4 ways in which noise can enter a signal cable and its control (photo credit: bicsi.org)
Constant noise can be due to the predictable 50 or 60 Hz AC hum from power circuits or harmonic multiples of
power frequency close to the data communications cable. This unpredictability makes the design of a data
communications system quite challenging.
Electrical noise occurs or is transmitted into a signal cable system in the following four ways:
1/5
4. Radio frequency interference (RFI) (in part 2)
If two signal channels within a single data cable share the same signal reference conductor (common return path),
the voltage drop caused by one channels signal in the reference conductor can appear as a noise in the other
channel and will result in interference. This is called galvanic noise.
Electrostatic noise is one, which is transmitted through various capacitances present in the system such as between
wires within a cable, between power and signal cables, between wires to ground or between two windings of a
transformer. These capacitances present low-impedance paths when noise voltages of high frequency are present.
Thus noise can jump across apparently non- conducting paths and create a disturbance in signal/data
circuits.
Electromagnetic interference (EMI) is caused when the flux lines of a strong magnetic field produced
by a power conductor cut other nearby conductors and cause induced voltages to appear across
them.
When signal cables are involved in the EMI process, this causes a noise in signal circuits. This is aggravated when
harmonic currents are present in the system. Higher order harmonics have much higher frequencies than the normal
AC wave and result in interference particularly in communication circuits.
Radio frequency interference involves coupling of noise through radio frequency interference. We will now describe
these in some detail.
For situations where two or more electrical circuits share common conductors, there can be some coupling between
different circuits with deleterious effects on the connected circuits. Essentially, this means that the signal current
from one circuit proceeds back along the common conductor resulting in an error voltage along the return bus,
which affects all the other signals.
The error voltage is due to the capacitance, inductance and resistance in the return wire. This situation is shown in
Figure 1 below.
Obviously, the quickest way to reduce the effects of impedance coupling is to minimize the impedance of the
return wire. The best solution is to use a balanced circuit with separate returns for each individual signal shown in
Figure 2.
Go back to Index
This form of coupling is proportional to the capacitance between the noise source and the signal wires. The
magnitude of the interference depends on the rate of change of the noise voltage and the capacitance between the
noise circuit and the signal circuit.
2/5
In Figure 3, the noise voltage is coupled into the communication signal wires through the two capacitors C1 and C2,
and a noise voltage is produced across the resistances in the circuit.
The size of the noise (or error) voltage in the signal wires is proportional to the:
Inverse of the distance of noise voltage from each of the signal wires
Length (and hence impedance) of the signal wires into which the noise is induced
Amplitude (or strength) of the noise voltage
Frequency of the noise voltage.
There are four methods for reducing the noise induced by electrostatic coupling. They are:
Notes:
The shield must be of a low-resistance material such as aluminum or copper. For a loosely braided copper
shield (85% braid coverage) the screening factor is about 100 times or 20 dB that is, C3 and C4 are about 1/100 C1
or C2. For a low-resistance multi- layered screen, this screening factor can be 35 dB or 3000 times.
Twisting of the signal wires provides a slight improvement in the induced noise voltage by ensuring that C1 and
C2 are closer together in value; thus ensuring that any noise voltages induced in the signal wires tend to cancel one
another out.
Provision of a shield by a cable manufacturer ensures that the capacitance between the shield and the wires is
equal in value (thus eliminating any noise voltages by cancellation).
Reference: Practical Grounding, Bonding, Shielding and Surge Protection G. Vijayaraghavan, B.Eng (Hons)
Consulting Engineer, Chennai, India
3/5
Figure 2 Impedance coupling eliminated with balanced circuit
4/5
Figure 3 Electrostatic coupling