average commercial building
Energy Consumption

Others
15%

Lifts/escalators Air-conditioning
11% 55%
Lighting
19%

s u s t a i n a b I l I t y
EarthWise Systems?

Energy
Efficiency

Emissions

s u s t a i n a b I l I t y
EarthWise Systems
Chiller system:
Low flow, low temperature
high efficiency systems
What do they do?
How do they do it?
Why use them?

s u s t a i n a b I l I t y
Low Flow, Low Temperature,
High Efficiency Systems

+/-$ ~/$
air handlers ductwork

+/-$

controls

+/-$

~/$
piping +/-$
chillers
s u s t a i n a b I l I t y
How?
Supply temperature Flow rates Fans

Ductwork

Temperature differential Pump

Piping

s u s t a i n a b I l I t y
Why Use LLH Systems?
Good for business: Offers the potential to
lower first cost and/or operating cost while
enhancing comfort, IAQ, and acoustics
Environmentally responsible: Reduced utility
generated greenhouse gas emissions and
uses less natural resources
Ideal for use in health care, institutional,
governmental, office building, education, and
other markets where VAV systems are used

s u s t a i n a b I l I t y
EarthWise Systems

s u s t a i n a b I l I t y
EarthWise Systems
100

95

90
LEED
% of HVAC energy consumption

85

80
EAc1
75

70

65

60
Conventional System Trane EarthWise System
Atlanta 100% 83%
Minneapolis 100% 93%
Los Angeles 100% 70%
Denver 100% 83%
Philadelphia 100% 89%
Portland 100% 80%

s u s t a i n a b I l I t y
EarthWise Systems
1970s 2007

18%
9% 31%

73%
17% 51%

Chiller
Cooling tower
Water pumps
s u s t a i n a b I l I t y
History of Chiller Performance

8.0 Centrifugal
Chiller efficiency, COP

>600 tons
Screw
6.0 150-300 tons
Scroll
<100 tons
4.0
Reciprocating
<150 tons

2.0

0.0
1977 1980 1989 1999 best
available
ASHRAE Standard 90.1

s u s t a i n a b I l I t y
Cool More or Pump More?
Pump efficiency 70%
COP 0.7
Chiller COP 7.0
Chiller COP 10x the pump COP
Conclusion work your most efficient
equipment harder

s u s t a i n a b I l I t y
Old Rule (ARI Standard)

Evaporator flow Condenser flow Standard


Chiller Type
Compressor
Piston 2.4 gpm/ton 3.0 gpm/ton ARI
Scroll [0.043 L/s/kW] [0.054 L/s/kW] 550/5901998
Screw
Centrifugal

6.7C - Supply water temp.


5.5C - Evaporator T
5.5C - Condenser T

s u s t a i n a b I l I t y
Earthwise Systems
Earthwise reduces energy for circulation
Basic Equation:

Q = cp x G x DT
Btuh = 500 x gpm x DT(0F)
Watts = 4184 x lps x DT(0C)

Saves
energy
s u s t a i n a b I l I t y
New Rule ( EarthWise System)

Evaporator flow Condenser flow


Chiller Type
Compressor
Piston EarthWise
1.5 gpm/ton 2.0 gpm/ton
Scroll System
Screw [0.027 L/s/kW] [0.036 L/s/kW]
Centrifugal

5C - Supply water temp.


9C - Evaporator T
8C - Condenser T

s u s t a i n a b I l I t y
Basic Rule
Fan :
Velocity1 / Velocity2 = Airflow1 / Airflow2
SP1 / SP2 = (Airflow1 / Airflow2 )2
Power1 / Power2 = (Airflow1 / Airflow2 )3

Pump :
Velocity1 / Velocity2 = Flow1 / Flow2
Pressure1 / Pressure2 = (Flow1 / Flow2 )2
Power1 / Power2 = (Flow1 / Flow2 )3

SP: Static Pressure


s u s t a i n a b I l I t y
Basic Rule

Meaning:

40% reduce in flow Power


consumption remaining:

[(0.6) X (0.6) X (0.6)] = 0.21

or reduce 80% in power consumption.

s u s t a i n a b I l I t y
Show Me the Impact
Cooling towers
Cooling coils
Pumps
Chillers
Air handlers
Controls

s u s t a i n a b I l I t y
waterside example
Cooling Tower Performance
(800 tons)

37/32/28 C 39/31/28 C
2400 GPM(151 l/s) 1600 GPM(100 l/s)

5C range 8C range
4C approach 3C approach
32 kW 32 kW

s u s t a i n a b I l I t y
waterside example
Cooling Tower: Size?, Cost?

37/32/28 C 39/31/28 C 39/32/28 C


2400 GPM 1600 GPM 1600 GPM
(151 l/s) (100 l/s) (100 l/s)
5C range 8C range 7C range
4C approach 3C approach 4C approach
32 kW 32 kW 24 kW

Same Tower Smaller Tower

s u s t a i n a b I l I t y
lessons learned
Cooling Tower Performance

!Tower water
should be hot!
Towers should use
inverters!

s u s t a i n a b I l I t y
Cooling Coil
MBH 504 504

WTR 5.5C 9C

GPM/Ton 2.4 1.5

EWT 6.5C 5C

LWT 12C 14C

GPM 101 63.0


GPM reduction of 37.5%

s u s t a i n a b I l I t y
Chilled Water Pump (800 tons)

Lu lng 1920 gpm 1200 gpm


121 l/s 75.6 l/s
Ct p 33.5 Hm 15 Hm
Hiu sut bm 80 % 80 %
Hiu sut motor 95 % 95 %
CS in 52 kW 16 kW

In this installation:
a 37.5% reduction in flow =
nearly 70% reduction in chilled water
pumping energy consumption
s u s t a i n a b I l I t y
lessons learned:
Cooling Cool Performance

!Chilled water
should be cold!

s u s t a i n a b I l I t y
waterside example
Chiller Energy (800 tons)
Capacity 800 tons

LWT 7C
Power 464 kW

LWT 5C
Power 490 kW

s u s t a i n a b I l I t y
waterside example
System Power (Chilled Water)

Low Low
delta T flow

Chiller 464 kW 490 kW +26 kW

CHW pump 52 kW 16 kW - 36 kW

Total 516 kW 506 kW - 10 kW

s u s t a i n a b I l I t y
lessons learned
Chiller Performance

!Chillers should be
efficient!

Factory witness tested

s u s t a i n a b I l I t y
Airside: What is different?
Common Low air
practice temp.system

Supply air 14C 8 9C


Room setpoint 24C 25C
Airside delta T 10C 17C

Lowers the required air flow by 30-40%

s u s t a i n a b I l I t y
air handler options
Fan Room Floor Area

10x

s u s t a i n a b I l I t y
CDQ OA OA

EarthWise
airside system EA
OA CA EA
for floor-by-floor applications

RA
SA
to EA
occupied
space

MA

RA
SA
to EA
occupied
space

MA
Yeah, but.
Cold downdrafts
Condensation

s u s t a i n a b I l I t y
Eliminating Cold Downdrafts

Parallel fan-powered units


on the perimeter
Using linear slot diffusers...

s u s t a i n a b I l I t y
What about Condensation?
Cold surfaces must be kept inside the
humidity controlled envelope
Positive building pressure is critical for
no condensation and IAQ
Install a vapor barrier with reasonable
construction
Design the P traps and pitch the condensate
drains correctly

s u s t a i n a b I l I t y
EarthWise Systems

Energy
Efficiency

Emissions

s u s t a i n a b I l I t y
s u s t a i n a b I l I t y
Projects designed with
EarthWise system in Vit Nam
- Nh My Intel Viet Nam HCM: 2350RT x 4 = 9800 Tons
- Financial Tower ( Bitexco) 68 tng HCM: 1100RT x 6=6600RT
- Nh My in T Hoya Hanoi: 2100 Tons
- Nh My Canon Hanoi: 2930 Tons
- Nh My in t Panasonic Hanoi: 2100 Tons
- Nh My Thy Sn Nam Vit An Giang: 750 Tons
- Khch sn Sheraton Nha Trang: 700RT x 3 = 2100 Tons
- VINCOM + EDEN Tower- HCM: 1000RT x 8 = 8000 Tons
- Linh m Project- Hanoi: 4 x 600RT = 2400 Tons
- Crown Plaza Hanoi: 4 x 750 RT = 3000 Tons