: New drives designed with 3VX or 5VX belts should be tensioned at the respective
deflection force value shown in above table.
GAS
Fig. 6
WARNING: Do not use the blower with a direction of rotation or a flow direction which
differs from that shown in figure 6.
WARNING: Remove the protective covers from the blower openings before connecting the pipes.
4.5.2 Outlet pipe
4.5.1 Inlet pipe Connect a silencer directly to the outlet
5.3.1 Connect a silencer directly to the inlet of of the blower.
the blower. Support the piping at the point nearest
5.3.2 Thoroughly clean. to the flexible coupling.
5.3.3 If necessary install a dirt filter for Insulate the pipes so as to avoid heating
the first 100 working hours. the environment and as a precaution
5.3.4 Install a pressure gauge to check the dirt filter. to accidental contact.
5.3.5 Support the pipe.
WARNING: Install the safety valves as close as possible to the inlet/outlet at the blower,
without placing shut-off valves in-between.
Blower Engineering Instructional Manual
8
4.8 Electrical connection
Use only authorized specialists to set up the electrical system, working in compliance with
regulations applying to the place of installation and in accordance with the requirements of
the local body supplying electrical energy. Check on the motor plate:
Voltage Frequency
Number of phases Absorbed current
Connect the cables as shown in the diagram accompanying the terminal box of the motor. If the
diagram has not been supplied, request it from the motor manufacturer. Use electrical cables of
suitable size, depending on the nominal current of the electrical motor. Keep the electric cables
away from heat sources and/or pointed edges. The motor must be protected by means of an
automatic switch set at the value of the rated current shown on the plate. For the safety of
personnel, the system must be protected by a suitable grounding device.
WARNING: Blower service must be carried out only after disconnecting the electric supply.
5.4 Start up
5.2.1 First start-up
WARNING: During this operation personnel are in direct contact with the blower, and
for this reason noise protection must be worn.
Open the shut-off valve.
Check that the safety valve has been set at the operating value.
Check the rotation by jogging the motor.
WARNING: Do not rotate the blower in the wrong direction for more than a few revolutions.
Start the blower
Increase the operating pressure gradually until the rated value is reached.
After about 10 to 20 minutes check that there are no oil leakages and strange noises or
vibrations. If such problems are found, stop the blower immediately.
5.2.2 Normal start-ups With direct start-up the motor starts even with the maximum dis-
charge counter-pressure. With star-delta start-up, on the other hand, or with the starter; the
counter-pressure must be zero.
1 Check after first 50 hours With the blower shut down, check:
The oil level.
0 Oil leaks.
1 Auxiliary circuit leaks.
2 Belt tension.
5.3.3 Check every 500 hours With the blower shut down, check:
The oil level.
0 Oil viscosity and condition.
1 Belt wear.
2 Flexible coupling inserts.
3 Auxiliary circuits.
The blower can also be stopped in the presence of the counter-pressure but, because of the
high current absorption of the electric motor; problems with the electric circuit could result.
WARNING: Check that the deceleration of the blower is even and without vibrations.
WARNING: Dispose of the used oil in accordance with the local regulations.
WARNING: Regardless, stick to the half way mark on the oil level sight glass.
TL10 - 20 0.33 0.31 0.71 0.67 1.04 0.98 0.22 0.21 0.44 0.41 0.66 0.62
TL30-40-41 0.6 0.56 1.11 1.05 1.7 1.61 0.4 0.38 0.76 0.72 1.16 1.1
TL50-60-61 0.85 0.8 1.75 1.65 2.6 2.45 0.57 0.54 1.1 1.04 1.67 1.58
TL70-80-81 1.67 1.58 3.3 3.11 4.97 4.69 1.11 1.50 2.11 2.0 3.22 3.05
TL90-100-101 3.2 3.0 5.8 5.5 9.0 8.5 1.8 1.7 3.44 3.25 5.24 4.95
TL110-120 4.23 4.0 9.0 8.5 13.23 12.5 2.64 2.5 5.3 5.0 7.94 7.5
TL900 9.5 9.0 19.0 18.0 28.5 27.0 6.34 6 10.6 10.0 16.94 16.0
2 1
2 1
Vertical Horizontal
Fig. 7 Fig. 7
Inlet temperature different from design value Check inlet temperature and reset to rated value
Compression ratio is not the same as the Check inlet and outlet pressures and reset to
design conditions rated values
Rotors are worn Measure clearances of rotors
Oil level too high Reset correct oil level (see paragraph 6.1.1)
Oil too viscous Use less viscous oil
High differential pressure See paragraph 7.2
Oil produces foam Change the type of oil
7.7 Unusual noises and/or vibrations (stop the blower immediately)
Differential pressure exceeds rated value Check inlet and outlet pressures and reset to
rated values
Discharge temperature exceeds rated value see paragraph 7.3
Rotors making contact Stop blower immediately, measure gear and
rotor clearances
Scale on internal parts Thoroughly clean the rotors and compression
chamber
Bearings are worn Measure bearing clearances and, if necessary,
replace them
Intake of foreign particles Remove foreign particles, clean the inside of
the blower
13 Blower Engineering
Instructional Manual
9.3 During blower service
Check that all operations described in Paragraph 9.2 have been completed.
0 Use adequate equipment and procedures to disconnect and handle the system piping.
1 Use adequate equipment to disassemble the blower components.
2 Use adequate equipment and procedures to hoist the blower and its main parts.
The weight could exceed 66 lbs (30 kg).
1 Oil type
Oil Type ISO Class Acc. To
Mineral oil for general use C, CL, CLP DIN 51517
Mineral oil for hydrostatic and hydrodynamic circuits H, HL DIN 51524
Mineral oil for internal combustion engines HD
Synthetic oil
27
29
25
46
26
33 16 13
48
32
7 24 23 35 1 14 38 21 11 17 6 9 39 19 2 45 34 47 5
15 Blower Engineering
Instructional Manual
29 26 44 14 21 40 39 41 12 17 19 43 3
8
27
25
33
31
16
13
46
45
34
30 47 7 24 23 35 1 38 6 11 9 2
TL50, TL60 & TL61
Qty Per Part Part
Blower Number Description
2 47 gear locking nut
1 46 extraction ring
1 45 extraction ring
28 44 bolt
1 43 headplate, drive
1 41 cylinder
1 40 headplate, gear
4 39 oil splash disc
3 38 circlip
2 35 inner cover
1 34 oil slinger, drive
1 33 oil slinger, gear
1 31 drive sump
1 30 gear sump
2 29 lock washer
1 27 washer
2 26 washer
1 25 bolt
6 24 adjusting ring
2 23 gear spacer
2 21 spacer
2 19 spacer
Qty Per Part Part
Blower Number Description
4 17 sealing chamber
1 16 lock nut, driveshaft
4 14 pre-load washer
1 13 key, shaft
1 12 driven rotor
1 11 drive rotor
4 9 ring holder
1 8 gear, driven
1 7 gear, drive
16 6 piston sealing ring
1 5 shaft sleeve
1 4 lip seal
1 3 bearing
1 2 bearing
2 1 bearing
Listings not shown
8 49 o-ring
8 37 adjusting washer
1 32 spring pin, gear
2 22 bearing washer
4 15 oil level sight glass
2 6
25
27
29 4
42
16
4 7
13
33
64
03
34
31
7 35 1 9 71 6 41 11 2 44
TL70, TL80 & TL81
Qty Per Part Part
Blower Number Description
2 47 gear locking nut
2 46 spacer
32 45 bolt
1 44 headplate, drive
1 41 cylinder
1 40 headplate, gear
4 39 oil splash disc
3 38 circlip
2 35 inner cover
1 34 oil slinger, drive
1 33 oil slinger, gear
1 31 drive sump
1 30 gear sump
2 29 lock washer
2 27 washer
2 26 washer
1 25 bolt
6 24 adjusting ring
2 23 gear spacer
2 21 spacer
2 19 spacer
17 Blower Engineering
Instructional Manual
23 45 40 38 9 6 24 41 47 21 44 1
30
27
8
25
16
34
2
12
4
13
26
5 11
29 28
31
33
7
35 1 17 3 46
14 19
45
3
27
26 25
36
8
2
33
13
5
16
28
29 31
7
46
30
23 51 1 38 21 6 9 14 11 47 19 24 34
19 Blower Engineering
Instructional Manual
3 51 50 1 21 6 12 41 10 45
8 36
25
27
34
4
29
5 11
33
26
13
16 28
7
54
30
2
31
23 35 49 53 40 9 17 14 47 19 24 44 46 55
TL900
Qty Per Part Part
Blower Number Description
1 55 thrower ring, bearing
1 54 shaft seal housing
3 53 circlip
2 51 bearing spacer
32 50 bolt
2 49 gear side bearing
support
2 47 ring holder
1 46 spring holding ring
1 45 drive side bearing
support
1 44 drive headplate
1 41 cylinder
1 40 driven headplate
4 36 bolt
2 35 inner cover
1 34 oil slinger, drive
1 33 oil slinger, gear
1 31 drive sump
1 30 gear sump
2 29 lock washer
1 28 key, slinger
1 27 washer
2 26 washer
1 25 bolt
19
13
22
27
32
9
34 1 16
41 24 18 45
31
23
33
2
6
14
12
51
29
15
36
17 20 5
26
16
29
33
30 23 51 1 38 21 6 9 14
12 47 44 1
45
27
25
36
34
2
5 13
53
28 31
46
11
47 19 24
Sq. key
VERTIC LAOLF W
#
eMod l A B C D E F G H I L M N O P Holes Q V W X Z Wei ght
in Flg. s(lb .)
01LT 9 7. 4 55. 0 82. 21 8. 5 68. 8 54. 9 . 534 . 184 3. 81 257. 4 . 6 5 7. 0 4 78.10 40. 01 5216.0 0.25 31.52 146
02LT 6. 01 3. 4 55. 0 82. 21 48. 7 596. 42. 01 . 534 . 18498. 91 3 6 . 778 . 0 7 4 78.10 40. 01 5216.0 0.25 31.52 162
03LT 6. 11 5. 8 36. 0 3. 41 67. 9573. 01 526. 11 3. 6 . 196 22 3 6 778. 7. 0 4 6. 21 24. 11 .15 0.375 36.52 22 4
04LT 6. 11 4.10 36. 0 3. 41 18. 11 5. 11 67.12 63. . 19662. 42 3 6 778. .07 4 . 21 6. 11 24 .15 0.375 36.52 52 0
14LT 6. 11 1336. 0 3. 41 6152. 31 57.14 3. 6 96. 1 82 4 .75 686. 7. 0 8 6. 21 . 11 24 .15 0.375 36.52 284
05LT 4. 31 8.10 7. 058. 61 2. 21521. 21 52. 31 9. 6 90. 2 . 52573 4 . 7 5 66. 8 7. 0 887. 31 . 41 71 . 157 07.3 5 4.562 73 6
06LT 4. 31 4.13 7. 058. 61 53. 51 57. 31 57. 41 9. 6 . 290 5. 82 4 . 7 5 66. 8 .0 7 8 . 31 87 . 41 71 . 157 07.3 5 4.625 14 2
16LT 1. 81 4.11 7. 0 3. 02 7. 31526. 51 0. 71 9. 6 90. 2 . 23526 5 .85 01 7. 0 8 87.13 . 41 71 . 157 0.537 46. 25 94 8
07LT 6. 41 4.12 49. 0 51. 81 46. 41 26. 31 51 . 858 46. 2 26. 82 5 .85 01 9. 0 8 7. 71 . 71 31 .5221 .05 48.57 06 8
08LT 6. 41 1749. 0 51. 81 7. 81 17. 51 90. 71 . 858 46. 2 . 23 8 6 . 9 5. 11 22 9. 0 8 7. 71 . 71 31 .5221 .05 48.57 96 4
18LT 6. 41 2249. 0 51. 81 71.24 64.18 48. 91 58. 8 . 246 . 83 3 6 . 9252. 11 9. 0 8 . 71 7. 71 31 .5221 .05 4.587 08 8
09LT 9. 61 . 51 5249. 0 8. 22 46. 71 5. 61 57.19 . 948 . 35532. 63 6 . 9 5. 11 22 9. 0 896. 91 . 12 24 .5273 0.625 . 7 0 59 4
001LT 9. 61 7.19 49. 0 8. 22 10. 22 5. 81 0. 22 48. 9 . 353 5. 04 8. 11 57 . 31 5 9. 0 8 . 91 9624. 12 .5273 . 0 625 7.0 1058
101LT 9. 61 6.25 49. 0 8. 22 49. 82 0. 22 5. 52 48. 9 . 353 5. 74 8. 11 57 . 31 5 9. 0 8 . 91 9624. 12 .5273 . 0 625 7.0 1258
011LT 5. 12 52. 02 49. 076. 52 16. 22 52. 81 5. 12 . 21 471. 4 . 93 57 8. 11 57 . 31 5 . 0 9 8 248. 57.25 . 2 5 . 0 625 71.52 1450
o N et l: A l
mea eusmer
ntsr a eni
nihcse .
OHZI RTNO
LWAOLF
#
Wei ght
1LT 021. 61 45. 22 49. 0 7. 91 2. 62 8. 02 . 42 069. 9 31. 41 8. 44 01. 41 52. 51 9 . 0 9 21 8. 42 . 72 10 .25 02.6 5 7.1256616
9LT 00 . 22 3 02 49. 0 2. 62 4. 42 41. 62 42. 03 53. 12 66. 62 . 65 83 21 71 91 1 21 . 03 17. 24 16 .35 0.587 7.6 297 6
o
p
e
r
a
t
i
o
n
t
o
m
i
n
i
m
i
z
e
a
i
r
0 Heavy- li
Duty v
and er
ribbed e
cast d
iron in
housing a
and end n
covers: u
Reduce n
noise c
levels o
and nt
increas a
e heat m
dissipat in
ion. at
1 Versatile e
Mounti d,
ng: oi
Horizo l
ntal or fr
vertical e
airflow e
is easily st
achieve at
d by e.
relocati 4 T
ng the h
remova e
ble
mounti u
ng feet n
incorpo i
rated in t
all m
models. a
2 Splash y
Oil
Lubrica b
tion: e
Assures
improv c
ed o
bearing u
life and p
operati l
onal e
simplic d
ity.
d
3 Gas
i
or
r
air
e
is
c
de
tl ze
y d
o by
r a
d pai
ri r
v of
e tim
n ing
b ge
y ars
V ha
- vin
b g
e hel
lt ica
s. l,
5 Rotat har
ion de
of ne
the d
imp an
elle d
rs is gro
syn un
chr d
oni tee
th.
TRI-LOBE
BLOWER
PERFORMAN
CE
Tri-Lobe P Vacuum Inlet Volume CFM
Max Max
Model 30 145 300 600 1200 2400 4800 5200
PSIG "Hg
TL 10 13 13
TL 20 13 13
TL 30 15 15
TL 40 15 15
TL 41 11 12
TL 50 15 15
TL 60 15 15
TL 61 11 12
TL 70 15 15
TL 80 15 15
TL 81 11 12
TL 90 15 15
TL 100 15 15
TL 101 10 12
TL 110 15 15
TL 120 12 13
TL 900 12 13
Pressure
Performance data
based on the
following; Gas
handled: Air, Inlet
pressure: 14.7 PSIA,
Inlet Temp.: 68F
Vacuum Performance
data based on the
following; Gas
handled: Air,
Discharge pressure:
29.92 HG A, Inlet
Temp.: 68F
25
Blower Engineering
Instructional Manual
Packaged System from Blower
Engineering
www.blowerengineering.com
Lewiston, New York Enfield, Connecticut Murrieta, California Aurora, Canada
1-800-388-1339 1-860-749-7431 1-951-219-0997 1-905-841-2215