Note 1: These distances shall not apply where protective structures having a
BELOW GROUND minimum fire resistance rating of two hours interrupt the line of site between
BELOW GROUND the uninsulated portions of the bulk oxygen storage installation and the
Bulk COMBUSTIBLE Liquid Storage Bulk FLAMMABLE Liquid Storage exposure. This wall should be no closer than 3 ft. to the system to allow for
ventilation and system maintenance. The wall should be designed to
To The Vessel To the Vessel withstand anticipated wind and seismic forces. The protective structure in lieu
<1000 gal C = 15 N = # 0 = 15 Inlet of an of distance protects uninsulated oxygen storage containers or supports, control
C = 15 N = 15 0 = 15 underground
>1000 gal C = 30 N = # 0 = 30 equipment enclosures, and system piping from external fire exposure.
sewer,
To Any Fill Connections, Vents drains. Note 2: NFPA 50-2001 defines a building of wood frame construction as a
C = 40 N = 25 0 = 40 To any Fill Connections , Vents
C = 50 N = 25 0 = 50 C=8 building construction, Type V, as defined in NFPA 220, which includes any
Note # 1 N=8 building whose exterior walls are made wholly or partially of wood or do not
Note # 1 have a fire resistance of 2 hours.
O=#