Beruflich Dokumente
Kultur Dokumente
Copyright 1919. By A. I. E. E.
FOREWORD
As a result of the large development which has been made in
the relay practises in the last few years, the Protective Devices
Committee felt it was desirable to make an analysis of the trans-
mission line protective relay situation throughout the country
and prepare a summary to bring before the profession, experi-
ences of the operating companies with this protective apparatus.
With this in view questionnaires were sent out to sixty-one
operating companies asking for their experience and present
practise in regard to relay protection.
Replies were received from 32 of the operating companies and
from these the following general analysis was made of the prac-
tise of relay protection for transmission lines.
The nomenclature used by the different operating and manu-
facturing companies for the various classes of relays is not in har-
mony and the Protective Devices Committee undertook the work
of standardizing the nomenclature which it is hoped will be
adopted by all parties so that any particular class of relays will
be given a definite name. The following nomenclature has
therefore been proposed by the Protective Devices Committee
and this nomenclature is used throughout this paper.
+s 1< . I t/ X X 0~~~VE 1
0 6-
AC 9 1
60 __ -__ - IT *- -URt6EMESS9N.
WIT
-CURVE M.
:E \ \ \ z iORT CI~~~~~~~~~~~~~~~~~EUNERARt
STAINt
4
30 000 S0 00
,r s 4 <4 DI2REW!TONALANOI.T.
CQRKNUPE-7 RELAYr5
I I ,
~MtTICME N I.
5I B 5TA110h US.
C m j
I I I CO 1 CM1 eb 4. | C E1?EN
XE1 DTT.
C t t OT~~~~~~~~CNuRRENT RELAy5
~ CL'P~~~ IN
IOA.AD CURRENT QELAY5
_RRD PSTW ZlELTION W_ X IMES N9 Z
ICutpExtT RnLAy
_VfDIZEC-TIONALAPD IT.
5oB STATEOP1 B)s.THE TSME C1
r VPLVES
I .Xi
^%E PVEELT IEI I TIMEA0
T
I
Co
'sPrV T 5ZXXTEOU'S*5
IOWE R PLC FO - IMN9|
im
which in the first case were incoming will now be outgoing and
vice versa. The directional relays are also installed if the
time of an incoming line is lower than an outgoing line further
from the source. This must be checked separately for each
end, in turn, considered opened at the generator station.
In order to secure the operation of the directional relays
under bad power factor conditions, the connections are made
so that the maximum torque is obtained with lagging power
GENERATING STATION BU5
INVEM 'TIME CueQZE-4 IZE9 _ |
TIME Ne6
IS-EeA
| ' TIUE. CRRENTelZAYS
TIME Nr6
ACIT
D ABSCTIOPAL
C1ZWENTREA'f5
'
I '. S
:
DI2ECTIONAL AND I.T.
CURREr.T 12ft.A'y'.
TAE tl4
I ELAS M : C
sB s
E -
-T,.
z
I I m N
OLBECOBSE.BEES
IT.CC2SSNT ELVESECTESEEs-. ABS IT CuoEEBSE SeLAy!.
Tisi.&NA3. TimETN03-
TU STATEs-N fl5 ZELCEENE ASSIE.S LAWE!. F1ASe-
5TA1ION A 57ATION B
+ OILCS. - CURTAR.T I- +
5STA-Tiom A __
i=F ~~-
___ mor 5
FAULT
STATIOM A TAIOF B
(NOT DISCRIMINATING)
OVER op4wTRANS.
CF.CU (EST.
ILE %-TL-K-TIAL. COILS Ar4v Com4C TIONS
.
._ ~~~OMITTE17 FMOM PIREC-TIONAL. lELAIS _
5TA-noN A S5TO1B
A~~~~~AL
t==D~~~~
_ _
5-rparioI A 5TATIOT' 5
_~ ~ ~~
AL
___________
~ ~ 15~~~~~ ~ ~ ~~
~ ~ ~ I=~~ ~
OPE
________
10 I I I N
FIG. 12
5TATION A 5TATION B
X- FAUt-r
if four lines are in, 13 continuous and one open at one point)
an overload of three times normal on each feeder would be
required before any trouble could be encountered.
One installation of this scheme is described in a paper by
Mr. Philip Torchio, "Relays for High-Tension Lines," TRANS.
A. I. E. E., Vol. XXXVI, page 361, March 1917.
Split-Conductor Protection. Split-conductor cables are being
tried out. in this country by two operating companies who report
good results to date. The cable is comprised of six conductors,
each of the three phases being "split" into two halves. A
section of the cable used is shown in Fig. 14.
.5A1mOrm A 5TATION B
Aw C:L CU2-RETAN5,
CUUS11T
Rtf6f
g HEAULY COVPIrT,N
-AnRows IroDCA-M RELA-P& P1,Cr0TS
H
VIvD r uMIIr Hi-m
siri OF CUotBVT FLS
5,TATioN A 5TATiorl B
5TA,TioT1 A-mor
FAuJLr COHorTom
FIGS. 15, 16 AND 17-SPLIT-CONDUCTOR SYSTEM PROTECTION
relay which releases the lock when the voltage falls below a
predetermined value (approximately 70 per cent). Upon the
occurrence of a short circuit the voltage drops and when it
has fallen below the predetermined point the voltage relays
act to unlock the circuit breakers which are then free to be
opened by the over-current relay or other over-current device.
Thus, in most cases, only the breakers in the affected section
can open on short circuit. It sometimes happens, however,
that when two stations are close together, breakers in an un-
affected section may be unlocked but usually the over-current
device will act to open the proper ones only and clear the trouble
before the others can operate.
Referring to the diagram Fig. 19 the under-voltage relays
are connected to the secondaries of potential transformers on
MAQNETJCALLY AUKE5wROPEN WHEN
OPKEA'T&VLOCK 1RAKIOPPEN.
O'VERLOAv TRIp
A'TTACMMENT
POIENTIAL 5TATtION ERVICE 10 CuempENT
,TRAN 5, TRAN5FORMEMS.
4POLE 9Sv[TCN
TO CVT OU-T
X n
"^LLJ
LOCKS
n _CICUIT BREAKEZ
LOCKS AMP RELAS _ITCH TO CUT
UNOERVOLTAGL RELAY
FIG. 19-UNDERVOLTAGE AND OVERCURRENT RELAY-SCHEME OF CON-
NE CTIONS
tion in the reports; for example, some give as high as 90 per cent
to ground while others give as low as 25 per cent to ground. We
feel this discrepancy is probably due to the fact that some of the
operating companies have no records to show what portion of
the trouble did actually start from the ground.
Ques. 8.-Do you ordinarily keep all transmission lines in service or do
you keep some lines dead and in reserve?
Ans.-Of the operating companies reporting 93 per cent keep all of
their good transmission lines in service without any held in
reserve with the exception of two cases where with overhead high-
voltage transmission lines one of two parallel lines is taken out
of service for reserve during lightning disturbances and in one of
these cases the line is grounded at this time.
Ques. 9.-Where you have several schemes of relay protection that accom-
plish practically the same purpose, will you kindly state your preference
and your reasons?
Ans.-Of the companies reporting 13 per cent prefer the combination
of time-current and directional relay schemes, 13 per cent the
balanced pair, 6 per cent split conductor, 6 per cent straight
inverse-time-current protection, and 3 per cent balanced relay
with pilot wires.
And of the remaining systems there was only one relay scheme in
operation from which no comparison could be drawn.
Ques. 10.-Have you any scheme of relay protection which in your opinion
is particularly effective for your conditions? If so will you kindly state
in some detail the desirable features of this system?
Ans.-Of the companies reporting, 32 per cent feel that some form
of a balanced relay protection is well adapted for their condi-
tions. Of this 32 per cent, 6 2 per cent prefer the split-conductor
scheme, 612 per cent, two lines operated as a unit with balanced
overload protection: 16 per cent, two lines in multiple with the
balanced directional and current relays for disconnecting a single
defective line only; and 3 per cent use pilot wires.
22 per cent find that the current-directional relay combination
gives particularly good results for their conditions and some of
these find that the connection of the potential circuits of the
directional relay to the substation bus side of transformers,
where not in parallel on high-tension side, give preferable
operating conditions, as a higher voltage is maintained under
short-circuit conditions.
3 per cent find special ground relays desirable (Refer to A. I. E. E.
TRANSACTIONS p. 361 vol. 26).
6 per cent prefer definite time-limit relays as they have given very
satisfactory service.
3 per cent prefer no automatic protection on very high-tension lines.
3 per cent find that a combination current and under-voltage relay
system has solved, for their conditions, difficulties that they have
not been able to overcome with any other scheme.
Balance report no special conditions.
822 WOODROW, ROPER, TRA VER, MACGAHAN: [June 24
Ques. 15 a. b. & c.-What are the principal difficulties that you have
experienced with relay protective system?
Have you experienced any false operations or failures of relays to operate?
Have you been able to attribute such difficulties to defects in the relay, the
design of the relay protective system, the difficulties in making proper
connections, or to the irregular operation of oil circuit breakers? Please
answer in some detail?
Ans.-Practically all the companies report trouble with the operation
of their protective relay system. Of these troubles there are
46 per cent reported due to the difficulties in the relay, 20 per
cent to improper application of the relays, 15 per cent to improper
settings of the relays, 9 per cent to defective wiring, and 10 per
cent to defective operation of the oil circuit breakers.
Several of the companies reporting trouble with the relays find
that they were due to the chattering of the bellows type of relay
in which cases some of the trouble had been eliminated by
replacing this relay with other time-current types and in some
cases it was eliminated by the installation of a saturating reactor
in shunt with the relays. The shunt reactor eliminated the
trouble and gave a desirable characteristic time curve at a
considerably lower cost than required to replace the relays.
Some defective operations of directional relays are reported, in
most cases of which the relays were of the old type.
Some companies report a change in calibration with time and
although these eases are not very explicit, the trouble could
probably be avoided by a more frequent check and inspection
of the relay.
Of the troubles due to improper wiring, some of these are attributed
to a wrong connection of the potential element of directional
relays and some to a wrong connection of the balanced or
differentially connected relays and the remainder is due to poor
workmanship.
Ques. 16-What is the maximum current that can flow into a short circuit
on a transmission line just outside the generating station?
a. The maximum instantaneous current?
b. The maximum sustained current?
Ans.-Report covers the experience from thirty-one operating com-
panies with systems varying from 25,000 to 455,000 kv-a. whose
short-circuit currents, at any point, vary in value from 100,000
to 1,650,000 kv-a. and sustained short-circuit kv-a. values vary
from 20,000 to 340,000 kv-a.
DIAGRAM A
About one-third of the companies reporting had tie lines that could be
classified under this connection. Of these-
55 per cent of the lines -were protected by means of inverse-time-current
relays only.
5 per cent use balanced protection with pilot wires.
5 per cent use split-conductor installations.
35 per cent were provided with directional and current relay protection.
GEERAT1tNG,TING
buSI B BUS.
SOB -STiTION
.us
DIAGRAM B
About one-fifth of the companies reporting had tie lines that could be
classified under this connection. Of these-
85 per centof the lines reported were provided with inverse-time-
current relays only.
15 per cent were provided with current and directional protection.
SUB- S qrANrAIr
BUE5
qENEeA'TIN
TINU ERTING._UI
DIAGRAM C
About one-fourth of the companies reporting had tie lines that were
classified under this connection. Of these-
50 per cent of the lines reported were protected by inverse-time-current
relays only.
25 per cent by current anid directional relays.
10 per cent were provided with balanced protection using pilot wires.
15 per cent were provided with balanced pair protection.
BEU5ATN
~~~~~~~~~~~~q.ENE1ZAZI4
0 0
5U5 5Tfi7IO0
5us~~~~~us
usT71N
DIAGRAM D
About one-tenth of the companies reporting had tie lines that were
classified under this connection. Of these-
65 per cent of the lines reported were protected by means of inverse-
time-current relays.
35 per cent were equipped with current and directional relays.
1919] TRANSMISSION LINE RELAY PROTECTION 825
ENERAItNG 1I SUB-5-TA-nON
5us ~ -- - 1 E
DIAGRAM E
DIAGRAM F
,.14
About one-half of the companies have lines in this classification. Of
thqse-
40 per cent of the lines were reported to have current and directional
protection.
55 per cent were equipped with inverse-time-current relays only.
5 per cent were protected by balanced relays of the interconnected
directional type.
QENERATIN BUTS
S)S SuN
505 0 ~~~~~~~SUB
&A7O
DIAGRAM G
About one-tenth of the companies have lines under this classification
of which one-half are protected by inverse-time-current relays and one-
half by balaneed connections.
C;ENEr,UNT STATION
1Sob 'BU~~5LS
5SU-S-TA-ioiO
5U_5
BUS
DIAGRAM H
About two-fifths of the companies have lines under this classification.
Of these-
55 per cent were reported to have inverse-time-current relay protection.
30 per cent were equipped with directional and current protection.
72 per cent were equipped with balanced relay protection with pilot
wires.
826 WOODROW, ROPER, TRA VER, MACGAHAN: [June 24
7Y2 per cent were equipped with balanced relay protection scheme
using directional relays.
Q EN ER^m
A- 5UB-SAIT
SQ- , SeSTrir
B'uS bus
DIAGRAM I
About one-eighth of the companies have line classifications in this list.
Of these-
75 per cent were reported to be protected by means of current relays
and directional relays.
25 per cent by means of inverse-time-current relays only.
NE~T1r~
CiENEMTINC4 0 i
$uB-5TArJOM
oo .
DIAGRAM J
Two companies reported lines in this classification and in both cases
straight inverse-time-current relay protection was used.