The F01D2000 cabinet supports the 220 VAC power supply and uses the ETP48150
power system to convert the 220 VAC input into the 48 VDC.
The AC power cable is routed into the cabinet through the bottom of the cable
distribution compartment, and then connected to the mains AC MCB in AC PDU. Then
the cable is connected to the filter in the AC PDU and then routed in the following
two directions:
One channel supplies power to the maintenance sockets in the device
compartment and cable distribution compartment.
The other channel supplies power to the heat exchangers, service devices, and
maintenance illuminators after the AC is converted into the 48 VDC by the ETP48150
power system.

The power shelf of the ETP48150 power system provides two outputs for two battery
groups.

6
The ETP48150 power system converts one AC input into six DC outputs to implement
the DC power distribution. It can be connected to one to two battery groups and use
its monitoring module to manage batteries. The ETP48150 power system can also use
the external sensor transfer box to collect and report the status of sensors (such as
temperature, humidity, door status, and smoke) and standby detected parameters.

7
The ETP48150 power system can be configured with five rectifier modules, which are
connected in parallel for output.
The ETP48150 is a box-type power system that supplies power for -48 V DC
communications equipment. It uses 30 A rectifiers and provides a maximum output
current of 150 A.

8
9
10
The door status sensor uses a magnetic switch as the probe. The door status switch
consists of two parts and is covertly installed. The spring plates of the door status
switch are attracted together through the electromagnetic interaction.
The temperature and humidity sensor monitors the ambient temperature and
humidity of the cabinet in real time.
The smoke sensor is sensitive to the white smoke that is generated in burning. It
probes the smoke and prompts the fire in advance in case of fire.
The sensor transfer box provides various sensor ports to connect the external sensors
to monitoring module, collecting signals from the sensors and forwarding the signals
to the monitoring module.

11
The cabinet has the built-in MDF and ODF. The MDF is used to connect the internal
subscriber cable and the external subscriber cable. The ODF is used to connect the
optical fibers and optical communication devices.

12
When the F01D2000 cabinet is configured with the MA5600T, you can change the
number of broadband subscribers (ADSL2+/VDSL2 subscribers) and narrowband
subscribers (POTS subscribers) according to the actual requirements. Table 3-1, lists
the maximum number of subscribers supported by the F01D2000 cabinet configured
with the MA5600T.

13
When the F01D2000 cabinet is configured with the UA5000, you can change the
number of broadband subscribers (ADSL2+ subscribers) and narrowband subscribers
(POTS subscribers) according to the actual requirements. Table 3-2 lists the maximum
number of subscribers supported by the F01D2000 cabinet configured with the
UA5000.