Model box mech.

classes (EN 1886)


- Casing Strength: D1
- Air Leakage: L1
- Filter Bypass: F9
- Thermal Transmittance: T2
- Thermal Bridging: TB2
TRANE participates in the ECC
programme for Air Handling Units
(AHU); check ongoing validity of
certificate online
www.eurovent-certification.com or
using www.certiflash.com.
SFP 1.9 W/l/s = 1.9 kW/m3/s
calculated using EN BS 13779
standards.
Designed at mid-point filter status,
wet coil condition.

Offer N 16-0219 Rel. 3.3.1.22 01-10-2015-


User SEM AHU1050/1000/376.696
Client Date 18-02-2016
Unit reference City
Project
Serial number
SUPPLY AIRFLOW m/h 3000 RETURN AIRFLOW // m/h

UNIT TYPE - CLCF 1 FC - Comfort


Insulation Polyurethane Foam (40 kg/m3) Panel thickness mm: 25
Roof Absent Panel internal side Galvanised Steel
Type of roof Absent Panel external side Painted Galvanised Steel
Absent/No Roof Coil conn cabinet Absent
Support With baseframe Door type Removable
Damper class Standard: Class 1 EN1751 Screw and bolts Galvanised Steel (standard)
Drain pan material Galvanised Steel Packing type: Plastic Wrapping
Internal frame Galvanised Steel Eyes bolts Present
Inspection side (supply air Right Connection side (supply Right
flow on back) air flow on back)

Width mm 1274 Height + basement mm 400 + 30


Length mm 3285 Total weight kg 558

Section 1 LENGTH: (mm) 645 Weight :(kg) 165


Section accessories

Intake Section ALUMINUM PROFILE DAMPER


Damper - 1 off insp.side shaft dimensions 360x1220 mm .
Airflow 3000 m/h
Motorisable (linkage not incl.)
With blade gasket (Leakage Class 1 according to EN1751)

CLCFWin Rel. 3.3.1.22 01-10-2015- 3/7


AHU1050/1000/376.696
18-02-2016
FAN TYPE Plug fan AIRFLOW 2X1500 m/h
!"#$%&'(% SIZE GR25C 115666/A01 EXTERNAL STATIC PRESSURE 250 Pa
N FANS 2 TOTAL STATIC PRESSURE 393 Pa
RPM/SIGN. 2542 rpm / 7.1 V
)(**& ABSORBED POWER 0.3 kW
+,%-./#$(".,% EFFICIENCY 60 %
In duct sound power: (dBA) 73.4
Octave in duct power level
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 64 60 66 67 68 68 63 60
Fans interconnection

PROTECTION IP 54 RPM 3600


0,",$&1+&234! INSTALLED POWE 2X0.78 kW POWER SUPPLY 230V/1ph/50Hz
N MOTORS 2 RATED AMPS (A)
POWER INPUT: (kW) 0.58
)."5&.%"!/$("!6& SFPv (SFPe): (W/l/s) 2X0.6
7,%"$,**!$

Section 2 LENGTH: (mm) 1150 Weight :(kg) 71


Section accessories

Custom section Heat recovery section

Components 45 Kg Section length 1150 mm


Pressure drop 260 Pa

Plate heat exchanger section


PHE model: BI AL 06 N 0340 F1 AR CD SC
Entering air winter mode (supply part): -15C/80% rH
Entering air winter mode (supply part): -2,3C/18,2% rH
Entering air summer mode (supply part): 35C/50% rH
Entering air summer mode (supply part): 30,5C/64,6% rH
Fresh air damper included
Exhaust air damper included

Section 3 LENGTH: (mm) 1490 Weight :(kg) 322


Section accessories

MATERIAL DIMENSIONS N. EFFICIENCY


./.6&8(/&'.*"!$ DP CL(Pa) 68
class M6 EN779 DP MP(Pa) 102
Synthetic Des. Temp. 2.3 C DP DT(Pa) 136
fiber 592 x 287 x 290 mm 2 Vtunnel 1.95 m/s
Filter frame Galvanised Steel
Side removal

CLCFWin Rel. 3.3.1.22 01-10-2015- 4/7


AHU1050/1000/376.696
18-02-2016-Offer N16-0219/A
TUBES Cu/0.4 TYPE 40x34.6 CAPAC. (kW) 19.9 FLUID Water

Heating coil FINS Al/0.12 DIM (mm) 320x1029 EAT (C) 2.3 FLOW. (Kg/h) 860
FRAME Zn/1.5 ROWS (n) 1 LAT (C) 22.0 EWT/LWT 80 60
(C)
CONN.. 1/2" F.SPACE (mm) 2.5 Vcoilface 2.53 DP (kPa) 11.8
VOL. (lt) 2.2 CIRCUITS (n) 1 DP tot/dry (Pa) 25/25
FTA (mm) 1159
Cu-Al-FeZn P40AC 1R-8T-1029A-2.5pa 1C 1/2"

TUBES Cu/0.4 TYPE 40x34.6 CAPAC. (kW) 11.8 FLUID Water

Cooling coil FINS Al/0.12 DIM (mm) 320x1029 EAT/RH (C-%) 30.5-65 FLOW. (Kg/h) 2024
FRAME Zn/1.5 ROWS (n) 2 LAT/RH (C-%) 24.0-85 EWT/LWT 7 12
(C)
CONN.. 3/4" F.SPACE (mm) 3 Vcoilface 2.53 DP (kPa) 27.0
VOL. (lt) 4.3 CIRCUITS (n) 2 DP tot/dry (Pa) 98/52
FTA (mm) 1189
Sens./Tot. 0.57
Cu-Al-FeZn P40AR 2R-8T-1029A-3.0pa 2C 3/4"

FAN TYPE Plug fan AIRFLOW 2X1500 m/h


9#44*3&'(% SIZE GR25C 115666/A01 EXTERNAL STATIC PRESSURE 250 Pa
N FANS 2 TOTAL STATIC PRESSURE 752 Pa
RPM/SIGN. 3166 rpm / 8.8 V
)(**& ABSORBED POWER 0.5 kW
+,%-./#$(".,% EFFICIENCY 61 %
In duct sound power: (dBA) 78.6
Octave in duct power level
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 77 68 76 74 74 72 66 64
Fans interconnection

PROTECTION IP 54 RPM 3600


0,",$&1+&234! INSTALLED POWE 2X0.78 kW POWER SUPPLY 230V/1ph/50Hz
N MOTORS 2 RATED AMPS (A)
POWER INPUT: (kW) 1.08
)."5&.%"!/$("!6& SFPv (SFPe): (W/l/s) 2X1.2
7,%"$,**!$

Intake Section ALUMINUM PROFILE DAMPER


Damper - 1 off insp.side shaft dimensions 360x1220 mm .
Airflow 3000 m/h
Motorisable (linkage not incl.)
With blade gasket (Leakage Class 1 according to EN1751)

CLCFWin Rel. 3.3.1.22 01-10-2015- 5/7


AHU1050/1000/376.696
18-02-2016-Offer N16-0219/A
AHU sound levels Octave band (dB/Hz)
Tot. dB(A) 63 125 250 500 1000 2000 4000 8000
Sound power level supply inlet 69 55 53 57 70 66 48 38 33
Sound power level supply outlet 78 73 70 80 74 74 71 63 62
Sound power level return inlet
Sound power level return outlet
Airborne sound power 78 68 76 74 74 72 66 64

- before installing the unit, read the IOM


- make the electrical wiring following the drawing inside of the motor power box or on motor label
- to avoid electrical motors overload, do not start the unit without filters or other component or without ducts or with
door open
- the unit has been designed with the required external static pressure and considering a status of filters: with plant
pressure drop less then the required, with different status of filters and without proper control, the airflow and the
sound power will be more than the indicated
- the cross flow recuperator has been designed in order to resist to the indicated differential pressure between the
plates. Do not exceed this value enslaving properly dampers or other interception devices. RHW and PHE are not
airtight devices and leakage between flows always occurs. Exact value can depends on static pressure and unit
configuration; to avoid contamination, the pressures on the fresh air side shall be higher than on the return air side
- performance data of the heat recuperator are considered for counterflow of air; in case both flows are in same
direction, performance data could be substantially different from those
- unit is designed for a maximum air temperature of 55C
- depending on supply air temperature and outdoor condition, condensate on profiles can occur
- if water temperature entering the coil is below 1C, freezing of coil fins can occur
- link the fan working to intercepting devices, as dampers or similar, avoiding fan working with those devices closed
- filter frame side removable could cause filter bypass due to not perfect airtight between filter cells
- if unit is provide of roof in kit, it will be provide separately, to mount on site by customer
- standard painted panel skin colour RAL9002
- if the door lenght is < 360 mm, also if selected, the inspection window will not be provided
- in some cases the inspection window could be partially occluded by components or components frame
- calculate sound pressure levels are indicative only. It corresponds to: free filed hemispheric sound radiation from the
unit casing, the inlet and outlet opening. Other sources, acoustic character of the room, air flow noise, duct connection
and vibration can influence the sound pressure in dependence. In practise, therefore measured values on site may be
different from the calculation ones
- unit has been designed in wet condition
- unit weight does not include water/refrigerant and control (if provided)
- tolerance on sound levels are: - airborne level : +/-3 Db; duct level : +/-5 Db @ 63-125 Hz
and +/-3 Db @ 250-8000 Hz
- due to the gasket between sections, the total length of the unit will be around mm.5+ longer for each break point
- dimensions of CLCF unit could be increase by mm.4 due to the plastic profile
- in case unit is provided of flat roof, it will be mm.20 out all around the unit
- in case unit is provided of sloped roof, it will be mm.100 out all around the unit
- due to bigger heater and bends, the steam coil finned area will be light reduced respect what indicated, with
consequent increase of the air velocity thought it
This technical sheet and the attached drawing is the only document reporting the air handling unit construction
features, also if not in conformity with offer or other requests/documents sent to us, including mechanical
specifications, technical description or similar.
For general construction features not indicated in it, refer to available documentation.

CLCFWin Rel. 3.3.1.22 01-10-2015- 6/7


AHU1050/1000/376.696
18-02-2016-Offer N16-0219/A
ErP compliance
Considering that: The European directive 2009/125/EC defines Ecodesign requirements and relating regulations for different products; The
product on this data sheet may be not a non!residential ventilation unit (as defined by EU 1253/2014); The product could result Not
Compliant to EU 1253/2014; A not compliance is allowed, in case of a ventilation unit is covered by the exemptions, as stated in regulation
No. EU 1253/2014 and later official interpretations; In some cases it may be possible that the conformity is only given after the installation
of the product into a complete system (it means that only the complete system is a compliant ventilation unit as defined by the
regulation); The product on this datasheet is a customized product and the selection and production is done according to the Customer
requirements; The Manufacturer is not informed about the exact scope and use of the product and Manufacturer is not aware if an
exemption can be applied as defined by EU 1253/2014;
Manufacturer assumes that an exception to this Regulation has be checked by the Customer and that, ordering this product, the client
accept the following clauses: The product is sold by Manufacturer as out of scope of the regulation EU 1253/2014; A declaration of
conformity and CE marking according the regulation EU 1253/2014 by TRANE is not possible for that reason; It is obligation of the Customer
to check the need of conformity of the installed product in the whole plant to European or national legislation (in this case the obligation
given by the relevant legislation has to be fulfilled by the installer of the product).

CLCFWin Rel. 3.3.1.22 01-10-2015- 7/7