Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-factor


Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
tained when exposed to corrosive at-
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the
Description standard corrosion tests of the appli-
cable approval agencies, the testing is
The Series TY-FRB, 2.8, 4.2, 5.6, and not representative of all possible cor-
8.0 K-factor, Upright and Pendent rosive atmospheres. Consequently, it
Sprinklers described in this data sheet is recommended that the end user be
are quick response - standard cover- consulted with respect to the suitability
age, decorative 3 mm glass bulb type of these coatings for any given corro-
spray sprinklers designed for use in sive environment. The effects of ambi-
light or ordinary hazard, commercial ent temperature, concentration of
occupancies such as banks, hotels, chemicals, and gas/chemical velocity,
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY-FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be
plicable, is intended for use in areas exposed.
with a finished ceiling. It uses either a An intermediate level versions of the
two-piece Style 10 (1/2 inch NPT) or Series TY-FRB Pendent Sprinklers
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de-
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece WARNINGS
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY-FRB Sprinklers de-
inch NPT) Recessed Escutcheon with scribed herein must be installed and
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro-
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
standards of any other authorities hav-
ing jurisdiction. Failure to do so may Model/Sprinkler
pipe drops to the sprinklers must be
cut.
impair the performance of these de-
vices. Identification
Corrosion resistant coatings, where
applicable, are utilized to extend the
The owner is responsible for maintain-
ing their fire protection system and de-
Numbers
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2"NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2"NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2"NPT
with any questions. TY2231 - Pendent 4.2K, 1/2"NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2"NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2"NPT
Sheet TFP700 for the INSTALLER TY4131 - Upright 8.0K, 3/4"NPT
WARNING that provides cautions TY4231 - Pendent 8.0K, 3/4"NPT
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 10 APRIL, 2006 TFP171


Page 2 of 10 TFP171

ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20


PLATE SEATING NOMINAL RECESSED
SURFACE 1/2" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6

5
7/16"
2-1/4" (11,1 mm) 4
(57,2 mm) NOMINAL
MAKE-IN 2
1-9/16" 2-3/16" 3
(39,7 mm) WRENCH (55,6 mm)
FLATS 1

7
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **

PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION

1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to


2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT

ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20


PLATE SEATING NOMINAL RECESSED
SURFACE 1/2" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6*

7/16" 5
2-3/16" (11,1 mm)
(55,6 mm) NOMINAL 4
MAKE-IN
1-1/2" 2
2-3/16"
(38,1 mm) WRENCH (55,6 mm)
FLATS 3

1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **

PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION


1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.

FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
TFP171 Page 3 of 10

ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20


PLATE SEATING NOMINAL RECESSED
SURFACE 1/2" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6*

7/16" 5
2-3/16" (11,1 mm)
(55,6 mm) NOMINAL 4
MAKE-IN
1-1/2" 2
2-3/16"
(38,1 mm) WRENCH (55,6 mm)
FLATS 3

1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **

PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION


1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.

FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT

ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40


PLATE SEATING NOMINAL RECESSED
SURFACE 3/4" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6*

1/2" 5
2-5/16" (12,7 mm)
(58,7 mm) NOMINAL 4
MAKE-IN
2
1-9/16" 2-1/4"
(39,7 mm) WRENCH (57,2 mm)
FLATS 3

1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 3/4" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION

1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to


2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Page 4 of 10 TFP171

SPRINKLER FINISH (See Note 7)


K TYPE TEMP. BULB NATURAL CHROME WHITE***
Technical
LIQUID BRASS PLATED POLYESTER Data
135F/57C Orange Approvals
PENDENT UL and C-UL Listed.
155F/68C Red
(TY1231) 1, 2, 3, 5 FM, LPCB, and NYC Approved.
and 175F/79C Yellow (Refer to Table A and B for complete
UPRIGHT 200F/93C Green approval information including corro-
(TY1131) sion resistant status.)
2.8 286F/141C Blue
1/2" Maximum Working Pressure
NPT 135F/57C Orange Refer to Table C.
RECESSED
155F/68C Red Discharge Coefficient
PENDENT
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1/2)
(TY1231)* 175F/79C Yellow
K = 4.2 GPM/psi1/2 (60,5 LPM/bar1/2)
Figure 5 200F/93C Green 1, 2, 5 K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2)
135F/57C Orange
RECESSED Temperature Ratings
155F/68C Red
PENDENT Refer to Table A and B
(TY1231)** 175F/79C Yellow
Finishes
Figure 6 200F/93C Green Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
135F/57C Orange
Chrome Plated, or Brass Plated.
PENDENT
155F/68C Red
(TY2231)
and 175F/79C Yellow Physical Characteristics
UPRIGHT Frame . . . . . . . . . . . . Bronze
200F/93C Green Button . . . . . . . . Brass/Copper
(TY2131)
4.2 286F/141C Blue Sealing Assembly . . . . . . . . . .
1/2" 1, 2 . . . . . Beryllium Nickel w/Teflon
NPT 135F/57C Orange Bulb . . . . . . . . . . . . . . Glass
RECESSED Compression Screw . . . . . Bronze
155F/68C Red
PENDENT Deflector . . . . . . . Copper/Bronze
(TY2231)* 175F/79C Yellow Bushing (K=2.8) . . . . . . . Bronze
Figure 7 200F/93C Green

RECESSED
135F/57C Orange Operation
155F/68C Red
PENDENT The glass Bulb contains a fluid which
(TY2231)** 175F/79C Yellow expands when exposed to heat. When
Figure 8 the rated temperature is reached, the
200F/93C Green
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
NOTES:
activate and water to flow.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
Design
klers.
5. Approved by the City of New York under MEA 354-01-E. Criteria
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers. The Series TY-FRB Pendent and Up-
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment right Sprinklers are intended for fire
Recessed Escutcheon, as applicable. protection systems designed in ac-
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment cordance with the standard installation
Recessed Escutcheon, as applicable. rules recognized by the applicable
*** Frame and Deflector only. Listings and approvals apply to color (Special Order). Listing or Approval agency (e.g., UL
N/A: Not Available Listing is based on the requirements of
DuPont Registered Trademark

NFPA 13, and FM Approval is based


TABLE A on the requirements of FMs Loss Pre-
LABORATORY LISTINGS AND APPROVALS vention Data Sheets ). Only the Style
2.8 AND 4.2 K-FACTOR SPRINKLERS 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
TFP171 Page 5 of 10

SPRINKLER FINISH (See Note 8)


K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD
LIQUID BRASS PLATED POLYESTER COATED

135F/57C Orange
PENDENT
155F/68C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175F/79C Yellow
UPRIGHT 200F/93C Green
(TY3131)
5.6 286F/141C Blue
1/2"
NPT 135F/57C Orange
RECESSED
155F/68C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175F/79C Yellow
Figure 9 200F/93C Green
135F/57C Orange
RECESSED
155F/68C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231)** 175F/79C Yellow
Figure 10 200F/93C Green
135F/57C Orange
PENDENT
155F/68C Red
(TY4231) 1, 2, 5
and 175F/79C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200F/93C Green
(TY4131)
8.0 286F/141C Blue
3/4"
NPT 135F/57C Green
RECESSED
155F/68C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175F/79C Red
Figure 11 200F/93C Yellow
135F/57C Orange
RECESSED
155F/68C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231)** 175F/79C Yellow
Figure 12 200F/93C Green

NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available

TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 10 TFP171

SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED POLYESTER COATED

PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2" RECESSED PENDENT
NPT (TY323)

PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT
NPT (TY4231)

PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" 175 PSI (12,1 BAR)
RECESSED PENDENT
NPT (TY323) N/A
(SEE NOTE 1)

PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
3/4" RECESSED PENDENT
NPT (TY4231) N/A

NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.

TABLE C, MAXIMUM WORKING PRESSURE

nections. Higher levels of torque may The Series TY-FRB Recessed Pen-
Installation distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
dent Sprinklers must be installed in
accordance with the following instruc-
The Series TY-FRB Sprinklers must tions.
be installed in accordance with the fol- Do not attempt to make-up for insuffi-
lowing instructions: cient adjustment in the escutcheon Step A. After installing the Style 10.
plate by under- or over-tightening the 20, 30, or 40 Mounting Plate, as appli-
NOTES sprinkler. Readjust the position of the cable, over the sprinkler threads and
Do not install any bulb type sprinkler if sprinkler fitting to suit. with pipe thread sealant applied to the
the bulb is cracked or there is a loss of pipe threads, hand tighten the sprin-
The Series TY-FRB Pendent and Up-
liquid from the bulb. With the sprinkler kler into the sprinkler fitting.
right Sprinklers must be installed in
held horizontally, a small air bubble accordance with the following instruc- Step B. Tighten the sprinkler into the
should be present. The diameter of the tions. sprinkler fitting using only the W-Type
air bubble is approximately 1/16 inch 7 Recessed Sprinkler Wrench (Ref.
(1,6 mm) for the 135F/57C to 3/32 Step 1. Pendent sprinklers are to be
Figure 14). With reference to Figure 1,
inch (2,4 mm) for the 286F/141C installed in the pendent position, and
2, 3, and 4, the W-Type 7 Recessed
temperature ratings. upright sprinklers are to be installed in
Sprinkler Wrench is to be applied to
the upright position.
A leak tight 1/2 inch NPT sprinkler joint the sprinkler wrench flats.
should be obtained with a torque of 7 Step 2. With pipe thread sealant ap-
Step C. After the ceiling has been in-
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- plied to the pipe threads, hand tighten
stalled or the finish coat has been ap-
mum of 21 ft. lbs. (28,5 Nm) of torque the sprinkler into the sprinkler fitting.
plied, slide on the Style 10, 20, 30, or
may be used to install sprinklers with Step 3. Tighten the sprinkler into the 40 Closure over the Series TY-FRB
1/2 NPT connections. A leak tight 3/4 sprinkler fitting using only the W-Type Sprinkler and push the Closure over
inch NPT sprinkler joint should be ob- 6 Sprinkler Wrench (Ref. Figure 13). the Mounting Plate until its flange
tained with a torque of 10 to 20 ft.lbs. With reference to Figures 1, 2, 3, and comes in contact with the ceiling.
(13,4 to 26,8 Nm). A maximum of 30 4, the W-Type 6 Sprinkler Wrench is to
ft.lbs. (40,7 Nm) of torque is to be used be applied to the sprinkler wrench
to install sprinklers with 3/4 NPT con- flats.
TFP171 Page 7 of 10

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm)
5/81/4" 1/21/8" 1/2" (12,7 mm)
(15,96,4 mm) 1/4" (6,4 mm) (12,73,2 mm) 1/4" (6,4 mm)
2-1/4" DIA. 2-1/4" DIA.
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE

SERIES 1-5/16" (33,3 mm) SERIES 1-5/16" (33,3 mm)


CLOSURE CLOSURE
TY-FRB 13/16" (20,6 mm) TY-FRB 1-1/16" (27,0 mm)

FIGURE 5 FIGURE 6
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm)
5/81/4" 1/21/8" 1/2" (12,7 mm)
(15,96,4 mm) 1/4" (6,4 mm) (12,73,2 mm) 1/4" (6,4 mm)
2-1/4" DIA. 2-1/4" DIA.
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE
SERIES 1-1/4" (31,8 mm) SERIES 1-1/4" (31,8 mm)
CLOSURE CLOSURE
TY-FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm)

FIGURE 7 FIGURE 8
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT

objects; otherwise, non-operation in by brushing it with a soft bristle brush.


Care and the event of a fire or inadvertent opera-
tion may result.
Care must be exercised to avoid dam-
Maintenance Absence of an escutcheon, which is
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
The Series TY-FRB Sprinklers must used to cover a clearance hole, may aged by dropping, striking, wrench
be maintained and serviced in accord- delay the time to sprinkler operation in twist/slippage, or the like, must be re-
ance with the following instructions: a fire situation. placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
Sprinklers that are found to be leaking
NOTES liquid from its bulb. (Ref. Installation
or exhibiting visible signs of corrosion
Before closing a fire protection system Section).
must be replaced.
main control valve for maintenance Frequent visual inspections are rec-
work on the fire protection system that Automatic sprinklers must never be
ommended to be initially performed for
it controls, permission to shut down the painted, plated, coated or otherwise
corrosion resistant coated sprinklers,
affected fire protection system must be altered after leaving the factory. Modi-
after the installation has been com-
obtained from the proper authorities fied sprinklers must be replaced.
pleted, to verify the integrity of the cor-
and all personnel who may be affected Sprinklers that have been exposed to
rosion resistant coating. Thereafter,
by this action must be notified. corrosive products of combustion, but
annual inspections per NFPA 25
have not operated, should be replaced
The owner must assure that the sprin- should suffice; however, instead of in-
if they cannot be completely cleaned
klers are not used for hanging of any specting from the floor level, a random
by wiping the sprinkler with a cloth or
Page 8 of 10 TFP171

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm)
5/81/4" 1/21/8" 1/2" (12,7 mm)
(15,96,4 mm) 1/4" (6,4 mm) (12,73,2 mm) 1/4" (6,4 mm)
2-1/4" DIA. 2-1/4" DIA.
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE
SERIES 1-1/4" (31,8 mm) SERIES 1-1/4" (31,8 mm)
CLOSURE CLOSURE
TY-FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm)

FIGURE 9 FIGURE 10
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2" (12,7 mm)
5/81/4" 1/21/8"
(15,96,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (12,73,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE

CLOSURE SERIES 1-5/16" (33,3 mm) CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 13/16" (20,6 mm) TY-FRB 1-1/16" (27,0 mm)

FIGURE 11 FIGURE 12
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT 8.0 K-FACTOR, 3/4 INCH NPT

sampling of close-up visual inspec- WRENCH


tions should be made, so as to better RECESS
determine the exact sprinkler condi-
tion and the long term integrity of the WRENCH RECESS
corrosion resistant coating, as it may (END "A" USED FOR
be affected by the corrosive conditions 1/2" NPT MODELS)
present.
The owner is responsible for the in-
spection, testing, and maintenance of WRENCH RECESS
their fire protection system and de- PUSH WRENCH
(END "B" USED FOR
vices in compliance with this docu- IN TO ENSURE
3/4" NPT MODELS) ENGAGEMENT
ment, as well as with the applicable WITH SPRINKLER
standards of the National Fire Protec- FIGURE 13 WRENCHING AREA
tion Association (e.g., NFPA 25), in W-TYPE 6 SPRINKLER
addition to the standards of any other WRENCH FIGURE 14
authorities having jurisdiction. The in- W-TYPE 7 RECESSED
stalling contractor or sprinkler manu- SPRINKLER WRENCH
facturer should be contacted relative tested, and maintained by a qualified
to any questions. Inspection Service in accordance with
It is recommended that automatic local requirements and/or national
sprinkler systems be inspected, codes.
TFP171 Page 9 of 10

P/N 57 XXX X XXX


TEMPERATURE
MODEL/SIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2"NPT) TY1131 135 135F/57C

331 2.8K PENDENT (1/2"NPT) TY1231 1 NATURAL BRASS 155 155F/68C

340 4.2K UPRIGHT (1/2"NPT) TY2131 4 WHITE POLYESTER 175 175F/79C

341 4.2K PENDENT (1/2"NPT) TY2231 3 WHITE (RAL9010)* 200 200F/93C

370 5.6K UPRIGHT (1/2"NPT) TY3131 9 CHROME PLATED 286 286F/141C

371 5.6K PENDENT (1/2"NPT) TY3231 7 LEAD COATED

390 8.0K UPRIGHT (3/4"NPT) TY4131

391 8.0K PENDENT (3/4"NPT) TY4231 * Eastern Hemisphere sales only.

TABLE D
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS

charges, regardless of whether TFBP


Limited was informed about the possibility of
such damages, and in no event shall
Ordering
Warranty TFBPs liability exceed an amount Procedure
equal to the sales price.
Products manufactured by Tyco Fire & When placing an order, indicate the
Building Products (TFBP) are war- The foregoing warranty is made in lieu full product name. Refer to the Price
ranted solely to the original Buyer for of any and all other warranties, ex- List for complete listing of Part Num-
ten (10) years against defects in mate- press or implied, including warranties bers.
rial and workmanship when paid for of merchantability and fitness for a par-
ticular purpose. Contact your local distributor for avail-
and properly installed and maintained
ability.
under normal use and service. This This limited warranty sets forth the ex-
warranty will expire ten (10) years clusive remedy for claims based on Sprinkler Assemblies with NPT
from date of shipment by TFBP. No failure of or defect in products, materi- Thread Connections:
warranty is given for products or com- als or components, whether the claim Specify: (Specify Model/SIN), Quick
ponents manufactured by companies is made in contract, tort, strict liability Response, (specify K-factor), (specify
not affiliated by ownership with TFBP or any other legal theory. temperature rating), Series TY-FRB
or for products and components which
This warranty will apply to the full ex- (specify Pendent or Upright) Sprinkler
have been subject to misuse, improper
tent permitted by law. The invalidity, in with (specify type of finish or coating),
installation, corrosion, or which have
whole or part, of any portion of this P/N (specify from Table D).
not been installed, maintained, modi-
fied or repaired in accordance with ap- warranty will not affect the remainder.
Recessed Escutcheon:
plicable Standards of the National Fire Specify: Style (10, 20, 30, or 40) Re-
Protection Association, and/or the cessed Escutcheon with (specify*) fin-
standards of any other Authorities
ish, P/N (specify*).
Having Jurisdiction. Materials found
by TFBP to be defective shall be either * Refer to Technical Data Sheet TFP770.
repaired or replaced, at TFBPs sole
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W-Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56-000-6-387.
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for Specify: W-Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56-850-4-001.
curate or incomplete information sup-
plied by Buyer or Buyers repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
Page 10 of 10 TFP171

TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446