CALIBRATION PROCEDURE
FOR
DYN1 10794 CONTROLLERS
FOR STANADYNE PUMPS USING DYNC 70025 INTEGRATED ACTUATOR
1.2 Set the GAIN potentiometer at 30%, the INTEGRAL 1.6 After GAIN and SPEED are adjusted, load engine to
UPPER LIMIT completely counterclockwise (CCW) [see 100% (full load).
NOTE], and the DROOP potentiometer completely coun- a) While observing FREQUENCY or RPM Meter,
terclockwise (CCW). turn Integral Upper Limit potentiometer slowly clock-
wise (CW) until frequency or RPM starts to decrease.
1.3 Place the IDLE RUN SWITCH in the IDLE position
and adjust the IDLE speed by turning the 20 turn poten- b) Turn Integral Upper Limit potentiometer slowly
tiometer clockwise (CW) to increase and counterclock- counterclockwise (CCW) until the frequency or RPM
wise (CCW) to decrease speed. returns to the original set speed.
DYNA 143-4
3.0 WIRING DIAGRAM
+ +
1 2 3 4 5 6 7 8 9 10 11
IDLE COM
+ - RMT SPD
BATTERY ACT MPU
101.6 BSC
RUN
100 [ 4.000 ]
RUN SPD
IDLE SPD 100
GAIN 112.7 1.0
DROOP
[ 4.437 .040 ]
INTEGRAL UPPER LIMIT
100
+ +
4.0 .6 5.56 .4
[ .160 .024 ] [ .219 .016 ]
.8 [ .03 ]
41.9 2
MAX 134.9
[ 1.650 ] BSC 5.56 .4
[ 5.312 ]
[ .219 .016 ]
54.6 MAX
[ 2.150 ] 146.1 1.0
[ 5.750 .040 ]
AAA
AAAAAAAA
1 2 3 4 5 6 7 8 9 10 11
18 GA
AAAAA COMMON
TWISTED
+ -
IDLE
+ - MAG 120K 1 RUN
BATTERY
PICKUP
12 OR 24
VDC SUPPLY CW 5K CCW
18 GA
TWISTED
DYNC
ACTUATOR
1 2 3 4 5 6 7 8 9 10 11
A
AAA
AAAA
+ -
AAAAAA
AAAAAAA
AAAAAAA
AAAAAAA
Wht Blk No
Connection
Battery Actuator Chassis
Gnd +7.5V External +3.75V
Screw Speed
Adjust
Magnetic Pick-up Chassis
Gnd
Screw Idle
Run
2
5.0 TROUBLESHOOTING CHART
Problem Detection Corrective Action
I. System appears dead. 1. CHECK BATTERY VOLTAGE AT CONTROLLER with power switch Check connections to battery.
ON. Measure DC battery voltage between terminal 1 (B+) and
terminal 2 (B-). Battery voltage should be present.
2. NO SIGNAL OR WEAK SIGNAL FROM MAGNETIC PICKUP. Check for damage to or improper
Measure AC voltage between terminals 5 & 6 on the controller while adjustment of magnetic pickup.
cranking engine. Voltage should be 2.5 volts RMS or greater. (AC Replace or re-adjust.
input impedance of meter must be 5000 ohms/volt or greater)
Note
The following checks are to be made with nothing
connected to the terminals.
c. Terminal 7 to terminal 2 7.5 volts .5V to be measured. Replace controller if voltage is not present.
d. Terminal 8 to terminal 2 3.75 volts .5V to be measured. Replace controller if voltage is not present.
e. Terminal 9 to terminal 2 3.75 volts .5V to be measured. Replace controller if voltage is not present.
e. Momentarily turn "ON" the DC power. The actuator should go to If actuator doesnt get to full fuel, then check
full fuel and the DC voltage must be greater than 80% of supply. actuator leads. If voltage is less than specified,
check for loose or poor connections to battery,
24 VDC @ 80% = 19.2 VDC or get larger supply leads or larger power
12 VDC @ 80% = 9.6 VDC supply.
3
NOTE
Barber-Colman believes that all information provided herein is
correct and reliable and reserves the right to update at any
time. Barber-Colman does not assume any responsibility for
its use unless otherwise expressly undertaken.
CAUTION
As a safety measure, the engine should be equipped with an
independent overspeed shutdown device in the event of
failure which may render the governor inoperative.