GMDSS Batteries: Tests and

checks mariners must know


Written by Capt Rajeev Jassal on January 31, 2016

GMDSS batteries provide power to GMDSS equipments in case ships main as


well as emergency power fail. The requirement of GMDSS batteries is governed
by Regulation 13, Chapter 4 of SOLAS.

As per SOLAS, GMDSS batteries should provide power to operate GMDSS for

1. 1 hour in case GMDSS has the power from emergency generators

2. 6 hours in case GMDSS does not have the power from emergency generators.

3. Batteries must be recharged to the required minimum in less than 10 hours.


4. The capacity of the batteries must be checked at interval of less than 12 months.

Maintaining the GMDSS batteries in excellent condition is important to have them


ready in emergency. There are typically three type of tests/Maintenance done on
GMDSS batteries.

1. Daily on Load/Off Load test

2. Yearly Capacity test

3. General Maintenance required on the battery.

1. Daily On Load / Off Load test

On load / off load test is done to ensure that

1. GMDSS equipments can have the power from battery. This ensures that all the
connections from the battery to the GMDSS equipmemts are intact.

2. Battery is able to provide power during operation of the GMDSS equipments. That
is when load is put on battery, it does not drain out too quickly.

For the on Load / Off load test, Following procedure should be followed

1. First Switch off the AC power to the GMDSS station. The power button is
usually under the GMDSS panel or on some ships in the radio room (if you still
have one). If you have different AC source for charging the battery, that too need
to be switched off. This is because if the battery is on continuous charge, this will
not show any drop in voltage which we intend to find out with On Load/Off Load
test.
However most of the time, GMDSS power source flow is AC power to batteries to
GMDSS equipments. Switching off the AC power automatically ensures batteries
are not on continuous charging during test. So after the GMDSS equipments are on
battery power, note down the voltage of the batteries.

2. Press the PTT button to transmit on a non-distress and idle R/T frequency. Note
down the on-Load voltage while the PTT is pressed.

3. The drop in voltage should not be more than 1.5 volts.

2. Capacity Test

All batteries have a life span. The capacity of a battery can reduce with age. There
has to be a way to measure the capacity. And with Capacity test we do exactly that.

We can understand the capacity test with the comparison to a water tank. We do
not know how much water it can hold. The one way of measuring its capacity
would be filling the water tank to full and then measuring it by draining.
Measurement can be with flow meter or with smaller measuring buckets/container.

With capacity test, we measure the capacity of battery by same method. We charge
the battery to full and then measure it by discharging. To discharge the battery, we
apply a known load to measure its capacity. Capacity of the battery is measured in
Ampere hour (Ah). So 200 Ah means the battery can give a current of 200 Ampere
for one hour or 20 Amperes for 10 hours and so on.

Before we proceed further, lets agree on these two staements

1. The voltage is not the measure of capacity of the battery.

2. A battery 100% full (Fully charged) does not mean that it will or can produce the
rated capacity.

Looking at the first statement, if the voltage is not the measure of capacity, what is
? As we already discussed, The measure of capacity of a battery is how much
current it can produce for how many hours. With capacity test, that is what we
aim to measure.

It would be easier to understand the second statement with example of a laptop. A


new computer with 100% battery might last for 8 hours . After few years same
battery 100% charged would only last 4-5 hours. This is due to the ageing of the
battery. With age, battery looses its storage space.

Another analogy to understand the second statement would be the same water tank
example. If the capacity of the water tank is 2000 Litres and if it is 100% full, does
that mean it contains 2000 litres of liquid. We cannot be sure of that as we do
know know what is in the bottom of the tank. There could be number of stones at
the bottom. This figure can better explain what we are referring to here
Avoiding Deep Discharge

There is another SOLAS requirement about deep discharge of the battery while
performing capacity test. In the simplest of the terms, deep discharge means the
least voltage a battery can be brought to. If we discharge the battery below this
voltage, the battery can loose its capacity to a level where it cannot be used
again. For Nickel based batteries this voltage is 1.0V per cell. So for 24V battery
pack (1.2V x 20 Cells), the deep discharge voltage will be 20V. While performing
capacity test, we should never allow the battery voltage to go below 20V or
1V/Cell.

Now we all must be knowing this basic physics

Power = Voltage x Current

The GMDSS battery is usually in the range of 200 Ah which is required to give
24V.
We need to test if it still has 200Ah left in it. For this we need to remove the
batteries from charging and the existing load (connections to GMDSS
station) and attach some known load to it. Usually a rig which consists of number
of 100W bulbs in series is attached to the batteries terminals. Say, if 6 bulbs (600W
)are attached to the battery, it would draw 25A of current from the battery bank.
This is because

600 watts / 24 Volts = 25 Amp

Once the load is attached to the battery bank, we need to measure the voltage and
the current across each battery bank terminal. We need to do this at least
every hour. This will continue and we shall stop the test only if

1) The one battery cell is failing. That is drop of voltage in one battery cell is
different than others. In this case we need to isolate this failing cell and then
continue the test.
2) The voltage has reached the deep discharge voltage. SOLAS requires that while
performing the capacity test, deep discharge of the battery shall be avoided. We
have already discussed what deep discharge is. During the test we need to measure
the voltage of each cell. The voltage should not go below 1V in any cell or 20V for
the battery pack.

3) The test has performed for sufficient time to show that battery has 100% of its
rated capacity. Say it has been 8 hours since the test started. And for 8 hours the
current measure was 25A. So the battery has already delivered 200Ah (25A x 8
Hours). This shows that batterys capacity is still 100%. In this case, this would
conclude the test.

If we stop the test because of 3rd point, the battery is fine. If we stop the test
because we have come to deep discharge voltage. We need to measure how much
Ampere Hour has the battery delivered at this point. If it is less than 80% of its
rated capacity, the capacity test has failed.

Charging the battery after capacity test

If the measured capacity is more than 80% of the rated capacity, we can move to
next step where we measure the time required to charge the battery. There are two
parameters to show the percentage level a battery is charged. These are terminal
voltage reading or the specific gravity of the electrolyte. A 24V battery when fully
charged would show a voltage of around 25.4V and specific gravity of 1.265.
Determining the state of charge with voltage can be tricky as voltage can change
with temperature. Specific gravity of electrolyte is considered more accurate way
to determine state of charge of battery. So after the capacity test, we need to
measure the time a battery takes to charge to 100%. SOLAS require this time to be
less than 10 hours.
3. General maintenance required on GMDSS
Batteries

The onboard batteries do not need much of maintenance as such. There are two
things that need to be checked. First is the electrolyte level and second is the
specific gravity of the electrolyte. If you have maintenance free batteries onboard,
you do not need to check anything on that except the conditions in which it is
stored.

Level of the electrolyte

The level of electrolyte can reduce due to various reasons but it is important that
the level is maintained as per the manufacturers instructions. If the level is low,
the battery cell must only be refilled with distilled water.

Checking specific gravity of the electrolyte

Specific gravity of the electrolyte is considered more accurate measure of state of


charge of the battery. Specific gravity must be checked daily and recoded in
battery log alonwith voltage. Specific gravity can reduce because
of sulfation which causes the charging plates to be deposited with crystals. This
causes reduction of holding charge and thus the capacity of the battery is reduced.
BCI (Battery Council Internation defines specific gravity of 1.265 as 100% state of
charge. 1.225 is considered 75% state of charge. It is still better to refer to
manufacturers instructions as some manufacturers can go upto specific gravity
of 1.280 as the sign of 100% state of charge.

Conclusion

GMDSS batteries are important equipment which ensures that emergency


equipments gets power in real emergency. It is thus important to maintain these
batteries in an excellent condition. Various tests/checks ensure that GMDSS
batteries would provide the required power. Daily on load/off load test ensures that
all connections are intact and when on load batteries do not drop voltage too
quickly. Annual capacity test measures the capacity of the battery in Ampere
hours. We should replace the battery if capacity is less than 80% of the rated
capacity. Finally we should daily check the batteries state of charge by measuring
the specific gravity and level of electrolyte.