70052-0180-01

PRODUCT OPTION 09/2006

ION7300 Series Revenue Meter


ThisdocumentprovidesanoverviewofthePowerLogicION7300seriesrevenue
meter.

In This Document

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
RevenueMeterModels ................................................. 2
RevenueMeterInstallation.............................................. 2
TerminalCoverInstallation(OFGEMmeters) ............................. 2

Differences Between Standard and Revenue Models . . . . . . . . . . . . . . . . . . . 3


RevenueMeterEnergyRegisterLabels ................................... 3
AdditionalRevenueMeteringModules(RMICANmeters) .................. 3
SecurityMechanisms................................................... 3
AntiTamperSeals ..................................................... 4
PasswordProtectedMin/MaxRegisterResets ............................. 5
HardwarebasedSecurity ............................................... 5

Configuring the Revenue Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6


BeforeDisassemblingtheMeter ......................................... 6
InsertingtheKey ...................................................... 6
CT&PTSelection ..................................................... 7

Additional Information
ION7300SeriesInstallationGuide
ION7300SeriesUsersGuide

Electrical equipment should be


installed, operated, serviced, and
maintained only by qualified
personnel. No responsibility is
assumed by Schneider Electric for
any consequences arising out of
the use of this material.
2006 Schneider Electric.
All rights reserved.
www.powerlogic.com
Introduction ION7300 Series Revenue Meter Option

Introduction
Arevenuemeterprovidesmeasurementsthatpassindustrystandardsfor
accuracyoveradefinedrangeofoperatingconditions.Theyalsoensureadequate
protectionagainstunauthorizedalterationofthesemeasuredquantities.
Internationalandnationalstandardsdefineindustryacceptedaccuracylimits
whilenationalandutilitybasedstandardsregulateprotectionagainst
unauthorizedalterationofmeasurements.

Revenue Meter Models


FourrevenuemetermodelsareavailablefortheION7300series;eachmodelis
designatedbythecertificationitholds.

Security Anti-tamper
Model Certification Achievement Current Inputs Hardware Lock
Option Sealing Kit

Complies with the accuracy requirements of


RMANSI Rated for 0.1 Amps
2 the ANSI C12.16 Revenue Metering Enabled Provided
(unsealed) to 10 Amps AC
Standard

RMICAN Rated for 0.1 Amps


3 Canadian Revenue Metering Standards Enabled Provided
(unsealed) to 10 Amps AC

RMICAN Rated for 0.1 Amps


4 Canadian Revenue Metering Standards Enabled Factory Installed
(sealed) to 10 Amps AC

Rated for 0.1 Amps


6 OFGEM1 IEC 60687 Class 0.5 (for 5 Amps nominal)
to 10 Amps AC
Enabled Provided

1
The OFGEM option is only available in the United Kingdom. It comes standard with a terminal cover.

Revenue Meter Installation


SeetheION7300SeriesInstallationGuide(includedwithyourmeter)for
instructions.

Terminal Cover Installation (OFGEM meters)


SeetheTerminalCoverRetrofitInstallationInstructions(includedwithyourmeter).

Page 2 2006 Schneider Electric. All rights reserved.


ION7300 Series Revenue Meter Option Differences Between Standard and Revenue Models

Differences Between Standard and Revenue Models


AllION7300seriesrevenuemetershavedifferentenergyoutputregisterlabelsin
theirmeterfirmware;somealsohaveadditionalmodulesforrevenuecalculations.

Revenue Meter Energy Register Labels


Therevenueandnonrevenuemetersdifferinhowtheylabelenergyflow.
Power Provider/Utility Power Consumer

LINE LOAD

Delivered Imported

Received Exported

Revenue Model Standard Model

TheenergylabelsforkVAh,kVARhandkWharedifferentfromthenonrevenue
devicesasfollows:

Revenue Meter Non-revenue Meter

Delivered Imported

Received Exported

Total = Delivered + Received Total = Imported + Exported

Net = Delivered Received Net = Imported Exported

Forexample,themetersoutputregisterkVARhtotwillbekVARhdel+recinthe
revenuemetermodel.

Additional Revenue Metering Modules (RMICAN meters)


ThereareadditionalmodulesincorporatedintothetemplateofION7300series
RMICANrevenuemeters.Someofthesemodulesareusedinthecalculationand
loggingofbothV2handI2h(usedfortransformerandlinelosscompensation).

Security Mechanisms
TomeetGovernmentregulationsandUtilitysecurityrequirements,therevenue
meterincorporatesthreetypesofsecuritysystems:
traditionalantitampermechanicalsealonthemeterbaseunit

2006 Schneider Electric. All rights reserved. Page 3


Security Mechanisms ION7300 Series Revenue Meter Option

passwordbasedsecuritysystemthatpermitspasswordprotectedminimum/
maximumresets(forexample,SlidingWindowDemandreset)
hardwarebasedsecuritysystemthatpreventsmodificationofrevenue
quantitiesafterthemeterissealed

Anti-Tamper Seals
TheION7300seriesrevenuemeterincorporatesoneortwosealingcansthrough
whichtraditionallead/wiresealscanbeinserted.Thesesealseffectivelyprevent
unauthorizedpersonnelfromgainingaccesstometerinternals.Sealsareprovided
withthemeterandareinstalledasfollows:
1. Removethescrewfromoneoftherearpanelcornerholes.Placethesealing
canovertheholeandinsertthescrewbackintothehole,throughthesealing
can.

Use any of the four corner


Back of Meter
holes (see arrows).

2. Inserttheballbearingintothesealingcanovertheheadofthescrew.Installthe
wirethroughthetwoholesinthesealingcan.

3. Twistthewireandcrimptheleadsealingtabontothewire.

Page 4 2006 Schneider Electric. All rights reserved.


ION7300 Series Revenue Meter Option Security Mechanisms

Password Protected Min/Max Register Resets


Themeterfrontpanelincorporatesapasswordthatmustbeenteredinorderto
resetanyoftheminimum/maximumorpeakdemandregistervalues.

Hardware-based Security
TheION7300seriesrevenuemeterisequippedwithacomprehensivesecurity
systemthatprovidesprotectionagainstunauthorizedalterationortamperingof
revenuerelatedquantities.ThissecuritysystemlocksallrevenuerelatedION
modules,linksandsetupregisters.Basicmeterconfigurationparametersincluding
voltsmode,PTratio,andCTratioarelocked.Theselocksareenabledatthefactory
forallsealedrevenuemeters.Typicalvaluesthatareprotectedinclude:
kWh,kVARh,kVAhdelivered,received,delrec,del+rec
kW,kVAR,kVAThermalandSlidingWindowdemandminandmaxvalues
DigitalOutputscontrollingtheenergypulsingapplications
AllPowersystemsettings,includingPTanCTratios

Foralistofallthelockedmodulesforyourmeter,seetheIONDeviceTemplates
documentavailablefromthePowerLogicwebsiteatwww.powerlogic.com.

Atwopinjumperblockisusedtoenableanddisablethehardwaresecurityas
describedinthenextsection.

2006 Schneider Electric. All rights reserved. Page 5


Configuring the Revenue Meter ION7300 Series Revenue Meter Option

Configuring the Revenue Meter


Whenenabled,therevenuemetersecuritysystempreventsunauthorized
alterationofrevenuerelatedquantities.Bydefault,allION7300seriesrevenue
metersareshippedfromthefactorywiththesecuritysystemenabled.Youcan
temporarilydisablethesecuritytoconfigureyourrevenuemeter.Thisisdoneby
removingthemetersbackplate,andplacingajumperintothemeter.

Before Disassembling the Meter


Beforeattemptingtoremovethebackplateoftherevenuemeter,ensurethatitis
protectedagainststaticelectricitydischarge.Topreventdamagetotheunit,wear
anantistaticwriststrapatalltimes.

DANGER
During normal operation of an ION7300 series revenue meter, hazardous voltages are present which
can cause severe injury or death. These voltages are present on the terminal strips of the device and
throughout the connected potential transformer (PT), current transformer (CT), status input, relay, and
control power circuits. Installation and servicing should be performed only by qualified, properly trained
personnel.

1. OpenallPTfuses(ordirectvoltageinputfuses)andcloseallCTshorting
blocks.
2. TurnoffallpowertotherevenuemeteranddisconnecttheLineandNeutral(or
DCpower)wiresfromtheSupplyPowerinputs.
3. Disconnectallotherwiring(orpoweroffallothercircuits)thatmaypresent
potentiallyhazardousvoltagetotheunit,suchasconnectionstotherelay
outputs.
4. EnsurethatallcablesstillconnectedtotherevenuemeterareNOTlive.

Inserting the Key


Inordertoconfiguretherevenuemeter,ensurethatadequatesafetyprecautions
havebeenexercisedasabove.

CAUTION
The components inside an ION7300 series revenue meter are extremely sensitive to electrostatic
discharge. To prevent damage to the unit, always wear an anti-static wrist strap when working inside the
unit. Failure to use proper equipment during servicing will void the meters warranty.

1. Removethethumbscrewsandretainerbarsfromtheunit.
2. Removetheantitamperwiresealandfourscrewsontherearpanel.
3. Slideouttherearplateofthedevicetorevealtheunitscircuitboardpanels.
4. LocatethetwopinjumperheaderlabeledJ1onthecommunicationscard.

Page 6 2006 Schneider Electric. All rights reserved.


ION7300 Series Revenue Meter Option Configuring the Revenue Meter

Jumper Block

5. PlacethejumperblockontotheJ1twopinheader(thisdisablesthehardware
basedsecurity).Slidetherearplatebackintothedeviceandreplacethefour
screwsontotherealpanel.Reconnectthemeterspowersupply.
6. Configurethemeter(e.g.Voltsmode,PTandCTratios,Pulseoutputs).
7. Disconnectthemeterspowersupply.
8. Slidetherearplateoutandremovethejumperblockfromthetwopinheaderto
reenablethehardwarebasedsecurity.
9. Replacetherearplateandreapplytheantitamperseals.

CT & PT Selection
ConsultyourlocalRevenueMeteringauthoritiestoobtainstandardsforCTand
PTselectionforrevenuemeteringapplicationsinyourregion.

2006 Schneider Electric. All rights reserved. Page 7