Airtype - reactor
linear magnetic behaviour (L - constant)
spreading magnetic field around reactor (weak EMC behaviour)
damping of reactor noise is difficult
space consuming
earth-quake withstand capability expensive
Oiltype reactor
nonlinear magnetic behaviour for high currents (L decreasing at high currents)
almost no electromagnetical radiation outside tank
antinoise damping can easily be provided by enclosure or by tank wall damping
cooling equipment (radiator bank) free placeable
PTD T PN E R&D PTD T PN E R&D
Dr. Pltner, 2017-06-12 12:14 Seite 1
Design of oil-type current-limiting reactors
application
comparison between oil-type and dry-type
- noise request
- EMC
- space available
- impedance (L-I-curve, symmetry between phases)
- earth-quake conditions
range of magnetic linearity -> impedance at normal and at short-circuit cond.
zero-sequence impedance
available current level for heat-run test
1
L L_rated
0.9
0.8
0.7
5 10
15
I I_rated
20 25
1
L L_rated
0.9
0.8
0.7
1.5 2 2.5 3 3.5 4 4.5 5
I I_rated