1 A. A 25 KVA, 11 kV/400 V, 50 Hz single phase transformer has a no load losses of 700 W and full load
ohmic losses of 1200 W. The full load voltage regulation at 0.8 pf lagging is 13.5%.
(i) Obtain the readings of meters connected on HV side during short circuit test.
(ii) Maximum efficiency at upf. 6
1 B. Draw the connection diagram for Sumpners test on two similar single phase transformer. Explain
how the equivalent circuit parameters of each transformer are computed using test readings. 4
4 A. What do you mean by under commutation in DC generators? Discuss its effect on the operation of
the machine and suggest a method to compensate the same. 3
4 B. A 3 phase, 50 Hz, 12 pole, 420 V delta connected induction motor has the following equivalent
circuit parameters:
Stator impedance = (2.95 + j 6.82) per phase;
Stand still rotor impedance referred to stator = (2.08 + j 4.11) per phase.
Neglect exciting branch admittance.
When running at 4 % slip, determine:
(i) Electrical input to the motor (ii) Stator and Rotor copper losses
(iii) Useful torque if rotational losses are 750 W (iv) Efficiency 7
Page 1 of 2
5 A. Draw a neat sketch of a 3-point starter used for DC shunt motors. Explain how it protects the
machine under low voltage and over load conditions. 4
5 B. A 230 V DC shunt motor has an armature resistance of 0.2 and shunt field resistance of 75 .
When drawing a line current of 60 A, the speed is 1200 rpm developing certain torque. It is desired
to increase the speed by inserting 20 resistance in series with field circuit, maintaining the same
torque. Determine the new speed of the motor. 6
6 A. With relevant justification, compare the torque developed in single and double cage induction
motors. 4
6 B. A 20 HP, 400 V, 50 Hz, 4 pole, 3 phase star connected slip ring induction motor gave the following
test results:
No load test: 400 V, 9 A, 1310 W;
Blocked rotor test: 200 V, 50 A, 7100 W;
Assume stator resistance = rotor resistance referred to stator = 0.5 per phase
Stator to rotor phase turns ratio = 1.75
Draw the circle diagram and calculate:
(i) Line current, power factor and efficiency at rated load.
(ii) External resistance to be added in rotor circuit to get maximum torque at starting. 6
**************