Beruflich Dokumente
Kultur Dokumente
s u s t a i n a b I l I t y
average commercial building
Energy Consumption
Others
15%
Lifts/escalators Air-conditioning
11% 55%
Lighting
19%
s u s t a i n a b I l I t y
EarthWise Systems?
Energy
Efficiency
Emissions
s u s t a i n a b I l I t y
EarthWise Systems
Chiller system:
Low flow, low temperature
high efficiency systems
What do they do?
How do they do it?
Why use them?
s u s t a i n a b I l I t y
Low Flow, Low Temperature,
High Efficiency Systems
+/-$ ~/$
air handlers ductwork
+/-$
controls
+/-$
~/$
piping +/-$
chillers
s u s t a i n a b I l I t y
How?
Supply temperature Flow rates Fans
Ductwork
Piping
s u s t a i n a b I l I t y
Why Use LLH Systems?
Good for business: Offers the potential to
lower first cost and/or operating cost while
enhancing comfort, IAQ, and acoustics
Environmentally responsible: Reduced utility
generated greenhouse gas emissions and
uses less natural resources
Ideal for use in health care, institutional,
governmental, office building, education, and
other markets where VAV systems are used
s u s t a i n a b I l I t y
EarthWise Systems
s u s t a i n a b I l I t y
EarthWise Systems
100
95
90
LEED
% of HVAC energy consumption
85
80
EAc1
75
70
65
60
Conventional System Trane EarthWise System
Atlanta 100% 83%
Minneapolis 100% 93%
Los Angeles 100% 70%
Denver 100% 83%
Philadelphia 100% 89%
Portland 100% 80%
s u s t a i n a b I l I t y
EarthWise Systems
1970s 2007
18%
9% 31%
73%
17% 51%
Chiller
Cooling tower
Water pumps
s u s t a i n a b I l I t y
History of Chiller Performance
8.0 Centrifugal
Chiller efficiency, COP
>600 tons
Screw
6.0 150-300 tons
Scroll
<100 tons
4.0
Reciprocating
<150 tons
2.0
0.0
1977 1980 1989 1999 best
available
ASHRAE Standard 90.1
s u s t a i n a b I l I t y
Cool More or Pump More?
Pump efficiency 70%
COP 0.7
Chiller COP 7.0
Chiller COP 10x the pump COP
Conclusion work your most efficient
equipment harder
s u s t a i n a b I l I t y
Old Rule (ARI Standard)
s u s t a i n a b I l I t y
Earthwise Systems
Earthwise reduces energy for circulation
Basic Equation:
Q = cp x G x DT
Btuh = 500 x gpm x DT(0F)
Watts = 4184 x lps x DT(0C)
Saves
energy
s u s t a i n a b I l I t y
New Rule ( EarthWise System)
s u s t a i n a b I l I t y
Basic Rule
Fan :
Velocity1 / Velocity2 = Airflow1 / Airflow2
SP1 / SP2 = (Airflow1 / Airflow2 )2
Power1 / Power2 = (Airflow1 / Airflow2 )3
Pump :
Velocity1 / Velocity2 = Flow1 / Flow2
Pressure1 / Pressure2 = (Flow1 / Flow2 )2
Power1 / Power2 = (Flow1 / Flow2 )3
Meaning:
s u s t a i n a b I l I t y
Show Me the Impact
Cooling towers
Cooling coils
Pumps
Chillers
Air handlers
Controls
s u s t a i n a b I l I t y
waterside example
Cooling Tower Performance
(800 tons)
37/32/28 C 39/31/28 C
2400 GPM(151 l/s) 1600 GPM(100 l/s)
5C range 8C range
4C approach 3C approach
32 kW 32 kW
s u s t a i n a b I l I t y
waterside example
Cooling Tower: Size?, Cost?
s u s t a i n a b I l I t y
lessons learned
Cooling Tower Performance
!Tower water
should be hot!
Towers should use
inverters!
s u s t a i n a b I l I t y
Cooling Coil
MBH 504 504
WTR 5.5C 9C
EWT 6.5C 5C
s u s t a i n a b I l I t y
Chilled Water Pump (800 tons)
In this installation:
a 37.5% reduction in flow =
nearly 70% reduction in chilled water
pumping energy consumption
s u s t a i n a b I l I t y
lessons learned:
Cooling Cool Performance
!Chilled water
should be cold!
s u s t a i n a b I l I t y
waterside example
Chiller Energy (800 tons)
Capacity 800 tons
LWT 7C
Power 464 kW
LWT 5C
Power 490 kW
s u s t a i n a b I l I t y
waterside example
System Power (Chilled Water)
Low Low
delta T flow
CHW pump 52 kW 16 kW - 36 kW
s u s t a i n a b I l I t y
lessons learned
Chiller Performance
!Chillers should be
efficient!
s u s t a i n a b I l I t y
Airside: What is different?
Common Low air
practice temp.system
s u s t a i n a b I l I t y
air handler options
Fan Room Floor Area
10x
s u s t a i n a b I l I t y
CDQ OA OA
EarthWise
airside system EA
OA CA EA
for floor-by-floor applications
RA
SA
to EA
occupied
space
MA
RA
SA
to EA
occupied
space
MA
Yeah, but.
Cold downdrafts
Condensation
s u s t a i n a b I l I t y
Eliminating Cold Downdrafts
s u s t a i n a b I l I t y
What about Condensation?
Cold surfaces must be kept inside the
humidity controlled envelope
Positive building pressure is critical for
no condensation and IAQ
Install a vapor barrier with reasonable
construction
Design the P traps and pitch the condensate
drains correctly
s u s t a i n a b I l I t y
EarthWise Systems
Energy
Efficiency
Emissions
s u s t a i n a b I l I t y
s u s t a i n a b I l I t y
Projects designed with
EarthWise system in Vit Nam
- Nh My Intel Viet Nam HCM: 2350RT x 4 = 9800 Tons
- Financial Tower ( Bitexco) 68 tng HCM: 1100RT x 6=6600RT
- Nh My in T Hoya Hanoi: 2100 Tons
- Nh My Canon Hanoi: 2930 Tons
- Nh My in t Panasonic Hanoi: 2100 Tons
- Nh My Thy Sn Nam Vit An Giang: 750 Tons
- Khch sn Sheraton Nha Trang: 700RT x 3 = 2100 Tons
- VINCOM + EDEN Tower- HCM: 1000RT x 8 = 8000 Tons
- Linh m Project- Hanoi: 4 x 600RT = 2400 Tons
- Crown Plaza Hanoi: 4 x 750 RT = 3000 Tons
s u s t a i n a b I l I t y
- The End -
s u s t a i n a b I l I t y