Beruflich Dokumente
Kultur Dokumente
10000
9000
8000
7000
6000
5000
4000 Through-fault protection curve Through-fault protection curve
for faults that will occur frequently for faults that will occur frequently
3000 (typically not more than 10 in (typically not more than 10 in
transformer lifetime) transformer lifetime)
2000
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
Time in seconds
50
40
30
20
10
9
8
7
6
5
4
3
2
12 10 8 7 6 4 5 This curve may also be
K transformer impedance used for back-up
protection where the
1 transformer is exposed
0.9
0.8 For fault currents from 70% to 100% of maximum to frequent faults
0.7 possible : I 2t= K normally cleared by
0.6 high-speed relaying
0.5 where I = Symmetrical fault current in times normal
0.4 base current (AN SI/IEEE C57.12.00-1980)
0.3 K = Constant determined at maximum I with
t = 2 seconds
0.2
Note = Sample I 2t= K curves have been plotted for
selected transformer impedances as noted.
0.1
3 4 2 5 6 7 8 9 10 20 30 40 50 2 3 4 5 6 7 8 9 10 20 30 40 50
Times normal base current
10000
9000
8000
7000
6000
5000
4000 Through-fault protection curve Through-fault protection curve
for faults that will occur frequently for faults that will occur frequently
3000 (typically not more than 5 in (typically not more than 5 in
transformer lifetime) transformer lifetime)
2000
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
Time in seconds
50
40
30
20
10
9
8
7
6
5
4
3
2
12 10 8 7 6 4 5 This curve may also be
K transformer impedance used for back-up
protection where the
1 transformer is exposed
0.9 For fault currents from 50% to 100% of maximum
0.8 to frequent faults
0.7 possible : I 2t= K normally cleared by
0.6 high-speed relaying
0.5 where I = Symmetrical fault current in times normal
0.4 base current (ANSI/IEEE C57.12.00-1980)
0.1
2 4 53 6 7 9 10
8 20 30 40 50 2 3 4 5 6 7 8 910 20 30 40 50
Times normal base current