#1
Startby DifferentialProtectionof6600VInductionmotor
BaljinderBansal
0817201404:09AM IndifferentialProtection(likeinTransformers)wehaveCT'sinstalledatPrimarysideandsecondarysideofthet/f.Howisthe
DifferentialProtectionofthe6600VInductionmotorisachievedastheCT'sareinstalledinthepanelofInductionmotorthattoo
onthefeederofthemotor?
SomebodytoldmethatDifferentialCT'sarealsoinstalledontheIncomeroftheswitchboardonwhichMotorpanelisinstalled
buthecouldn'texplainhisAnswer?
0817201406:48AM Top#2
ANANDKUMARGUPTA Howhavedreamtthatthe6600VInductionMotorconcernedisprotectedbyDifferentialProtection?Iamaskingthisquestion
0817201406:48AM becauseitisveryunusualtoprovideDifferentialProtectionforsuchmotors.
Theoreticallyspeaking,therecanbetwoscenariosasfollows.
Scenario1:StatorWindingofthemotorconcernedisStarConnectedandtheStarPointhasbeentaknoutthroughaBushing
andisavailableforinstallationofaCTthroughwhichtheStarPointcaneitherbegrounded.InsuchaScenariothreeCTs,each
ofproperratiosoastocorrespondtoatleast110%ofFullLoadCurrentshouldbeprovidedforphasesatoutgoingterminalsof
theSwitchgearandtheCTofsameRatioprovidedatMotorNeutralformeasurementofNeutralCurrenttoGround(whichwould
normallybeZero).Withsuch4CTsaRESTRICTEDEARTHFAULTSetupcanbecreatedsoastoprovidehighlysensitive
protectiontomotorstatorwindings.
Scenario2:All6TerminalsoftheMotorStatorWindingsareavailableoutsidethroughrespectiveBushing.InsuchScenario
conventionalDifferentialProtectionSetupcanbemade.
However,inreallifeprovidinganyofthetwotypesofprotectionasdescribedabovewouldbehighlyunconventionaland
uneconomicalbasedonCost/BenefitRatio.
0817201409:36AM Top#3
JohnLevine,P.E. Toprovidethemaximumprotectiontolargemotors(typicallyover2500HP)youwant3kindsofcurrentprotection.1)Youwant
0817201409:36AM asetofCT'stoprovidephaseovercurrentprotection.2)YouwantaCTtogoaroundall3conductors(zerosequenceCT)to
providephasetogroundprotection,.3)Youwanteither1setor2setsofCT'stoprovidedifferentialprotection.Thiswillprotect
againstphasetophaselowlevelsofcurrent.Inordertododifferentialprotection,allsixleadsmustbebroughtoutofthemotor
soyoucanlookatthecurrentgoingintoandoutofeachphase.YoucandownloadtheGEMultilin469manualandseethe
recommendedwiringtoaccomplishthis.Seefigures317to319.Inreallifethisisprovidedandisveryinexpensiveinsurance
topreventmajordamagetolargemotors.
0817201411:46AM Top#4
SANKARANARAYANAN CTshavetobeintroducedonthelineside(U1V1W1)andandonneutralside(U2V2W2)ofthemotorandthenstarisformed
SWAMINATHAN formotordifferentialprotection.
0817201411:46AM Sankaranarayanan
0817201402:07PM Top#5
Ing.OleKnudsen Wehavejustinstalled17offsuchmotors,includingDiff.protection.
0817201402:07PM Motors:11kV,2.7MWeach.
Protection:
1:ProtectionRelayisABB630REM
2:Corebalanceprotection,throughlargeCTatbottomoffeederswitchgearcabinet.Itisalwaysabattletogettheelectricians
toconnectthecablearmourtoearthoutsidethissummationCT,andtoleadanypotentialscreenconnectionsbackout,tohave
themearthedoutsidethisCT.
3:StandardOverCurrentprotection,throughindividualCTsforeachphase.TheseCTsareinstalledinthemainswitchgear
panels.
4:Differentialprotection,throughadditionalCTsinstalledineachmotorsStarPointjunctionbox.
Thisinstallationisjustabouttobecommissioned,overthenextcoupleofmonths.
Themainquestionwillbetoconfiguretheprotectionrelayscorrectly,sincethedifferentburdenoneachsetofCTsperphasewill
bequitedifferent,duetothedifferenceincablelengths.ThestarpointCTsareuptoabout400mfromtheswitchgear,and
furthermore,theyareofdifferentmanufacture,butIhavebeenreassuredthatthesemodernrelayscanbesetuptocompensate
forallthesedifferences.
Ifthesemotorsweretobedeltaconnected,for6.6kV,thenthedifferentialprotectionwouldhavetoincludeaseparatesetofCTs
inthemainjunctionbox.ThereisnoreasonwhytheseCTscouldnotserveastheO/CCTs.
0817201404:39PM Top#6
subratadeb Thequestioniswhysometimewehavetoprovideseparatedifferentialprotectionformotor
0817201404:39PM inspiteofhavingsomanyprotections?Probably,theansweriswherethestartingcurrent
ofthemotoristoohigh&veryclosetothesystemshortcircuitcurrent,wehavetosetthe
instantaneousrelayabovethestartingcurrentinordertoallowthemotortostart.Butinthat
processtherelaywillfailtodetectanyshortcircuitcurrentwhichislessthantherelaysettingcurrent.Butthedifferential
protectionwilloperatewheneverthereisafaultinthe
regionbetweenthetwosetsofCT(lineside&neutralside)
0817201407:01PM Top#7
Ing.OleKnudsen Maybeitisnotquitesosimple.
0817201407:01PM Itisquiteeasyforthemodernrelaytohaveanumberofsettingswithsometimedependentcorrelationwithascaleof
overcurrentlimits.
Thisstylewillallowthestartinginrushcurrentprofile,butoncethemotorisuptospeed,itcannoteasilydistinguishbetween
somepartialfault,whilethemotorisonlypartloaded.
Thisiswhereadifferentialprotectionrelaycancomeinhandy,becauseitcansenseifanypartialcurrentintooneendofa
windingdoesnotcomeoutoftheotherendofthatsamewinding.Itcouldhaveasmallproportiongoingtoframe,ortoanother
windingduetosomeinsulationbreakdowninthewinding.Inordertominimisedamagestothestatoriron,andmaybeevenlimit
thenumberofcoilsthatneedtobereplacedafterafault,itisofbenefittodetectthistypeoffaultasearlyaspossible.
Yourmentionofprotectionproblemsduringstartupisnoteasilysolvedthroughthedifferentialprotection,becauseitisdifficultto
keepthediff.prot.CTsfromsaturatingduringtheincreasedstartingcurrent,andespeciallyduringthefirstfewcycleswhilethe
wholemagneticsystemundergoesitsfirstunsymmetricstabilisation.
0817201409:25PM Top#8
shashibhargava MrBaljinderBansal,
0817201409:25PM Ithinkthedifferentialprotectionisnecessaryinalllargemotors.Itdoesjustifythecost/benefitratio.Theanswersaboveare
perfectandyoucantakeacuefromthis.
0 ReplytoThread
Youmayinterested Blogposts
Realtimeintelligentalarmingandguidancesystemforproductionprocess Thecauseofharmonicsinvariablefrequencydrive
control TransformerMagneticDesign
Lowcostcontrollerwithintegratedswitch ControlServomotorwithavariablefrequencydrive
Solarpanelsforofficewith7800KWpowerconsumption Variablefrequencydrivekeyfunctions
Continuousprocessplantcontrolstheplantwithoutmanualoperations Howisfrequencyinvertersavingenergy?
NeedhelpinBuckVs.Flyback
Gozuk2017AllRightReserved Contact|Terms