Protection, Substation Automation, Power Quality and Measurement
Siemens is one of the worlds leading suppliers of protection Section 6.2.2 gives an overview of the various product lines of
equipment for power systems. Thousands of Siemens relays the Siemens protection.
ensure rst-class performance in transmission and distribution
systems on all voltage levels, all over the world, in countries Section 6.2.3 offers application hints for typical protection
with tropical heat or arctic frost. For many years, Siemens has schemes such as:
also signicantly inuenced the development of protection tCables and overhead lines
technology: tTransformers
tMotors and generators
tIn 1976, the rst minicomputer (process computer)-based tBusbars
protection system was commissioned: A total of 10 systems for
110 / 20 kV substations was supplied and is still operating To ensure a selective protection system, section 6.2.4 gives hints
6
satisfactorily today. for coordinated protection setting and selection for instrument
tIn 1985, Siemens became the rst company to manufacture a transformers. The Relay Selection Guide in section 6.2.5 provides
range of fully numerical relays with standardized an overview of the relay function mix as a guide for selecting the
communication interfaces. Siemens now offers a complete right protection relay for the corresponding protection applica-
range of protection relays for all applications with numerical tion.
busbar and machine protection.
6.2.2 SIPROTEC and Reyrolle Relay their grids in an intelligent, ecological, reliable and efcient way,
Families and to operate them economically. As a pioneer, Siemens has
decisively inuenced the development of numerical protection
systems (g. 6.2-4). The rst application went into operation in
Solutions for today's and future power supply systems Wrzburg, Germany, in 1977. Consistent integration of protec-
for more than 100 years tion and control functions for all SIPROTEC devices was the
SIPROTEC has established itself on the energy market for innovation step in the 90ies. After release of the communication
decades as a powerful and complete system family of numerical standard IEC 61850 in the year 2004, Siemens was the rst
protection relays and bay controllers from Siemens. manufacturer worldwide to put a system with this communica-
tion standard into operation.
SIPROTEC protection relays from Siemens can be consistently
used throughout all applications in medium and high voltage. How can system operators benet from this experience?
With SIPROTEC, operators have their systems rmly and safely tProven and complete applications
under control, and have the basis to implement cost-efcient tEasy integration into your system
solutions for all duties in modern, intelligent and smart grids. tHighest quality of hardware and software
Users can combine the units of the different SIPROTEC device tExcellent operator friendliness of devices and tools
series at will for solving manifold duties because SIPROTEC tEasy data exchange between applications
stands for continuity, openness and future-proof design. tExtraordinary consistency between product- and
systemengineering
As the innovation driver and trendsetter in the eld of protection tReduced complexity by easy operation
systems for 100 years, Siemens helps system operators to design tSiemens as a reliable, worldwide operating partner
SIPROTEC easy
SIPROTEC easy are CT power supplied or auxiliary power sup-
plied, numerical time-overcurrent protection relays, which can
be used as line and transformer protection (back-up protection)
in electrical power supply systems with single-ended supply.
They offer denite time-overcurrent and inverse time-overcur-
rent protection functions according to IEC and ANSI. The com-
fortable operation via DIP switch is self-explanatory and simple.
SIPROTEC Compact
Perfect protection, smallest space reliable and exible protection
for energy distribution and industrial systems with minimum
space requirements. The devices of the SIPROTEC Compact
family offer an extensive variety of functions in a compact and
thus space-saving 1/6 x 19" housing. The devices can be used as
main protection in medium-voltage applications or as back-up
protection in high-voltage systems.
SIPROTEC Compact system features Fig. 6.2-12 shows exemplary how the most different tasks can
Field devices in energy distribution systems and in industrial be easily and safely solved with the matching
applications must cover the most varying tasks, and yet be SIPROTEC Compact devices.
adjustable easily and at short notice. These tasks comprise, for
example: Operation
t Protection of different operational equipment such as lines, During the development of SIPROTEC Compact, special value
cables, motors and busbars was placed not only on a powerful functionality, but also on
tDecoupling and disconnecting of parts of the power supply simple and intuitive operation by the operating personnel. Freely
system assignable LEDs and a six-line display guarantee an unambig-
tLoad shedding and load restoration uous and clear indication of the process states.
tVoltage and frequency protection
tLocal or remote control of circuit-breakers In conjunction with up to 9 function keys and the control keys
tAcquisition and recording of measured values and events for the operational equipment, the operating personnel can
tCommunication with neighboring devices or the control center react quickly and safely to every situation. This ensures a high
operational reliability even under stress situations, thus reducing
the training effort considerably.
Infeed
7SJ80 7RW80
SIEMENS
Backup transformer SIEMENS
Voltage/frequency
52 protection protection
Busbar protection Load shedding
via reverse interlocking Load restoration
6
MV substation
52 7SD80 52 7SJ80 52
7SJ80 52 7SJ80 7SJ80
SIEMENS
Busbar protection SIEMENS SIEMENS SIEMENS 52 SIEMENS
G M
52 52
Cable Generation
Load Balancing
Balance the load within a feeder by moving the Normally Open
Point
Section Isolation
Isolate a dedicated section of a feeder for maintenance without
affecting other sections
Local operation
All operations and information can be
executed via an integrated user interface:
2 operation LEDs
4 navigation keys
Fig. 6.2-14b:
Battery compartment accessible from outside. with closed cover
and open battery
compartment
All binary inputs are independent and the pick-up thresholds are
settable using software settings (3 stages). The relay current
transformer taps (1 A / 5 A) are new software settings. Up to 9
function keys can be programmed for prede ned menu entries,
switching sequences, etc. The assigned function of the function
keys can be shown in the display of the relay.
Fig. 6.2-15: 7SK80, 7SJ80, 7SD80 Fig. 6.2-17:
rear view Current terminal block
If a conventional (inductive) set of primary voltage transformers
is not available in the feeder, the phase-to-ground voltages can
be measured directly through a set of capacitor cones in the
medium-voltage switchgear. In this case, the functions direc-
tional time-overcurrent protection, ground (ANSI 67N), voltage
protection (ANSI 27/59) and frequency protection (ANSI 81O/U)
are available. With overcurrent protection 7SJ81 there is also a
device for low-power current transformer applications.
6 * RU = rack unit
Fig. 6.2-18: 7SJ81 rear view Fig. 6.2-19: 7RW80 rear view
Current terminals ring cable lugs
L = 10 mm (0.39 in) or L = 12 mm
Conductor sleeve with plastic sleeve
(0.47 in)
SIP-0004a-de.ai
System solutions
IEC 60870
Devices with IEC 60870-5-103 interfaces can be connected to
SICAM in parallel via the RS485 bus or radially via optical ber.
Via this interface, the system is open for connection of devices Fig. 6.2-22: Bus structure for station bus with Ethernet and
from other manufacturers. IEC 61850, ring-shaped optical-ber connection
IEC 61850
An interoperable system solution is offered for IEC 61850 together
with SICAM. Via the 100 Mbit/s Etherbus, the devices are con-
nected electrically or optically to the station PC with SICAM. The
interface is standardized, thus enabling the direct connection of
devices from other manufacturers to the Ethernet bus.
Engineering has moved from schematic diagrams toward a Thus, service personnel are now able to correct the failure upon
parameter denition procedure. The powerful user-denable occurrence, resulting in a signicantly upgraded availability of
logic of SIPROTEC 4 allows exible customized design for protec- the protection system.
tion, control and measurement.
6
52
21 67N FL 79 25 SM ER FR BM
85
SIPROTEC Line protection
kA, ER
to remote line end kV,
FR
Hz,
MW, SM
21 Distance protection MVAr,
67N Directional earth-fault protection MVA BM
Load monitor
FL Distance-to-fault locator
79 Auto-reclosure Fault report
25 Synchrocheck
Fault record
85 Carrier interface teleprotection
SM Self-monitoring Relay monitor
ER Event recording
FR Fault recording Breaker monitor
BM Breaker monitor Supervisory control
Adaptive relaying
Numerical relays now offer reliable, convenient and comprehen- 1000 Parameter
1100 Line data D
sive matching to changing conditions. Matching may be initiated 1000 .
Parameter
.
either by the relays own intelligence or from other systems via 1100 Line
1200data O/C C Phase settings
1000 .
Parameter .
contacts or serial telegrams. Modern numerical relays contain a . . B
1100 Line data
1200 O/C Phase settings
1000 .
Parameter . 1500 O/C Earth settings
number of parameter sets that can be pretested during commis- . . A .
1100 Line data .
sioning of the scheme. One set is normally operative. Transfer to . 1200 O/C Phase
1500 settings
O/C Earth settings
. . . 2800 Fault recording
. . .
the other sets can be controlled via binary inputs or a serial data 1200 O/C Phase settings
1500
.
. . O/C Earth settings
2800 Fault
3900recording
Breaker failure
link (g. 6.2-28). . . .
1500 O/C Earth .
settings
. 2800 Fault
3900recording
Breaker failure
. .
There are a number of applications for which multiple setting .
2800 Fault
3900recording
Breaker failure
groups can upgrade the scheme performance, for example: .
.
tFor use as a voltage-dependent control of overcurrent-time 3900 Breaker failure
relay pickup values to overcome alternator fault current
decrement to below normal load current when the automatic
Fig. 6.2-28: Alternate parameter groups
voltage regulator (AVR) is not in automatic operation
tFor maintaining short operation times with lower fault
currents, e.g., automatic change of settings if one supply
transformer is taken out of service
tFor switch-onto-fault protection to provide shorter time
settings when energizing a circuit after maintenance so that
normal settings can be restored automatically after a time
delay
tFor auto-reclosure programs, that is, instantaneous operation
for rst trip and delayed operation after unsuccessful reclosure
tFor cold load pickup problems where high starting currents
may cause relay operation
tFor ring open or ring closed operation.
6
Implemented functions
SIPROTEC relays are available with a variety of protective func-
tions (please refer to section 6.2.6). The high processing power
of modern numerical units allows further integration of non-pro-
tective add-on functions.
With the well-proven SIPROTEC 4 family, Siemens supports both The following solutions are available within one relay family:
stand-alone and combined solutions on the basis of a single tSeparate control and protection relays
hardware and software platform. The user can decide within tFeeder protection and remote control of the line circuit-breaker
wide limits on the conguration of the control and protection, via the serial communication link
and the reliability of the protection functions (g. 6.2-30). tCombined relays for protection, monitoring and control.
Busbar
7SJ61/62/63/64 7SJ62/63/64 2)
52
Local/remote control CFC logic Metering values
Command/feedback 25 Synchronization
Set points,
mean values, I, V, Watts,
Trip circuit Vars, p.f., f V, f, P
74TC Lockout 86 Min/Max-Log
supervision P<>
Q<> p.f. df/dt
Motor 33 Communication RTD1) box Energy meter: 32 55 81R
control modules interface calculated and/or by impulses
f<> V> V<
HMI RS232/485/FO/ Fault Motor protection 81O/U 59 27
Ethernet recording Bearing Starting Fault
temp. I< time locator Directional
IEC60870-5-103
IEC61850 38 37 48 21FL phase-sequence
47 monitoring
Probus-FMS/-DP
DNP 3.0 14 Locked 66/86
Restart I dir.>> I E dir.>>
rotor inhibit I dir.> I E dir.>
MODBUS RTU Ipdir. I Epdir.
67 67N
I E >,
I>> I>, Ip I E >> I Ep I2 > >
Inrush Interm.
50 51 50N 51N 46 49 restraint earth t. 50BF
Dir. sensitive
Breaker failure earth-fault detection
protection I EE>>
I E >, High-impedance Auto- I EE> VE>
I E >> I Ep restricted earth-fault 79 reclosure I EEp
51N 87N 67Ns 64
50N
Mechnical design
Terminals: standard relay version with screw-type terminals
SIPROTEC 4 relays are available in 1 / 3 to 1 / 1 of 19 wide hous-
Current terminals
ings with a standard height of 243 mm. Their size is compatible
with that of other relay families. Therefore, compatible exchange
Connection Wmax =12 mm
is always possible (g. 6.2-31 to g. 6.2-33).
Ring cable lugs d1 =5 mm
Wire size 2.7 4 mm2 (AWG 13 11) All wires (cables) are connected at the rear side of the relay with
Direct connection Solid conductor, exible lead, or without ring cable lugs. A special relay version with a
connector sleeve detached cable-connected operator panel (g. 6.2-34) is also
Wire size 2.7 4 mm2 (AWG 13 11) available. It allows, for example, the installation of the relay
Voltage terminals itself in the low-voltage compartment, and of the operator panel
separately in the door of the switchgear.
Connection Wmax =10 mm
Current terminals
Screw type (see standard version)
Voltage terminals
2-pin or 3-pin connectors
Fig. 6.2-31: 1 / 1 of 19 housing
Fig. 6.2-34: SIPROTEC 4 combined protection, control and monitoring Process and relay information can be displayed on the large
illuminated LC display either graphically in the form of a mimic
relay with detached operator panel diagram or as text in various lists.
The keys mainly used for control of the switchgear are located
on the control axis directly below the display.
Two key-operated switches ensure rapid and reliable changeover
between local and remote control, and between interlocked
and non-interlocked operation.
The r.m.s. values are calculated from the acquired current and
voltage along with the power factor, frequency, active and
reactive power. The following functions are available depending
on the relay type
tCurrents IL1, IL2, IL3, IN, IEE (67Ns)
tVoltages VL1,VL2, VL3, VL1-L2,VL2-L3, VL3-L1
tSymmetrical components I1, I2,3I0; V1, V2,3V0
tPower Watts, Vars, VA / P, Q, S
tPower factor p.f. (cos )
tFrequency
tEnergy kWh kVarh, forward and reverse power ow
tMean as well as minimum and maximum current and voltage
values Fig. 6.2-37: Operational measured values
tOperating hours counter
tMean operating temperature of overload function
tLimit value monitoring
6 Limit values are monitored using programmable logic in the
CFC. Commands can be derived from this limit value indication.
tZero suppression
In a certain range of very low measured values, the value is set
to zero to suppress interference.
Display editor All setting parameters are stored in the Flash EPROM and are not
A display editor is available to design the display on SIPROTEC 4 lost if the power supply or battery fails. The SIPROTEC 4 unit
units with graphic display. The predened symbol sets can be remains fully functional.
expanded to suit the user. The drawing of a single-line diagram
is extremely simple. Load monitoring values (analog values) and Commissioning support
any texts or symbols can be placed on the display where Special attention has been paid to commissioning. All binary
required. inputs and output contacts can be displayed and activated
directly. This can signicantly simplify the wiring check for the
Four predened setting groups for adapting relay settings user. Test telegrams to a substation control system can be
The settings of the relays can be adapted quickly to suit changing initiated by the user as well.
network congurations. The relays include four setting groups
that can be predened during commissioning or even changed CFC: Programming logic
remotely via a DIGSI 4 modem link. The setting groups can be With the help of the CFC (Continuous Function Chart) graphic
activated via binary inputs, via DIGSI 4 (local or remote), via the tool, interlocking schemes and switching sequences can be
integrated keypad or via the serial substation control interface. congured simply via drag and drop of logic symbols; no special
knowledge of programming is required. Logical elements, such
Fault recording up to ve or more seconds as AND, OR, ip-ops and timer elements are available. The user
The sampled values for phase currents, earth (ground) currents, can also generate user-dened annunciations and logical combi-
line and zero-sequence currents are registered in a fault record. nations of internal or external signals.
The record can be started using a binary input, on pickup or
when a trip command occurs. Up to eight fault records may be Communication interfaces
stored. For test purposes, it is possible to start fault recording via With respect to communication, particular emphasis has been
DIGSI 4. If the storage capacity is exceeded, the oldest fault placed on high levels of exibility, data integrity and utilization
record in each case is overwritten. of standards commonly used in energy automation. The design
of the communication modules permits interchangeability on
For protection functions with long delay times in generator the one hand, and on the other hand provides openness for
protection, the r.m.s. value recording is available. Storage of
relevant calculated variables (V1, VE, I1, I2, IEE, P, Q, f-fn) takes
future standards.
6
place at increments of one cycle. The total time is 80 s. Local PC interface
The PC interface accessible from the front of the unit permits
Time synchronization quick access to all parameters and fault event data. Of particular
A battery-backed clock is a standard component and can be advantage is the use of the DIGSI 4 operating program during
synchronized via a synchronization signal (DCF77, IRIG B via commissioning.
satellite receiver), binary input, system interface or SCADA (e.g.,
SICAM). A date and time is assigned to every indication.
Continuous self-monitoring
The hardware and software are continuously monitored. If
abnormal conditions are detected, the unit immediately signals.
In this way, a great degree of safety, reliability and availability is
achieved.
Fig. 6.2-39: Protection relay Fig. 6.2-40: Communication Fig. 6.2-43: Rear view with wiring, terminal safety cover and serial
module, optical interfaces
Substation
control system
MODBUS RTU
MODBUS is also a widely utilized communication standard and is
used in numerous automation solutions.
DNP 3.0
DNP 3.0 (Distributed Network Protocol, version 3) is a messag-
ing-based communication protocol. The SIPROTEC 4 units are
fully Level 1 and Level 2-compliant with DNP 3.0, which is
supported by a number of protection unit manufacturers.
Control
In addition to the protection functions, the SIPROTEC 4 units also
support all control and monitoring functions required for oper-
ating medium-voltage or high-voltage substations. The main
application is reliable control of switching and other processes.
The status of primary equipment or auxiliary devices can be
obtained from auxiliary contacts and communicated to the relay Fig. 6.2-47: Protection engineer at work
via binary inputs.
Therefore, it is possible to detect and indicate both the OPEN The positions of the circuit-breaker or switching devices are
and CLOSED positions or a faulty or intermediate breaker monitored by feedback signals. These indication inputs are
position. The switchgear can be controlled via: logically assigned to the corresponding command outputs. The
tIntegrated operator panel unit can therefore distinguish whether the indication changes as
tBinary inputs a consequence of a switching operation or due to a spontaneous
tSubstation control system change of state.
tDIGSI 4
6 Automation
Indication derivation
A further indication (or a command) can be derived from an
With the integrated logic, the user can set specic functions for existing indication. Group indications can also be formed. The
the automation of the switchgear or substation by means of a volume of information to the system interface can thus be
graphic interface (CFC). Functions are activated by means of reduced and restricted to the most important signals.
function keys, binary inputs or via the communication interface.
Switching authority
The following hierarchy of switching authority is applicable:
LOCAL, DIGSI 4 PC program, REMOTE. The switching authority is
determined according to parameters or by DIGSI 4. If the LOCAL
mode is selected, only local switching operations are possible.
Every switching operation and change of breaker position is
stored in the status indication memory with detailed information
and time tag.
Command processing
The SIPROTEC 4 protection relays offer all functions required for
command processing, including the processing of single and
double commands, with or without feedback, and sophisticated
monitoring. Control actions using functions, such as runtime
monitoring and automatic command termination after output
check of the external process, are also provided by the relays.
Typical applications are:
tSingle and double commands using 1, 1 plus 1 common
or 2 trip contacts
tUser-denable feeder interlocking
tOperating sequences combining several switching operations,
such as control of circuit-breakers, disconnectors (isolators)
and earthing switches
tTriggering of switching operations, indications or alarms by
logical combination of existing information (g. 6.2-47).
For system operators, holistic workow in SIPROTEC 5 means: Smart automation for transmission grids
An end-to-end tool from system design to operation even The extraordinary range of integrated functionalities for all the
allowing crossing of functional and departmental boundaries demands of your smart grid.
saves time, assures data security and transparency throughout
the entire lifecycle of the system. Climate change and dwindling fossil fuels are forcing a total
re-evaluation of the energy supply industry, from generation
to distribution and consumption. This is having fundamental
effects on the structure and operation of the power grids.
Operation Design
t%PDVNFOUBUJPO t"QQMJDBUJPO
t5FTUJOH t4QFDJmDBUJPO Smart automation is a major real-time component designed
t.BJOUFOBODF to preserve the stability of these grids and at the same time
conserve energy and reduce costs.
Holistic
SIPROTEC 5 offers the optimum smart automation platform for
Workow
smart grids.
tSmart functions, e.g., for power system operation, analysis Functional integration Protection
of faults or power quality (power systems monitoring, power SIPROTEC 5 provides all the necessary protection functions to
control unit, fault location) address reliability and security of power transmission systems.
tIntegrated automation with optimized logic modules based on System congurations with multiple busbars and breaker-and-a-
the IEC 61131-3 standard half schemes are both supported. The functions are based on
tHighly precise acquisition and processing of process values and decades of experience in putting systems into operation,
transmission to other components in the smart grid including feedback and suggestions from system operators.
tProtection, automation and monitoring in the smart grid.
The modular, functional structure of SIPROTEC 5 allows excep-
Functional integration tional exibility and enables the creation of a protection func-
Due to the modular design of its hardware and software and the tionality that is specic to the conditions of the system while
powerful engineering tool DIGSI 5, SIPROTEC 5 is ideally suited also being capable of further changes in the future.
for protection, automation, measurement and monitoring tasks
in the electrical power systems. Functional integration Control
SIPROTEC 5 includes all bay level control and monitoring func-
The devices are not only pure protection and control equipment, tions that are required for efcient operation of the substations.
their performance enables them to assure functional integration The application templates supplied provide the full functionality
of desired depth and scope. For example, they can also serve to needed by the system operators. Protection and control functions
perform monitoring, phasor measurement, fault recording, a access the same logical elements.
wide range of measurement functions and much more, concur-
rently, and they have been designed to facilitate future function- A new level of quality in control is achieved with the application
ality expansion. of communication standard IEC 61850. For example, binary
information from the eld can be processed and data (e.g., for
SIPROTEC 5 provides an extensive, precise data acquisition and interlocking across multiple elds) can be transmitted between
bay level recording for these functions. By combining device the devices. Cross communications via GOOSE enables efcient
functionality with communication exibility, SIPROTEC 5 has the solutions, since here the hardwired circuits are replaced with
ability to meet a wide range of todays applications and specic
project specications as well as the functional expansion capa-
data telegrams. All devices are provided for up to 4 switching
devices (circuit-breakers, disconnectors, earthing switches) in
6
bility to adapt to changing needs in the future. the basic control package. Optionally, additional switching
devices and the switching sequence block can be activated
With SIPROTEC 5 it is possible to improve the safety and reli- (Continuous Function Chart (CFC)).
ability of the operators application. Fig. 6.2-52 shows the
possible functional expansion of a SIPROTEC 5 device. Functional integration Automation
An integrated graphical automation function enables operators
to create logic diagrams clearly and simply. DIGSI 5 supports this
with powerful logic modules based on the standard IEC 61131-3.
Test
Meas.point I-3ph 1
1
CT 1 Phase current
2
K 51 OR Information exchange between FG
3-phase
3
Meas.point V-3ph 1 Interface
Circuit breaker
QA1
52 Voltage
21 Interface
K 3-phase
OR
VT 1
Meas.point I-3ph 2
Protection-function group Line 1 K
Protection-function
Phase current 50BF group
K
Line 1 3-phase Interface
Interface xx:yy
Trip. Trip command
K
CB function group QA1
Contacts Protection-function
QA2 K
Phase current
50BF group
52 3-phase
Interface
Interface xx:yy
Trip. Trip command
K
CT 2 CB function group QA2 K User can congure the assignment
with DIGSI 5
Application template: DIS overhead line, earthed power systems, 1.5 CB
Line 2 CB = Circuit-breaker
Fig. 6.2-53: System conguration with application template for one breaker-and-a-half scheme
Functional integration Cyber Security Optimizing the application template for the specic application
A multi-level security concept for the device and DIGSI 5 pro- The system operator can adapt the application templates to the
vides the user with a high level of protection against communi- corresponding application and create his own in-house stan-
cation attacks from the outside and conforms to the require- dards. The required number of protection stages or zones can be
ments of the BDEW Whitebook and NERC CIP. increased without difculty. Additional functions can be loaded
into the device directly from an extensive function library. Since
Functional integration Test the functions conform to a common design structure throughout
To shorten testing and commissioning times, extensive test and the SIPROTEC 5 system, protection functions and even entire
diagnostic functions are available to the user in DIGSI 5. These function groups including parameterization can be copied from
are combined in the DIGSI 5 Test Suite. one device to another.
The test spectrum includes, among other tests: Hardware and order congurator
tHardware and wiring test The SIPROTEC 5 hardware building blocks offer a freely congu-
tFunction and protection-function test rable device. System operators have the choice:
tSimulation of digital signals and analog sequences by
integrated test equipment Either to use a pre-congured device with a quantity structure
tDe-bugging of function charts already tailored to the corresponding application, or to build a
tCircuit-breaker test and AR (automatic reclosing) test function device from the extensive SIPROTEC 5 hardware building blocks
tCommunication testing themselves to exactly t their application.
tLoop test for communication connections
tProtocol test. The exible hardware building blocks offer:
tBase modules and expansion modules, each with different I/O
The engineering, including the device test, can therefore be modules
done with one tool. tVarious on-site operation panels
tA large number of modules for communication, measured
Application templates value conversion and memory extension
Application templates allow systems operators to fast track their
solution. A library of application templates is available that can be The SIPROTEC 5 hardware building blocks offer:
6
tailored to the specic functional scope for typical applications.
Durability and robustness
Fig. 6.2-54 shows an example of a system conguration with a tTailored hardware extension
breaker-and-a-half scheme. The functions in the application tRobust housings
template are combined in functional groups (FG). The functional tExcellent EMC shielding in compliance with the most recent
groups (FG) correspond to the primary components (protection standards and IEC 61000-4
object: line; switching device: circuit-breaker), thereby simpli- tExtended temperature range 25 C to +70 C/13 F to
fying the direct reference to the actual system. For example, if +158 F.
the switchgear concerned includes 2 circuit- breakers, this is also
represented by 2 circuit-breaker functional groups a sche- Modular principle
matic map of the actual system. tFreely congurable and extendable devices
tLarge process data range (up to 24 current and voltage
transformers for protection applications and up to 40 for
central busbar protection, as well as more than 200 inputs
and outputs for recording applications possible)
tOperation panel that is freely selectable for all device types
(e.g., large or small display, with or without key switches,
detached operation panel)
tIdentical wiring of ush-mounting and surface-mounting
housings.
6.2.3 Operating Programs DIGSI 4, IEC 61850 System Congurator and SIGRA 4
Description
The PC operating program DIGSI 4 is the user inter-
face to the SIPROTEC devices, regardless of their
version. It is designed with a modern, intuitive user
interface. With DIGSI 4, SIPROTEC devices are cong-
ured and evaluated it is the tailored program for
industrial and energy distribution systems.
Functions
Simple protection setting
From the numerous protection functions it is
possible to easily select only those which are really
required (see g. 6.2-56). This increases the clear-
ness of the other menus.
Fig. 6.2-56: DIGSI 4, main menu, selection of protection functions
Assignment matrix
The DIGSI 4 matrix shows the user the complete
conguration of the device at a glance (g. 6.2-57).
For example, the assignment of the LEDs, the
6
binary inputs and the output relays is displayed in
Fig. 6.2-57: DIGSI 4, assignment matrix
one image. With one click, the assignment can be
changed.
Commissioning
Special attention has been paid to commissioning.
All binary inputs and outputs can be set and read
out in targeted way. Thus, a very simple wiring test
is possible. Messages can be sent to the serial
interface deliberately for test purposes.
6
Fig. 6.2-59: Typical time-signal representation
SIGRA 4 can be used for all fault records using the COMTRADE
le format.
Functions
Different views of a fault record
In addition to the standard time signal representation,
SIGRA 4 also supports the display of circle diagrams (e.g.
R/X diagrams), vectors, which enable reading of angles,
and bar charts (e.g. for visualization of harmonics). To do
this, SIGRA uses the values recorded in the fault record to
calculate additional values such as positive impedances,
r.m.s. values, symmetric components, vectors, etc.
Operational features
The main aim of the developers of SIGRA 4, who were
6 assisted by ergonomic and design experts, was to produce
a system that was simple, intuitive and user-friendly:
tThe colours of all the lines have been dened so that
they are clear and easily distinguishable. However, the
colour, as well as the line style, the scale and other
surface features, can be adjusted to suit individual
requirements.
tPop-up menus for each situation offer customized
functionality thus eliminating the need to browse
through numerous menu levels (total operational
efciency).
tConguration of the individual diagrams is simple and
intuitive: Object-oriented, measured variables can be
simply dragged and dropped from one diagram to
another (also diagrams of different types).
tSnap-to-grid and snap-to-object movement of the Fig. 6.2-63: Vector diagrams
cursor lines for easy and accurate placement.
tRedundancy: Most user tasks can be achieved via up to
ve different operational methods, thus ensuring quick
and easy familiarization with the analysis software.
tUtilization of the available screen space is automatically
optimized by an intelligent function that, like the
synchronous mouse cursors, has since been patented.
Ring-main circuit
Infeed
General notes: Transformer
tOperating time of overcurrent relays to be coordinated with protection
see g. 6.2-84
downstream fuses of load transformers (preferably with strong 52 52
inverse-time characteristic with about 0.2 s grading-time
delay)
tThermal overload protection for the cables (option) 52 52
tNegative sequence overcurrent protection (46) as sensitive 7SJ80 *) 7SJ80 *)
I>, t I E >, t I2 >, t > I>, t I E >, t I2 >, t >
protection against asymmetrical faults (option)
51 51N 46 49 51 51N 46 49
Switch-onto-fault protection
If switched onto a fault, instantaneous tripping can be effected.
If the internal control function is used (local, via binary input or
via serial interface), the manual closing function is available 52
Busbar
without any additional wiring. If the control switch is connected
to a circuit-breaker bypassing the internal control function, TRIP (high-speed dead fault clearance) (511)
52 52 52
manual detection using a binary input is implemented.
I>>, I>>>
Feeder earthed 50
&
Manual close
Typical feeder (356 > m close) 7SJx, 7SAx
Blocking bus
tion is used for complete selective backup protection. If operated
50 7SJ80 *)
in a closed-circuit connection, an interruption of the transmis- Pick- *) Alternatives:
up
sion line is detected. 7SJ60
52
50
Blocking signal
Non-directional
6
50 7SJ80 *) fault detection
Pick- Direction
up of fault (67)
Sectionalizers
Fuses
52 Fuse opens on
sucessful reclosure
Circuit-breaker opens on
unsucessful reclosure
51
*) Alternatives:
7SJ60, 7SJ62/63/64, 7SJ80
6
Fig. 6.2-72: 3-pole multishot auto-reclosure (AR, ANSI 79)
52
52 52
Load Load
52 52
52
52 52 52 52
Load Backfeed
Fig. 6.2-76: Cables or short overhead lines with infeed from both ends
Load Backfeed
Fig. 6.2-77: Overhead lines or longer cables with infeed from both ends
Subtransmission line
Note:
Connection to open delta winding if available. Relays 7SA6 / 522
and 7SJ62 can, however, also be set to calculate the zero-
sequence voltage internally.
1)
6
zone
t8FBLJOGFFEUFSNJOBMT
are no problem (Echo
and Weak Infeed logic is
included)
Drawbacks t0WFSMBQQJOHPGUIF t;POFSFBDIBOETJHOBM Same as POTT Same as POTT
zone 1 reaches must be timing coordination with t4MPXUSJQQJOHoBMM
ensured. On parallel the remote end is teleprotection trips must
lines, teed feeders and necessary (current be delayed to wait for the
tapped lines, the reversal) eventual blocking signal
inuence of zero t$POUJOVPVTDIBOOFM
sequence coupling and monitoring is not
intermediate infeeds possible
must be carefully
considered to make sure
a minimum overlapping
of the zone 1 reach is
always present.
t/PUTVJUBCMFGPSXFBL
infeed terminals
Transmission line with reactor (g. 6.2-79) Teleprotection schemes based on distance relays therefore
have operating times on the order of 25 to 30 ms with digital
Notes: PCM coded communication. With state-of-the-art two-cycle
1) 51N only applicable with earthed reactor neutral. circuit-breakers, fault clearing times well below 100 ms (4 to 5
2) If phase CTs at the low-voltage reactor side are not available, cycles) can normally be achieved.
the high-voltage phase CTs and the CT in the neutral can be tDissimilar carrier schemes are recommended for main 1 and
connected to a restricted earth-fault protection using one main 2 protection, for example, PUTT, and POTT or
7VH60 high-impedance relay. Blocking / Unblocking.
tBoth 7SA522 and 7SA6 provide selective 1-pole and / or 3-pole
General notes: tripping and auto-reclosure.
tDistance relays are proposed as main 1 and main 2 protection. The earth-current directional comparison protection (67N) of
Duplicated 7SA6 is recommended for series-compensated the 7SA6 relay uses phase selectors based on symmetrical
lines. components. Thus, 1-pole auto-reclosure can also be executed
tOperating time of the distance relays is in the range of 15 to with high-resistance faults.
25 ms depending on the particular fault condition. The 67N function of the 7SA522 relay can also be used as
These tripping times are valid for faults in the underreaching time-delayed directional overcurrent backup.
distance zone (80 to 85 % of the line length). Remote end tThe 67N functions are provided as high-impedance fault
faults must be cleared by the superimposed teleprotection protection. 67N is often used with an additional channel as a
scheme. Its overall operating time depends on the signal separate carrier scheme. Use of a common channel with
transmission time of the channel, typically 15 to 20 ms for distance protection is only possible if the mode is compatible
frequency shift audio-tone PLC or microwave channels, and (e.g., POTT with directional comparison). The 67N may be
lower than 10 ms for ON / OFF PLC or digital PCM signaling via blocked when function 21 / 21N picks up. Alternatively, it can
optical bers. be used as time-delayed backup protection.
6 CC
52L
52R
TC1 TC2
CVT
50/50N 51/51N BF
7SJ600
Reactor 87R
25 59 21/21N 25 21/21N
7VH60
2)
79 67N 79 67N
51N
7SJ600
68/79 BF 68/79 87 BF
1)
BF, 59
S Direct trip
85 Trip
R channel
7SA6 52L
7SA522
S Channel To remote
R 2 line end
S Channel
R 3
6
7VK61 7SA522 or
BF 85 7SA6
UBB1
1) 1) 2)
79
21/21N 67N 50/50N 51/51N 59
52
25
UBB1 UL1 or
UL1
UL2 or
UBB2
Line 1
7VK61 7SD5
87L
BF
52 79
25
UL2
Line 2
Fig. 6.2-82: Transmission line, one-breaker-and-a-half terminal, using 3 breaker management relays 7VK61
General notes for g. 6.2-82 and g. 6.2-83: tThe voltages for synchrocheck have to be selected according to
tFor the selection of the main 1 and main 2 line protection the circuit-breaker and disconnector (isolator) position by a
schemes, the comments of application examples g. 6.2-77 voltage replica circuit.
and g. 6.2-78 apply.
tAuto-reclosure (79) and synchrocheck function (25) are each General notes for g. 6.2-83:
assigned directly to the circuit-breakers and controlled by main tIn this optimized application, the 7VK61 is only used for the
1 and 2 line protection in parallel. In the event of a line fault, center breaker. In the line feeders, functions 25, 79 and BF are
both adjacent circuit-breakers have to be tripped by the line also performed by transmission line protection 7SA522
protection. The sequence of auto-reclosure of both circuit- or 7SA6.
breakers or, alternatively, the auto-reclosure of only one
circuit-breaker and the manual closure of the other circuit-
breaker, may be made selectable by a control switch.
tA coordinated scheme of control circuits is necessary to ensure
selective tripping interlocking and reclosing of the two circuit-
breakers of one line (or transformer feeder).
7SA522 or
UBB1 BF 85
1)
7SA6
1) 2)
6
52 21/21N 67N 50/50N 51/51N 59
25
UBB1
UL1 or
UL2 or
UBB2 UL1
Line 1
7VK61 7SD5
BF 87L
52 79
25
UL1 or UL2 or
UBB1 UBB2
Line 2
UL2
BB2
Fig. 6.2-83: Tranmission line, breaker-and-a-half terminal, using 1 breaker management relay 7VK61
2. Transformers
Small transformer infeed
HV infeed
General notes: 52
tEarth faults on the secondary side are detected by current
relay 51N. However, it has to be time-graded against I>> I>, t IE > > I2 >, t
52 7VH60 51N
IE > 7SJ60
or 7SJ80
Distribution bus
52
O/C Fuse
relay
Load Load
Load bus
52 52
Load Load
Load
52 52 52 bus
Load Load
Three-winding transformer
HV Infeed
52
Notes:
1) The zero-sequence current must be blocked before entering I>>, I >, t > I2 >, t
Autotransformer
52
Notes:
1) 87N high-impedance protection requires special class
51N 50/BF 46 50/51 2) 87N 7VH60
current transformer cores with equal transformation ratios.
7SJ60, 7SJ61 or 7SJ80
2) The 7SJ60 relay can alternatively be connected in series with 1)
the 7UT613 relay to save this CT core.
52
6
3. Motors
Small and medium-sized motors < about 1 MW
General note:
tApplicable to low-voltage motors and high-voltage motors
I>> IE > > I2 >
with low-resistance earthed infeed (IE IN Motor)
50 51N 49 48 46
b) With high-resistance earthed infeed (IE IN Motor)
7SJ60/7SK80
Notes: M
1) Core-balance CT.
2) Sensitive directional earth-fault protection (67N) only
applicable with infeed from isolated or Petersen coil earthed
Fig. 6.2-92: Motor protection with effective or low-resistance
system (for dimensioning of the sensitive directional earth- earthed infeed
fault protection, see also application circuit no. 30)
3) The 7SJ602 relay can be applied for isolated and compensated
systems. 52
50 49 48 46 37 51U
IE > 2)
7XR96
1) 51N 67N
60/1A 3)
7SJ62/7SK80
52
Notes:
1) Core-balance CT.
I >> > I2 > U<
2) Sensitive directional earth-fault protection (67N) only
applicable with infeed from isolated or Petersen coil earthed 50 49 48 46 27
system. Optional
3) This function is only needed for motors where the startup IE > 2) I < 37
7XR96
time is longer than the safe stall time tE. According to 1) 51N 67N
IEC 60079-7, the tE time is the time needed to heat up AC 60/1A
windings, when carrying the starting current IA, from the Startup
super- 49T 87M
temperature reached in rated service and at maximum visor 3) 5) 7UM62
ambient air temperature to the limiting temperature. A
3)
separate speed switch is used to supervise actual starting of
Speed RTDs 4)
the motor. The motor circuit-breaker is tripped if the motor switch optional
does not reach speed in the preset time. The speed switch is
part of the motor supply itself.
4) Pt100, Ni100, Ni120
5) 49T only available with external temperature monitoring
device (7XV5662)
Fig. 6.2-94: Protection of large HV motors > about 1 MW
6
Cold load pickup
52
By means of a binary input that can be wired from a manual Trip
close contact, it is possible to switch the overcurrent pickup
I >> t I>t
settings to less sensitive settings for a programmable amount of
51.1 51.2
time. After the set time has expired, the pickup settings auto-
matically return to their original setting. This can compensate for Binary input 51.1
82
initial inrush when energizing a circuit without compromising (1727 > c/o) Trip
51.2
the sensitivity of the overcurrent elements during steady-state Desensitized
7SJ60x, 7SJ61
conditions. during inrush
52 or 7SJ80
Busbar
52 52 52 52
Trip
M
I >> t I > t
51.1 51.2
Typical feeder
Binary input 51.1
(1727 > C/O = cold
(1727 > C/O)
51.2 load pickup of over-
7SJ60x, 7SJ61 current pickup)
or 7SK80
4. Generators
LV
Generators < 500 kW (g. 6.2-96 and g. 6.2-97)
Note:
If a core-balance CT is provided for sensitive earth-fault protec- G I >, I E >, t I2 > >
tion, relay 7SJ602 with separate earth-current input can be used.
51/51N 46 49
Generators, typically 13 MW
(g. 6.2-98) 7SJ60 or 7SJ80
Note:
Two VTs in V connection are also sufcient. Fig. 6.2-96: Generator with solidly earthed neutral
Generators > 13 MW
(g. 6.2-99) MV
Notes:
1) Functions 81 and 59 are required only where prime mover G1 I >, I E >, t I2 > >
can assume excess speed and the voltage regulator may Generator 2
permit rise of output voltage above upper limit. 51/51N 46 49
1)
2) Differential relaying options: 7SJ60 or 7SJ80
Low-impedance differential protection 87.
Restricted earth-fault protection with low-resistance UN
RN
earthed neutral (g. 6.2-98). 0.5 to 1 Irated
1)
I >/U <
50/27
59 U <
Field 1)
f 1) 87
G 81
81 f
RG Field <
G 64R
I E >, t IG >, t
2)
51N 51N 87N
7UM61 7UM62
Fig. 6.2-98: Protection for generators 13 MW Fig. 6.2-99: Protection for generators >13 MW
Generators > 5 10 MW feeding into a system For the most sensitive setting of 2 mA, we therefore need 20 mA
with isolated neutral secondary earth current, corresponding to (60 / 1) 20 mA =
(g. 6.2-100) 1.2 A primary.
52 3)
I>/U<
Redundant 50/27
protection IG 67N IG
67N
U<
27
27 U < 59N 87 I
59 U > 4) U >
O
64R 59 U >
46 I2 > 81 f >
<
81 f >
<
32 40 51V I > t, U < L. O. F. P > I2 >
P L. O. F. I > t, U < 51V 40 32 49 46
7UM61 or 7UM62 2) 7UM62
Unit
Overvolt. 59 aux.
81 51N
Overfreq. Trans.
78
Loss of neut.
sync. 24 OC
40 Volt/Hz
87T
A
Stator Loss of Trans.
eld
6
O.L. diff.
49S 32
E Reverse
Generators > 50 100 MW in generator transformer 87G power
unit connection Gen.
(g. 6.2-101) 2) diff.
64R 64R
Field Field 46 21
Notes:
grd. grd.
1) 100 % stator earth-fault protection based on 20 Hz voltage Neg. Sys.
seq. backup
injection
2) Sensitive rotor earth-fault protection based on 13 Hz voltage
injection
59/GN
3) Non-electrical signals can be incoupled in the protection via
Gen.
binary inputs (BI) neut. OV
1)
4) Only used functions shown; further integrated functions 51/GN
available in each relay type.
Fig. 6.2-101: Protections for generators > 50 MW
Number
Relay of relays
Functions 4)
type required
7UM62 21 24 32 40 46 49
1) 2)
51GN 59GN 59 64R 64R 78 2
Synchronization of a generator
Bus
Fig. 6.2-103 shows a typical connection for synchronizing a
generator. Paralleling device 7VE6 acquires the line and gener- 52 U1
ator voltage, and calculates the differential voltage, frequency
and phase angle. If these values are within a permitted range, a
CLOSE command is issued after a specied circuit-breaker make 7VE6
U2
time. If these variables are out of range, the paralleling device U f
25
automatically sends a command to the voltage and speed con-
troller. For example, if the frequency is outside the range, an
actuation command is sent to the speed controller. If the voltage
is outside the range, the voltage controller is activated. G
6 5. Busbars
Busbar protection by overcurrent relays with reverse
interlocking
Infeed
General note: Reverse interlocking
tApplicable to distribution busbars without substantial
(< 0.25 IN) backfeed from the outgoing feeders. I >, t0 I >, t
50/50N 51/51N
52 7SJ60
t0 = 50 ms
52 52 52
General notes:
87BB
tNormally used with single busbar, one-breaker-and-a-half, and
double busbar schemes, different transformation ratios can be
adapted by matching transformers.
52
86 6
tUnlimited number of feeders.
52 52 52 7SS601
tFeeder protection can be connected to the same CT core.
50BF
7SV60
50BF
7SV60
50BF
7TM70
7SV60 G 7SS60
Load
General notes:
tSuitable for all types of busbar schemes.
tPreferably used for multiple busbar schemes where a
disconnector (isolator) replica is necessary. 52 52 52 52
tThe numerical busbar protection 7SS52 provides additional 50BF 50BF 50BF 50BF
breaker failure protection. 50 50 50 50
tDifferent CT transformation ratios can be adapted numerically. 51 51 51 51
tThe protection system and the disconnector (isolator) replica Bay
units 50N 50N 50N 50N
are continuously self-monitored by the 7SS52.
51N 51N 51N 51N
tFeeder protection can be connected to the same CT core.
7SS523 FO 7SS523 FO 7SS523 FO 7SS523 FO
87BB 50BF
Central unit 7SS522
6. Power systems
Load shedding
In unstable power systems (e.g., isolated systems, emergency Overexcitation protection
power supply in hospitals), it may be necessary to isolate U >, t; U >>, t U/f >, t; U/f >>, t; U/f=f(t)
f >,t; f <, t; U <, t U >, t; U >>, t f >,t; f <, t; U <, t U >, t; U >>, t
81 27 59 81 27 59
7RW600, 7RW80, 7SJ62 or 7SJ80 7RW600, 7RW80 or 7SJ62 M
Decoupling Load shedding
6 is thus possible to detect and record any major active power loss
in the power system, to disconnect certain consumers accord-
f
fm
ingly and to restore the system to stability. Unlike frequency t
protection, rate-of-frequency-change protection reacts before 49
fa
the frequency threshold is undershot. To ensure effective protec-
fb
tion settings, it is recommended to consider requirements
throughout the power system as a whole. The rate-of-frequency- fc
change protection function can also be used for the purposes of
system decoupling. 48
0 1 2 3 4 5
Rate-of-frequency-change protection can also be enabled by an t
underfrequency state.
52
General note:
CB 1
The SIPROTEC protection relay 7SJ64 disconnects the switchgear
Connection to power utility
from the utility power system if the generator feeds energy back
Switch- Customer switchgear with autonomous supply
into the power system (protection function Preverse>). This
disconnector
functionality is achieved by using exible protection. Disconnec-
1)
tion also takes place in the event of frequency or voltage uctua- 7UT612
tions in the utility power system (protection functions
<, >, U<, U>, Idir >, IEdir > / 81, 27, 59, 67, 67N). G
Notes:
1) The transformer is protected by differential protection and
inverse or denite-time overcurrent protection functions for
the phase currents. In the event of a fault, the circuit-breaker 52 52
CB1 on the utility side is tripped by a remote link. Circuit- CB 2 CB 3
breaker CB2 is also tripped.
2) Overcurrent-time protection functions protect feeders 1 and 2
against short-circuits and overload caused by the connected 7SJ64
loads. Both the phase currents and the zero currents of the f< f> U< U> Sync. I>dir I E>dir
Preserve >
feeders can be protected by inverse and denite-time 32 81 81 27 59 25 67 67N
overcurrent stages. The circuit-breakers CB4 and CB5 are
Busbar
tripped in the event of a fault.
7SJ61/ 2) 7SJ61/ 2)
7SJ80 7SJ80
52 52
CB 4 CB 5
6
Feeder 1 Feeder 2
The relay operating times, depending on the current, can be 51F 51F
derived from the diagram or calculated with the formula given in 0.2-0.4
g. 6.2-117. Time grading
Fault Fault Interruption of
The Ip / IN settings shown in g. 6.2-116 have been chosen to get inception detection fault current
t 51F t 52F
pickup values safely above maximum load current. Circuit-breaker
Set time delay interruption time
This current setting should be lowest for the relay farthest down-
Overshoot*
stream. The relays further upstream should each have equal or t OS Margin tM
higher current settings.
t 51M
The time multiplier settings can now be calculated as follows: *also called overtravel or coasting time
Time grading
Station C:
trs = t51M t51F = t52F + tOS + tM
tFor coordination with the fuses, we consider the fault in
location F1. Example 1 tTG =0.10 s + 0.15 s + 0.15 s = 0.40 s
The short-circuit current Iscc. max. related to 13.8 kV is 523 A. Oil circuit-breaker t52F = 0.10 s
This results in 7.47 for I / Ip at the overcurrent relay in location C. Mechanical relays tOS = 0.15 s
tWith this value and Tp = 0.05, an operating time of tA = 0.17 s
Safety margin for
can be derived from g 6.2-114.
6
measuring errors, etc. tM = 0.15 s
Example 2 tTG = 0.08 + 0.02 + 0.10 = 0.20 s
This setting was selected for the overcurrent relay to get a safe
grading time over the fuse on the transformer low-voltage side. Vacuum circuit-breaker t52F = 0.08 s
Safety margin for the setting values for the relay at station C are Numerical relays tOS = 0.02 s
therefore: Safety margin tM = 0.10 s
tPickup current: Ip / IN = 0.7
tTime multiplier: Tp = 0.05 Fig. 6.2-115: Time grading of overcurrent-time relays
Station B:
The relay in B has a primary protection function for line B-C and Load
a backup function for the relay in C. The maximum through-fault 13.8 kV/ Fuse: D
A F4 B F3 C F2 F1
0.4 kV 160 A
current of 1.395 A becomes effective for a fault in location F2. Load
For the relay in C, an operating time time of 0.11 s (I / Ip = 19.93) 13.8 kV 625 kVA L.V. 75
is obtained. 51 51 51 5.0 % Load
7SJ60 7SJ60 7SJ60
It is assumed that no special requirements for short operating
times exist and therefore an average time grading interval of Station Max. ISCC. max* CT Ip / IN** Iprim*** I max
load ratio I / Ip = scc.
0.3 s can be chosen. The operating time of the relay in B can Iprim
A A A
then be calculated.
A 300 4,500 400 / 5 1.0 400 11.25
B 170 2,690 200 / 5 1.1 220 12.23
ttB = 0.11 + 0.3 = 0.41 s C 50 1,395 100 / 5 0.7 70 19.93
1,395 A D 523
tValue of Ip / IN = = 6.34 (g. 6.2-116)
220 A *) ISCC. max = Maximum short-circuit current
**) Ip / IN = Relay current multiplier setting
tWith the operating time 0.41 s and Ip / IN = 6.34, ***) Iprim = Primary setting current corresponding to Ip / IN
Tp = 0.11 can be derived from g. 6.2-117.
Fig. 6.2-116: Time grading of inverse-time relays for a radial feeder
Note:
To simplify calculations, only inverse-time characteristics have
been used for this example. About 0.1 s shorter operating times
could have been reached for high-current faults by additionally Normalinverse
applying the instantaneous zones I>> of the 7SJ60 relays. 0.14
t = T (s)
(I / Ip)0.02 1 p
Coordination of overcurrent relays with fuses and low-voltage
trip devices Strong inverse characteristics may be used with expulsion-type
The procedure is similar to the above-described grading of fuses (fuse cutouts), while extremely inverse versions adapt
overcurrent relays. A time interval of between 0.1 and 0.2 s is better to current limiting fuses.
usually sufcient for a safe time coordination.
In any case, the nal decision should be made by plotting the
Strong and extremely inverse characteristics are often more curves in the log-log coordination diagram.
suitable than normal inverse characteristics in this case.
Fig. 6.2-119 shows typical examples. Electronic trip devices of LV breakers have long-delay, short-
delay and instantaneous zones. Numerical overcurrent relays
Simple distribution substations use a power fuse on the sec- with one inverse-time and two denite-time zones can closely
ondary side of the supply transformers (g. 6.2-119a). be adapted to this (g. 6.2-119b).
Ip = 0.7 IN
Bus-C
Tp = 0.05 s
I>> =
100/5 A Ip = 0.10 4.00 IN
Tp = 0.05 3.2 s
52 7SJ600 I>> = 0.1 25 IN
13.8/0.4 kV
TR 625 kVA
5.0%
6 MV bus
MV bus
Time Inverse-time relay
51
50/51
Other Fuse
consumers
n
a n
LV bus a
LV bus
Fuse 0.2 s
Current
a) Maximum fault available at HV bus
Fig. 6.2-119: Coordination of an overcurrent relay with an MV fuse and low-voltage breaker trip device
Coordination of distance relays Where measured line or cable impedances are available, the
The distance relay setting must take into account the limited protected zone setting may be extended to 90 %. The second
relay accuracy, including transient overreach (5 %, according to and third zones have to keep a safety margin of about 15
IEC 60255-6), the CT error (1 % for class 5P and 3 % for class to 20 % to the corresponding zones of the following lines.
10P) and a security margin of about 5 %. Furthermore, the line The shortest following line always has to be considered
parameters are often only calculated, not measured. This is a (g. 6.2-120).
further source of errors. A setting of 80 to 85 % is therefore
common practice; 80 % is used for mechanical relays, while 85 % As a general rule, the second zone should at least reach 20 %
can be used for the more accurate numerical relays. over the next station to ensure backup for busbar faults, and the
third zone should cover the longest following line as backup for
the line protection.
VTratio
XPrim Min = XRelay Min
CTratio
6
XPrim Min
lmin =
XLine R1A R 2A R 3A
A R
The shortest setting of the numerical Siemens relays is 0.05
for 1 A relays, corresponding to 0.01 for 5 A relays. This allows
distance protection of distribution cables down to the range of
some 500 meters.
CT data 50BF
The prerequisite for a high-impedance scheme is that all CTs A
used for that scheme must have the same ratio. They should also N
P1 D
be of low leakage ux design according to Class PX of O
IEC 60044-1 (former Class X of BS 3938) or TPS of IEC 60044-6, R
P1: primary P 2: alternate P2
when used for high-impedance busbar protection schemes. protection protection
When used for restricted earth-fault differential protection of,
e.g., a transformer winding especially in solidly earthed systems, Fig. 6.2-122: Breaker failure protection, logic circuit
CTs of Class 5P according to IEC 60044-1 can be used as well. In
each case the excitation characteristic and the secondary
winding resistance are to be provided by the manufacturer. The
knee-point voltage of the CT must be at least twice the relay
Fault incidence BFI =
pickup voltage to ensure operation on internal faults. breaker failure
Normal interrupting time initiation time
Current (intermediate
Relay detector relays, if any)
(50 BF)
The relay can be either: Protect. Breaker inter. reset time Margin BFT =
breaker failure
a) a dedicated design high-impedance relay, e.g., designed as a time time tripping time
sensitive current relay 7VH60 or 7SG12 (DAD-N) with external (1~) (2~) (1~) (2,5~) (auxilary relays,
[2~] [4~] [2~] [2,5~] if any)
series resistor Rstab. If the series resistor is integrated into the
relay, the setting values may be directly applied in volts, as with (5~) (2~)
0,5~ 0,5~
[8~] [4~]
the relay 7VH60 (6 to 60V or 24 to 240 V); or
BFI BF timer (F) (62BF) BFT Adjacent
b) a numerical overcurrent protection relay with sensitive current
6 input, like 7SJ6 or 7SR1 (Argus-C). To the input of the relay a series
stabilizing resistor Rstab will be then connected as a rule in order
Total breaker failure interrupting time
(9~) [15~]
breaker
int. time
Calculation example: Moreover, Rstab must have a short-time rating large enough to withstand
Restricted earth-fault protection for the 400 kV winding of 400 MVA the fault current levels before the fault is cleared. The time duration of
power transformer with Ir, 400 kV = 577 A installed in a switchgear with a 0.5 seconds can be typically considered (Pstab, 0.5s) to take into account
rated short-time withstand current of 40 kA. longer fault clearance times of back-up protection. The r.m.s. voltage
Given: developed across the stabilizing resistor is decisive for the thermal stress
N = 4 CTs connected in parallel; Ipn / Isn = 800 A / 1 A CT ratio; of the stabilizing resistor. It is calculated according to formula:
Uk = 400 V CT knee-point voltage;
Im = 20 mA CT magnetizing current at Uk; I sn
Urms,relay 1.3u 4 Uk3 u Rstab u I k,max,int 1.3u 4 400 3 u 1000u 50 1738.7 V
RCT = 3 CT internal resistance; I pn
Rlead = 2 secondary wiring (lead) resistance
Relay: 7SJ612; time-overcurrent 1-phase input used with setting range The resulting short-time rating Pstab, 0.5 s equals to:
Iset = 0.003 A to 1.5 A in steps of 0.001 A; relay internal burden
Urms, relay2 1,7392
Rrelay = 50 m Pstab, 0.5s = = = 3023 W
Rstab 1,000
Stability calculation
Isn 1 Check whether the voltage limitation by a varistor is required
Us ,min = Ik, max, thr (RCT + Rlead) = 10,000 (3+2) = 62.6 V
Ipn 800 The relay should normally be applied with an external varistor which
should be connected across the relay and stabilizing resistor input termi-
with Ik, max, thr taken as 16 . Ir, 400 kV = 16 . 577 A = 9,232 A, rounded up to 10 kA.
nals. The varistor limits the voltage across the terminals under maximum
The actual stability voltage for the scheme Us can be taken with internal fault conditions. The theoretical voltage which may occur at the
enough safety margin as Us = 130 V (remembering that 2Us < Uk). terminals can be determined according to following equation:
Fault setting calculation Isn 1
For the desired primary fault sensitivity of 125 A, which is approx. 22 % Uk, max, int = Ik, max, int (Rrelay + Rstab) = 40,000 (0.05 + 1,000) = 50,003 V
Ipn 800
of the rated current of the protected winding Ir, 400 kV (i.e., Ip, des =
125 A) the following current setting can be calculated: with Ik,max,int taken as the rated short-circuit current of the switchgear = 40 kA.
Isn Us 1 130 The resulting maximum peak voltage across the panel terminals
Iset = Ip, des N . Im = 125 4 . 0.02 = 0.13 A
Ipn Uk 800 400 (i.e., tie with relay and Rstab connected in series):
through-fault stability but also to higher CT magnetizing and CT requirements for protection relays
varistor leakage currents, resulting consequently in a higher
primary pickup current. Instrument transformers
Instrument transformers must comply with the applicable
A higher voltage setting also requires a higher knee-point voltage IEC recommendations IEC 60044 and 60186 (PT),
of the CTs and therefore greater size of the CTs. A sensitivity of ANSI / IEEE C57.13 or other comparable standards.
10 to 20 % of Ir (rated current) is typical for restricted earth-fault
protection. With busbar protection, a pickup value Ir is normally Voltage transformers (VT)
applied. In systems with neutral earthing via impedance, the Voltage transformers (VT) in single-pole design for all primary
fault setting shall be revised against the minimum earth-fault voltages have typical single or dual secondary windings of 100,
conditions. 110 or 115 V / 3, with output ratings between 10 and 50 VA
suitable from most applications with digital metering and pro-
Non-linear resistor (varistor) tection equipment, and accuracies of 0.1 % to 6 % to suit the
Voltage limitation by a varistor is needed if peak voltages near or particular application. Primary BIL values are selected to match
above the insulation voltage (2 kV 3 kV) are expected. A those of the associated switchgear.
limitation to Urms = 1,500 V is then recommended. This can be
checked for the maximum internal fault current by applying the Current transformers
formula shown for Umax relay. A restricted earth-fault protection Current transformers (CT) are usually of the single-ratio type
may sometimes not require a varistor, but a busbar protection in with wound or bar-type primaries of adequate thermal rating.
general does. However, it is considered a good practice to equip Single, double or triple secondary windings of 1 or 5 A are
with a varistor all high impedance protection installations. The standard. 1 A rating should, however, be preferred, particularly
electrical characteristic of a varistor can be expressed as U = C I in HV and EHV substations, to reduce the burden of the con-
where C and are the varistor constants. nected lines. Output power (rated burden in VA), accuracy and
saturation characteristics (rated symmetrical short-circuit current The requirements for protective current transformers for tran-
limiting factor) of the cores and secondary windings must meet sient performance are specied in IEC 60044-6. In many prac-
the requirements of the particular application.The CT classica- tical cases, iron-core CTs cannot be designed to avoid saturation
tion code of IEC is used in the following: under all circumstances because of cost and space reasons,
tMeasuring cores particularly with metal-enclosed switchgear.
These are normally specied with 0.2 % or 0.5 % accuracy CT dimensioning formulae
(class 0.2 or class 0.5), and an rated symmetrical short-circuit
Rct + Rb
current limiting factor FS of 5 or 10. Kssc = Kssc (effective)
Rct + Rb
The required output power (rated burden) should be higher
than the actually connected burden. Typical values are 2.5, 5 Iscc max
with Kssc Ktd (required)
or 10 VA. Higher values are normally not necessary when only Ipn
electronic meters and recorders are connected.
A typical specication could be: 0.5 FS 10, 5 VA. The Siemens relays are therefore designed to tolerate CT satura-
tCores for billing values metering tion to a large extent. The numerical relays proposed in this
In this case, class 0.25 FS is normally required. guide are particularly stable in this case due to their integrated
tProtection cores saturation detection function. The effective symmetrical short-
The size of the protection core depends mainly on the circuit current factor K'SSC can be calculated as shown in the
maximum short-circuit current and the total burden (internal table above. The rated transient dimensioning factor Ktd
CT burden, plus burden of connected lines, plus relay burden). depends on the type of relay and the primary DC time constant.
Furthermore, a transient dimensioning factor has to be For relays with a required saturation-free time from 0.4 cycle,
considered to cover the inuence of the DC component in the the primary (DC) time constant TP has little inuence.
short-circuit current.
CT design according to BS 3938 / IEC 60044-1 (2000)
IEC Class P can be approximately transfered into the IEC Class PX (BS
Glossary of used abbreviations Class X) standard denition by following formula:
(according to IEC 60044-6, as dened)
Kssc = Rated symmetrical short-circuit current factor (Rb + Rct) In Kssc
6
Uk =
(example: CT cl. 5P20 Kssc = 20) 1.3
Kssc = Effective symmetrical short-circuit current factor Example:
Ktd = Transient dimensioning factor IEC 60044: 600 / 1, 5P10, 15 VA, Rct = 4
Issc max = Maximum symmetrical short-circuit current
(15 + 4) 1 10
Ipn = CT rated primary current IEC PX or BS: UK = = 146 V
1.3
Isn = CT rated secondary current Rct = 4
Rct = Secondary winding d.c. resistance at 75 C / 167 F For CT design according to ANSI / IEEE C 57.13 please refer to page 331
(or other specied temperature)
Rb = Rated resistive burden The CT requirements mentioned in table 6.2-3 are simplied
in order to allow fast CT calculations on the safe side. More
Rb = Rlead + Rrelay = connected resistive burden
accurate dimensioning can be done by more intensive calcula-
TP = Primary time constant (net time constant)
tion with Siemenss CTDIM (www.siemens.com/ctdim) program.
UK = Knee-point voltage (r.m.s.) Results of CTDIM are released by the relay manufacturer.
Rrelay = Relay burden
2l Adaption factor for 7UT6, 7UM62 relays in g 6.2-122
Rlead = (limited resolution of measurement)
A
with Ipn INrelay Ipn 3 UnO INrelay
l = Single conductor length from CT to relay in m FAdap = = Request: 8
InO Isn SNmax Isn
= Specic resistance = 0.0175 mm2 / m (copper wires)
at 20 C / 68 F (or other specied temperature) 7SD52, 53, 610, when transformer inside protected zone
A = Conductor cross-section in mm2
In-pri-CTmax 1
8
In-pri-CTmin Transformer ratio*
In general, an ac-curacy of 1 % in the range of 1 to 2 times
nominal current (class 5 P) is specied. The rated symmetrical * If transformer in protection zone, else 1
short-circuit current factor KSSC should normally be selected so
In-pri-CT-Transf-Site 2 In-Obj-Transf-Site AND
that at least the maximum short-circuit current can be trans-
mitted without saturation (DC component is not considered). In-pri-CT-Transf-Site In-Obj-Transf-Site with
InO = Rated current of the protected object
This results, as a rule, in rated symmetrical short-circuit current UnO = Rated voltage of the protected object
factors of 10 or 20 depending on the rated burden of the CT in INrelay = Rated current of the relay
relation to the connected burden. A typical specication for pro- SNmax = Maximun load of the protected object
tection cores for distribution feeders is 5P10, 10 VA or 5P20, 5 VA. (for transformers: winding with max. load)
Relay type Transient dimensioning Min. required sym. short- Min. required knee-point
factor Ktd circuit current factor Kssc voltage Uk
6
Ktd (a) Ktd (a) (Rct + Rb) Isn
(with distance function) Ktd (a) 1 2 4 4 Ipn 1.3 Ipn
Ktd (b) 4 5 5 5 and: and:
Iscc max (zone 1 end fault) Iscc max (zone 1 end fault)
Ktd (b) Ktd (b) (Rct + Rb) Isn
Ipn Ipn
132 kV, 50 Hz
*) without
CB arrangement inside power plant is not shown distance function
xd = Generator direct axis subtransient reactance in p.u.
uk 1-2 = Transformer impedance voltage HV side LV side in %
Rrelay = Assumed with 0.1 , (power consumption for above relays is below 0.1 VA)
1) Current from side 3 is due to uk 2-3 and xd of G2 in most cases negligible
Fig. 6.2-125: Example 1 CT verication for 7UM62, 7UT6, 7SD52 (7SD53, 7SD610)
Ktd = 5 (from table 6.2-3) Ktd = 3 (from table 6.2-3) Ktd = 3 (from table 6.2-3) Ktd = 1.2 (from table 6.2-3)
Iscc max (ext. fault) Iscc max (ext. fault) Iscc max (ext. fault)
Kssc Ktd Kssc Ktd Kssc Ktd
Ipn Ipn Ipn
Sn 20 VA Sn 20 VA Sn 50 VA
Rb = = = 20 Rb = = = 20 Rb = = = 2
I2sn 1 A2 I2sn 1 A2 I2sn (5 A)2
18 + 20 18 + 20 0.96 + 2 17,000 A
= 20 = 40.8 = 20 = 41.2 = 20 = 30.6 = 1.2 (0.8 + 0.625 ) 5 A
18 + 0.625 18 + 0.450 0.96 + 0.975 1.3 1,000 A
= 111.8 V
Kssc required = 28.8, Kssc required = 17.9, Kssc required = 18.7, UK required = 111.8 V,
Kssc effective = 40.8 Kssc effective = 41.2 Kssc effective = 30.6 UK effective = 200 V
28.8 < 40.8 17.9 < 41.2 18.7 < 30.6 111.8 V < 200 V
CT dimensioning is ok CT dimensioning is ok CT dimensioning is ok CT dimensioning is ok
Ipn 3 UnO INrelay Ipn 3 UnO INrelay Ipn 3 UnO INrelay Ipn max
FAdap = FAdap = FAdap = 8
SNmax Isn SNmax Isn SNmax Isn Ipn min
Attention (only for 7UT6 V4.0): When low-impedance REF is zone): Maximum ratio between primary currents of CTs at the
used, the request for the REF side (3-phase) is: end of the protected line:
1/ F 1
4 Adap 4, (for the neutral CT: / 8 FAdap 8) Ipn max
8
Further condition for 7SD52x, 53x, 610 relays (when used as Ipn min
line differential protection without transformer inside protected
Specic resistance:
Iscc max 30,000 A mm2
= = 50 = 0.0175 (copper wires) at 20 C / 68 F
Ipn 600 A m
1
Kssc 50 = 25
2 CT design according to ANSI / IEEE C 57.13
6
15 VA Class C of this standard denes the CT by ist secondary terminal
Rb = = 15
1 A2 voltage at 20 times rated current, for which the ratio error shall
not exceed 10 %. Standard classes are C100, C200, C400 and
Rrelay = 0.1 C800 for 5 A rated secondary current.
2 0.0175 50
Rlead = = 0.3 This terminal voltage can be approximately calculated from the
6
IEC data as follows:
Rb = Rlead + Rrelay = 0.3 + 0.1 = 0.4
ANSI CT denition
Rct + Rb 4 + 15 Kssc
Kssc = Kssc = 10 = 43.2 Us.t.max = 20 5 A Rb
Rct + Rb 4 + 0.4 20
with
Pb
Rb = and INsn = 5 A, the result is
Isn2
Result:
The effective Kssc is 43.2, the required Kssc is 25. Therefore the Pb Kssc
Us.t.max =
stability criterion is fullled. 5A
Example:
Relay burden IEC 600 / 5, 5P20, 25 VA,
The CT burdens of the numerical relays of Siemens are below 0.1 60044
VA and can therefore be neglected for a practical estimation. ANSI (25 VA 20)
Exceptions are the busbar protection 7SS60 and the pilot-wire C57.13: Us.t.max = = 100 V, acc. to class C100
5A
relays 7SD600.
SIPROTEC Compact
SIPROTEC 600er
Device series
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
7PG2111
7SG163
7SG164
7SD610
7SA522
7SG18
7SD60
7SD80
7SD84
7SD86
7SD87
7SA61
7SA63
7SA64
7SA84
7SA86
7SA87
7SD5
ANSI Function Abbr.
Protection functions for 3-pole
tripping
3-pole p p p p p p p p p p p p p p p p p p
Protection functions for 1-pole
tripping
1-pole 1 1 1 1 p 1 1 1 p
6 FL
24
Fault locator
Overexcitation protection
FL
V/f
p p p p p
p
p p p
p p p
p
p
Synchrocheck, synchronizing
25
function
Sync 1 1 1 1 1 1 1 1 1 1 1 1 1
27TN/59TN Stator ground fault 3rd harmonics V0<, > (3rd harm.)
SIPROTEC Compact
SIPROTEC 600er
SIPROTEC easy
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
7SR23 1)
7SJ85 1)
7SR210
7SR220
7SR224
7SJ600
7SJ602
7PG23
7SG12
7SC80
7SR11
7SR12
7SL86
7SL87
7SJ45
7SJ46
7SJ80
7SJ81
7SJ61
7SJ62
7SJ63
7SJ64
7SJ86
p p p p p p p p p p p p p p p p p p p p p p p
p p 1
1 1 1 1
p p
p
p
1
1
1
1
1
1
1
1
6
1 1 1 1 1) 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 p p p
1 1 1 1 1 1 1 1 1
p p p p p p p 2) p 1 1 p p p p
1 1 1 1 1 1 1 1)
1 1 p p p p p p p p p p p 1 1 p p p
1 1 p p p p p p p p p p p 1 1 p p p
p p 1 1 1 p p p p p p p p p
1 1 1 1
1 1 p p p p p p p p p p p 1 1 p p p
p p p p p p p p p p p p p p p p p p p p
1 1 p p 1 1 1 p 1) 1 1 1 1 1 1 1) 1 1 p p p
p 1) 1 1 1
1 1 1 1
1 1 p p p p p p p p p 1 1 p p p p p
p p p p p p p p p p p p p p p p p p p p
1 1) p p p p p
SIPROTEC Compact
SIPROTEC 600er
Device series
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
7PG2111
7SG163
7SG164
7SD610
7SA522
7SG18
7SD60
7SD80
7SD84
7SD86
7SD87
7SA61
7SA63
7SA64
7SA84
7SA86
7SA87
7SD5
ANSI Function Abbr.
55 Power factor cos p p p p p p p p p p p p
66 Restart inhibit I 2t
6 67
Directional time-overcurrent
protection, phase
Directional time-overcurrent
I>, IP (V, I) p p p p 1 1 1 1 1 1 1 1
67N
protection for ground-faults
IN>, INP (V, I) 1 1 1 1 1 1 1 1 1 1 1 1 1
79 Automatic reclosing AR 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
85 Teleprotection p p p p p p p 1 1 p p p p 1 p
86 Lockout p p p p p p p p p p p p p p p p
87 Differential protection I p p p p p p p p p
87N Differential ground-fault protection IN p p 1 1
SIPROTEC Compact
SIPROTEC 600er
SIPROTEC easy
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
7SR23 1)
7SJ85 1)
7SR210
7SR220
7SR224
7SJ600
7SJ602
7PG23
7SG12
7SC80
7SR11
7SR12
7SL86
7SL87
7SJ45
7SJ46
7SJ80
7SJ81
7SJ61
7SJ62
7SJ63
7SJ64
7SJ86
p p 1 1 1 1 p 2) 1 p 2) p 2)
1 1 1 1 1 1 1 1 1 1 1 p p p
1 1) 1 1
1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 p p p
6
1 1 1 1 1 1 1 1 1 1 p p p
1 1) 1 1) 1 1 1 p 1) 1 1 1 1 11)
1 1
p p p p p p p p p 1) p p p p p p p p p p p
1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 p
1 1 1 1 1 1 1 1 1 1 p p p
1 1 1 1 1
p p 1
p p p p p p p p p p p p p p p p
p p p p p
p p 1 1 1 1 1 1 1 1 p p p
p p
1 1 1 1
SIPROTEC Compact
SIPROTEC 600er
Device series
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
7PG2111
7SG163
7SG164
7SD610
7SA522
7SG18
7SD60
7SD80
7SD84
7SD86
7SD87
7SA61
7SA63
7SA64
7SA84
7SA86
7SA87
7SD5
ANSI Function Abbr.
Further functions
Measured values p p p p p p p p p p p p p p p p p
Switching-statistic counters p p p p p p p p p p p p p p p p
Logic editor p p p p p p p p p p p p p
Inrush-current detection p p p 1 p p p p p p
Fast-scan recorder
Slow-scan recorder
Continuous recorder
GOOSE recorder
Sequence-of-events recorder
SIPROTEC Compact
SIPROTEC 600er
SIPROTEC easy
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
7SR23 1)
7SJ85 1)
7SR210
7SR220
7SR224
7SJ600
7SJ602
7PG23
7SG12
7SC80
7SR11
7SR12
7SL86
7SL87
7SJ45
7SJ46
7SJ80
7SJ81
7SJ61
7SJ62
7SJ63
7SJ64
7SJ86
p p p p p p p p p p p p p p p p p p p p
p p p p p p p p p p p p p p p p p
p p p p p p p p p p p p p p p p p
p p p p p p p p p p p p p p p p
p p p p p p p p p p p p 2) p p p p p p p p
p p p p p p p p p p p p p p p p p p 6
p p p p p p p p p p p p p p p p p p p p
p p p p p p p p p p p p p p p p p p p p
p p p p 1 1 p p p p p
8 8 8 8 1 1 1 1 4 4 4 4 4 4 4 8 8 4 4 8 8 8
SIPROTEC Compact
Device series
SIPROTEC 5
SIPROTEC 4
SIPROTEC 4
SIPROTEC 5
Reyrolle
7SK85 1)
7UM61
7UM62
6MD61
6MD63
6MD66
6MD85
6MD86
7SG17
7SK80
7SK81
ANSI Function Abbr.
Protection functions for 3-pole tripping 3-pole p p p p p p 1 1
Protection functions for 1-pole tripping 1-pole
FL Fault locator FL 1
p p
6
24 Overexcitation protection V/f
SIPROTEC Compact
SIPROTEC 600er
SIPROTEC 600er
SIPROTEC 4
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
Reyrolle
7KE85 1)
7UT85 1)
7UT86 1)
7UT87 1)
7SG117
7SG118
7UT612
7UT613
7RW60
7RW80
7VK61
7VK87
7SG14
7SG15
7UT63
7SR24
7SS60
7SS52
7VE6
p p p p p p p p p p p p 1 p p p
p p p
1 1 1 1 1 1
6
1 1 1 1 p p p 1
1 1 1 1 1 1 1 1 1 1 p p p
1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1 p p
1 1 1 1 1 1 p p
p p p p p p p p p
p p p p p p 1 1
1 p p p p p p 1 1 1 1
1 1 1 1
p 1 1 1 1 1 1 1 p p p
1 p p p p p p 1 1 1 1
SIPROTEC Compact
Device series
SIPROTEC 5
SIPROTEC 4
SIPROTEC 4
SIPROTEC 5
Reyrolle
7SK85 1)
7UM61
7UM62
6MD61
6MD63
6MD66
6MD85
6MD86
7SG17
7SK80
7SK81
ANSI Function Abbr.
55 Power factor cos 1 1 p 2) 1 1
66 Restart inhibit I 2t p p p 1 1
67N
ground-faults
IN>, INP (V, I) 1 1 1 p p
79 Automatic reclosing AR 1 1 1
81 Frequency protection f<, f> 1 1 1 p p 1 1
81R Rate of change of frequency df/dt 1 1 p p
85 Teleprotection
86 Lockout p p p p p p
87 Differential protection I p
SIPROTEC Compact
SIPROTEC 600er
SIPROTEC 600er
SIPROTEC 4
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
Reyrolle
7KE85 1)
7UT85 1)
7UT86 1)
7UT87 1)
7SG117
7SG118
7UT612
7UT613
7RW60
7RW80
7VK61
7VK87
7SG14
7SG15
7UT63
7SR24
7SS60
7SS52
7VE6
p p p 1 1 1
1 1 1 1 1 1 1 1 1 1 p p p
1 1 1 1
6
1 1 1
1 1) 1 1) 1 1)
1 p p p p p p p p p p p p p
p p
1 1 1 1 1 1 1 1 1 p p 1
1 p p
1 1
p p p p 1 1 1 p p p p p p
p p p p p p p p p p
1 1 1 p p p
p p p
1 1 1 1 p
p = basic 1 = optional (aditional price) = not available 1) in preparation 2) via CFC
SIPROTEC Compact
Device series
SIPROTEC 5
SIPROTEC 4
SIPROTEC 4
SIPROTEC 5
Reyrolle
7SK85 1)
7UM61
7UM62
6MD61
6MD63
6MD66
6MD85
6MD86
7SG17
7SK80
7SK81
ANSI Function Abbr.
Further functions
Measured values p p p p p p 1 p p p p
Switching-statistic counters p p p p p p p p p p p
Logic editor p p p p p p p p p
Inrush-current detection p p p 1 1 1
External trip initiation p p p p p
Control p p p p p p p p p p
6 Fault recording of analog and binary signals
Extended fault recording
p
p
p
p
p
p
1
p
p
Fast-scan recorder
Slow-scan recorder
Continuous recorder
Power quality recorder (class S)
GOOSE recorder
Sequence-of-events recorder
Extended trigger functions
Monitoring and supervision p p p p p p p p p p p
Protection interface, serial 1 p 1 1) 1 1)
No. Setting groups 4 4 8 2 2 8 4 4 4 8 8
SIPROTEC Compact
SIPROTEC 600er
SIPROTEC 600er
SIPROTEC 4
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
SIPROTEC 4
SIPROTEC 5
Reyrolle
Reyrolle
Reyrolle
7KE85 1)
7UT85 1)
7UT86 1)
7UT87 1)
7SG117
7SG118
7UT612
7UT613
7RW60
7RW80
7VK61
7VK87
7SG14
7SG15
7UT63
7SR24
7SS60
7SS52
7VE6
p p p p p p p p p p p p p p p p p p
p p p p p p p p p p p p p p p
p p p p p p p p p p p p
p p p p p p p p p
p p p p p p p p p p p 1 p 1 p p
p p p p p p p p p p p p p p p
p p p p p p p p p p p p p p p p p p 6
p
p
p
p
1 1)
1 1)
1 1)
1
p p p p p p p p p p p p p p p p p p
p p p p p 1 p p p
1 1 4 4 4 8 8 8 8 8 4 8 4 8 1 4 8 8
Even in such congurations, the user can benet from full blocks are designed to substitute conventional terminal blocks,
automation and communication capabilities. This means that thereby realizing a very economic design. Existing protection
classical RTU solution, interfaces to other IEDs are included, and relays can be connected either by IEC 60870-5-103 or by the
HMIs for station operation and supervision can be added as an more enhanced IEC 61850.
option. Also, the protection relays are connected to the RTU, so
that data from the relays are available both at the station opera- In new substations, the amount of cabling can be reduced by
tion terminal and in the control centers. decentralizing the automation system. Both protection relays
and bay controllers are situated as near as possible to the pri-
All members of the SICAM AK, TM, BC, EMIC and MIC family can mary switchgear. Typically they are located in relay houses (EHV)
be equipped with different combinations of communication, both or in control cabinets directly beneath HV GIS feeders. The
serial and Ethernet (TCP / IP). Different protocols are available, rugged design with maximum EMC provides high security and
mainly IEC standards, e.g., IEC 60870-5-101 / 103 / 104 IEC 61850, availability.
IEC 62056-21, but also a lot of other well-known protocols from
different vendors. For station control, two different products are available: SICAM PAS
is a software-oriented product based on standard industrial
Fig. 6.3-2 shows an example of refurbishment and centralized hardware, whereas SICAM AK, TM, BC, EMIC and MIC represents
data acquisition in an MV substation. The interface to the pri- the modular hardware-oriented design which bridges the gap
mary equipment is connected via a marshalling rack, but can use between remote terminal units (RTUs) and substation automa-
any peripheral voltage (DC 24220 V). The electronic terminal tion (SA) (g. 6.3-3).
Control centers
SICAM 230
SICAM AK
6
IEC 61850 Ethernet TCP/IP
SIPROTEC
PE elements
Protection relais Parallel data Alternative interface
(from marshalling rack) (substitution of terminal blocks)
Control centers
SICAM 230 or
SICAM AK, TM, SICAM SCC
SICAM PAS BC, EMIC, MIC
IEC 61850 Ethernet TCP/IP
IEC - 104
SIPROTEC
SICAM MIC
High-voltage Medium-voltage Station data
n x bays m x relais
Fig. 6.3-3: Basic principle of a SICAM station automation solution with alternative station controllers
Control center
SICAM AK
IEC 61850 Ethernet TCP/IP
SIPROTEC
SICAM MIC
Combined control and protection, Station data
situated directly in low-voltage compartments
Fig. 6.3-4: Combined control and protection, situated directly in low-voltage compartments
Control center
6
IEC 61850 Ethernet TCP/IP
IEC -104
SIPROTEC
SICAM MIC
Combined control and protection, Station data
situated directly in low-voltage compartments
The exible Siemens solutions are available for every kind of single-point data input. This means that multiple data input is
substation: avoided. Even if different engineering tools are necessary for
tFor different voltage levels, from ring main unit to certain congurations, these tools exchange their data for more
transmission substation efcient engineering.
tFor new substations or refurbishment
tFor gas-insulated or air-insulated switchgear Example of a small medium-voltage substation: Typically it
tFor indoor or outdoor design consists of 4 to 16 MV feeders and is unmanned. In most cases,
tFor manned or unmanned substations combined bay control and protection devices are located directly
in the low-voltage compartments of the switchgear panels.
Communication is the backbone of every automation system.
Therefore, Siemens solutions are designed to collect the data A station operation terminal is usually not required, because
from the high-voltage equipment and present them to the such substations are normally remote-controlled, and in case of
different users: the right information for the right users at the local service / maintenance they are easy to control at the front
right place and time with the required quality and security. side of the switchgear panels (g. 6.3-4).
Here are some default examples for typical congurations. They Example of a distribution substation in industry supply: In
are like elements which can be combined according to the principle they are similar to the conguration above, but they
respective requirements. The products, which are the bricks of are often connected to a control center via local area network
the congurations, are an integral part of the harmonized (LAN). A distinctive feature is the interface to low-voltage
system behavior, and support according to the principle of distribution boards and sometimes even to the industrial auto-
Control centers
IEC - 101
IEC - 104
SIPROTEC
SICAM MIC
n x HV feeders n x MV feeders Station data
combined
control and protection
SICAM AK
(reduntant)
IEC 61850 Ethernet TCP/IP
6
IEC - 104
SICAM MIC
mation system for data exchange. Here, the compatibility with operation and maintenance of such substations, such as voltage
SIMATIC products simplies system integration (g. 6.3-5). regulation by controlling on-load tap changers, synchrocheck,
automatic command sequences, etc. (g. 6.3-7).
A subtransmission substation requires even more complexity: 2 or
3 voltage levels have to be equipped; a station operation terminal The devices are as exible as the congurations: Bay controllers,
is usually required; more communication interfaces to external protection relays, station control units, station operation units
locations, separated control and protection devices on HV level, and RTUs can be congured from small to very large. The well-
powerful LAN based on IEC 61850, and remote maintenance known products of the SICAM and SIPROTEC series are a well
access are typical features of such applications (g. 6.3-6). proven base for the Siemens solutions.
In transmission substations, typically two to four voltage levels Secure and reliable operation
are to be automated. According to the high importance of such Siemens solutions provide human machine interfaces (HMI)
substations, availability is of the highest priority. Therefore, for every control level and support the operators with reliable
redundancy at substation level is generally required, both for information and secure, easy-to-use control features.
station control units and station operation. Multiple operator
stations are often required, multiple communication links to At feeder level:
different control centers or neighboring substations are stan- tConventional panels with pushbuttons and instruments
dard. Although most standard applications are IEC protocols, for refurbishment
specic protocols also have to be offered for interfacing existing tElectronic front panels combined with bay control units
third-party devices. Complex automation functions support the (default)
tAccess points for remote terminals connected to the station are maintenance free and easy to expand at a later date. Last but
operation units not least, the powerful services for remote maintenance (diag-
tPortable touch panels with wireless access in dened areas nosis, settings, updates, test, etc.) provide a very economic way
to keep any substation up-to-date and running.
At substation level:
tSingle or redundant HMI Simple handling of the solutions is provided by:
tDistributed server / client architectures with
multiple and / or remote terminals tSame look and feel of all HMI on different levels.
tInterface to ofce automation tVertical and horizontal interoperability of the involved
products.
All images and pictures of the HMIs are designed according to tPlug and play for spare parts by simple exchange of ash cards.
ergonomic requirements, so as to give the operators clear infor-
mation that is easy to use. Control commands are only accepted Reduction of engineering effort by
if access rights are met, the local / remote switches are in the tSeamless data management, only single data input for
right position and the multi-step command sequence is actively whole project.
handled. Care is taken that only commands which are intended tEasy up and downloads, even remote.
and explicitly given are processed and sent to the switchgear. tIntegrated test tools.
Reduction of complexity by seamless communication control centers, and IEC 60870-5 for remote communication.
tWorldwide standard IEC 61850 promoted by Siemens They form the strong backbone for the seamless solutions in
tIntegrated IT security concepts energy automation. Additionally, the systems are tested in
tLatest technology integrated rugged environmental conditions and certied according to
applicable IEC standards.
Efcient and state-of-the-art projects
The solutions for energy automation are part of the extensive Investments in our solutions are secured by the evergreen
programme, Siemens One. This means that energy automation concept, which denes migration methods when a new genera-
solutions are integrated in different applications of the vast tion of products is introduced to the markets, e.g., the migration
activity and expertise of Siemens: solution for SICAM LSA 678 from the early 90ies: By substituting
tPower grids in transmission and distribution the station control device with todays SICAM PAS, it is possible
tComplete building automation to retain the installed feeder devices and import the existing
tSolutions for pipelines and infrastructure
tTurnkey railway systems
Professional implementation of complete solutions from
They all make use of the energy automation solutions and the competence centers
associated transfer of expertise for efcient project and order Consulting
execution. Our worldwide engineering centers are always close Engineering
services Training
to the system operators (g. 6.3-9).
USA CH OES
6
USA
ITL IND CHN
MEX
SICAM PAS
Fiber-optic
connections
ILSA protocol TCP/IP
IEC61850
Fiber-optic
Bay 1 ... n connections
ILSA protocol
Switchgear
Bay 1 ... n
Switchgear
database with the settings into the new tool SICAM PAS UI. This System overview, application and functionality of SICAM PAS
method reduces the refurbishment work signicantly and adds tSICAM PAS is an energy automation solution; its system
new features to the system: In the next years the substation can architecture makes it scalable.
be expanded with new feeder devices through the use of tSICAM PAS is suitable for operating a substation not only from
IEC 61850, even though some parts of the system might already one single station level computer, but also in combination with
be older than 15 years (g. 6.3-10). further SICAM PAS or other station control units. Communica-
tion in this network is based on a powerful Ethernet LAN.
Our solutions are not only compatible with older devices, they tWith its features and its modular expandability, SICAM PAS
are also very innovative. The Frost&Sullivan Technology Leader- covers a broad range of applications and supports distributed
ship Award 2006 was presented to Siemens for pioneering in the system congurations. A distributed SICAM PAS system
development of an innovative technology, the IEC 61850. operates simultaneously on several computers.
tSICAM PAS can use existing hardware components and
With Siemens energy automation solutions, every user is on the communication standards as well as their connections.
safe side: The combination of long-term experience and the tSICAM PAS controls and registers the process data for all
newest innovation supplies safety for many years to come. devices of a substation, within the scope of the data transfer
protocols supported.
tSICAM PAS is a communication gateway. This is why only one
single data connection to a higher-level system control center
is required.
tSICAM PAS enables integration of a fully graphical process
6.3.3 SICAM PAS visualization system directly in the substation.
tSICAM PAS simplies installation and parameterization of new
SICAM PAS (Power Automation System) meets all the demands devices, thanks to its intuitive user interface.
placed on a distributed substation control system both now tSICAM PAS is notable for its online parameter setting features,
and in the future. Amongst many other standardized communi- particularly when the system has to be expanded. There are no
cation protocols, SICAM PAS particularly supports the IEC 61850 generation times; loading into a target system is not required
6 standard for communication between substations and IEDs.
SICAM PAS is an open system and in addition to standardized
at all or only required if conguration is performed on a
separate engineering PC.
data transfer processes it features user interfaces for the tSICAM PAS features integrated testing and diagnostic functions.
integration of system-specic tasks and offers multiple automa- tIts user-friendliness, its operator control logic, its orientation
tion options. SICAM PAS can thus be easily included in existing to the Windows world and its open structure ideally suit users'
systems and used for system integration, too. With modern requirements.
diagnostics, it optimally supports commissioning and mainte- tSICAM PAS is developed in accordance with selected security
nance. SICAM PAS is clearly structured and reliable, thanks to its standards and meets modern demands placed on safe
open, fully documented and tested system (g. 6.3-11). communication.
Corporate
network TCP/IP
Control center
HMI
Station bus Ethernet TCP/IP
Serial hub
IEC 61850
Fig. 6.3-11: Typical SICAM PAS conguration; IEDs are connected to the station unit with IEC 61850 and various other protocols
(IEC 60870-5-103,DNPV3.00, etc.). The station unit communicates with the higher-level system control center by means
of IEC 60870-5-101 and / or 104
System architecture
SICAM PAS works on industrial-standard hardware with the
Microsoft Windows operating systems. The advantages of this
platform are low hardware and software costs, ease of opera-
tion, scalability, exibility and constantly available support. With
the powerful real-time data distribution system, applications can
be allocated among several computers, thus boosting perfor-
mance, connectivity and availability.
Corporate
network TCP/IP
HMI
Station unit clients Station unit
Full Server Full Server
Station bus
Ethernet TCP/IP
IEC 61850
Fig. 6.3-15: Typical redundant conguration: The station unit and the HMI server are
based on a redundant structure to boost availiability
the Web clients. SICAM Diamond allows access to archive les Automation tasks
and fault recordings through the World Wide Web. The archive can be congured in SICAM PAS with the CFC (Continuous
les can be saved on the Web client for evaluation, e.g. with
Microsoft Excel. Fault recordings can be visualized directly in
Function Chart), which conforms to IEC 61131. In this editor,
tasks are congured graphically by wiring function blocks.
6
the Internet Explorer. SICAM PAS comes with an extensive library of CFC function
blocks, developed and system-tested specially for energy auto-
Further station control aspects mation.
During, e.g., maintenance work or for other operational reasons,
information exchange with the control centers or the substation Applications range from generation of simple group indications
itself can be blocked with the telecontrol blocking and bay through switching interlocks to complex operating sequences.
blocking functions. The telecontrol blocking function can also be Creation of operating sequences is supported by the SFC Editor
congured for specic channels so as to prevent the transfer of (Sequential Function Chart).
information to one particular control center during operation,
while transfer continues with other control centers. The bay In this context, additionally pre-congured and system-tested
blocking and telecontrol blocking functions act in both the applications such as frequency-based load shedding, transformer
signaling and the command directions. Channel-specic monitoring and SF6 gas monitoring can be optionally licensed.
switching authority also makes it possible to distinguish Besides special functional components and CFCs, the scope of
between local control (SICAM SCC) and remote control for the supply also covers operating images for SICAM SCC.
switching direction, but also between control center connec-
tions. For these three functions, information-specic exceptions Redundancy
can be declared additionally, so that, e.g., certain messages are SICAM PAS features comprehensive redundancy functions to
transmitted despite an activated block, or special commands are boost the availability of the station automation system:
processed and issued despite of a dened switching authority. tThe substation control unit can be used in a duplicate
While a 1-out-of-n check is normally effective in IEDs, i.e. only conguration (system redundancy)
one command is accepted and issued at the same time, an tThe communication to IEDs and RTUs can be redundant
m-out-of-n check is supported on the side of the substation (interface redundancy)
control system with SICAM PAS. This helps to dene how many tSubordinate units can be duplicated (redundancy at the bay
commands can be processed at the same time for all IEDs. control level)
Circuit-breakers can be controlled in synchronized/unsynchro- tSubunits that are only designed for communication with one
nized mode. master (e.g., with only one serial interface) can be supported.
0A
TP 0 TP 0 TP 0 TP 0
= K01/02
6 The individual applications (communication protocols) operate With a distributed PAS system using a full server and up to 6
independently of each other in a hot/standby connection, i.e. a DIPs, a maximum of 350 IEDs and 20,000 data points can be
changeover, e.g., of the IEC 61850 client from one station supported.
control unit to the other due to a disturbance has no effects on
the communication connection to the control center, which Process visualization with SICAM SCC
remains on the rst station control unit without interruption. In the operation of a substation, SICAM PAS is used for config-
Apart from a higher stability in unaffected communication uration purposes and as a powerful data concentrator.
connections, the redundancy changeover of affected compo- SICAM SCC serves as the process visualization system. Several
nents takes place within a very short time (depending on appli- independent SICAM SCC servers can be connected to one
cation and conguration, between 250 ms and max. 3 sec). SICAM PAS. Connection of redundant servers is also possible.
Adjustments during operation such as bay/telecontrol blocking, SICAM SCC supports the connection of several SICAM PAS sys-
switching authority, but also marking commands to the SoftPLC tems. In the signal lists, the original time stamps are logged in
for operational control of the automation functions, are kept ms resolution as they occur in the devices. With every signal, a
synchronous in both station control units during redundancy series of additional data is also presented to provide information
operation. The current adjustments are also valid after a redun- about causes (spontaneous, command), event sources (close
dancy changeover. SICAM SCC communicates simultaneously range, local, remote), etc. Besides process signals, command
with both redundant station control units. A redundant structure signals are also logged. IndustrialX controls are used to control
is also possible for process visualization with SICAM SCC and and monitor switchgear. These switching-device objects support
fault-record archiving with SICAM PQ Analyzer as shown in four different forms of presentation (IEC, DIN, SINAUT LSA,
g. 6.3-15. SICAM) for circuit-breakers and disconnectors. It is also possible
to create bitmaps (dened for a specic project) to represent
Scope of information switching devices, and to link them to the objects. For informa-
The amount of information to be processed by SICAM PAS is tive visualization, not only nominal and spontaneous ashing
essentially determined by the following factors: are supported, but also the display of various device and com-
tComputer network concept (multiple-computer network or munication states (e.g., up-to-date / not up-to-date, feeder and
single-station system) telecontrol blocking, etc.). Measured values and switching
tPerformance data of the hardware used device states that are not continuously updated due to, e.g.,
tPerformance data of the network device or communication failure or feeder blocking, may be
tSize of the database (RDBMS) updated directly via the operation panel with SICAM SCC
tRate of change of values (g. 6.3-16).
In conjunction with the SICAM PAS station unit, the switching SICAM SCC is based on SIMATIC WinCC, which has advanced to
devices can be controlled either directly or with select before become both the industrial standard and the market leader in
operate. When visualizing the process by single-line diagrams, Europe. It features:
topological coloring can be used. The WinCC add-on SIMATIC tMultilingual capability
Web navigator can be used for control and monitoring via the tAll operation and monitoring functions on board. These
Internet. SICAM Valpro can be used to evaluate measured and include not only the graphics system for plant displays and the
metered values. It not only allows a graphical and a tabular signaling and archiving system for alarms and measured
display of archived values, but also enables subsequent evalua- values, but also a reporting and logging system. Further
tion functions such as minimum, maximum and averages values advantages are integrated user administration, along with the
(on an hourly or daily basis). For protection devices connected granting and checking of access rights for conguration and
with the protocols IEC 61850, IEC 60870-5-103 as well as runtime operations.
PROFIBUS FMS (SIPROTEC 4) or SINAUT LSA ILSA, fault record- tEasy and efcient conguration
ings can be retrieved and archived automatically. SICAM PQ Conguration is assisted by dialogs, wizards and extensive
Analyzer with its component Incident Explorer is used for man- libraries.
agement and evaluation of the fault recordings. tConsistently scalable, even via the Web
In conformity with requirements, the bandwidth ranges from
SICAM SCC V7.0 SP1 can also be used as a process visualization small single-user stations up to client/server solutions with
system for user stations on the Web as well as support of the server
tSICAM AK, TM, BC, EMIC and MIC redundancy.
tIEC 61850 devices (for example, SIPROTEC 4) tWinCC/Redundancy increases system availability by
redundant WinCC stations or servers monitoring each other
SICAM SCC for SICAM AK, TM, BC, EMIC and MIC mutually, ensuring the operability of the system and enabling
For communication with SICAM AK, TM, BC, EMIC and MIC, the complete data acquisition.
protocol IEC 60870-5-104 or IEC 61850 can be used. Both tOpen standards for easy integration
SICAM TOOLBOX II V5.0 and SICAM SCC V7.0 SP1 support Using any external tools, archived data can be accessed
exchange of conguration data. through a series of open interfaces (such as SQL and ODBC)
Overview of the operator control philosophy and A common feature of all views is that they have an Explorer
user interface window that shows the system conguration in a clearly
The SICAM PAS user interface is based on customary Windows arranged tree structure. As in the Windows Explorer, it is pos-
technology, which allows to navigate in the familiar Windows sible to open individual levels of this tree structure to work in
environment both when conguring the system and during them. Meanwhile, other levels can be closed to improve clarity.
ongoing operation. The system distinguishes between congu- Depending on the current navigation level and the chosen
ration and operation of a substation. In SICAM PAS, these two component, in the context menu (right mouse button)
tasks are rmly separated by two independent programs. SICAM PAS offers precisely those program functions that are
currently appropriate.
The SICAM PAS UI conguration program (g. 6.3-17) is used
to create and edit a project-specic conguration. To enhance Operation takes place through the necessary steps in the data
clarity, four views are distinguished: window on the right. Here, parameters can be set, information
selected and assignments dened to form a user-specic, process-
tConguration oriented system topology. The user interface is uncomplicated and
tMapping structured according to the task denition, so as to enable intuitive
tSystem topology working and to simplify changes. The user interface assists the
tDevice templates editing process by displaying parameter descriptions and messages
when incorrect parameters are entered. In the tabular views for
Power supply
Primary power supply
DC 24 60 V
AC/DC 110 230 V
Secondary power supply
without
DC 24 60 V
AC/DC 110 230 V no secondary power supply
CPU type
CPU module with single core CPU
(Celeron M 440, 1.86GHz), 2 x 4GB CF, 2GB RAM, image SU V2 20, backup DVD
CPU module with dual core CPU
(Core Duo T2500, 2GHz), 2 x 4GB CF, 2GB RAM, image SU V2 20, backup DVD
CPU module with dual core CPU with RAID System
(Intel Core 2 Duo L7500 1.6GHz), 2 x 4GB CF, 4GB RAM, Image SU V2 20,
Backup DVD, incl. RAID controller and RAID system level 1 incl. 2x100GByte hard disks
I/O boards
None
One digital I/O module (32 binary contacts)
Two digital I/O modules (64 binary contacts)
PCI adapter
without PCI-adapter
with PCI-adapter
Optional extensions:
tExternal USB-DVD drive for image DVD
tExternal USB hard disk for backup
tUSB memory stick
tPCI adapter for up to 4 PCI cards
tCOM-port extension cards
tPROFIBUS card
tGPS / DCF 77 time signal receiver manufactured by Hopf
tUp to 64 binary I/O-contacts
6.3.5 Conguration Examples Several SICAM PAS full servers connected to a human-
machine interface (HMI)
Conguration for medium to large applications The example illustrates a SICAM SCC human-machine interface
If the subsgtation comprises 30 to 150 bay control units, (HMI) with 2 SICAM station units to which bay devices are
SICAM PAS and SICAM SCC must run on separate PCs. The connected. This conguration makes sense in cases where no
example below illustrates the connection of the bay control units spatially distributed human-machine interface and no failsafe
to a SICAM station unit (g. 6.3-23). SICAM SCC are required (g. 6.3-25).
6
Feeder devices
Feeder devices
Fig. 6.3-23: Connection of feeder devices to a SICAM station unit Fig. 6.3-25: SICAM SCC with several SICAM station units
Feeder devices
Feeder devices
Fig. 6.3-24: Connection of feeder devices in a distributed system Fig. 6.3-26: Redundant SICAM PAS in client / server conguration
Distributed system with full server and DIP tRedundant full servers
The example shows a distributed SICAM PAS system. It consists tRedundant SICAM SCCs implemented in server/client
of a full server and DIP, and communicates with a control center architecture
via TCP/IP. Bay control units and substations are connected to a tConnection of bay control units to 2 SICAM PAS stations
distributed system via Ethernet and serial interfaces (g. 6.3-27).
Bay control units with 2 interfaces are required for the redun-
Redundant connection of bay control units and substations dant connection of bay control units. Alternatively, bay control
SICAM PAS supports the redundant connection of bay control units equipped with one interface can be connected redundantly
units and substations. The example illustrates the following via a splitter (g. 6.3-28).
conguration:
Control center
Internet
SICAM SCC
Fig. 6.3-27: Example of a distributed SICAM PAS system with full server and DIPs
SICAM SCC
clients
Company network
TCP/IP
Redundant
SICAM SCC
servers
Fig. 6.3-28: SICAM PAS station bus conguration with redundant connection of the feeder devices and the redundant SICAM SCC station controller
6.3.6 SICAM AK, TM, BC, EMIC and MIC All components of the ACP family are using the same communi-
cation modules, and therefore they can use all available proto-
Versatile functionality and high exibility are fundamental for a cols. In addition to standards like IEC 60870-5-101 / 103 / 104
modern remote control system. SICAM AK, TM, BC, EMIC and and IEC 61850 (client and / or server), also DNP 3.0 and Modbus
MIC adds comprehensive options for communication, automa- are available in addition to a lot of legacy and third-party proto-
tion and process interfaces. The different components of cols for connecting third-party devices.
SICAM AK, TM, BC, EMIC and MIC offer optimal scalability regard-
ing the number of interfaces and signals. Nevertheless these Another joint feature of all components is the integrated ash
components are all based on the same system architecture, the memory card, where all parameters and rmwares are stored. A
same technology, and are handled with the same engineering simple exchange of a component is now possible, just by
tool (SICAM TOOLBOX II). changing the memory card.
tSICAM AK is the large automation component for a exible mix
of communication, automation and I / O. It offers optimal The SICAM TOOLBOX II offers all functions for an integrated,
support as master controller or RTU, gateway or front-end, seamless engineering of complete projects, and works with all
with local or distributed I / O. Versatile redundancy concepts components of SICAM AK, TM, BC, EMIC and MIC. It supports all
are another asset of these components. phases of an RTU or station automation project. Data exchange
tSICAM TM is the solution for compact applications. This with DIGSI and PAS UI means a single entry point for data engi-
component offers up to 4 communication interfaces plus neering avoiding multiple manual data inputs for a mixed con-
automation function and process interface per distributed guration.
terminal modules. All modules are easily mounted to standard
DIN rails. The terminal modules can be distributed up to 200 m With SICAM AK, TM, BC, EMIC and MIC there is always enough
with ber-optic cables. performance at hand: The modular multiprocessor concept
tSICAM BC is the ruggedized component for highest EMC and grows with every enhancement of the system. The distributed
direct process interface up to DC 220 V. High switching architecture and the principle of evolutionary development
capacity and direct interface for measurement transformers, cater for a future proof system with long lifetime expectation
plus expandability with TM modules provide exible and high security of investment. SICAM AK, TM, BC, EMIC and
6 application in centralized and distributed congurations. Up to
3 communication interfaces and automation functions are
MIC carries the experience of more than 30 years of remote
control and automation; many references are proving the ex-
integrated. ible ways of application.
tSICAM MIC is a small RTU and offers either a serial interface
according to IEC 60870-5-101 or an Ethernet interface with Automation component SICAM AK
IEC 60870-5-104. Up to 8 terminal modules for I / O can be
connected. A simplied automation function and a Web server Longevity through continuity and innovation
for easy engineering are integrated. SICAM AK features high functionality and exibility through the
tSICAM EMIC, the new smart automation system. Thanks to its implementation of innovative and reliable technologies, on the
node functionality with 3 interfaces,SICAM EMIC has many stable basis of a reliable product platform.
different potential applications. It can be used as an ordinary
telecontrol substation with any kind of communication to a
control center. If SICAM EMIC doesnt offer adequate signal
scope, it can be connected additional. Freely programmable
application programs for local control functions complete the
all-round versatility of the SICAM EMIC.
For this, the system concept ACP (Automation, Control and Scalable redundancy:
Protection) creates the technological preconditions. Balanced tComponent redundancy
functionality permits the exible combination of automation, tDoubling of processing / communication elements
telecontrol and communication tasks. Complemented with the
scalable performance and various redundancy congurations, an The intelligent terminal SICAM TM, EMIC and MIC:
optimal adaptation to the respective requirements of the process tDirect connection of actuators and sensors with wire cross-
is achieved (g. 6.3-29). sections up to 2.5 mm2
tCan be located remotely up to 200 m
SICAM AK is thus perfectly suitable for automation with inte- tBinary input / output also for DC 110 / 220 V
grated telecontrol technology as: tAssembly on 35 mm DIN rail
tTelecontrol substation or central device
tAutomation unit with autonomous functional groups Versatile communication capability
tData node, station control device, front-end or gateway With SICAM AK, a variety of media can be utilized for local and
tWith local or remote peripherals remote communication. (wire connections, FO, radio, dial-up
tFor rear panel installation or 19 inch assembly trafc, GSM, GPRS, WAN, LAN, eld bus etc.)
SICAM AK the forward-looking product Through the simple installation of serial interface modules, in
Versatile communication: total up to 66 communication interfaces are possible in one
tUp to 66 serial interfaces according to IEC 60870-5-101 / 103 SICAM AK, whereby a different individual protocol can be used
tLAN / WAN communication according to IEC 60870-5-104 for each interface.
tLAN communication according to IEC 61850
tVarious third-party protocols possible For standard communication protocols according to IEC 60870-
5-101 / 103 / 104 and IEC 61850 are implemented.
Easy engineering with SICAM TOOLBOX II:
tObject-oriented data model Besides the standard protocols there are also a variety of third-
tCreation of open-loop and closed-loop control application party protocols available (DNP 3.0, Modbus etc.).
programs according to IEC 61131-3
tAll engineering tasks can also be carried out remotely Simple process interfacing
6
In addition to the central acquisition and output of process
Plug and play for spare parts: signals within an SICAM AK mounting rack, it is possible to use
tStorage of parameters and rmware on a ash card SICAM TM, EMIC and MIC peripheral elements (g. 6.3-30).
tSpare part exchange does not require additional loading with
SICAM TOOLBOX II An essential feature of the SICAM TM, EMIC and MIC peripheral
elements is the efcient and simple interfacing possibility of the
Open system architecture: process signals. This takes place on so-called I / O modules, which
tModular, open and technology-independent system structure are distinguished through a robust casing, a secure contact as
tSystem-consistent further development and therefore an well as solid electronics. The I / O modules are lined up in rows.
innovative and future-proof product The contact takes place during the process of latching together,
Fig. 6.3-29: SICAM AK Fig. 6.3-30: SICAM TM, EMIC and MIC peripheral elements
without any further manipulation. Thereby each module remains Consequently, with the exchange of modules, new loading is no
individually exchangeable. longer required, since new modules obtain all data from the
memory card. With the replacement of spare parts, plug and
A clearly arranged connection front with LEDs for the status play becomes a reality: No special tool is required, even loading
display ensures clarity locally. The structure of the terminals is no longer necessary.
enables a direct sensor / actuator wiring without using interme-
diate terminal blocks with wire cross-sections up to 2.5 mm2. Thereby, work during a service operation is reduced to a min-
Modules for binary inputs and outputs up to DC 220 V open imum.
further saving potentials at the interface level.
Open system architecture
Depending on the requirements, the I / O modules can be tted The basis for this automation concept is a modular, open and
with either an electrical bus or an optical bus, through which the consequently technology-independent system architecture for
peripheral signals can be acquired as close as possible to the processing, communication and peripherals (multi-processor
point of origin. In this way, broad cabling can be reduced to a system, rmware).
minimum.
Standardized interfaces between the individual elements again
Easy engineering permit, even with further developments, the latest state of
An essential aspect in the overall economical consideration are technology to be implemented, without having to modify the
the costs that occur for the creation, maintenance and service. existing elements. In this way, a longevity of the product and
For this, the reliable SICAM TOOLBOX II is used. consequently investment security and continuity can be ensured
tObject orientation: (g. 6.3-31).
The object orientation makes it possible to also utilize the
same characteristics of same-type primary-technology units Every board and every module on which a rmware can run,
and operational equipment (e.g., disconnectors, circuit- forms, together with the function-determining rmware, one
breakers, feeders etc.) for the conguration. The close system element.
coupling with the design tool ensures the consistent, uniform
6 documentation of the entire plant through to circuit diagram.
Through this, considerable rationalization results with
The adaptation to the specic requirements of the application is
achieved through the individual conguration and through the
engineering. loading of standard rmware and parameters. Within their
tOpen-loop and closed-loop control according to IEC 61131-3: dened limits, the parameters thereby not only inuence the
Open-loop and closed-loop control application programs are behavior of the rmware functions, but also that of the hard-
created by means of CAEx plus according to IEC 61131-3, a ware functions. With that, for all module types, all mechanical
standard that is generally accepted and recognized in the parameter settings are omitted, such as e.g., the changing of
market. As a result, the training periods are reduced jumpers or loads, thus enabling not only the online change, but
considerably. also a consistent documentation of the set parameters by the
tAll engineering tasks can also be carried out remotely: SICAM TOOLBOX II as well as a simplied storage.
All engineering tasks, from the system diagnostic through to
the online test, can also be performed remotely with the System overview
SICAM TOOLBOX II. For this, a separate communication link Mechanics
between SICAM TOOLBOX II and SICAM AK is not necessary: Fig. 6.2-32 and g. 6.2-33 show two types of basic mounting
Every available communication interface can be used. Using racks: module CM-2832 with 9 slots and module CM-2835 with
further automation units of SICAM TM, AK or BC, the 17 slots.
SICAM TOOLBOX II can be remotely positioned over an
arbitrary number of hierarchies. Module CM-2833 (not pictured here) is the expansion mounting
rack for up to 16 peripheral elements outside the basic
The access to the engineering data is fundamentally protected mounting rack.
by a password.
With the mechanics, value has been placed on exibility and
Plug and play for spare parts easy handling. Consequently, the mounting rack is available for
All data of an automation unit such as rmware and parame- rear panel installation or for 19 (swing) frame installation.
ters are stored non-volatile centrally on an exchangeable ash
card. With a restart of the automation unit, and also with Almost all necessary external connectors (e.g., communication,
a restart of individual modules, all necessary data are automati- peripherals, external periphery bus) can be connected with the
cally transferred from the ash card to all CPUs and modules. help of standard cables or prefabricated cables without any
additional tools (g. 6.3-34, g. 6.3-35, g. 6.3-36).
Decoupled from
individual
Protected area = Internal communication technology and
functionally
standardized
Autonomous
unit for
expansions and
renewals
Interfaces
(process,
communication)
Functions and
Open area = Adaption to the current concepts
technical and economic demands Technology
Fig. 6.3-32: CM-2832 SICAM AK mounting rack with 9 slots Fig. 6.3-33: CM-2835 SICAM AK mounting rack with 17 slots
Guide plate of
Seating frame Wall bracket
3
Hook 2
Unlocking lever
1
6 CP-2012
CP-2010
Master control element Processing and
comunication element
SIM0
SIM0
SIM1
X13
X11 SI3 (X3) X12
SI1 (X1)
X10 X11
SI2 (X2)
SI0 (X0) X10
SI1 (X1)
CM-2837
CM-2835
SI0 (X0)
Fig. 6.3-36: RJ45 connection technique for external Ax 1703 peripheral bus
SICAM AK
Processing and Communication
supply
supply
Power
Power
Master Control Element
Protocol element(s)
Protocol element(s)
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
element
optional
6
supply
supply
Power
optional Power
optional
Process
PE PE PE PE
2 2 2 2
Peripheral elements outside the basic mounting rack
Peripheral elements may be PE PE PE PE
tinstalled in the basic mounting rack (as shown above), and / or 16 16 16 16
supply
Power
Power
Master control element
Functions of the master control element:
Protocol element(s)
Protocol element(s)
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
tCommunication with installed peripheral elements via the
6 serial Ax 1703 peripheral bus
tOpen / closed-loop control function with a freely programmable
optional
element
supply
Power
Power
diagram technology
tCommunication with other automation units via protocol
optional optional
elements installable on the master control element (up to 2
interfaces)
tCentral coordinating element for all system services and all
Process
internal and overlapping concepts, such as e.g.,
Data ow control
Monitoring functions Fig. 6.3-39: Master control element
Diagnostic
Time management and time synchronization via minute
pulse, serial time signal (DCF77 / GPS-receiver), serial
communication link, NTP Server over LAN / WAN
Local SICAM TOOLBOX II connection
Storage of parameters and rmware on a ash card
supply
Power
Power
Master control element
user program according to IEC 61131-3, e.g., in function
Protocol element(s)
Protocol element(s)
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
diagram technology
element
tCommunication with other automation units via protocol optional
supply
supply
Power
Power
Peripheral element
Peripheral elements, as shown in g. 6.3-41, are used for optional optional
6
SICAM AK SICAM AK
Progessing and communication
Processing and communication
supply
supply
supply
Master control element
Power
Power
Power
Protocol element(s)
Protocol element(s)
Protocol element(s)
Protocol element(s)
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
element
element
optional optional
supply
supply
supply
supply
Power
Power
Power
Power
optional optional optional optional
Process Process
SICAM AK
SICAM TM
supply
supply
Peripherial element
Power
Power
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
optional
supply
supply
Power
Power
Process
optional optional
Process
The peripheral elements deliver over the Ax 1703 peripheral bus System elements in SICAM AK
tperiodical information, Master control element
tmessages with process information, and Module Designation
tmessages with system information (e.g., diagnostic CP-2010 / CPC25 System functions, processing
information) and communication
Power supply
SICAM AK The mounting racks CM-2832, CM-2835 and CM-2833 are to be
equipped with 80W power supplies of the following types:
Processing and communication
Designation
supply
supply
Power
Power
Master control element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
Periphal element
(DC 24 60 V)
element
optional
PS-5622 Power supply
(DC 110 220 V, AC 230 V)
supply
supply
Power
Power
optional optional
Process
14
1 2 3 4 5 6
Peripheral elements
Ax 1703 peripheral
bus (electrical) 16
Communication 16 Mbps patch cable,
with other length up to 3 m
automation units
Ax 1703 peripheral
bus (electrical)
16 Mbps USB cable, 15
length up to 3 m
max. 8 I/O-modules
Note: PE-6410
all in all up to 16 peripheral elements PS-663x
Fig. 6.3-43: SICAM TM system architecture: connection of up to 16 peripheral elements via bus interface (electrical) 6
Function packages
Telecontrol System services
The function package Telecontrol includes the following System Services is a function package providing general
functions: functions and basic services in an automation unit, which are
tProcess input and output on peripheral elements required by other function packages:
tCommunication with other automation units tCommunication with the engineering system
tProtocol elements tData ow control
tAutomatic data ow routing tAddressing
tData storage tTime management
tPriority control tGeneral interrogation
tRedundant communication routes tSelf-test
tCommunication within the automation unit tFailure
tProtocol element control and return information tDiagnostic and signaling
tAutonomy
Automation
The function package Automation includes the following System concept SICAM TM
functions: SICAM TM is designed especially for easy installation and pow-
tProcess input and output on peripheral elements erful application. Due to consequent development it ts opti-
tTelecontrol functions mally both for automation and telecontrol systems (g. 6.3-43).
Treatment for commands according to
IEC 60870-5-101 / 104 An essential feature of SICAM TM is its efcient and simple way
Change monitoring and generation of messages of interfacing to the process signals. This is accomplished by
with time tag so-called I / O modules boasting a robust housing, reliable con-
tOpen / Closed-loop control function tacting, and sound electronics. The I / O modules are arranged
side-by-side. Contact between them is established as soon as
they engage with one another, without requiring any further
manual intervention. Even so, it is still possible to replace every
Product overview
Master control unit IEC 60870-5-104
Module Designation
CP-6014 / CPCX65 Processing and communication
6 DI-6101
(2 8, DC 24-60 V)
Binary input
(28, DC 110 / 220 V)
IEC 60870-5-101
unbalanced master
of the SICAM Ax,
SICAM TM, AK, BC Master station
DO-6200 Binary output transistor
(2 8, DC 24-60 V) or third party
CP-6020 CP-6020
6
CP-6020 CP-6020
Fig. 6.3-48: SICAM MIC conguration simple dial-up trafc Fig. 6.3-49: SICAM MIC conguration multi-master dial-up trafc
The master control modules are: tClosed-loop control for arc suppression coils (option)
tCP-6020 master control module (V.28 / 8 modules) tOperation cycle counter
tCP-6040 master control module (ET10TX / V.28 / 8 modules) tCalculation of r.m.s. values of currents and voltages, active
and reactive power
Conguration
The following gures show the congurations of multi-point Local control panel for feeder operation
trafc (g. 6.3-47), of dial-up trafc (g. 6.3-48), of multimaster The bay control unit comes in two mechanical sizes (g. 6.3-53):
dial-up trafc (g. 6.3-49), of LAN / WAN (g. 6.3-50) and of SICAM BC is designed for compact feeders (typical in distribu-
GPRS (g. 6.3-51). tion); SICAM BC is the modular version for larger amounts of I / O
(typical in transmission).
Bay control units
The Bay Control Unit (BCU) is the linking member between the Both versions are based on the same system architecture and
station control level and the primary system, and is integrated in use the same modules. They are ruggedised for use as near as
the feeder-related local control cubicle. possible to the primary equipment featuring the highest EMC
and a broad temperature range, and the I / O-modules are
It is therefore designed for rough electric and thermal ambient designed for direct interfacing of all signals from the process
conditions and is based on the SICAM BC bay controller. without any interposing level (e.g., interposing relays, mea-
suring transducers, etc.). This means a peripheral voltage of up
The bay control unit acquires all feeder-relevant process data to DC 220 V or direct interfacing of transformers with 1 A to 6 A
and time tags them at a resolution of 1 ms. All feeder related or AC 110 / 220 V.
functions are executed autonomous in the bay control unit:
tInterlocking Architecture of SICAM BC
tSynchrocheck A SICAM BC forms an automation unit of the SICAM system
tAutomatic voltage regulation by control of transformer onload family and consists of the following elements:
tap changer (option)
Router Corporate
network
Internet
s
Base Packet
station
controller
Router
(BSC) Tele
p hon Central station
e ca
ll s
PSTN
Network
Master station
Substation controller (MSC)
General features
tPower supply is available in DC 110220 V / AC 230 V (80 W) or
DC 2460 V (80 W) and a second power supply can be added
for redundancy
tThe signal acquisition has a 1 ms resolution of real-time
stamping.
As shown in the picture, the bay control units are designed for
rough electric and thermal environments.
Supply
Power
Master Control Element
Processing Element
Periphal Element
Periphal Element
Operation and Display Panel
combined both with the compact and the modular version of the
bay controller. It can be directly attached to the SICAM BC, or be
used separated with only two connecting cables (up to 3 m). The
integrated and divided frame allows for either surface mounting,
Supply
without the need for a big cut-out in the door, or for ush Power
Element
Element
Periphal
Periphal
6.3.7 SICAM EMIC a Member of the Thanks to its node functionality, SICAM EMIC has many different
potential applications. SICAM EMIC can be used as an ordinary
Proven SICAM Family
telecontrol substation with any kind of communication to a
With growing pressure on costs in virtually all processes, there is control center. If SICAM EMIC doesnt offer adequate signal
an increasing need to also automate smaller stations to make scope, additional SICAM EMIC systems can be connected. Freely
better and more reliable use of existing equipment. Modern, programmable application programs for local control functions
high-performance automation systems allow the integration of complete the all-round versatility of the SICAM EMIC.
smaller stations to provide universal and reliable management of
complex processes. But smaller stations are also being equipped Highly exible options for communication
with greater functionality because of the increased demand for to the control center
more information. tMulti-point trafc
External data transmission equipment can be connected
From straightforward monitoring activities to control functions via the V.28 interface for multi-point trafc transmission.
and the integration of additional equipment, modern systems tDial-up trafc
need to offer a wide range of functionality. A wide range of connection-oriented trans-mission media
(analog, ISDN, GSM, TETRA) are supported as standard for
Flexible use of SICAM EMIC dial-up trafc as well.
As the logical consequence of these demands, SICAM EMIC tLAN/WAN
(Terminal Module SICAM enhanced microcontrol) represents the IEC 60870-5-104/DNPi communication based on Ethernet
expansion of the provenproduct SICAM MIC. SICAM EMIC is a TCP/IP is used for communication via LAN/WAN networks.
low-cost, exible and modular telecontrol station, and is part of
the proven SICAM AK, TM, BC, EMIC and MIC automation family. SICAM EMIC the system in detail
The hardware consists of a master control element and various Functions of the master control element:
I/O modules, and is designed for DIN railmounting. The proven tCentral processing functions
I/O modules can be used and tted on all products in the tStoring of the parameters and the rmware on a ash card
SICAM AK, TM, BC, EMIC and MIC family. tInterfacing and supplying of the I/O modules
6 The master control element is used for interfacing and supplying
t3 communication interfaces, with different individual
communication protocols (IEC 60870-5-101, 103, 104,
the I/O modules and provides three communication interfaces Modbus, DNP 3.0, other protocols on request)
(1 Ethernet and 2 serial) to meet a wide range of require-
ments. Complete exibility is ensured here as well, becausedif-
ferent communication protocols can be allocatedfreely. The
option of automation functions roundsout the range of function-
ality of the SICAM EMIC.
Control system
IEC 60870-5-104
... ...
e.g. Modbus
SICAM EMIC
IEC 60870-5-103 /
...
IEC 60870-5-101
IEC 60870-5-103
IED
Modbus
...
SICAM EMIC
...
...
6.4 Power Quality and tioning as required even when small disturbances occur. In
practice, the voltage can never be perfect.
Measurements
Electrical supply is one of the most essential basic services
supporting an industrial society. Electricity consumers require
6.4.1 Introduction this basic service:
tTo be available all the time (i.e. a high level of reliability)
tTo enable all consumers electrical equipment to work safely
Power quality and satisfactorily (i.e. a high level of power quality).
To avoid the high cost of equipment failures, all customers must Everybody is now aware of the effects of poor power quality but
6 make sure that they obtain an electricity supply of satisfactory
quality, and that their electrical equipment is capable of func-
few really have it under control. The levels of power quality
disturbances need to be monitored weekly, sometimes even
Vo
lt ag
ed
ist
ur
ba
nc
es
Cu
rre
nt
dis
tu
rb
an
ce
s
Fig. 6.4-1: Power quality monitoring provides value to everyone to the local utility, to the consumer, to the local economy and to the
environment
Harmonic
Reactive power
Flicker
Unbalance
Harmonic
predistortion
Voltage dips/swells
Voltage variations
Interruption
Fig. 6.4-2: Utility and industries, both are responsible for voltage quality
three minutes
power in a specic area and maintain power to your area t-PTTPGDPNQVUFSDPOUSPMMFS
Momentary interruptions lasting t"DDJEFOUT
BDUTPGOBUVSF
FUD memory
0 0.1 0.2 time (s) 0.4 0.5
from a half second to 3 seconds t'VTFT
BDUJPOTCZBQSPUFDUJPO t1SPEVDUJPOMPTTFTPSEBNBHF
Temporary interruptions lasting function, e.g. automatic recloser
from 3 seconds to 1 minute cycle
-POHUFSNJOUFSSVQUJPOTMBTUJOH
longer than 1 minute
short voltage dip Voltage dip / sag or swell: t4UBSUVQPSTIVUEPXOPGWFSZ t.FNPSZMPTT
EBUBFSSPST
EJNPS
Any short-term (half cycle to large item of consumer bright lights, shrinking display
Voltage signal
6
reduced voltage level
Variation in the voltage level above change due to normal changing due to undervoltage or even
Voltage signal
or below the nominal voltage under load situations overheating and / or damage to
normal operating conditions equipment due to overvoltage
0 0.1 0.2 time (s) 0.4 0.5
t3FEVDFEFGmDJFODZPSMJGFPG
electrical equipment
Transients
Transient: t6UJMJUZTXJUDIJOHPQFSBUJPOT
t1SPDFTTJOHFSSPST
A transient is a sudden change in starting and stopping heavy t%BUBMPTT
voltage up to several thousand equipment, elevators, welding t-PDLVQPGTFOTJUJWFFRVJQNFOU
volts. It may be of the impulsive or equipment static discharges, and t#VSOFEDJSDVJUCPBSET
oscillatory type (also termed lightning
impulse, surge, or spike)
Notch:
This is a disturbance of opposite
polarity from the waveform
PQ
Description Hardware Measurements
application
6
System
System
improvement
Project Dening PQ installation Start
Evaluation and/or
phases objectives and measuring
counter-
conguration
measures
Standards are different, there are also many other regional or national
The purpose of power quality indexes and measurement objec- recommendations, mainly described in Grid Codes, dening
UJWFTJTUPDIBSBDUFSJ[FQPXFSTZTUFNEJTUVSCBODFMFWFMT4VDI specic or adapted limit values.
indexes may be dened as voltage characteristics and may be
stipulated in a Grid Code that applies to electrical system inter- These local standards are normally the result of practical voltage
faces. Power quality Grid Codes make use of existing standards quality measurement campaigns or the system experience,
or guidelines dening voltage and current indexes to be applied which are mostly acquired through a permanent and deep
to interfaces in low, medium, or high-voltage systems, for electrical system behavior know-how. Measuring according to
example, EN 50160. This standard denes and describes the EN 50160 is, however, only part of the power quality measure-
main characteristics of the voltage at the system operators ment process. Another important standard for power quality
TVQQMZUFSNJOBMTJOQVCMJD-7BOE.7QPXFSEJTUSJCVUJPOTZTUFNT measurement is IEC 61000-4-30, which denes the measure-
Indexes for HV-EHV will also be described in the new edition of ment methodology.
&/4JODFFMFDUSJDBMTZTUFNTBNPOHSFHJPOTBOEDPVOUSJFT
IEC 61000-4-30
Measurement of voltage quality
Fig. 6.4-4: Overview of international and national standards for Fig. 6.4-5: Illustration of a voltage dip and a short supply
power quality interruption, classied according to EN 50160; VN
nominal voltage of the supply system (r.m.s.), VA
amplitude of the supply voltage, V(r.m.s.) the actual r.m.s.
value of the supply voltage
6 Voltage magnitude
variations
3BQJEWPMUBHFDIBOHFT
-7
.7GPSPGXFFL
NFBO
minutes r.m.s. values (g. 6.4-5)
-7OPSNBMJOGSFRVFOUMZPlt 1 for
7
11
5
3.5
9
15
1.5
0.5
4
6 24
1
0.5
95 % of week
MV: 4 % normal 6 % infrequently Plt 1 for 13 3 21 0.5
95 % of week 17 2
4VQQMZWPMUBHFEJQT .BKPSJUZEVSBUJPOT
EFQUI-PDBMMZ 19 1.5
MJNJUFEEJQTDBVTFECZMPBETXJUDIJOHPO-7
10 50 %, MV: 10 15 % 23 1.5
4*$".1JTBWBJMBCMFXJUINPVOUJOHEJNFOTJPOPGNN
mm and can be ordered with or without display.
L1 L2 L3 N L1 L2 L3
W B2 B1
N/- N/+
DC: 24-250 V
AC:100-230 V
L1 k l
L2 k l
RS485
L3 k l Master
N station
PE RS232
Parameterization
Other
SICAM P SICAM P SICAM P SICAM P SICAM P
Application eld
The input modules can be used for acquisition, display and devices
further processing of external signals with a measurement range Device without
display
PGoN"%$
Fig. 6.4-10: SICAM P with PROFIBUS-DP, MODUBS and
Measured values can be shown together with their units on the IEC 60870-5-103
display. Transmission of the current status of a measured signal
UPBDFOUSBMNBTUFSTUBUJPOWJB130'*#64%17
.0%#64
356"4$**PS*&$JTBMTPQPTTJCMF 'JHTIPXTBOFYBNQMFPGFYUFOEFE*0GPSWBSJPVTBQQMJDB-
tions.
In addition, mean values of all external analog channels as well
as states of digital channels can be recorded and saved into the Application example (g. 6.4-10)
memory. 4*$".1BTBQBOFMNPVOUFEPSTOBQPONPVOUFEEFWJDFGPSVTF
on a process bus.
All recorded quantities and binary state information can be read
PVUwBOEFWBMVBUFEXJUIUIFDPOmHVSBUJPOTPGUXBSF4*$".1 /FUXPSLMJOLJOHJTQPTTJCMFXJUIUIFJOUFHSBUFE34QPSUXJUI
Manager. UIFTUBOEBSE130'*#64%1BOE.0%#64356"4$**DPNNVOJDB-
UJPOQSPUPDPM'VSUIFSNPSF
JUJTBMTPQPTTJCMFUPJOUFHSBUF
0VUQVUNPEVMFTDBOCFVTFEGPSDPOWFSTJPOPGBOZFMFDUSJDBM 4*$".1JOUPDPNNVOJDBUJPOOFUXPSLTXJUI*&$
RVBOUJUZ DVSSFOU
WPMUBHF
FUD
JOUPBooN"%$PVUQVU BTTUBOEBSEQSPUPDPM5IBUBMMPXTTFWFSBM4*$".1NFBTVSFE
signal, generation of impulses for metering, indication of limit parameters to be indicated, evaluated and processed at a central
value violations, as well as for switching operations. master station.
Device type
tTop-hat rail mounted device
t1MBTUJDDBTFNNNNNN
JODI 8)%
t%FHSFFPGQSPUFDUJPO*1
Fig. 6.4-12: SICAM T electrical measurement transducer
Input and output circuits
t4 inputs for alternating voltage measurements
t3 inputs for alternating current measurements up to 10 A tActive, reactive and apparent power
continuous tActive, reactive and apparent energy
tPQUJPOBM%$BOBMPHPVUQVUTGSFFMZDPOmHVSBCMF tPower frequency
%JSFDUDVSSFOUTN"UPN"
N"UPN" tPhase angle
and 20 mA to 20 mA tPower factor and active power factor
% JSFDUWPMUBHFT7UP7BOEo7UP7 tVoltage and current unbalance
tindividually programmable binary outputs. Mean value of the 3 phase voltages: Vavg
6 Signalization LEDs
Mean value of the 3 phase currents: Iavg
V, I V, I V, I
Alarms, measurements
and indications
Ethernet/MODBUS TCP or
Serial: MODBUS RTU or IEC 60870-5-103 (optional)
IEC 61850 (7KG9662)
Main features
t%FTJHODPNQBDUBOESPCVTUGPSnFYJCMFBQQMJDBUJPOJO
industrial and utility environments
tConnections in 1-phase systems, in 3-wire and 4-wire systems
tApplications: exible for power utilities, industrial and
commercial sectors applications
tMeasurements: up to 60 measured or calculated values
available
t5FNQFSBUVSFSBOHFo$UP$oUP'
6
tHigh accuracy: typically 0.1 % for voltage and current at rated
input IEC 60688, and 0,2s acc. to IEC 62053-21
tHigh EMC immunity: according to standards EN 61000-6-2 and
EN 61000-6-4 for the EMC directives, and with the standard
EN 61010-1 for the low-voltage directive
t6-$FSUmDBUJPO5IJTQSPEVDUJT6-DFSUJmFEUP4UBOEBSE
6-
8JUI4*$".2
UIFRVBMJUZPGUIFQPXFSTVQQMZTZTUFNDBOCF
continuously monitored. This can be based on the quality criteria
dened in the European electricity supply system quality stan-
dard EN 50160 or other assessment criteria. Moreover, data that
are above or below the dened threshold values are stored and
can thus be used for a meaningful overall analysis. It provides
information that allows to see the whole electrical healthy of the
power system! Fig. 6.4-15: SICAM Q80 the quality recorder
Features
t4VJUBCMFGPSNPOJUPSJOHTJOHMFQIBTF
BOEXJSFQPXFS Central 1 Central 2
systems (up to 1,000 Vrms)
t4 voltage, 4 current, or 8 voltage measuring channels
t4UBOEBSECJOBSZJOQVUT
CJOBSZPVUQVUT
t4BNQMJOHSBUFL)[GPSOFUXPSLBOBMZTJT
tMeasurement accuracy 0.1 % of the range
tHigh local storage capability: removable compact ash
TUBOEBSEEFMJWFSZ(#
NTP synchronization
tEnhanced data compression process (power quality data)
Ethernet
tAutomatic data transfer
tAutomatic comparison and reporting of the power quality
prole according to EN 50160 or your local standards Substation 1 Substation 2
tAutomatic notication in case of a fault or violations by e-mail,
Ethernet Ethernet
4.4
BOEGBY
tExport functions
tEthernet and modem communication interfaces for
parameterization, remote monitoring and polling
t(14%$'*3*(#BOE/51GPSTZODISPOJ[BUJPO
tNetwork trigger system GPS synchronization GPS synchronization
t4JNQMFPQFSBUJPO
DPNQBDUBOESPCVTUEFTJHO
Function overview
t*OUFHSBUJPOUP4*1305&$GBNJMZ
Consistent HW concept
Variety of extension modules
%*(4*BTDPOmHVSBUJPOUPPM Fig. 6.4-17: Generator and motor protection device 7KE85
Choice of functionality via functional points
t%JTUVSCBODFSFDPSEFSDMBTT4GPSBQQMJDBUJPOTJOTVCTUBUJPOTBU
MV / HV / EHV level and in power plants
'BTU4DBOSFDPSEFS
4MPX4DBOSFDPSEFS
$POUJOVPVTSFDPSEFS
t1PXFSRVBMJUZSFDPSEFSDMBTT4BDDPSEJOHUP&/GPS
analysis and recording / archiving of power quality problems of
all power applications
6 tEvent recorder for binary signals for observation of the status
of various primary components like circuit-breakers,
disconnectors, etc.
t1.6BDDPSEJOHUP*&&&$
tCommunication with IEC 61850
t4BNQMJOHGSFRVFODJFTQSPHSBNNBCMFCFUXFFOL)[BOE,)[
t5JNFTZODISPOJ[BUJPOWJB*3*(#%$'4/51
tInternal mass storage:
(#ZUFSJOHCVGGFS
) FBMUINPOJUPSJOH-PTTMFTTEBUBDPNQSFTTJPO
t'MFYJCMFSPVUJOH Fig. 6.4-18: Expansion module
Any assignment of a measured value to each recorder
'SFFDPNCJOBUJPOPGNFBTVSJOHHSPVQTGPSQPXFSDBMDVMBUJPO
t3FDPSEFERVBMJUZCJUT
Quality statement for each recorded value + monitoring of
DIBOOFMRVBMJUZJO4*(3"PS4*$".12"OBMZ[FS
t3FDPSEJOHPGBOEUSJHHFSJOHPO(004&WBMVFT
t$SFBUJOHPGnFYJCMFUSJHHFSDPOEJUJPOTXJUI$'$ $POUJOVPVT
'VODUJPO$IBSU
'JHTIPXTUIFQSJODJQMF"NFBTVSFNFOUPGDVSSFOUBOE V2
voltage with regard to amplitude and phase is performed with 2
1.6TPOTFMFDUFETVCTUBUJPOTPGUIFUSBOTNJTTJPOTZTUFN%VFUP
the high-precision time stamps assigned to these phasor quanti-
Substation 4
UJFTCZUIF1.6
UIFTFNFBTVSFEWBMVFTDBOCFEJTQMBZFE
together at a central analysis point. This provides a good over-
view of the condition of the system stability, and enables the
Substation 2
display of dynamic processes, e.g., power swings.
Substation 3
V3
3
Region 1 Region 2
User interface 1 User interface 2
6
PDC 2
PDC 1
IEEE C37.118
Fig. 6.4-21: Connection of 3 Phasor Measurement Units with two Phasor Data Concentrators (PDCs) SIGUARD PDP
QB1 QB2
QA1 52
MP
V4
V-1ph 1 FG PMU
QB9
I1 V-1ph
MP V-3ph
I2
I-3ph 1
I3 I-3ph
I4
Phasor calculation for Comm.
V1 V and I IEEE C37.118
MP
V2
V-3ph 1
V3
6 Line
FG
MP
Function group
Measuring point
PMU Phasor Measurement Unit
Solution 2:
Solution 1:
Evaluated with:
Evaluated with:
SICAM PQS
SICAM PQS
PQ Analyzer
PQ Analyzer
7KE85
7KE85
Fig. 6.4-23: Monitoring the power feed Fig. 6.4-24: Monitoring the infeed
220 kV
Solution:
7KE85
Evaluated with:
SICAM PQS
PQ Analyzer 6
110 kV
7KE85
20 kV
Solution: 20 kV
7KE85
Evaluated with:
SICAM PQS
PQ Analyzer
400 V
SICAM PQ Analyzer
Extended
Complete documentation
SIPROTEC Others SICAM R 7KE85 Others SICAM Q80 SICAM P855 Others SICAM P/P850 SICAM T Others
6 Fig. 6.4-27: SICAM PQS One System for all Power Quality Data
SICAM PQS fault record and power quality analysis software The power quality analysis is based on the applicable standards
5IF4*$".124TPGUXBSFQBDLBHFJTTVJUBCMFGPSVTFJOQFSTPOBM EN 50160 and IEC 61000 or on any user-dened Grid Code, and
DPNQVUFSTQSPWJEFEXJUIUIFPQFSBUJOHTZTUFNT.48JOEPXT uses an effective reporting tool that provides automatic informa-
It is used for remote transmission IEC61850, evaluation and tion about any deviations from the dened limit value.
archiving of the data received from 7KE85, digital protection
EFWJDFTBTXFMMBTGSPN4*$".2QPXFSRVBMJUZSFDPSEFST5IF The data transmission is preferably effected via WAN (Wide Area
program is used to setup the system conguration and to param- /FUXPSL
PSUFMFQIPOFOFUXPSL%FQFOEJOHPOUIFQPXFSTZTUFN
FUFSJ[FUIF,&BOE4*$".2VOJUTJOTUBMMFEJOUIFmFME*U XIJDIIBTUPCFNPOJUPSFEUIF4*$".124TZTUFNDBOCFBMJHOFE
enables fully-automated data transmission of all recorded data BDDPSEJOHMZ5IFNPEVMBSTUSVDUVSFPG4*$".124QFSNJUTUIFVTF
(fault records, events, mean values) from the acquisition units to of individual functional packages perfectly matched the require-
POFPSNPSFOFUXPSLFE4*$".124FWBMVBUJPOTUBUJPOTUIF NFOUT'VSUIFSNPSFUIF4*$".124DBOBMTPFBTJMZFYQBOEUP
received data can then be immediately displayed and evaluated create a station control system for combined applications. The
and benchmarked according to quality standards so called Grid program fully supports server / client system architecture.
Codes (g. 6.4-27).
Highlights
4*$".124PGGFSTBWBSJFUZPGBQQMJDBUJPOTBOEFWBMVBUJPOUPPMT tVendor-neutral integration of fault recorders, protection
enabling the operator to carry out detailed fault record analysis devices and power quality equipment via standard protocols or
by using time diagrams with curve proles, vector diagrams etc. $0.53"%&12%*'JNQPSU
The individual diagrams can, of course, be adjusted to individual tQuick overview of system quality through the chronological
requirements with the help of variable scaling and zoom func- display of the PQ index
tions. The different quantities measured can be immediately t4FBNMFTTEPDVNFOUBUJPOPGQPXFSTZTUFNRVBMJUZ
calculated by marking a specic point in a diagram with the tAutomatic notication in case of violation of thresholds of a
cursor (impedance, reactance, active and reactive power, har- predened Grid Code.
monics, peak value, r.m.s. value, symmetry, etc.). tAutomatic and precise fault location with parallel line
compensation
Additionally automatic distance to fault calculation and report t4USVDUVSFE
DPOTJTUFOUBOEQFSNBOFOUEBUBEPDVNFOUBUJPO
generation will be executed after an event was recognized in the and archiving
power supply system. tAutomatic generation of cyclic power quality report
Incident explorer
Incident explorer is the central navigation interface of
4*$".124*UBDUTBTBDPDLQJUGPSUIFVTFSBOEEFMJWFSTBTUSVD-
tured overview of events throughout the whole system. It
visualizes the contents of the entire power quality archive with
fault records, fault locating reports, post-disturbance review
reports, power quality reports, and the ability for manual fault
location and manual import of comtrade les. The comtrade
viewer, which is part of the scope of delivery, makes it possible
to analyze the fault (g. 6.4-28).
PQ inspector
The PQ inspector is a supplementary module that shows at a
glance the power quality condition of the entire network for a
selected period. This allows for quick identication of the origin
and type of violation. Another feature of PQ inspector is the
6
option of generating power quality reports through step-by-step
user prompting and on the basis (g. 6.4-29).
PQ explorer
PQ explorer makes detailed analyses possible based on com-
paring the measured power quality data directly with the Grid
Codes. This comparison and the large number of different
diagrams available for displaying power quality data make it
possible to understand the nature and extent of a power quality
violation very quickly and to initiate adequate (g. 6.4-30).
Report browser
3FQPSUTBSFDSFBUFEBVUPNBUJDBMMZBUXFFLMZ
NPOUIMZ
BOE
annual intervals and in the event of a violation of the Grid Code.
The report browser shows an overview of these automatically
generated reports in selected time ranges and the assessment of
the results. The individual reports can be opened directly in the
report browser (g. 6.4-31).
C
Ca
e
bl
bl
e
Ca
B
Field 31 Field 32
Station 3
SDS
Internet / Intranet 6
Fig. 6.4-33: SICAM PQS V7.01 / SICAM Diamond V4.0 HF1 goes Web via SICAM Diamond
5IJTJTXIFSF4*(6"3%1%1 1IBTPS%BUB1SPDFTTPS
DPNFTJO -300
This system for network monitoring using synchrophasors helps
6 with fast appraisal of the current system situation. Power swings
and transients are indicated without delay to help the control
-400
center personnel nd the causes and take countermeasures. Fig. 6.4-32: Voltage vector of two measurement points in the
network
Highlights
tPhasor data processor per IEEE C37.118 standard
t2 selectable monitoring modes: t1PXFS4XJOH3FDPHOJUJPO
0OMJOFNPEF "MMNFBTVSFEWBMVFTGSPN1.6TDBOCFEJTQMBZFEBOE
0GnJOFNPEF BOBMZTJTPGQBTUFWFOUT
monitored with easy-to-con gure phasor diagrams and time
tVector view or time chart view can be selected for all p hasors charts. Any power swings that occur are quickly and reliably
tCalculation and display of the power system status curve detected. The zone being monitored can be exibly adjusted
t4ZTUFNNPOJUPSJOH
JODMDPNNVOJDBUJPOMJOLTBOE1.6TUBUVT to the current situation in terms of time, geography, and
tGeographic overview (based on Google Earth) content.
t#BTJTGPSGBTUSFQPSUJOHBGUFSGBVMUT tEvaluation of the damping of power swings
t'MFYJCMFBOBMZTJTXJUIGPSNVMBFEJUPSGPSDBMDVMBUJPOTCBTFEPO 6TJOHUIFGVODUJPOi1PXFS4XJOH3FDPHOJUJPOw BWBJMBCMFBT
measured values from Version V2.1), an incipient power swing is detected and
t-JNJUWBMVFTUIBUDBOCFDIBOHFEPOMJOF UIFBQQSPQSJBUFEBNQJOHEFUFSNJOFE%FUFDUJPOPGBQPXFS
t3VOTVOEFS8JOEPXT91BOE8JOEPXT
BTBQVSF1%$ swing and, if applicable, its insufcient or non-existent
XJUIPVUVTFSJOUFSGBDF
BMTPVOEFS8JOEPXT4FSWFS damping is signaled (alarm list).
tMonitoring of the load on transmission corridors often as necessary. This makes dynamic events transparent,
The voltage-stability curve is especially suitable for displaying BOESFQPSUTDBOCFRVJDLMZBOEQSFDJTFMZDPNQJMFE4JNQMZDPQZ
the instantaneous load on a transmission corridor. The UIFJOGPSNBUJWFEJBHSBNTGSPN4*(6"3%1%1JOUPZPVSSFQPSUT
currently measured operating point is shown on the work tAlarming on limit value violation with an alarm list and color
curve of the line (voltage as a function of the transmitted change in the geographic network overview map
power). In this way, the remaining reserve can be shown at This allows you to locate the position and cause of the
BOZUJNF5IJTSFRVJSFT1.6TBUCPUIFOETPGUIFMJOF disturbance quickly. This function is also available for
analyzing the archive.
t%JTQMBZPGUIFQPXFSTZTUFNTUBUVTBTBDIBSBDUFSJTUJDWBMVFGPS
MlhM to NbgH
the stability of the power system
kV 500
%VFUPUIFDPOTUBOUBWBJMBCJMJUZPGUIFQPXFSTZTUFNTUBUVT
curve in the upper part of the screen, the operator is
400
constantly informed about trends in system dynamics and any
remaining reserves. This curve shows a weighted average of
300 the distances of all measured values, to their limit values.
200
100
0
-1.50 -1.00 -0.50 0.00 0.50 1.00 1.50 For further information:
GW www.siemens.com/powerquality
6
Fig. 6.4-33: Voltage stability curve