Compressor, 'Wet'Demonstration test of the system is carried-out in order to confirm all necessary
communication link is working as per design and as per logic diagram.
This is to ensure also that all bypass items are confirm removed or remain as required in the test.
Check
Step-1 Line up L/O System & Seal Gas System Vendor JGC OO
Step-6 Lube Oil Pressure Low Alarm & Low Low Trip Test
This activity is
done, 1-day Line-up compressor system as per marked-up P&ID
ahead. Tightness test using I.A, test pressure 4.0 BarG
Pressurise with Nitrogen and purge-out air
Pressure rise up to suction pressure of 4.0 barG
Step-2
Line-up seal gas and Lube oil system.
- Line up L.O & Seal Gas system as per attached marked-up P&ID
Step-3
Introduce IA to Seal Gas System/Motor purge Sys.
Step-4
Clear 50-KA-23-01A/B/C Trip Signals & Create Start Permissive
Step-6
Start Aftercooler and put Pitch control auto mode
Step-7
Start 50-KA-23-01A/BC for 2-hours Mech.run test
'- Start the machine from UCP/DCS
'- Check machine condition and aux. condition are healthy
' -Take data and record them
' -Closely monitor: Suction filter differential and discharge temperature
-Vibrations of: Motor, Gearbox, and Compressors
Step- 8 Stopping :
- Stop using local switch button or UCP,If suction filter differential pressure approaching to 1.0 BarG.
- Stop compressor if any of the vibrations and temperature approaches to high level
Remarks:
The 4-hours mech-run shall be put on trend in DCS and a printed copy shall be obtain for record keeping
as evidence of motor-solo run test.
The following parameters required for trending are: Lube oil pressure and temperature, bearing temperature
motor, gear and compressors vibrations,
357924872.xls/solorun 2/4
Recompressor Main-Motor Solo run Checklist
Check
N.P JGC-INT OO
- Line up L.O & Seal Gas system as per attached marked-up P&ID
Step-6 Main motor start automatically when Rundown tank level ok.
Step- 7 Stopping :
Remarks:
357924872.xls/motorsolo 3/4
FLARE PILOT IGNITION PROCEDURE
Purge pilot gas line for 6-minutes with pilot gas setting
regulator at 1-Bar. : 1.0 Bar
Confirm light-on from ICS and from pilot lamp on indication at panel
Flame detector setting TSH/L = 150 deg. C
Step-6 Repeat Step-4 to Step-5 for other ignition line for other pilot burner
0.4 bar
Ignitor
FG
1.2 bar
IA
Pilot Gas
1.0 bar
357924872.xls/Mech.run 4/4