Beruflich Dokumente
Kultur Dokumente
I
I
I
nstantaneous-trip, molded-case circuit I
breakers (MCCBs) have been applied success- I
I
fully for low-voltage motor protection for I
many years. In recent years, however, the I
I
changes in motor-starting characteristics have cre- I
ated more difficult challenges for the application I
I
engineer. The major challenge is successfully start- I
ing the low-voltage motor without causing the in- I
I
stantaneous-trip breaker to falsely trip without I
exceeding equipment ratings or violating limita- I
tions in the National Electrical Code (NEC) 111. I
I
Right sizing circuit breakers for use in I
low-voltage combination motor starters is critical to I
I
the successful, reliable operation of plant and pro- I
cess facilities. If not properly applied, false tripping I
I
on motor starting and contact welding ofcontactors I
may occur. Moreover, changes in the NBC and im- I
I
proved motor efficiencies have impacted equipment I
selection and protection. The following information I
I
is intended to guide application engineers in their I
selection ofthe right breaker and its setting for more I
I
reliable motor protecrion: I
Combination motor-starter components, I
I
Circuit breaker characteristics, I
Circuit breaker and combination starter troller and a disconnecting means. The controller I
, testing, may or may not contain overload protection,
short-circuit protection, or both. Where an indi-
I
I
Motor starting characteristics, and I
Component selection using coordination ex- vidual controller is enclosed, it includes an external I
means for operating the disconnecting means 131. I
amples. I
The examples show how selecting the right Then, it defines a combination motor controller as I
a combination controller intended for motor ser- I
breaker and breaker setting can avoid false tripping I
during starting, mitigate contact welding, and vice. A combination starter is one form of a com- I
bination motor controller and is supplied as an I
provide backup protection for overload conditions. I
I
Lorraine K. Padden is with Padden Engineering, LLC, I
I
Combhution Motor-Starter Components of Katy, Texas. George D. Gregory is with Square D I
I
UL 508. the Underwriters Laboratories (UL) Stan- -- - . of Cedar Ratiias, Iowa. Both authors are Se-
ComDany
I
dard for Industrial Control Equipment, defines a nior Members ofthe IEEE. This article appeared in its I
combination controller as an open or enclosed de- oviginalfirni at the 1998 IEEE IAS Petroleum ana I
I
vice containing both a magnetic or solid-state con- Chemical Indnstry Conference. I
I
I
I
I Circuit Breaker Characteristics
I There are two basic types of MCCBs: inverse time
I and instantaneous trip. Inverse-time circuit break-
I
I ers may have either a thermal-magnetic or elec-
I tronic sensing element. The instantaneous-trip
I
I circuit breaker is essentially a thermal-magnetic
I circuit breaker with the thermal sensing element
I
I removed. This section provides a discussion of the
I operation and tripping characteristics of these two
I
I types of breakers. As a comparison, Figs. 3 and 4
a
I Pig. 1. Comnhirzation motor starter components. show the tripping characteristics of the thermal-
*
I
I -
Electromagnetic
Force
W = F*dx
ThermdMagnetic C haracteristic
The most commonly available MCCB is ther-
m a I - m a g ne t i c . A t y p i c a1 thermal - mag net i c
I
I
I
I
I
MCCB characteristic appears in Fig. 4. A ther- I
mal-magnetic circuit breakers inverse-time func- I
I
tion can provide the thermal overload protection if I
I
I
I
F = Force I
i(f) = Instantaneous Current I
1
W =Work I
I
Fig. 2. Illustrution of the force and work done by the I
electrornugnet to trip the breaker. I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Fig. 3. Asymmetricdl wuueform shouling the RMS I
I
v a l m , which corresponcls to the trip setting und Fig8 4. Time-current characteristic for U 150-A I
coordinution plot vulzies. I
arljustuhle trip thermul-mugnetic M C C B . I
a
I
I
I
I
I
is done on each pole of each tested sample before I
I
and after each test sequence to verify tripping I
within Table I tolerances. Dielectric withstand I
testing is also done following each test sequence. I
I
A short-circuit interrupting test is performed for I
the listed circuit breaker at the standard level, lim- I
I
ited available current. In this test, a trip coil is per- I
mitted to burn out. However, ifa trip coil burns out, I
I
a second set of samples is subjected to a repeat of the I
short-circuit test with an impedance equivalent to I
I
that of an overload relay, in which test the trip coil I
may not burn out. For three-pole circuit breakers up load relay. The circuit breaker trip setting is ad- I
justed to maximum or its mechanism is impaired I
to 800 A, rated 480 or 600 V, this test consists of I
two short circuits on each pole with 8660 A avail- to prevent its tripping during the test. I
Con~actor-OverloadTest:A magnetic or a vacuum I
able a t line-to-line voltage and a common I
three-phase short-circuit with 10,000 A available. contactor is required to break 1000% ofmaximum I
These seven short-circuit operations are followed by FLC (based on the hp and voltages in NEC Table I
I
a calibration and a dielectric withstand test. 430-150) at maximum-rated voltage and 50% I
power factor for three operations under conditions I
I
Combination Motor-Starter Tests of maximum voltage, power, and current for each I
Refer to Fig. 1 for the components. Component rating of the combination controller. For example, I
I
tests of the circuit breaker were discussed above. a size 4 contactor is used for a 50-hp motor at 230 V I
The overload relay and contactor will each be with FLC of 130 A, and for a 100-hp motor at 460 I
I
tested as a component under UL 508 131. Then, the V with a FLC of 96 A. It would be break tested at I
combination is subjected to the following tests: 1300 A (10 X 130 A) at probably 600 V. During I
I
Temperature, the test, the contactor is required to break the cir- I
Dielectric withstand, cuit without mechanical or electrical breakdown I
I
Current withstand, and without contact weld. I
Combination Short-Civcait Test: Bach combina- I
Contactor overload, I
Combination short-circuit, and tion controller is subjected to a specified short-cir- I
cuit level corresponding to its horsepower rating. I
High available short-circuit current. I
A brief description is provided for tests related These are shown in Table 11. Connection wire is I
sized to at least 125% of the FLC rating of the cur- I
to this article. For the current-withstand test and I
all short-circuit tests, a wide range of combination rent element. Four feet of wire on the supply side I
connect the unit to test station terminals, and an I
controller samples are tested to cover the possible I
combinations of overload relays, current elements, additional four feet ofwire on the load side connect I
the unit to the short-circuit point. The circuit I
and instantaneous-trip circuit breaker trip coils. I
Temperature Test: The combination controller is breaker is adjusted to its maximum setting. The I
required to carry FLC continuously and retain tem- number of short-circuit operations varies and is I
I
peratures compatible with materials and compo- shown in Table 11. I
Criteria for acceptance include the following I
nents used in the combination controller. I
Current-Withstand Test: The combination con- points: I
m The circuit breaker or contactor must clear I
troller is required to carry 600%, and then 1000%, I
of FLC without damage to any parts or connected the circuit. I
wire that would impair their function. The test is The circuit breaker must retain its integrity I
I
continued until the circuit is opened by the over- and demonstrate compliance with calibra- I
I
I
I
I
CombinationRating Short-Circuit l e v e l I
Number of Short-circuit Operations I
I
I hP 1000 A Three for one-phose I
I
Two for three-phase I
I
2 to 50 hp 5000 A Three for one-phose I
I
Two for three-phase I
F I
I
51 to 200 hp 10,000 A Two for three-phose I
I
~ ~~~~
Fig. 6. Illustration of the FLC of 1 per tinit RMS, the symmetrical LRC, and the
50 I
neous-trip circuit breaker setting for NEMA De- asymmetrical starting current with an XIR ratio of 9.95.The instantaneous-tri)
sign B energy efficient motors to be 17 X FLC. This range i s illustrated in RMS values.
change does not require a larger contactor in Sec-
tion 430-83, but the design engineer must provide
equipment that is capable of interrupting the ex-
pected fault current per Sections 110-9 and
110-10. These considerations are reviewed in more
detail below.
Coordination Discussion
The two components of coordination are protec-
tion and selectivity. The NEC addresses the pro-
tection requirements in the following sections:
110-9 Equipment intended to interrupt
current at fault levels shall have an interrupt-
ing rating sufficient for the nominal circuit I I
voltage and the current that is available at the Fig. 7. One-linediagram for a 100-hp motor showing the Combination starter.
I
I
I
I
I
I
I but no higher than 1300% (13 X 124 A =
I
I 1612 A) for the Design B motor if demon-
I strated by an engineering evaluation.
I
I w A setting of 12 X FLC was chosen for this ex-
I ample to review possible false tripping and
I
I view interaction with other components.
I
I
I Fulse Tripping and Contactor Ruting Isszles
I Finding an appropriate circuit breaker setting that
I
I will permit starting current to flow while provid-
I ing protection for the contactor may be a challenge.
I
I An asymmetrical starting current can be several
I Fulse-Tripping Example times LRC. Recall that tlie circuit breaker settings
I
I Instantaneous-trip MCCBs can have false-tripping are marked in RMS terms. For this example, the
I problems when standard efficiency NEMA B mo- asymmetrical starting current was calculated at
I
I
tors are started due to the asymmetrical starting 1276 A, which would occur in the first half cycle.
I current and tlie tripping band on the instanta- The size 4 contactor should be tested to break up to
I neous-trip breakers, while staying within the lim-
I 10 x the maximum motor FLC, as previously dis-
I its of the NEC trip setting. Refer to Fig. 7 for the cussed; 130-A FLC and 1300-A tested breakvalue.
I simplified one-line diagram of a standard effi-
I It would seem that asetting of 1300 A would be
I ciency motor application with potential false-trip- satisfactory to permit starting current to flow
I ping problems.
I while protecting the contactor. However, the trip-
I The coordination plot in Fig. 8 was developed ping band of the circuit breaker must be consid-
I using the information in Fig. 7. The coordination
I ered. Using Table I, the tripping band for a setting
I analysis includes the following information: of 1300 A would be a range of 1040 to 1690 A. Op-
I Consider the maximum permissible setting eration at tlie low end of the band could see false
I
I foraDesignB motorof8009L ofFLC(8Xl24 tripping on starting. At the high end, the
I A = 992 A) in NEC Table 430-152. contactor might try to open above its tested break
I
I Determine whether false tripping is expected current value on a high-impedance fault, and a con-
I when starting. A typical asymmetrical start- tact weld is possible.
I ing current is assumed and calculated as fol-
I A setting of 1500 A (12 X FLC) was selected for
I lows: 1.76 X LRC (1.76 X 725 = 1276 A) in Fig. 8 to illustrate a high setting available on a typ-
I RMS terms {8]-[10], [12}. This indicates
I ical breaker without exceeding tlie NEC limit.
I that false tripping will occur with the 800% This selection still leaves a gap in which the
I setting.
I contactor is unprotected and overlaps a small range
I 1 Using NEC 430-52(~)(3) Ex 1, i t is permissi- in which the breaker could trip during motor start.
I ble to adjust the setting higher than 800%,
I An asymmetrical starting current value of 1.76
I x the LRC is a typical value used for industrial ap-
I
I plications [l1}-[13]. This assumption illustrates
I the coordination issues that arise for industrial ap-
I
I plications. In some cases, the multiplier may be
I lower or higher. W i t h tlie advent of energy-effi-
I
I cient motors, high starting current issues are in-
I creasing significantly as previously highlighted.
I
I
I Fulse-Tripping Solutions
I
I If false tripping during start still occurs when the
I instantaneous-trip setting is at tlie maximum al-
I
I lowed by tlie 1999 NEC, several options should be
I considered:
I
I w Use a thermal-magnetic MCCB or fuse in
I place of the instantaneous-trip MCCB.
I
I Fixed-trip thermal-magnetic MCCBs have
I an instantaneous-trip range higher than the
I
I instantaneous-trip MCCB, thereby allow-
I ing the motor to start. Ratings of the
I
I
contactor and other components should be
I reviewed for protection. Adjustable-trip
I thermal-magnetic breakers may provide the
I Fig. 8. Time-current coordiiaation plot for a 1 00-hp
best of both worlds, allowing a higher in-
i
motor showing the unprotected area of the contactor.
I
I
I
I
I
I
stantaneous setting within the NEC re- rating of 10 times the maximum motor FLC value. I
quirements while providing the maximum These are generally smaller in size than comparable I
I
possible protection for other components magnetic contactors, but are more expensive. A I
such as the contactor. As the design engi- costibenefit analysis may be needed to determine I
I
neer would expect, the instantaneous-trip the contactor type. I
devices are the least expensive, fixed-trip Fig. 9 shows the protected contactor at a higher I
I
thermal-magnetic breakers are more expen- instantaneous-trip setting. A size 5 contactor and a I
sive, ancl adjustable-trip thermal-magnetic breaker with an instantaneous-trip setting of 1610 A I
I
breakers are the most expensive. are illustrated. Note the NEC permits 13 x full-load I
Use an MCCB with time-delay or damping current for the setting, which would be 1612 A. The I
I
to override starting current, although they maximum trip is 2093A (1610 X 130%).The mini- I
are not readily available. mum trip is 1288 A (1610 X 80%). I
I
Use a reduced-voltage starter, such as an For this case, the size 5 contactor is protected I
autotransformer, during starting to reduce using a trip setting of l 6 1 0 A because thecontactor I
I
the starting current. Equipment size and cost break value of 2490 A (10 times maximum motor I
may be limiting. FLC) is not exceeded. Also, the breaker should not I
trip on motor start because the minimum trip is I
For energy-efficient NEMA B motors, con- I
sider allowing the instantaneous-trip setting 1288 A, which is above the asymmetrical starting I
to be 17 x the motor FLC. Cazttion! The in- current of 1276 A. I
I
stantaneous-trip setting should not be set above the This solution satisfies the protection criteria. As I
cornbinationstarter tested value. Be aware that the a result of the high starting current, protection of I
I
contactor is not tested to interrupt current above 10 the motor is not as close as might be desired. Also, I
times tbe maximum motor FLC value. selective coordination with devices on the supply I
I
side will be more of a challenge than with a lower I
Mitigating Contactor Damage setting. However, false tripping should not occur I
I
An option to avoid applying the contactor at levels and the contactor should be protected. I
above those for which it has been tested to break is I
I
to specify a larger contactor with a higher current Backap Protection I
rating. Contactors are rated to break current at 10 The design engineer should evaluate the need for I
I
times the maximum motor FLC value. Therefore, backup protection in the overload region. First, the I
the larger contactor would be protected with a overload device is normally the only line of protec- I
tion from overloads and high impedance faults I
higher setting of the instantaneous-trip MCCB I
(within the NEC requirements). when using instantaneous-trip circuit breakers. A I
If space is a factor in upsizing the contactor, vac- failure of the overload device, overload wiring, or I
I
uum contactors should be considered. They are contactor can prevent the circuit from being iso- I
typically manufactured with full-load current rat- lated due to overload or high-impedance fault con- I
I
ings of 160,320,600, and 720 A and have a break ditions. Where backup protection is desired for I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Fig. 9 . Time-current plot f o r a 1OO-hp motor Fig. IO. Backup protection using n thernanl- I
I
showing the protected contactor. mugnetic ucGiLstable instuntuneous AICCB. I