O sistema foi simulado considerando as contribuioes da gerao e da carga.

Outos diagrama de simulao


esto em anexo.

Tabela 2 - Correntes de curto-circuito do sistema fase terra na linha a 50%// ANAFAS (RNT-EP, 2013)

A-G simulao de Calculo de Icc/Monofsico

Equaes Resultados da Simulao

3V2 = -26,8976148192136+0,694158419159422i

3I2 = 3,99403295861937-11,9219188431628i

Rg = 5,078302

Xg = 15,1584

Zg = 5,07830235002686+15,1583898043224i

I1 = 1,33134431953979-3,97397294772094i

V1 = 58,0341283935955+0,231386139719852i

V2 = -8,96587160640454+0,231386139719852i

V0 = -26,7349234538576-0,462772279439777i

3I2 = 3I0 = Ia = 3,99403295861937-11,9219188431628i

Va = 22,3333333333334-7,2997163869104E-14i

Vb = -51,269051847453-58,717860472717i

Vc = -51,2690518474531+57,3295436343978i

1 = 3,994 11,922 = 12,57 71,47A = 62,85 71,47A


Tabela 3 - Correntes de curto-circuito do sistema fase terra na linha a 50%/ ANAFAS (RNT-EP, 2013)

A-B simulao de Calculo de Icc/Bifasico visto pelo rel

Equaes Resultados da Simulao

3V2 = 66,9999999999998-1,98951966012828E-13i

3I2 = -10,7081072910374+29,4202829872224i

Zpp = 2,19576932015079+6,03282662544553i

I1 = 3,56936909701243-9,80676099574079i

V1 = 44,6666666666667+1,50990331349021E-14i

V2 = 22,3333333333333-1,50990331349021E-14i
Ib = -16,9858083023078-6,18232862699178i

Ic = 16,9858083023078+6,18232862699178i

Vap = 67

Vbp = -33,4999999999999-19,3412340178525i

Vcp = -33,5000000000001+19,3412340178526i

2 = 2 16,985 + 6,18 2 = 36,1519,99A = 180,7519,99A


Tabela 4 - Correntes de curto-circuito do sistema trifsico na linha a 50%/ ANAFAS (RNT-EP, 2013)

A-B C simulao de Calculo de Icc/Trifasico visto pelo rel

Equaes Resultados da Simulao

3V2 = 2,88253302987606+9,12556317887688i

3I2 = 0,96084434329202+3,04185439295896i

Zpp = 0,720633257469017+2,28139079471922i

Zppp = 1,0978846600754+3,01641331272277i

I1 = 7,13873819402486-19,6135219914815i

V1 = 22,3333333333336-2,66453525910038E-14i

Iappp = 63,773819402486-19,6135219914815i

Ibppp = -20,5551773993202+3,62443236874897i

Icppp = 66,85164392052953+15,9890896227326i

Vappp = 22,3333333333336-2,66453525910038E-14i

Vbppp = -11,1666666666668-19,3412340178527i

Vcppp = -11,1666666666668+19,3412340178527i

3 = 66,85 + 63,77 = 92,3943,65 = 461,9543,65


Depois de conhecermos as correntes de curto circuito nas linhas j possvel determinar o ajuste da unidade
temporizada de corrente.