CONTENTS

1. OUTLINE OF MULTI VRF .......................................................................................................... 3


2. SUMMARY OF SYSTEM EQUIPMENTS ...................................................................................... 5

3. BASIC SYSTEM CONFIGURATION ........................................................................................... 14

4. EQUIPMENT SELECTION PROCEDURE ..................................................................................... 18

5. REFRIGERANT PIPING DESIGN ................................................................................................ . 25

6. WIRING DESIGN ....................................................................................................................... 35

7. ACCESSORIES ............................................................................................................................ 40
8. TECHNICAL SPECIFICATION .................................................................................................... 41

9. CRICUIT DIAGRAW .. .. ................................................................................................................ 68

10. FAN CHARACTERISTICS .. ..... .................................................................................................... 70


11. DIMENSIONAL DRAWINGS .................................................................................................... 72
Modular Digital Multi VRF Technical Sales Guide

1 OUTLINE OF MULTI VRF


Shortest Route Design by Free Branching
Combination of line and branching is highly flexible.
This follows for the shortest design route possible,
thereby saving on installation time and cost.

Outdoor unit

Branching joint

Indoor unit

Simple Wiring
2-wire multiplex transmission system makes it
possible to connect multiple indoor units to one
outdoor unit with a 2-core wire, thus simplify the
wiring operation.

Power
supply

Power
supply
Transmission system

Allowable pipe length:


175m(514ft) equivalent length Outdoor unit
High Lift Design
175m(574ft) Equivalent length and 50m(164ft)
unit and outdoor unit:50m(49ft)
Height difference between indoor
units:15m
Height difference between indoor

1st branching
Height difference is allowed of GREE GMV. section

Level difference between indoor units of 15m(149ft)


is the highest in the industry.The condition make
flexibility more greater the location of the system.

From 1st branching to the


farthest indoor unit:40m(131ft)
Energy Saving
Because each room is controlled individually, only those rooms requiring air conditioning are cooled
or heated. In addition, due to digital technology, the level of air conditioning can be precisely
controlled by the condition of each room. High IPLV is achieved thanks to cutting-edge technology,
and contributing to smooth and economical operation. The highest IPLV value can reach-
4.01w/w(13.68 Btu/w-hr), Compared with the conventional chiller fan coil system, Multi VRF system
can realized better energy saving.

Self Diagnostics System


Comprehensive troubleshooting code was displayed when problems happened.
Self diagnostics examples
Malfunction code Nature of malfunction
E1 Compressor high pressure protection
E2 Indoor unit prevent frostbite protection
E3 Compressor low pressure protection
E4 Compressor discharge temperature pr
otection
E5 Compressor over loading protection
E6 Communication error

Compact Unit Design


We offer a wide lineup of outdoor and indoor units to
answered the needs of building size and interior design. The
length of refrigerant pipes is layed without narrow on design,
thus it allowing of flexibility more greater in planning.
Indoor units are so lightweight and compact that they can
be installed in any ceiling space. Outdoor units do not
require the special cranes or conveyors to move them. They
can even be hauled in a building elevator. the diameter of
pipes is narrow,and the number is few, so making layout
simpler. Inspection after installation is straightforward.

Intelligent Control

GREE GMV intelligent controls and modulating valves could


deliver the required capacity, according to the load variation
from 10% to 135%. The intelligent controls and modulating
valves limit or increase the cooling capacity dynamically, so
(Cooling) GMV System(GREE PID Controls)
humidity and temperature are kept in the comfort range ON/OFF controlled air conditioner(2.5HP)
Electronic expansion valves respond to the changes in load
Suction air temp.

of indoor units and continually control the flow rate of the


refrigerant. In this way, We can get a nearly constant room
temperature with the GMV system without the typical
temperature changes that occurs with a conventional Time
ON/OFF control system. The extremely refined PID controls
to maintains the room temperature within 0.5 of the set
temperature.

4
Modular Digital Multi VRF Technical Sales Guide

Wide Control Application


Central control available (be provided with weekly timer function )
Monitoring system available
Single remote controller and wired controller of indoor units
Region monitoring controller
Region wired controller

2 SUMMARY OF SYSTEM EQUIPMENTS

2.1 Outdoor Unit

Digital multi variable outdoor unit Appearance

Model GMV-Rm224W/Na-M GMV-Rm280W/Na-M

Cooling Capacity(kW) 22.4 28

Heating Capacity(kW) 25 31

Digital multi variable outdoor unit Appearance

Model GMV-Rm335W/Na-M GMV-Rm400W/Na-M

Cooling Capacity(kW) 33.5 40

Heating Capacity(kW) 36.5 44

Digital multi variable outdoor unit Appearance

Model GMV-Rm450W/Na-M GMV-Rm504W/Na-M

Cooling Capacity(kW) 45 50.4

Heating Capacity(kW) 49.5 55

Digital multi variable outdoor unit Appearance

Model GMV-Rm560W2/Na-M

Cooling Capacity(kW) 56

Heating Capacity(kW) 60

5
Digital multi variable outdoor unit Appearance

Model GMV-Rm615W2/Na-M

Cooling Capacity(kW) 61.5

Heating Capacity(kW) 65

Digital multi variable outdoor unit Appearance

Model GMV-Rm670W2/Na-M GMV-Rm730W2/Na-M

Cooling Capacity(kW) 67 73.5

Heating Capacity(kW) 73 80

Digital multi variable outdoor unit Appearance

Model GMV-Rm800W2/Na-M GMV-Rm850W2/Na-M

Cooling Capacity(kW) 80 85

Heating Capacity(kW) 85 90

Digital multi variable outdoor unit Appearance

Model GMV-Rm900W2/Na-M GMV-Rm954W2/Na-M

Cooling Capacity(kW) 90 95

Heating Capacity(kW) 98 103

Digital multi variable outdoor unit Appearance

Model GMV-Rm1008W2/Na-M

Cooling Capacity(kW) 100.8

Heating Capacity(kW) 111.3

6
Modular Digital Multi VRF Technical Sales Guide

Digital multi variable outdoor unit Appearance

Model GMV-Rm1070W3/Na-M

Cooling Capacity(kW) 107

Heating Capacity(kW) 115

Digital multi variable outdoor unit Appearance

Model GMV-Rm1125W3/Na-M GMV-Rm1200W3/Na-M

Cooling Capacity(kW) 113 120

Heating Capacity(kW) 124 130

Digital multi variable outdoor unit Appearance

Model GMV-Rm1250W3/Na-M GMV-Rm1300W3/Na-M

Cooling Capacity(kW) 125 130

Heating Capacity(kW) 140 143

Digital multi variable outdoor unit Appearance

Model GMV-Rm1350W3/Na-M GMV-Rm1405W3/Na-M

Cooling Capacity(kW) 135 140.5

Heating Capacity(kW) 145 150

Digital multi variable outdoor unit Appearance

Model GMV-Rm1458W3/Na-M GMV-Rm1512W3/Na-M

Cooling Capacity(kW) 145.8 151.2

Heating Capacity(kW) 160 165

7
Digital multi variable outdoor unit Appearance

Model GMV-Rm1600W4/Na-M GMV-Rm1650W4/Na-M

Cooling Capacity(kW) 160 165

Heating Capacity(kW) 175 180

Digital multi variable outdoor unit Appearance

Model GMV-Rm1700W4/Na-M GMV-Rm1750W4/Na-M

Cooling Capacity(kW) 170 175

Heating Capacity(kW) 185 190

Digital multi variable outdoor unit Appearance

Model GMV-Rm1800W4/Na-M GMV-Rm1854W4/Na-M

Cooling Capacity(kW) 180 185.4

Heating Capacity(kW) 195 200

Digital multi variable outdoor unit Appearance

Model GMV-Rm1908W4/Na-M GMV-Rm1962W4/Na-M

Cooling Capacity(kW) 190.8 196.2

Heating Capacity(kW) 205 210

Digital multi variable outdoor unit Appearance

Model GMV-Rm2016W4/Na-M

Cooling Capacity(kW) 201.6

Heating Capacity(kW) 215

8
Modular Digital Multi VRF Technical Sales Guide

(1) Nomenclature
GMV R W * / Na

Power complement
M:380V, 3N~ , 50Hz
K :220V ~, 50Hz

Refrigerant:R410A

Compressor quantity

Outdoor unit

Nominal cooling capacity


224:22.4KW 280:28KW 335:33.5KW
400:40KW 450:45KW 504:50.4KW

Modular

Digital scroll

GREE multi variable

Example: GMV-Rm280W/Na-M, a modular digital scroll outdoor unit of GREE using R410A
refrigerant, with two compressors and the nominal cooling capacity is 30kw. The power supply is
(2) Rated Conditions
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB
Outdoor air temperature 35 (95.4 ) DB/24 (75.6 ) WB
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB
Outdoor air temperature 7 (44.6 ) DB/6 (42.8 ) WB
2.2 Y-shape Branching joints

Model name Indoor unit capacity code total X Appearce


FQ01A/A X 200
FQ01B/A 200<X 300
Y-shape
FQ02/A 300 <X 700
branching joint
FQ03/A 700 <X 1350
FQ04/A 1350 <X

For FQ03/A and FQ04/A (see the picture in the above table), there are two branch pipes on
the right. The ratio of the two branch pipes of indoor units, capacity can not exceed 3:1.

Model name Outdoor unit capacity code total X Appearce


Y-shape
branching joint
ML01 224<X 2016
between Outdoor
units

9
2.3 Indoor Unit

Type Appearance Model Capacity Code Cooling Capacity(kW) Heating Capacity(kW)


GMV-R28T/Na-K 28 2.8 3.2
GMV-R36T/Na-K 36 3.6 4.0
GMV-R45T/Na-K 45 4.5 5.0
GMV-R50T/Na-K 50 5.0 5.8
GMV-R56T/Na-K 56 5.6 6.3
4-way
Cassette Type GMV-R63T/Na-K 63 6.3 7.0
GMV-R71T/Na-K 71 7.1 8.0
GMV-R80T/Na-K 80 8.0 8.8
GMV-R90T/Na-K 90 9.0 10.0
GMV-R100T/Na-K 100 10.0 11.0
GMV-R112T/Na-K 112 11.2 12.5
GMV-R125T/Na-K 125 12.5 13.5
GMV-R140T/Na-K 140 14.0 14.5
GMV-R22P/Na-K 22 2.2 2.5
GMV-R25P/Na-K 25 2.5 3.0
GMV-R28P/Na-K 28 2.8 3.1
GMV-R36P/Na-K 36 3.6 4.0
GMV-R45P/Na-K 45 4.5 5.0
GMV-R50P/Na-K 50 5.0 5.8
GMV-R56P/Na-K 56 5.6 6.6
GMV-R63P/Na-K 63 6.3 7.0
GMV-R71P/Na-K 71 7.1 8.0
Duct Standard Type
GMV-R80P/Na-K 80 8.0 9.0
GMV-R90P/Na-K 90 9.0 11.0
GMV-R112P/Na-K 112 11.2 13.0
GMV-R125P/Na-K 125 12.5 13.5
GMV-R140P/Na-K 140 14.0 15.0
GMV-R22G/NaB-K 22 2.2 2.5
GMV-R28G/NaB-K 28 2.8 3.2
GMV-R36G/NaB-K 36 3.6 4.0
Wall-mounted GMV-R45G/NaB-K 45 4.5 5.0
Type GMV-R50G/NaB-K 50 5.0 5.8
GMV-R56G/NaB-K 56 5.6 6.3
GMV-R71G/Na-K 71 7.1 8.0
GMV-R80G/Na-K 80 8.0 9.0
GMV-R28Zd/Na-K 28 2.8 3.2
GMV-R36Zd/Na-K 36 3.6 4.0
Floor ceiling
GMV-R50Zd/Na-K 50 5.0 5.8
Type
GMV-R71Zd/Na-K 71 7.1 8.0
GMV-R90Zd/Na-K 90 9.0 10.0
GMV-R112Zd/Na-K 112 11.2 12.5
GMV-R125Zd/Na-K 125 12.5 13.5

Note:
The cooling only type indoor units have no heating parameters.

10
Modular Digital Multi VRF Technical Sales Guide

(1) Nomenclature

GMV R / Na

Power Complement
K:220V~, 50Hz

Design Sequence.
B :Second generation

Refrigerant:R410A

Indoor unit
G:wall mounted P:ducted T:cassette
Zd:floor ceiling

Nominal cooling capacity


22:2.2KW 25:2.5KW 28:2.8KW 32:3.2KW
36:3.6KW 40:4.0KW 45:4.5KW 50:5.0KW
56:5.6KW 63:6.3KW 71:7.1KW 80:8.0KW
90:9.0KW 100:10KW 112:11.2KW 125:12.5KW
140:14.0KW

Digital scroll type

GREE multi variable

Example
GMV R22G/NaB-K A wall mounted indoor unit of GREE, and the nominal cooling capacity is
2.2kw. It's the second generation product, and It could connect the outdoor unit. with digital scroll the
power supply is 220V/ /50Hz.

(2) Rated Conditions

Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB


Outdoor air temperature 35 (95.4 ) DB/24 (75.6 ) WB

Heating : Indoor air temperature 20 (68 ) DB/15 C(59 ) WB


Outdoor air temperature 7 (44.6 ) DB/6 (42.8 ) WB

11
12
2.4 Controller

Name Model Name Appearance Application Function

Start / Stop
mode Changing
Temperature setting
Air flow changing
Timing setting
Z60151F ROOM TEMP
Self-diagnosis function
Wired Z60351F
C Display codes of trouble.
controller Z63151F Control by 2 remote control -
SET TEMP
Z63351F SWING lers is available.
C SWING
Two remote controllers can be
MELT connected to one indoor unit.
remote
controller The indoor unit can be
remote
controller separately operated from the
isolated places.

FAN. button
Press the button to change Start / Stop
the speed of the fan a
according to the
following order.
mode Changing
SWING FAN AUTOFAN SPEED
Temperature setting
AUTOFAN OPER
AUTO
AIR
Air flow changing
TEMP. button
Set temp. increases 1
by pressing + and SWING COOL Timing setting
decreases 1by pressing TIMER DRY
ON/OFF HR.
remote .once. FAN
Y512A1 Set temp.:16~30 HEAT
Set temp.:16~30
controller Set temp.:16~30
Set temp.:16~30
ON/OFF. button
Press the button to turn on
MODE. button the unit. Press the button
Press the button to change once again to turn off the
the mode according to the MODE ON/OFF unit and cancel timer.
following order

remote
controller
Name Model Name Appearance Application Function
A.
Region Controller has two functions.
01 Function mode:

SINGLE 1 2 3 4 5 6 7 8
Region monitoring controller
INQUIRY
CENTER 9 10 11 12 13 14 15 16 Individual control up to 16 indoor
FUNC units.
Central control up to 16 indoor units
ERROR ROOM TEMP SHIELD Each outdoor can only connect one
FAN Region monitoring
SPEED controller Region monitoring controller.
C
Region ZJA011 two control mode
controller (MC207006) B. Individual control mode
LOCK
SET Central control mode
TIMER C 02 Function mode:
HR
SWING ON/OFF
. Region wired controller
It can replace the No.1-16 selected
wired controllers to uniformly set or
control the indoor units.

Region wired
controller

Individual control up to 1024 indoor


units.
Up to 64 outdoor units are connectable.
4 type central control setting to inhibit
individual operation by remote
A
controller can be selected.
Communication Three control mode:
Indoor control Outdoor unit
module 1
Individual control mode
Centralized ZJ7011 Central control mode
Central control A
controller (MC207004) Select control mode
Communication Each indoor unit can set Timer
module N Indoor control Outdoor unit On/Off time by central, single or
(The max. of N is 64)
select control. Both Timer On and
Timer Off can be set at the same
time, and it is available that set the
timer which days of the 7 days from
Sunday to Saturday works.
Modular Digital Multi VRF Technical Sales Guide

13
3 BASIC SYSTEM CONFIGURATION
System Legend (ex.)

Model name of outdoor unit:


GMV-Rm280W/Na-M
Allowed max. indoor unit:
16 units
Allowed capacity code of indoor unit: Outdoor unit

Min. : 140 Max. : 370 Capacity code over


28kW the branch
(25+22=47)

Capacity code 124 79 47


300
Indoor unit
Total 280
Capacity code
NO. of total unit
(45) (32) (25) (22)
12
88 66 44
176

(22) (22) (22) (22)

88 66 44

Wire
Controller (22) (22) (22) (22)

14
Modular Digital Multi VRF Technical Sales Guide

Outdoor unit
Capacity code
Model name of outdoor unit: over the branch
(28+28=56)
45kW
GMV-Rm450W/Na-M
120 163 56
Allowed max. indoor unit: Indoor unit
16 units 560 Capacity code

Allowed capacity code of indoor unit: (36) (28) (28) (28)

Min. : 225 Max. : 600 88 66 44

C apacity code
(22) (22) (22) (22)
T otal 450 88 66 44
No. of total units
16 352

(22) (22) (22) (22)

88 66 44

(22) (22) (22) (22)


88 66 44

Outdoor unit
176
Capacity code over
56kW the branch (22) (22) (22) (22)
(28+22=50)
88 66 44
186 100 50
450
Indoor unit

Capacity code
Wire
(80) (56) (28) (22) controller (22) (22) (22) (22)

88 66 44
264

Model name of outdoor unit:


(22) ( 22) (22) (22) GMV-Rm560W2/Na-M
176 88 66 44 Allowed max. indoor unit:
32 units

(22) (22) (22) (22)


Allowed capacity code of indoor unit:
88 66 44 Min. : 280 Max. : 756

Wire C apacity code


Controller (22) (22) (22) (22)
T otal 560
No. of total units
24

15
Model name of outdoor unit:
GMV-Rm900W2/Na-M
Allowed max. indoor unit:
Outdoor unit
Capacity code
32 units over the branch
(56+36=92)
Allowed capacity code of indoor unit: 90kW

Min. : 450 Max. : 1215 253 163 92


Indoor unit

900 Capacity code


C apacity code
(90) (71) (56) (36)
T otal 900
119 79 47
No. of total units
32

(40) (32) (25) (22)


88 66 44

528

(22) (22) (22) (22)

88 66 44

(22) (22) (22) (22)


88 66 44

352

(22) (22) (22) (22)

88 66 44

(22) (22) (22) (22)


88 66 44

176

(22) (22) (22) (22)

88 66 44

Wire
controller (22) (22) (22) (22)

16
Modular Digital Multi VRF Technical Sales Guide

Model name of outdoor unit:


GMV-Rm1800W4/Na-M C apacity code
Allowed max. indoor unit: T otal 1800
64 units No. of total units
Allowed capacity code of indoor unit: 64
Min. : 900 Max. : 2430

Outdoor unit Capacity code


over the branch
(56+36=92)
180kW

253 163 92 253 163 92


Indoor unit

900 900 Capacity code

(90) (71) (56) (36) (90) (71) (56) (36)

119 79 47 119 79 47

(40) (32) (25) (22) (40) (32) (25) (22)


88 66 44 88 66 44

528 528

(22) (22) (22) (22) (22) (22) (22) (22)

88 66 44 88 66 44

(22) (22) (22) (22) (22) (22) (22) (22)


88 66 44 88 66 44

352 352

(22) (22) (22) (22) (22) (22) (22) (22)

88 66 44 88 66 44

(22) (22) (22) (22) (22) (22) (22) (22)


88 66 44 88 66 44

176 176

(22) (22) (22) (22) (22) (22) (22) (22)

88 66 44 88 66 44

Wire
(22) (22) (22) (22) controller (22) (22) (22) (22)

17
4 EQUIPMENT SELECTION PROCEDURE

4.1 Selection Flow Chart

1.Determination of indoor air conditioning load

2.Preliminary selection of indoor units

3.Preliminary selection of outdoor unit with indoor units

4.Capacity correction for piping length/height between indoor and outdoor units

5.Capacity correction based on indoor and outdoor temperature

6.Validate preliminary selection of indoor units

NO
7.Confirmation of selection for indoor unit and outdoor units
YES
END

18
Modular Digital Multi VRF Technical Sales Guide

4.2 Combination Conditions for Indoor Unit and Outdoor Unit


Capacity code of each indoor unit=Capacity of each indoor unit(unit:kW).
For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are
decided.
Capacity code Max. No. of
Model name of outdoor unit Total capacity code of indoor units
of outdoor unit indoor units
GMV-Rm224W/Na-M 224 16 112to302.4
GMV-Rm280W/Na-M 280 16 140to378
GMV-Rm335W/Na-M 335 16 167.5to452.25
GMV-Rm400W/Na-M 400 16 200to540
GMV-Rm450W/Na-M 450 16 225to607.5
GMV-Rm504W/Na-M 504 16 252to680.4
GMV-Rm560W2/Na-M 560 32 280to756
GMV-Rm615W2/Na-M 615 32 307.5to830.25
GMV-Rm670W2/Na-M 670 32 335to904.5
GMV-Rm730W2/Na-M 730 32 365to985.5
GMV-Rm800W2/Na-M 800 32 400to1080
GMV-Rm850W2/Na-M 850 32 425to1147.5
GMV-Rm900W2/Na-M 900 32 450to1215
GMV-Rm954W2/Na-M 954 32 477to1287.9
GMV-Rm1008W2/Na-M 1008 32 504to1360.8
GMV-Rm1070W3/Na-M 1070 48 535to1444.5
GMV-Rm1135W3/Na-M 1135 48 567.5to1532.25
GMV-Rm1200W3/Na-M 1200 48 600to1620
GMV-Rm1250W3/Na-M 1250 48 625to1687.5
GMV-Rm1300W3/Na-M 1300 48 650to1755
GMV-Rm1350W3/Na-M 1350 48 675to1822.5
GMV-Rm1405W3/Na-M 1405 48 702.5to1896.75
GMV-Rm1458W3/Na-M 1458 48 729to1968.3
GMV-Rm1512W3/Na-M 1512 48 756to2041.2
GMV-Rm1600W4/Na-M 1600 64 800to2160
GMV-Rm1650W4/Na-M 1650 64 825to2227.5
GMV-Rm1700W4/Na-M 1700 64 850to2295
GMV-Rm1750W4/Na-M 1750 64 875to2362.5
GMV-Rm1800W4/Na-M 1800 64 900to2430
GMV-Rm1854W4/Na-M 1854 64 927to2502.9
GMV-Rm1908W4/Na-M 1908 64 954to2575.8
GMV-Rm1962W4/Na-M 1962 64 981to2648.7
GMV-Rm2016W4/Na-M 2016 64 1008to2721.6

4.3 Cooling/Heating Capacity Characteristics


4.3.1 Cooling Capacity Calculation Method

Required cooling capacity = Cooling capacity Factor Factor -Factor )

19
Ambient Temperature vs. Capacity Correction Value

52 125.6
68

68
48 118.4

Outdoor air dry bulb temp. ( )


0.

0.
Outdoor air dry bulb Temp.( )

76

76
0.

0.
84

84
42 107.6
0.

0.
92

92
0.

0.
00

00
36 96.8
1.

1.
05

50
1.

1.
10

10
1.

1.
30 86.0
15

15
1.

1.
20

20
1.

1.
24 75.2
25

25
1.

1.
18 64.4
14 16 18 20 22 24 26 57.2 60.8 64.4 68.0 71.6 75.2 78.8

Indoor air wet bulb temp. ( ) Indoor air wet bulb temp. ( )

Connecting Pipe Length Between Indoor and Outdoor Units vs. Capacity Correction Value

Equivalent pipe length m/ft 5/16 10/32 15/49 20/65 25/82 30/98 35/114 40/131 45/147 50/164
Correction value 1.0 0.992 0.984 0.976 0.98 0.960 0.952 0.944 0.936 0.928

Equivalent pipe length m/ft 55/180 60/196 65/213 70/229 75/246 80/262 85/278 90/295 95/311 100/328
Correction value 0.920 0.912 0.904 0.896 0.888 0.880 0.872 0.864 0.856 0.848

Equivalent pipe length m/ft 105/344 110/360 115/377 120/393 125/410 130/426 135/442 140/459 145/475 150/492
Correction value 0.840 0.832 0.824 0.816 0.808 0.800 0.792 0.784 0.776 0.768

Equivalent pipe length m/ft 155/508 160/524 165/541170/557 175/574


Correction value 0.760 0.752 0.744 0.736 0.728

a. The calculation method of equivalent pipe length


Equivalent pipe length = The real pipe length between the farthest indoor unit and the outdoor unit +
The quantity of 90 o elbow between the outdoor unit and the farthest indoor unit the equivalent pipe
length of 90 o elbow (see the following table) + the quantity of branch joint between the outdoor unit
and the farthest indoor unit the equivalent of branch joint
b. The equivalent pipe length calculation method of 90 o elbow
The equivalent pipe length of 90 o elbow
Diameter of gas pipe mm(Inch) 12.7(1/2) 5.9(5/8) 19.05(3/4) 22.2(7/8) 25.4(1) 28.6(11/8) 34.9(13/8) 1.3(15/8)
Equivalent pipe length m(ft) 0.1(0.32) 0.1(0.32) 0.15(0.49) 0.15(0.49) 0.15(0.49) 0.2(0.65) 0.25(0.82) 0.25(0.82)

c. The equivalent pipe length of a branch joint is 0.5m.


Height Difference Between Indoor and Outdoor Units vs. Capacity Correction Value

Height difference between 5/16 10/32 15/49 20/65 25/82 30/98 35/114 40/131 45/147 50/164
indoor &outdoor(m/ft)
Correction value 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10

20
18
Modular Digital Multi VRF Technical Sales Guide

4.3.2 Heating Capacity Calculation Method

Required heating capacity = Heating capacity Factor (Factor -Factor )

Ambient Temperature vs. Capacity Correction Value

27 80.6
26 78.8
0.70

0.70
0.75

0.75
24 75.2

0.80
0.80
)

0.85

0.85
0.90
0.90

Indoor air dry bulb temp. (


0.95

0.95
Indoor air dry bulb Temp.(

22 71.6

1.00
1.00

1.05
1.05

1.10
1.10

1.15
1.15

20 68.0

18 64.4

16 60.8

14 57.2

12 53.6

10 50.0
-15 -10 -5 0 5 10 15 5.0 14.0 23.0 32.0 41.0 50.0 59.0

Outdoor air wet bulb temp. ( ) Outdoor air wet bulb temp. ( )

Connecting Pipe Length Between Indoor and Outdoor Units vs. Capacity Correction Value

Equivalent pipe length m/ft 5/16 10/32 15/49 20/65 25/82 30/98 35/114 40/131 45/147 50/164
Correction value 1.0 1.0 1.0 1.0 1.0 0.995 0.995 0.99 0.99 0.99

Equivalent pipe length m/ft 55/180 60/196 65/213 70/229 75//246 80/262 85/278 90/295 95/311 100/328
Correction value 0.985 0.985 0.985 0.98 0.98 0.98 0.975 0.975 0.975 0.965

Equivalent pipe length m/ft 105/344 110/360 115/377 120/393 125/410 130/426 135/442 140/459 145/475 150/492
Correction value 0.965 0.965 0.96 0.96 0.96 0.955 0.955 0.95 0.95 0.95

Equivalent pipe length m/ft 155/508 160/524 165/541170/557 175/574


Correction value 0.945 0.945 0.940 0.940 0.935

a. The calculation method of equivalent pipe length


Equivalent pipe length =The real pipe length between the farthest indoor unit and the outdoor uni+
The quantity of elbow between the outdoor unit and the farthest indoor unit the equivalent pipe
length of elbow (see the following table) + the quantity of branch joint between the outdoor unit and
the farthest indoor unit he equivalent of branch joint
o
b. The equivalent pipe length calculation method of 90 elbow
The equivalent pipe length of 90o elbow

Diameter of gas pipe mm(Inch) 12.7(1/2) 5.9(5/8) 19.05(3/4) 22.2(7/8) 25.4(1) 28.6(11/8) 34.9(13/8) 1.3(15/8)
Equivalent pipe length m(ft) 0.1(0.32) 0.1(0.32) 0.15(0.49) 0.15(0.49) 0.15(0.49) 0.2(0.65) 0.25(0.82) 0.25(0.82)

c. The equivalent pipe length of a branch joint is 0.5m.

21
Lift Difference Between Indoor and Outdoor Units vs. Capacity Correction Value

Height difference between 5/16 10/32 15/49 20/65 25/82 30/98 35/114 40/131 45/147 50/164
indoor &outdoor(m/ft)
Correction value 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10

4.3.3 Capacity Calculation for Each Indoor Unit

Capacity for each indoor unit


The nominal capacity of the indoor unit
= Capacity after correction of outdoor unit
Total nominal capacity of indoor unit

4.3.4 Working Range

Mode Range Outdoor temperature


Cooling -5 ~43 (23~109.4 )
Heating -15 ~27 (5~81 )

4.4 Example of Equipment Selection


4.4.1 Overview of Building Model

<Outside view> <Rooms configuration>


8m

2F 2 1 2 2 2 3 2 4 2 5 Office rooms
(2 1, 2 2 : Computer room)
2F

1F
2m

1 4
1 1
7.

14.4m 1F 1 3
1 2

Steel frame, reinforced concrete building,


Non-air conditioning zone
four stories above ground.
2
Total floor area : 210 m
Outdoor unit is installed on the roof.
Design indoor conditions
Cooling : 27.0 (81 )/19.0 (66.6 ) DB/WB
Design outdoor conditions
Cooling : 35 (95.4 ) DB (Standard condition)

22
Modular Digital Multi VRF Technical Sales Guide

4.4.2Selection Criteria for Each Floor

2F : Outdoor capacity exactly matches the total indoor capacity.

Total indoor HP = Outdoor unit HP Indoor : 2.5 HP x 2 units + 1.25 HP + 2 HP x 2 = 10.25 HP

Outdoor : 10 HP (Same capacity)

Heat load of room 2-1 and 2-2 is higher than other rooms.
1F : Consider the increasing heat load in the specific room.
Total indoor units HP > Outdoor unit HP
Select each indoor unit based on individual peak room load.

Indoor : 2.5HP + 2.5HP + 3.2HP + 2.0HP =10.2HP

Outdoor : 10HP (Same capacity)

The outdoor module should have sufficient capacity to cover the peak demand of the indoor unit
connected.

4.4.3 Procedure and Result of Equipment Selection

A. Procedure of Equipment Selection


Calculate cooling for every rooms.
Select an indoor unit to match the cooling load for every room.
Choose a tentative outdoor that will match with the indoor units. Perform capacity correction based on
the pipe length, system lift, indoor set temperature, outdoor temperature. Then, make sure the
corrected system cooling capacity satisfies the cooling load.
B.Equipment Selection and Capacity Check

Air conditioning load Equipment selection


Indoor unit Outdoor unit
Indoor cooling
Floor Room No Capacity(kW) Capacity(kW)
load(kW) Model Model
Cooling Heating Cooling Heating
2-1 6.0 GMV-R71P/Na-K 7.1 8.0
2-2 5.2 GMV-R56P/Na-K 5.6 6.3
1F 2-3 5.0 GMV-R56P/Na-K 5.6 6.3
2-4 3.2 GMV-R36P/Na-K 3.6 4.0
2-5 6.4 GMV-R71P/Na-K 7.1 8.0 GMV-Rm280 28 31.5
1-1 6.1 GMV-R71P/Na-K 7.1 8.0 W/Na-M
1-2 6.3 GMV-R71P/Na-K 7.1 8.0
2F
1-3 7.2 GMV-R71P/Na-K 7.1 8.0
1-4 5.1 GMV-R56P/Na-K 5.6 6.3

23
Piping distance Capacity correction Capacity check after correction
Pipe correction x temp.
Equivalent Height correction Capacity(kW)
Floor Room No. length (m) difference (m) Judgment
Cooling Heating Cooling Heating
2-1 7.0 7.6
2-2 (0.995-0) 5.6 6.0
(0.960-0)
2F 2-3 30 1.5 0.94 5.6 6.0 good
1.0=0.960
2-4 =0.935 3.5 3.8
2-5 7.0 7.6
1-1 6.7 7.6
1-2 (0.99-0.01) 6.7 7.6
(0.928-0.01) good
1F 50 5 0.94
1-3 1.0=0.918 =0.920 6.7 7.6
1-4 5.3 5.9

Conversion Formula: KW=Btu/h 3412


c. Schematic Diagram

GMV-Rm560W2/Na-M

Outdoor unit

1st branching 2rd branching 3th branching 4th branching


joint joint joint joint

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
GMV-R71P/Na-K GMV-R56P/Na-K GMV-R56P/Na-K GMV-R36P/Na-K GMV-R71P/Na-K

R R R R R

Computer
Computer Computer
Office Office Office
Room
Room Room
2 1 2 2 2 3 2 4 2 5

5th branching 6th branching 7th branching


joint joint joint

Indoor unit Indoor unit Indoor unit Indoor unit


GMV-R71P/Na-K GMV-R71P/Na-K GMV-R71P/Na-K GMV-R56P/Na-K

R R R R

Store Store Restaurant Kitchen


1 1 1 2 1 3 1 4

24
Modular Digital Multi VRF Technical Sales Guide

5 REFRIGERANT PIPING DESIGN


5.1 Warning on Refrigerant Leakage
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant
gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410 which is used in the air conditioner is safe, without the toxicity or combustibility of
ammonia. However, since it contains more than air, it poses the risk of suffocation if its concentration
should rise excessively. Suffocation from leakage of R410 is almost non-existent. With the recent
increase in the number of high concentration buildings, the installation of multi air conditioner systems
is on the increase because of the need for effective use of floor space, individual control, energy
conservation by curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant com
pared with conventional individual air conditioners. If a single unit of the multi conditioner system is to
be installed in a small room, select a suitable model and installation procedure so that if the refrigerant
accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency,
measures can be made before injury can occur).
In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or
install mechanical ventilation combined with a gas leak detection device.
5.1.1 The Concentration Limit of R410 Which is Used in Multi Air Conditioners
The concentration limit of R410 which means the concentration limit of R410 that can be control by
emergency measures to prevent human body from harming. The refrigerant concentration unit is kg/m3
(Which means the weight of refrigerant per m3 air ).

outdoor unit
(No.1 system)Refrigerant flow

Indoor unit

Fig.5.1
5.1.2 Check of Refrigerant Leakage
Calculate the refrigerant concentration as follows:
Calculate the Amount of Refrigerant of Each Refrigeration System
The amount of refrigerant of each system of outdoor unit:
Refrigerant amount of the outdoor unit at factory
Additional charged amount at field installation:
According to the liquid tube length and diameter
[The amount of refrigerant of each system of outdoor unit] + [Additional charged amount
at field installation]= System total amount of refrigerant(kg)

25
NOTE:

When single refrigeration system is consists of several independent refrigeration circuit, figure out the
total refrigerant amount by each independent refrigerant circuit.

For the amount of charge in this example:

Outdoor unit
e.g., charged e.g., charged
amount (12kg) amount (16kg)

Room A Room B Room C Room D Room E Room F


Indoor unit

Fig.5.2
The possible amount of leaked refrigerant gas in rooms A, B and C is 12kg.
The possible amount of leaked refrigerant gas in rooms D, E and F is 16kg.
No partition (shaded portion)

Outdoor unit

Indoor unit Indoor unit Indoor unit

Fig.5.3

Indoor unit Indoor unit

Fig.5.4

26
Modular Digital Multi VRF Technical Sales Guide

If an indoor unit is installed in each partitioned room and the refrigerant tubing is interconnected,
the smallest room of course becomes the object.

Outdoor unit

Indoor unit
The smallest
room

The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m3
Use the results of calculations and to calculate the refrigerant concentration:
The concentration is as given below.

Total amount of refrigerant (kg)


Concentration limit (kg/m 3 )
Min. volume of the indoor unit installed room (m 3 )

5.1.3 Measures When The Refrigerant Concentration Limit is Exceeded


When the refrigerant concentration exceeds the density limit value relative to indoor volume, take
proper actions according to following key points:
Method 1: Set up an opening for efficient air exchange
opening with a door, or an opening 0.15% or larger than the respective floor spaces at the top or
bottom of the door
Method 2: Decrease the total amount of refrigerant in refrigerant equipment
Shorten the Length of Refrigerant Pipe
Install the outdoor unit closer to the indoor unit and shorten the length of refrigerant pipe, hence to
decrease the total amount of refrigerant in refrigerant equipment.
Decrease the Capacity of Outdoor Unit
Split the outdoor unit into multiple sets, thus decreasing the capacity of each outdoor unit to which one
refriger ant system corresponds and hence to decrease the filling amount of refrigerant. -

If one 20HP system is split into 2 sets of 10HP systems, the amount of refrigerant in
For example:
one refrigerant system may be half decreased approximately.
Method 3: Set up an air exchange system
An air exchange system can be set to avoid too high concentration of refrigerant in event of refrigerant
leakage. The air exchange system includes twp types, i.e. external air import and air discharge. From
the property of refrigerant, it is recommended to adopt the external air import.
Exchanging Air Volume
According to the total amount of refrigerant of refrigerant equipment and the room volume, air
exchange volume should be greater than the volum e showed in Fig.5.6.

27
Choose of the exchange air volume

(m2)

The total amount of refrigerant of indoor units


55 150 3 /h
Range below the density limit of 0.3 kg/m3 0m 3 /h
50 m
(countermeasures not needed) 10
(When the ceiling is 2.7m high)

45 3 /h
m
P56 15
40 3 /h
m
100 20
Min. indoor floor area

35 P45 h
Room volume(m2) m/
3

30 25
P36
25 3 /h
P28 30m
20
50 Range above
15 P22 the density limit
3 /h of 0.3kg/m3
10 33m
(countermeasures
5
needed)
0
0
0 10 20 30 40 50

The total amount of refrigerant of outdoor unit

Fig:5.6

Detector and Interlink


In principle, the air exchange system shall always work normally no matter the air conditioner is used
or any person stays in the room. If it is impossible to realize long-term working, please use a detector
system to activate the air exchange system upon leakage of refrigerant.
Shown in Fig. 5.7 is the air exchange system in long-term working. Shown in Fig. 5.8 is the detector
interlink system.

Note:

In order to avoid malfunction of air exchange system, please do not choose the range showed in
oblique line in Fig. 5.6 even though equipped with air exchange system. If entering into this range,
should set effective air exchange port, expand room volume or decrease the amount of outdoor unit,
change the piping length in order to decrease total refrigerant amount, in principle according to
method 1 and 2.
Where an air exchange system is provided but it is impossible to take Method 1 or Method 2 when
the refrigerant concentration is within the range indicated by the oblique line in Fig. 5.6, please use
other means independent from air exchange system to ensure safety. In detail, we can set a
refrigerant cutoff valve that can be activated by the detector upon refrigerant leakage and as well,
set an alarm system that can notify the indoor person. The detector here is different from the
detector in aforementioned air exchange system. Shown in Fig. 5.9 is the status that a refrigerant
cutoff valve is set.
To set an air exchange system, please ensure to leave an efficient air exchange gap (e.g. gap below
the door) at the lowest part of the room.
For connection of pipes within living area, please make sure to comply with JIS specification and
perform thorough airtight test after the work is completed. Additionally, please ensure that the pipe
is installed with shockproof device to avoid damage due to earthquake or the other external forces.
(But on axial direction, a leeway shall be left to eliminate the stress caused by temperature variation).

28
Modular Digital Multi VRF Technical Sales Guide

Long Term Working Air Exchange System

Out air Import fan(always running)


Refrigerant piping

Connect with outdoor


and indoor units
indoor unit

Room

Floor board
Peristome

Fig.5.7

Detector Interlink System

Out air Import fan(always running)


Refrigerant piping

Connect with outdoor


and indoor units
indoor unit

Room

Floor board
Peristome

Gas leakage detector(including oxygen detector and refrigerant detector)


must be installed above 0.3m from the floor,where the refrigerant resort.
Fig.5.8

Position of Long Term Running Ventilation System and Refrigerant Cut-off Valve

Refrigerant cut-off valve


(stop when power OFF) Out air Import fan(always running)
Refrigerant piping

Connect with outdoor


and indoor units
indoor unit

Room

Floor board
Peristome

Gas leakage detector(including oxygen detector and refrigerant detector)


must be installed above 0.3m from the floor,where the refrigerant resort.
Fig.5.9

29
5.2 Flexidle Branching System
Line branching system

Outdoor unit

Y-shape branching joint

Indoor unit

Remote Controller

Outdoor unit
Y-shape branching joint

Remote Controller

Indoor unit

5.3 Allowable Length/Height Difference of Refrigerant Piping

GMV-Rm224W/Na-M GMV-Rm280W/Na-M GMV-Rm335W/Na-M


GMV-Rm400W/Na-M GMV-Rm450W/Na-M GMV-Rm504W/Na-M
GMV-Rm560W2/Na-M GMV-Rm615W2/Na-M GMV-Rm670W2/Na-M
GMV-Rm730W2/Na-M GMV-Rm800W2/Na-M GMV-Rm850W2/Na-M

Allowable Value Fitting Pipe

Total length (actual length) of fitting pipe 984ft 300m L1+L2+L3+L4+L5+L6+a+b+ +i+j

Length of farthest Actual length 328ft 100m


L1+L3+L4+L5+L6+j
fitting pipe Equivalent length 410ft 125m
Equivalent length from the 1st manifold pipe
131ft 40m L3+L4+L5+L6+ j
to farthest fitting pipe
Height difference Outdoor unit at upper 164ft 50m
between outdoor
unit and indoor
unit Outdoor unit at lower 131ft 40m

Height difference between indoor units 49ft 15m

30
Modular Digital Multi VRF Technical Sales Guide

Height difference between indoor unit and outdoor unit H 50M


Outdoor unit

L3 L4
L1 L2

1st Indoor unit

Height difference between indoor units H


branching a b c d
section

L5 Equivalent length of the farthest fitting pipe L

Equivalent length from the 1st manifold


pipe to farthest fitting pipe
L7 L8
L6

e f g h i
Indoor unit

Equivalent length is based on one Y-shape branching joint pipe per 1.64ft.

GMV-Rm900W2/Na-M GMV-Rm954W2/Na-M GMV-Rm1008W2/Na-M


GMV-Rm1070W3/Na-M GMV-Rm1135W3/Na-M GMV-Rm1200W3/Na-M
GMV-Rm1250W3/Na-M GMV-Rm1300W3/Na-M GMV-Rm1350W3/Na-M
GMV-Rm1405W3/Na-M GMV-Rm1458W3/Na-M GMV-Rm1512W3/Na-M
GMV-Rm1600W4/Na-M GMV-Rm1650W4/Na-M GMV-Rm1700W4/Na-M
GMV-Rm1750W4/Na-M GMV-Rm1800W4/Na-M GMV-Rm1854W4/Na-M
GMV-Rm1908W4/Na-M GMV-Rm1962W4/Na-M GMV-Rm2016W4/Na-M

Allowable Value Fitting Pipe

Total length (actual length) of fitting pipe 1640ft 500m L1+L2+L3+L4+L5+L6+a+b+ +i+j

Actual length 492ft 150m


Length of farthest
L1+L3+L4+L5+L6+j
fitting pipe
Equivalent length 574ft 175m

Equivalent length from the 1st manifold pipe


131ft 40m L3+L4+L5+L6+ j
to farthest fitting pipe

Height difference Outdoor unit at upper 164ft 50m


between outdoor
unit and indoor
unit Outdoor unit at lower 131ft 40m

Height difference between indoor units 49ft 15m

31
Outdoor unit
Height difference between indoor unit and outdoor unit H 50M

L3 L4
L1 L2

1st Indoor unit


a b c d

Height difference between indoor units H


branching
section

L5 Equivalent length of the farthest fitting pipe L

Equivalent length from the 1st manifold


pipe to farthest fitting pipe
L7 L8
L6

e f g h i
Indoor unit

Equivalent length is based on one Y-shape branching joint pipe per 1.64ft.

5.4 Selection of Refrigerant Piping

5.4.1 Size of Main Pipe

Capacity code of the Gas pipe (OD) Liquid pipe (OD)


indoor units Inch Inch
224<C 280 22.2 9.52
280<C 450 28.6 11/8 12.7 1/2
450<C 670 28.6 11/8 15.9 5/8
670<C 954 34.9 13/8 19.05 3/4
954<C 1350 41.3 15/8 19.05 3/4
1350<C 1600 44.5 4/7 22.2 7/8
1600<C 2100 54.1 17/8 25.4 1

5.4.2 Pipe Size Between Branching Joints


According to the total capacity code of indoor units at downstream side (take the total capacity code of
,
outdoor unit as while the total capacity code of indoor units exceed the outdoor unit s), pipe size
between branching joints as follows:

32
Modular Digital Multi VRF Technical Sales Guide

Capacity code of the indoor Gas pipe (OD) Liquid pipe (OD)
units at downstream side C Inch Inch
C 50 12.7 1/2 6.35 1/4
50<C 70 15.9 5/8 9.52 3/8
70<C 180 19.05 3/4 9.52 3/8
180<C 300 22.2 7/8 9.52 3/8
300<C 450 28.6 9/8 12.7 1/2
450<C 670 28.6 9/8 15.9 5/8
670<C 950 34.9 11/8 19.05 3/4
950<C 1350 41.3 13/8 19.05 3/4
1350<C 1600 44.5 7/4 22.2 7/8
1600<C 2100 54.1 17/8 25.4 1

5.4.3 Piping of Indoor Unit

Wall-mounted Type 4-way Cassette Type/ Duct Standard Type/Floor ceilingType

Capacity range Gas pipe (OD) Liquid pipe (OD) Capacity range Gas pipe (OD) Liquid pipe (OD)
of indoor unit C Inch Inch of indoor uni C Inch Inch
22 C 28 9.52 3/8 6.35 1/4 22 C 28 9.52 3/8 6.35 1/4
36 12.7 1/2 6.35 1/4 36 C 50 12.7 1/2 6.35 1/4
45 C 56 12.7 1/2 9.52 3/8 56 C 140 15.9 5/8 9.52 3/8
71 C 80 15.9 5/8 9.52 3/8

5.4.4 Selection for Branching Section

Total capacity of downstream Model Total capacity of downstream Model


indoor unit X indoor unit X
X 200 FQ01A/A 300<X 700 FQ02/A
Y-Type Manifold Pipe
700<X 1350 FQ03/A
200<X 300 FQ01B/A
X 1350 FQ04/A

5.4.5 Selection for Branching between Outdoor Section


The connection pipe between outdoor and first Y type refnet.
It is the same as the requirement of single unit system

R410a system

Single unit capacity C Gas pipe(mm) Liquid pipe(mm)


C 280 22.2 9.52
280<C 450 28.6 12.7
450<C 560 28.6 15.9

33
The connection pipe between the outdoor unit Y type refnet.
It is needed when there re more than two units combined together.

R410a system

Up stream single unit capacity C Gas pipe(mm) Liquid pipe(mm)


C 280 22.2 9.52
280<C 450 28.6 12.7
450<C 670 28.6 15.9
670<C 954 34.9 19.05
954<C 1350 41.3 19.05
1350<C 1600 44.5 22.2
1600<C 2100 54.1 25.4

Oil balance pipe


It is connected with 9.52 copper pipe, an 9.7 oil balancing connection three-way
valve is needed when there re more than two units combined together.

5.5 Charging Requirement with Additional Refrigerant


When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the
pipes at the site is not included. Calculate the additional amount needed, and add that amount to the
system.
Model name GMV-Rm224W/Na-K GMV-Rm280W/Na-M GMV-Rm335W/Na-M
Refrigerant amount charged in factory 14kg 16kg 17kg

Model name GMV-Rm400W/Na-M GMV-Rm450W/Na-M GMV-Rm504W/Na-M


Refrigerant amount charged in factory 18kg 20kg 20kg

5.5.2 [Additional Refrigerant Charge Amount] = [Real Length of Liquid Pipe]


[Additional Refrigerant Charge Amount Per Meter Liquid Pipe]
Amount of Additional Refrigerant to Be Filled Per Meter of Liquid Pipe kg/m
28.6 25.4 22.2 19.05 15.9 12.7 9.52 6.35
Liquid pipe dia.
Inch 11/8 1 7/8 3/4 5/8 1/2 3/8 1/4
Additional amount (kg/m) 0.680 0.520 0.350 0.250 0.170 0.110 0.054 0.022

Note: Standard pipe length is 49.2ft.1m=3.2808ft


If the liquid pipe length is shorter than 49.2ft, additional refrigerant isn't needed;
If the liquid pipe length is longer than 49.2ft, calculate the additional refrigerant amount according to
the above table.

34
Modular Digital Multi VRF Technical Sales Guide

6 WIRING DESIGN
6.1 General
(1) Perform wiring of the power supply in conformance with the regulations of the local electric
company..
(2) For the control wires connecting indoor units, and between indoor and outdoor units, use of
twisted-pair shield wires is recommended to prevent noise trouble.
(3) Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor
unit.
(4) Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each
outdoor unit.
(5) Store wiring system for control and refrigerant piping system in the same line.
(6) Arrange the cables so that the electric wires do not contact with high-temperature part of the
pipe;otherwise coating melts and an accident may be caused.
(7) Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe finish.

6.2 Electrical Wiring Design


6.2.1 Wiring Drawing

3-phase
50Hz 380 Earth

Outdoor
power supply

Earth leakage breaker hand switch

Earth leakage breaker


hand switch Pull box

Indoor power supply


Single phase
50Hz 220-240V

Indoor unit Indoor unit Indoor unit Indoor unit

Indoor unit Indoor unit Indoor unit Indoor unit

35
6.2.2 Selection of Power Supply Cabing and Fuse of Units

Outdoor unit
Model 2
Fiele fuse (A) Wire size (mm )
GMV-Rm224W/Na-M 20 4.0
GMV-Rm280W/Na-M 25 6.0
GMV-Rm335W/Na-M 32 6.0
GMV-Rm400W/Na-M 40 10.0
GMV-Rm450W/Na-M 40 10.0
GMV-Rm504W/Na-M 40 10.0
GMV-Rm560W2/Na-M 50 16.0
GMV-Rm615W2/Na-M 63 25.0
GMV-Rm670W2/Na-M 63 25.0
GMV-Rm730W2/Na-M 63 25.0
GMV-Rm800W2/Na-M 80 35.0
GMV-Rm850W2/Na-M 80 35.0
GMV-Rm900W2/Na-M 80 35.0
GMV-Rm954W2/Na-M 100 50.0
GMV-Rm1008W2/Na-M 100 50.0
GMV-Rm1070W3/Na-M 100 50.0
GMV-Rm1135W3/Na-M 100 50.0
GMV-Rm1200W3/Na-M 100 50.0
GMV-Rm1250W3/Na-M 125 70.0
GMV-Rm1300W2/Na-M 125 70.0
GMV-Rm1350W3/Na-M 125 70.0
GMV-Rm1405W3/Na-M 160 95.0
GMV-Rm1458W3/Na-M 160 95.0
GMV-Rm1512W3/Na-M 160 95.0
GMV-Rm1600W4/Na-M 160 95.0
GMV-Rm1650W4/Na-M 160 95.0
GMV-Rm1700W4/Na-M 160 95.0
GMV-Rm1750W4/Na-M 160 95.0
GMV-Rm1800W4/Na-M 160 95.0
GMV-Rm1854W4/Na-M 180 120.0
GMV-Rm1908W4/Na-M 180 120.0
GMV-Rm1962W4/Na-M 180 120.0
GMV-Rm2016W4/Na-M 180 120.0
Indoor Unit 6 1
Determine the wire size for indoor unit according to the number of connected indoor units downstream.
Observe local regulation regarding wire size selection and installation.
NOTE :

The connecting length indicated in the table represents the length from the pull box to the outdoor unit
when the indoor units are connected in parallel for power, as shown in the above illustration. A
voltage drop of no more than 2% is also assumed. If the connecting length will exceed the length
indicated in the table, select the wire thickness in accordance with local wiring standards.

36
Modular Digital Multi VRF Technical Sales Guide

CAUTIONS
Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems
together.
When running power wires and control wires parallel to each other. either run them through
separate conduits or (Current capacity of power wires: 10A or less for 300m, 50A or less for
500m).

6.3 Design of Control Wiring


6.3.1 Control Wiring Drawing

Transmission system
Transmission system

RS232-485

Region wired Wired controller


controller
GMV-Rm900W2/Na-M
Central remote controller
ZJ7011

Communication module
ZJ301-W
Region wired
controller

To next communication module


Up to 64 communication modules
are connectable
Region wired
controller
GMV-Rm280W/Na-M

6.3.2 Wire Specification, Quantity, Size of Crossover Wiring and Remote Controller Wiring

Name Quantity Size&Specification


Transmission wire between outdoor and indoor
2 cores
Transmission wire between outdoor and indoor
Ul 2835 24
wiring(indoor-wired conrtoller)

6.4 Wiring Diagram of Units

WIRED WIRED WIRED


CONTROLLER CONTROLLER CONTROLLER

OUTDOOR UNIT
(CN20)

PCB PCB PCB


CN10

CN14 CN14 CN14


CN15

CN16

CN15

CN16

CN15

CN16

PCB

INDOOR UNIT INDOOR UNIT INDOOR UNIT

Eearth leakage breaker


Eearth leakage breaker hand switch
hand switch

POWER POWER

37
6.5 Parameters
6.5.1 Outdoor Unit
Voltage Range Compressor Fan Motor Power Supply
Model name
Min Max RLA LRA kW FLA MOCP MCA
GMV-Rm224W/Na-M 342 457 14 84 0.75 7 19.6 16
GMV-Rm280W/Na-M 342 457 16.9 101.4 0.75 7 23.66 20
GMV-Rm335W/Na-M 342 457 20.4 122.4 0.8 8 28.56 25
GMV-Rm400W/Na-M 342 457 24.1 144.6 0.8 8 33.74 32
GMV-Rm450W/Na-M 342 457 28.6 171.6 0.8 8 40.04 40
GMV-Rm504W/Na-M 342 457 30.9 185.4 0.8 8 43.26 40
GMV-Rm560W2/Na-M 342 457 34 204 1.5 14 47.6 40
GMV-Rm615W2/Na-M 342 457 37 222 1.5 14 51.8 50
GMV-Rm670W2/Na-M 342 457 40.8 244.8 1.6 15 57.12 50
GMV-Rm730W2/Na-M 342 457 44.5 267 1.6 15 62.3 63
GMV-Rm800W2/Na-M 342 457 48.2 289.2 1.6 15 67.48 63
GMV-Rm850W2/Na-M 342 457 51 306 1.6 15 71.4 63
GMV-Rm900W2/Na-M 342 457 57 342 1.6 15 79.8 80
GMV-Rm954W2/Na-M 342 457 57 342 1.6 15 79.8 80
GMV-Rm1008W2/Na-M 342 457 61.8 370.8 1.6 15 86.52 80
GMV-Rm1070W3/Na-M 342 457 64.4 386.4 2.4 24 90.16 80
GMV-Rm1135W3/Na-M 342 457 68.6 411.6 2.4 24 96.04 100
GMV-Rm1200W3/Na-M 342 457 72.3 433.8 2.4 24 101.22 100
GMV-Rm1250W3/Na-M 342 457 75 450 2.4 24 105 100
GMV-Rm1300W3/Na-M 342 457 77.7 466.2 2.4 24 108.78 100
GMV-Rm1350W3/Na-M 342 457 85.8 514.8 2.4 24 120.12 125
GMV-Rm1405W3/Na-M 342 457 88.1 528.6 2.4 24 123.34 125
GMV-Rm1458W3/Na-M 342 457 89.2 535.2 2.4 24 124.88 125
GMV-Rm1512W3/Na-M 342 457 92.7 556.2 2.4 24 129.78 125
GMV-Rm1600W4/Na-M 342 457 96.4 578.4 3.2 30 134.96 125
GMV-Rm1650W4/Na-M 342 457 101.8 610.8 3.2 30 142.52 125
GMV-Rm1700W4/Na-M 342 457 104.4 626.4 3.2 30 146.16 125
GMV-Rm1750W4/Na-M 342 457 109.4 656.4 3.2 30 153.16 125
GMV-Rm1800W4/Na-M 342 457 114.4 686.4 3.2 30 160.16 160
GMV-Rm1854W4/Na-M 342 457 116.7 700.2 3.2 30 163.38 160
GMV-Rm1908W4/Na-M 342 457 119 714 3.2 30 166.6 160
GMV-Rm1962W4/Na-M 342 457 121.3 727.8 3.2 30 169.82 160
GMV-Rm2016W4/Na-M 342 457 123.6 741.6 3.2 30 173.04 160

Note:
The cooling only type indoor units have no heating parameters.

LEGEND:

MCA: Minimum Circuit Amps LRA: Locked Rotor Amps


MOCP: Maximum Overcurrent Protection(Amps) FLA : Full Load Amps
kW: Fan Motor Rated Output(kW) RLA: Rated Load Amps
Note: RLA is based on the following conditions.
Indoor temperature: Outdoor temperature:
27 (81 ) DB/19 (66.6 ) WB 35 (95.4 ) DB/24 (75.6 ) WB

38
Modular Digital Multi VRF Technical Sales Guide

6.5.2 Indoor Unit

Nominal Voltage Voltage Range


Type Model (V-Ph-Hz) Min Max
GMV-R28T/Na-K
GMV-R36T/Na-K
GMV-R45T/Na-K
GMV-R50T/Na-K
GMV-R56T/Na-K
4-way cassette type GMV-R63T/Na-K
220-240V~ 50HZ 198V 264V
GMV-R71T/Na-K
GMV-R80T/Na-K
GMV-R90T/Na-K
GMV-R100T/Na-K
GMV-R112T/Na-K
GMV-R125T/Na-K
GMV-R140T/Na-K
GMV-R22P/Na-K
GMV-R25P/Na-K
GMV-R28P/Na-K
GMV-R32P/Na-K
GMV-R36P/Na-K
GMV-R40P/Na-K
GMV-R45P/Na-K
GMV-R50P/Na-K
Duct type 220-240V~ 50HZ 198V 264V
GMV-R56P/Na-K
GMV-R63P/Na-K
GMV-R71P/Na-K
GMV-R80P/Na-K
GMV-R90P/Na-K
GMV-R100P/Na-K
GMV-R112P/Na-K
GMV-R125P/Na-K
GMV-R140P/Na-K
GMV-R22G/NaB-K
GMV-R28G/NaB-K
GMV-R36G/NaB-K
GMV-R45G/NaB-K
Wall-mounted type 220-240V~ 50HZ 198V 264V
GMV-R50G/NaB-K
GMV-R56G/NaB-K
GMV-R71G/Na-K
GMV-R80G/Na-K
GMV-R28Zd/Na-K
GMV-R36Zd/Na-K
GMV-R50Zd/Na-K
Floor Ceiling Type GMV-R71Zd/Na-K 220-240V~ 50HZ 198V 264V
GMV-R90Zd/Na-K
GMV-R112Zd/Na-K
GMV-R125Zd/Na-K

39
7 ACCESSORIES

7.1 Outdoor Unit

Provide
Accessories m odel name Standard Option for oneself
Commun ication Line between units
Y-shape Branching Joint and
Collecting Pipe
Power Cable

7.2 Indoor Unit

Accessories model name Standard Option Provide for oneself


Power Cable
Remote Control ler
Wired Controller
Connecting Cable for Line Controller (8m)
Communication Line between units
Drain Pipe

7.3 Controller

Accessories name Model name Standard Option Remark


Z60151F (30296013)
Wired remote Z60351F (30296014)
controller Z63151F (30296308)
Z63351F (30296309)
Wireless remote Y512 Common parts for
controller (305125063) all type model

model. But on the other hand


Region controller ZJA011 (M C207006)
unable Region controller when
Central remote controller or
Long-distance control system is
put into use.
Central remote
ZJ7011 (M C207004)
controller
Long-distance
FC232/422-W
control system --
(E N0230001)
for GMV
Communication Use for Central remote
ZJ301-W (E N0210001)
Module controller or Long-distance

40
Modular Digital Multi VRF Technical Sales Guide

8 TECHNICAL SPECIFICATIONS
8.1 Indoor Unit
4-way Cassette Type
GMV- GMV- GMV- GMV-
Model
R28T/Na-K R36T/Na-K R45T/Na-K R50T/Na-K
kW 2.8 3.6 4.5 5.0
Cooling Capacity
Btu/h 9,550 12,280 15,360 17,060
kW 3.2 4.0 5.0 5.8
Heating Capacity
Btu/h 10,900 13,650 17,060 19,790
m3/h 680 680 680 680
Air Flow Rate
CFM 400 400 400 400
Sound Pressure Level dB(A) 37/34 37/34 37/34 37/34
Power Supply 220-240V~ 50Hz

Input kW 0.06
. 0.06 0.065 0.065
Fan
Motor Running
A 0.27 0.27 0.27 0.27
Current
Gas mm 9.52 12.7 12.7
Pipe inch 3/8 1/2 1/2
Connect- Liquid mm 6.35 6.35 6.35
ing Pipes Pipe inch 1/4 1/4 1/4
Connection
Flare Connection Flare Connection
Method
Drain Pipes (External
mm 30 1.5
Dia. Thickness )
Unit Dimensions Main Body: 840 840 190
(W D H) mm
Panel: 950 950 60
Pakge Dimensions Main Body: 960 960 257
(W D H) mm
Panel: 1040 1025 115
Net Weight
kg 25/6.5
(Main Body/Panel)
Gross Weight kg
(Main Body/Panel) 36/9

Notes:
,
The technical parameters are changed along with the products improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB, Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB, Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

41
GMV- GMV- GMV- GMV-
Model
R56T/Na-K R63T/Na-K R71T/Na-K R80T/Na-K
kW 5.6 6.3 7.1 8.0
Cooling Capacity
Btu/h 19,100 21,500 24,230 27,300
kW 6.3 7.0 8.0 8.8
Heating Capacity
Btu/h 21,500 23 ,890 27,300 30,030
m 3/h 1180 1180 1180 1180
Air Flow Rate
CFM 695 695 695 695
Sound Pressure Level dB(A) 39/35 39/35 39/35 39/35
Power Supply 220-240V~ 50Hz

Input kW 0.083
. 0.083 0.083 0.083
Fan
Motor Running
A 0.37
. 0.37 0.37 0.37
Current
Gas mm 15.9
Pipe inch 5/8
Connect-
ing Pipes Liquid mm 9.52
Pipe inch 3/8
Connection
Flare Connection
Method
Drain Pipe(External
mm 30 1.5
Dia. Thickness)
Unit Dimensions Main Body:840 840 240
mm
(W D H) Panel:950 950 60
Pakge Dimensions Main Body:960 960 310
(W D H) mm
Panel:1040 1025 115
Net Weight
(Main Body /Pannel) kg 30/6.5

Gross Weight
(Main Body /Pannel) kg 41/9

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

42
Modular Digital Multi VRF Technical Sales Guide

GMV- GMV- GMV- GMV- GMV-


Model
R90T/Na-K R100T/Na-K R112T/Na-K R125T/Na-K R140T/Na-K
kW 9.0 10.0 11.2 12.5 14.0
Cooling Capacity
Btu/h 30,700 34,120 38,210 42,650 47,770
kW 10.0 11.0 12.5 13.5 14.5
Heating Capacity
Btu/h 34,120 37,540 42,650 46,060 49,470
m3/h 1860 1860 1860 1860 1860
Air Flow Rate
CFM 1095 1095 1095 1095 1095
Sound Level dB(A) 40/36 40/36 40/36 40/36 40/36
Power Supply 220-240V~ 50Hz

Input kW 0.133 0.133 0.133 0.133 0.133


Fan
Motor Running
A 0.59 0.59 0.59 0.59 0.59
Current
Gas mm 15.9
Pipe inch 5/8
Connect-
Liquid mm 9.52
ing Pipes
Pipe inch 3/8
Connection
Flare Connection
Method
Drain Pipe(External
mm 30 1.5
Dia. Thickness)
Unit Dimensions Main Body: 840 840 320
mm
(W D H) Panlel: 950 950 60
Pakge Dimensions Main Body: 960 960 394
(W D H) mm Panel: 1040 1025 115
Net Weight
kg 38/6.5
(Main Body/Panel)
Gross Weight
(Main Body/Panel) kg 46/9

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

43
Duct Type

Model GMV- GMV- GMV- GMV-


Item R22 P/Na-K R25 P/Na-K R28 P/Na-K R36P/Na-K
kW 2.2 2.5 2.8 3.6
Cooling capacity
Btu/h 7,510 8,530 9,550 10,280
kW 2.5 3.0 3.1 4.0
Heating capacity
Btu/h 8,530 10,236 10,577 13,650
m3/h 450 450 570 570
Air volume
CFM 265 265 335 335
Noise(H/L) dB(A) 37/33 37/33 39/35 39/35
Motor output power kW 0.02 0.02 0.02 0.02
Motor Running Current A 0.24 0.24 0.25 0.25
Indoor unit surplus pressure Pa 0/20 0/20 0/20 0/20
Phase number-Voltage-Frequency 220-240V 50Hz
mm 9.52 12.7
Gas Pipe
Inch
Connecting
mm 6.35 6.35
Pipes Liquid Pipe
Inch
Connection Method Flare Connection
The aperture of condensing
drainage pipe mm 20 1.5
External Dia. Thickness
Unit dimensions
mm 875 680 220
(W D H)

Package dimensions
mm 1012 708 275
(W D H)
Net Weight kg 27
Gross Weight kg 31

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

44
Modular Digital Multi VRF Technical Sales Guide

Model GMV- GMV- GMV-


Item R45 P/Na-K R50 P/Na-K R56 P/Na-K
kW 4.5 5.0 5.6
Cooling capacity
Btu/h 15,360 17,060 19,100
kW 5.0 5.8 6.6
Heating capacity
Btu/h 17,060 19,790 22,519
m3/h 840 840 1400
Air volume
CFM 494 494 823
Noise(H/L) dB(A) 40/36 40/36 42/38
Motor output power kW 0.07 0.07 0.15
Motor Running Current A 0.42 0.42 0.72
Indoor unit surplus pressure Pa 15/40 15/40 50
Phase number-Voltage-Frequency 220-240V 50Hz
mm 12.7 15.9
Gas Pipe
Inch
Connect-ing
mm 6.35 9.52
Pipes Liquid Pipe
Inch
Connection Method Flare Connection
The aperture of condensing
drainage pipe mm 30 1.5
External Dia. Thickness
Unit dimensions
mm 980 736 266 980 766 266 1112 756 300
(W D H)

Package dimensions
mm 1068 766 3201068 766 3601245 785 360
(W D H)
Net Weight kg 36 36 55
Gross Weight kg 39 39 59

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

45
Model GMV- GMV- GMV-
Item R71 P/Na-K R80 P/Na-K R90 P/Na-K
kW 7.1 8.0 9.0
Cooling capacity
Btu/h 24,230 27,300 30,700
kW 8.0 8.8 10.0
Heating capacity
Btu/h 27,300 30,025 34,120
m3/h 1400 1400 2000
Air volume
CFM 823 823 1177
Noise(H/L) dB(A) 41/37 41/37 44/40
Motor output power kW 0.150 0.150 0.225
Motor Running Current A 0.72 0.72 1.2
Indoor unit surplus pressure Pa 50 50 50
Phase number-Voltage-Frequency 220-240V 50Hz
mm 15.9
Gas Pipe
Inch 5/8
Connect-ing
mm 9.52
Pipes Liquid Pipe
Inch 3/8
Connection Method Flare Connection
The aperture of condensing
drainage pipe mm 30 1.5
External Dia. Thickness
Unit dimensions
mm 1112 756 300 1382 756 300
(W D H)

Package dimensions
mm 1245 785 360 1514 785 360
(W D H)
Net Weight kg 55 75
Gross Weight kg 59 79

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

46
Modular Digital Multi VRF Technical Sales Guide

Model GMV- GMV- GMV-


Item R112P/Na-K R125P/Na-K R140P/Na-K
kW 11.2 12.5 14.0
Cooling capacity
Btu/h 38,210 42,650 47,770
kW 12.5 13.5 15.0
Heating capacity
Btu/h 42,650 46,060 51,180
m3/h 2000 2000 2000
Air volume
CFM 1177 1177 1177
Noise(H/L) dB(A) 44/40 44/40 44/40
Motor output power kW 0.225 0.225 0.225
Motor Running Current A 1.2 1.2 1.2
Indoor unit surplus pressure Pa 50 50 50
Phase number-Voltage-Frequency 220-240V 50Hz
mm 15.9
Gas Pipe
Inch 5/8
Connecting
mm 9.52
Pipes Liquid Pipe
Inch 3/8
Connection Method Flare Connection
The aperture of condensing
drainage pipe mm 30 1.5
External Dia. Thickness
Unit dimensions
mm 1382 756 300 1382 756 300
(W D H)

Package dimensions
mm 1514 785 360 1514 785 360
(W D H)
Net Weight kg 49 75
Gross Weight kg 60 79

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

47
Wall-mounted Type
GMV- GMV- GMV- GMV-
Model R22G/NaB-K R28G/NaB-K R36G/NaB-K R45G/NaB-K
kW 2.2 2.8 3.6 4.5
Cooling capacity
Btu/h 7,510 9,550 12,280 15,360
kW 2.5 3.2 4.0 5.0
Heating capacity
Btu/h 8,530 10,920 13,650 17,060
m3/h 360 360 500 500
Air Flow Rate
CFM 212 212 294 294
Sound Pressure Level dB (A ) 37 /28 37 /28 43 /32 43 /32
Power Supply 220-240V~ 50Hz

Output kW 0.014 0.014 0.022 0.022


Fan
Motor Running
A 0.15 0.15 0.22 0.22
Current
mm 9.52 12.7 12.7
Gas Pipe
inch 3/8 1/2 1/2
Connect- Liquid mm 6.35 6.35 6.35
.
ing Pipes Pipe inch 1/4 1/4 1/4
Connection Flare Flare
Flare Connection
Method Connection Connection
Drain Pipes (External
mm 20 1.5 20 1.5 20 1.5
Dia. Thickness)
Unit Dimensions
mm 770 190 250 830 189 285 830 189 285
(W D H )
Pakge Dimensions
mm 955 330 272 1006 385 265 1006 385 265
(W D H )
Net Weight kg 8 11 11
Gross Weight kg 14.3 15.8 15.8

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

48
Modular Digital Multi VRF Technical Sales Guide

Model GMV- GMV- GMV- GMV-


R50G/NaB-K R56G/NaB-K R71G/Na-K R80G/Na-K
kW 5.0 5.6 7.1 8.0
Cooling capacity
Btu /h 17 ,060 19 ,100 24 ,230 27 ,300
kW 5.8 6.3 8.0 9.0
Heating capacity
Btu/h 19,790 21,500 27,300 30710
3
m /h 700 750 1200 1200
Air Flow Rate
CFM 412 412 706 706
Sound Level dB(A) 45/40 45/40 49/42 49/42
Power Supply 220 -240V~ 50Hz

Output kW 0.020 0.020 0.026 0.026


Fan
Motor Running
A 0.25 0.26 0.29 0.39
Current
mm 12.7 15.9 15.9
Gas Pipe
inch 1/2 5/8 5/8
Connect- mm 6.35
. 9.52 9.52
Liquid
ing Pipes
Pipe inc h 1/4 3/8 3/8
Connection
Flare Connection Flare Connection
Method
Drain Pipe(External
mm 30 1.5 30 1.5
Dia. Thickness)
Unit Dimensions
mm 1020 228 310 1178 227 326
(W D H)
Pakge Dimensions
mm 1178 325 390 1365 417 333
(W D H)
Net Weight kg 15.5 17.5
Gross Weight kg 20.5 23

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

49
Floor Ceiling Type
GMV- GMV- GMV- GMV-
Model
R28Zd/Na-K R36Zd/Na-K R50Zd/Na-K R71Zd/Na-K
kW 2.8 3.6 5.0 7.1
Cooling capacity
Btu/h 9,550 12,280 17,060 24,230
kW 3.2 4.0 5.8 8.0
Heating capacity
Btu/h 10,920 13,650 19,790 27,300
3
m /h 550 600 700 1170
Air Flow Rate
CFM 324 353 412 689
Sound Pressure Level dB(A) 43 44 50 48
Power Supply 220-240V~ 50Hz

Output kW 0.01 0.01 0.04 0.1


Fan
Motor Runn ing
A 0.1 0.1 0.4 1
Current
Gas mm 9.52 12.7 12.7 15.9
Pipe inch 3/8 1/2 1/2 5/8
Connect- Liquid mm 6.35 6.35 6.35 9.52
ing pipes Pipe inch 1/4 1/4 1/4 3/8
Connection
Flare Connection
Method

Drain Pipe mm 17
Unit Dimensions
mm 840 238 695 1300 188 600
(W D H)
Pakge Dimensions
(W D H) mm 1035 295 805 1514 248 724

Net Weight kg 28 28 28 34

Gross Weight kg 37 37 37 38

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

50
Modular Digital Multi VRF Technical Sales Guide

GMV- GMV- GMV-


Model
R90Zd/Na-K R112Zd/Na-K R125Zd/Na-K
kW 9.0 11.2 12.5
Cooling Capacity
Btu /h 30,700 38,210 42,650
kW 10.0 12.5 13.5
Heating Capacity
Btu/h 34,120 42,650 46,060
m 3/h 2100 2200 2300
Air Flow Rate
CFM 1236 1295 1354
ound Pressure Level dB(A) 51 54 55
Power Supply 220-240V 50Hz

Output kW 0.15 0.18 0.18


Fan
Motor Running
A 1.5 1.8 1.8
Current
Gas mm 15.9 15.9 15.9
Pipe inch 5/8 5/8 5/8
Connect- Liquid mm 9.52 9.52 9.52
ing pipes Pipe inch 3/8 3/8 3/8
Connection
Flare Connection
Method

Drain Pipe mm 17

Unit Dimensions
mm 1590 238 695
(W D H)
Pakge Dimensions
(W D H) mm 1814 330 830

Net Weight kg 44 44 44

Gross Weight kg 53 53 53

Notes:

The technical parameters are changed along with the products,improvement; please refer to the
nameplate of the unit for actual data.
The cooling only type (GMVL) has no heating parameter. The Heating capacity of the heat pump
type (GMV) is the capacity of heat pump.
The model GMVL is refers to cooling only while the model GMV is heat pump type. The model with
the last code of K is single phase.
Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due
to the environmental change.
Rated conditions:
Cooling : Indoor air temperature 27 (81 ) DB/19 (66.6 ) WB , Outdoor air temperature 35
(95.4 ) DB/24 (75.6 ) WB.
Heating : Indoor air temperature 20 (68 ) DB/15 (59 ) WB , Outdoor air temperature 7
(44.6 ) DB/6 (42.8 ) WB.

51
8.2 Outdoor Unit

Model GMV-Rm224W/Na-M GMV-Rm280W/Na-M GMV-Rm335W/Na-M GMV-Rm400W/Na-M

Cooling 22.4 28.0 33.5 40.0


Capacity
Heating 25.0 31.0 36.5 44.0

Noise dB(A ) 58 58 62 62
R410A Filling Amount kg 14 16 17 18
Power Supply 380-415V 3N~ 50Hz 380-415V 3N~ 50Hz 380-415V 3N~ 50Hz 380-415V 3N~ 50Hz
Cooling kW 8.3 10.7 12.6 16.1
Rated power
Heating kW 7.8 9.1 10.2 12.6
Cooling A 17.8 22.9 27 34.5
Rated current
Heating A 16.7 19.6 21.8 27

Width mm 930 930 1340 1340

Dimensions Depth mm 770 770 770 770


Height mm 1670 1670 1670 1670
Digital scroll Digital scroll Digital scroll compressor Digital scroll compressor
Compressor compressor +constant compressor +constant +constant speed scroll +constant speed scroll
speed scroll compressor speed scroll compressor compressor 1 compressor 2
Moisture protection IP24 IP24 IP24 IP24

Climate Type T1 T1 T1 T1
mm 22.2 22.2 28.6 28.6
Gas Pipe
Connection Inch 7/8 7/8 9/8 9/8
Pipes mm 9.52 9.52 12.7 12.7
Liquid Pipe
Inch 3/8 3/8 1/2 1/2

Connecting mode Brazing Connection Brazing Connection Brazing Connection Brazing Connection

Net Weight kg 280 300 410 450

Recommended Power cord mm 3


6.0 5 6.0 5 6.0 5 10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

52
Modular Digital Multi VRF Technical Sales Guide

Model GMV-Rm450W/Na-M GMV-Rm504W/Na-M

Cooling 45.0 50.4


Capacity
Heating 49.5 55.0

Noise dB(A ) 62 62
R410A Filling Amount kg 20 20
Power Supply 380-415V 3N~ 50Hz 380-415V 3N~ 50Hz

Cooling kW 18.0 18.8


Rated power
Heating kW 14.7 15.0
Cooling A 38.6 39.1
Rated current
Heating A 31.6 32.2

Width mm 1340 1340

Dimensions Depth mm 770 770


Height mm 1670 1670

Digital scroll compressor +constant Digital scroll compressor +constant


Compressor
speed scroll compressor 2 speed scroll compressor 2

Moisture protection IP24 IP24

Climate Type T1 T1
mm 28.6 28.6
Gas Pipe
Inch 9/8 9/8

Connection mm 12.7 15.9


Liquid Pipe
Pipes
Inch 1/2 5/8

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450 450

Recommended Power cord mm 3


10.0 5 10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

53
Model Combined unit GMV-Rm560W2/Na-M GMV-Rm615W2/Na-M

Model Single unit GMV-Rm280W/Na-M+ GMV-Rm280W/Na-M GMV-Rm280W/Na-M+ GMV-Rm335W/Na-M

Cooling 56.0 61.5


Capacity
Heating 60.0 65.0

Noise dB(A ) 62 62
R410A Filling Amount kg 16+16 16+17
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 10.7+10.7 10.7+12.6
Rated power
Heating kW 9.1+9.1 9.1+10.2
Cooling A 22.9+22.9 22.9+27.0
Rated current
Heating A 19.6+19.6 19.6+21.8

Dimensions(mm) (930 770 1670)+ (930 770 1670)+


mm
W D H (930 770 1670) (1340 770 1670)

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor compressor)+(Digital scroll compressor +constant
compressor) 2 speed scroll compressor 1)

Moisture protection IP24 IP24

Climate Type T1 T1
mm 28.6 28.6
Gas Pipe
Inch 9/8 9/8

Connection mm 15.9 15.9


Liquid Pipe
Pipes
Inch 5/8 5/8

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 300+300 300+410

Recommended Power cord mm 3


6.0 5+6.0 5 6.0 5+6.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

54
Modular Digital Multi VRF Technical Sales Guide

Model Combined unit GMV-Rm670W2/Na-M GMV-Rm730W2/Na-M

Model Single unit GMV-Rm335W/Na-M+ GMV-Rm335W/Na-M GMV-Rm335W/Na-M+ GMV-Rm400W/Na-M

Cooling 67.0 73.5


Capacity
Heating 73.0 80.0

Noise dB(A ) 62 63
R410A Filling Amount kg 17+17 17+18
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 12.6+12.6 12.6+16.1
Rated power
Heating kW 10.2+10.2 10.2+12.6
Cooling A 27.0+27.0 27.0+34.5
Rated current
Heating A 21.8+21.8 21.8+27.0

Dimensions(mm) mm (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
W D H

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor compressor 1)+(Digital scroll compressor +constant
compressor 1) 2 speed scroll compressor 2)

Moisture protection IP24 IP24

Climate Type T1 T1
mm 28.6 34.9
Gas Pipe
Inch 9/8 11/8

Connection mm 15.9 19.05


Liquid Pipe
Pipes
Inch 5/8 3/4

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 410+410 410+450

Recommended Power cord mm 3


6.0 5+6.0 5 6.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

55
Model Combined unit GMV-Rm800W2/Na-M GMV-Rm850W2/Na-M

Model Single unit GMV-Rm400W/Na-M+GMV-Rm400W/Na-M GMV-Rm400W/Na-M+GMV-Rm450W/Na-M

Cooling 80.0 85.0


Capacity
Heating 85.0 90.0

Noise dB(A ) 63 63
R410A Filling Amount kg 18+18 18+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 16.1+16.1 16.1+18.0
Rated power
Heating kW 12.6+12.6 12.6+14.7
Cooling A 34.5+34.5 34.5+38.6
Rated current
Heating A 27.0+27.0 27.0+31.6
Dimensions(mm) mm (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
W D H

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor
compressor 2) 2 compressor 2) 2

Moisture protection IP24 IP24

Climate Type T1 T1
mm 34.9 34.9
Gas Pipe
Inch 11/8 11/8

Connection mm 19.05 19.05


Liquid Pipe
Pipes
Inch 3/4 3/4

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450 450+450

Recommended Power cord mm 3


10.0 5+10.0 5 10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

56
Modular Digital Multi VRF Technical Sales Guide

Model Combined unit GMV-Rm900W2/Na-M GMV-Rm954W2/Na-M

Model Single unit GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M GMV-Rm450W/Na-M+ GMV-Rm504W/Na-M


Cooling 90.0 95.0
Capacity
Heating 98.0 103.0

Noise dB(A ) 63 63
R410A Filling Amount kg 20+20 20+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 18.0+18.0 18.0+18.8
Rated power
Heating kW 14.7+14.7 14.7+15.0
Cooling A 38.6+38.6 38.6+39.1
Rated current
Heating A 31.6+31.6 31.6+32.2
Dimensions(mm) mm (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
W D H
(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor
compressor 2) 2 compressor 2) 2

Moisture protection IP24 IP24

Climate Type T1 T1
mm 34.9 34.9
Gas Pipe
Inch 11/8 11/8

Connection mm 19.05 19.05


Liquid Pipe
Pipes
Inch 3/4 3/4

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450 450+450

Recommended Power cord mm 3


10.0 5+10.0 5 10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

57
Model Combined unit GMV-Rm1008W2/Na-M GMV-Rm1070W3/Na-M

GMV-Rm335W/Na-M+ GMV-Rm335W/Na-M
Model Single unit GMV-Rm504W/Na-M+ GMV-Rm504W/Na-M
+ GMV-Rm400W/Na-M
Cooling 100.8 107
Capacity
Heating 111.3 115

Noise dB(A ) 63 64
R410A Filling Amount kg 20+20 17+17+18
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 18.8+18.8 12.6+12.6+16.1
Rated power
Heating kW 15.0+15.0 10.2+10.2+12.6

Cooling A 39.1+39.1 27.0+27.0+34.5


Rated current
Heating A 32.2+32.2 21.8+21.8+27.0

Dimensions(mm) mm (1340 770 1670)+(1340 770 1670)+


(1340 770 1670)+(1340 770 1670)
W D H (1340 770 1670)

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor compressor 2) 2 compressor 2)+(Digital scroll compressor +
constant speed scroll compressor) 2

Moisture protection IP24 IP24

Climate Type T1 T1
mm 41.3 41.3
Gas Pipe
Inch 13/8 13/8

Connection mm 19.05 19.05


Liquid Pipe
Pipes
Inch 3/4 3/4

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450 410+410+450

Recommended Power cord mm 3


10.0 5+10.0 5 6.0 5+6.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

58
Modular Digital Multi VRF Technical Sales Guide

Model Combined unit GMV-Rm1135W3/Na-M GMV-Rm1200W3/Na-M

GMV-Rm335W/Na-M+ GMV-Rm400W/Na-M GMV-Rm400W/Na-M+ GMV-Rm400W/Na-M


Model Single unit
+ GMV-Rm400W/Na-M + GMV-Rm400W/Na-M
Cooling 113.0 120.0
Capacity
Heating 124.0 130.0

Noise dB(A ) 64 64
R410A Filling Amount kg 17+18+18 18+18+18
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 12.6+16.1+16.1 16.1+16.1+16.1
Rated power
Heating kW 10.2+12.6+12.6 12.6+12.6+12.6
Cooling A 27.0+34.5+34.5 34.5+34.5+34.5
Rated current
Heating A 21.8+27.0+27.0 27.0+27.0+27.0

Dimensions(mm) (1340 770 1670)+(1340 770 1670)+ (1340 770 1670)+(1340 770 1670)+
mm
W D H (1340 770 1670) (1340 770 1670)

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor compressor)+(Digital scroll compressor +constant compressor 2) 3
speed scroll compressor 2) 2

Moisture protection IP24 IP24

Climate Type T1 T1
mm 41.3 41.3
Gas Pipe
Inch 13/8 13/8

Connection mm 19.05 19.05


Liquid Pipe
Pipes
Inch 3/4 3/4

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450 450+450+450

Recommended Power cord mm 3


6.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

59
Model Combined unit GMV-Rm1250W3/Na-M GMV-Rm1300W3/Na-M

GMV-Rm400W/Na-M+ GMV-Rm400W/Na-M GMV-Rm400W/Na-M+ GMV-Rm450W/Na-M


Model Single unit
+ GMV-Rm450W/Na-M + GMV-Rm450W/Na-M
Cooling 125 130.0
Capacity
Heating 140 143.0

Noise dB(A ) 64 64
R410A Filling Amount kg 18+18+20 18+20+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 16.1+16.1+18.0 16.1+18.0+18.0
Rated power
Heating kW 12.6+12.6+14.7 12.6+14.7+14.7
Cooling A 34.5+34.5+38.6 34.5+38.6+38.6
Rated current
Heating A 27.0+27.0+31.6 27.0+31.6+31.6

Dimensions(mm) (1340 770 1670)+(1340 770 1670)+ (1340 770 1670)+(1340 770 1670)+
mm
W D H (1340 770 1670) (1340 770 1670)

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor
compressor 2) 3 compressor 2) 3

Moisture protection IP24 IP24

Climate Type T1 T1
mm 41.3 41.3
Gas Pipe
Inch 13/8 13/8

Connection mm 19.05 19.05


Liquid Pipe
Pipes
Inch 3/4 3/4

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450 450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

60
Modular Digital Multi VRF Technical Sales Guide

Model Combined unit GMV-Rm1350W3/Na-M GMV-Rm1405W3/Na-M

GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M


Model Single unit
+ GMV-Rm450W/Na-M + GMV-Rm504W/Na-M
Cooling 135.0 140.5
Capacity
Heating 145.0 150.0

Noise dB(A ) 64 64
R410A Filling Amount kg 20+20+20 20+20+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 18.0+18.0+18.0 18.0+18.0+18.8
Rated power
Heating kW 14.7+14.7+14.7 14.7+14.7+15.0
Cooling A 38.6+38.6+38.6 38.6+38.6+39.1
Rated current
Heating A 31.6+31.6+31.6 31.6+31.6+32.2

Dimensions(mm) (1340 770 1670)+(1340 770 1670)+ (1340 770 1670)+(1340 770 1670)+
mm
W D H (1340 770 1670) (1340 770 1670)

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor
compressor 2) 3 compressor 2) 3

Moisture protection IP24 IP24

Climate Type T1 T1
mm 41.3 44.5
Gas Pipe
Inch 13/8 7/4

Connection mm 19.05 22.2


Liquid Pipe
Pipes
Inch 3/4 7/8

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450 450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

61
Model Combined unit GMV-Rm1458W3/Na-M GMV-Rm1512W3/Na-M

GMV-Rm450W/Na-M+ GMV-Rm504W/Na-M GMV-Rm504W/Na-M+ GMV-Rm504W/Na-M


Model Single unit
+ GMV-Rm504W/Na-M + GMV-Rm504W/Na-M

Cooling 145.8 151.2


Capacity
Heating 160.0 165.0

Noise dB(A ) 64 65
R410A Filling Amount kg 20+20+20 20+20+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 18.0+18.8+18.8 18.8+18.8+18.8
Rated power
Heating kW 14.7+15.0+15.0 15.0+15.0+15.0
Cooling A 38.6+39.1+39.1 39.1+39.1+39.1
Rated current
Heating A 31.6+32.2+32.2 32.2+32.2+32.2

Dimensions(mm) (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
mm
W D H +(1340 770 1670) +(1340 770 1670)

(Digital scroll compressor +constant speed scroll (Digital scroll compressor +constant speed scroll
Compressor
compressor 2) 3 compressor 2) 3

Moisture protection IP24 IP24

Climate Type T1 T1
mm 44.5 44.5
Gas Pipe
Inch 7/4 7/4

Connection mm 22.2 22.2


Liquid Pipe
Pipes
Inch 7/8 7/8

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450 450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

62
Modular Digital Multi VRF Technical Sales Guide

Model Combined unit GMV-Rm1600W4/Na-M GMV-Rm1650W4/Na-M

GMV-Rm400W/Na-M+ GMV-Rm400W/Na-M GMV-Rm400W/Na-M+ GMV-Rm400W/Na-M


Model Single unit
+ GMV-Rm400W/Na-M+ GMV-Rm400W/Na-M + GMV-Rm400W/Na-M+ GMV-Rm450W/Na-M

Cooling 160.0 165.0


Capacity
Heating 175.0 180.0

Noise dB(A ) 65 65
R410A Filling Amount kg 18+18+18+18 18+18+18+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 16.1+16.1+16.1+16.1 16.1+16.1+16.1+18.0
Rated power
Heating kW 12.6+12.6+12.6+12.6 12.6+12.6+12.6+14.7
Cooling A 34.5+34.5+34.5+34.5 34.5+34.5+34.5+38.6
Rated current
Heating A 27.0+27.0+27.0+27.0 27.0+27.0+27.0+31.6

Dimensions(mm) (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
mm
W D H +(1340 770 1670)+(1340 770 1670) +(1340 770 1670)+(1340 770 1670)

(Digital scroll compressor 1 +constant speed scroll (Digital scroll compressor 1 +constant speed scroll
Compressor
compressor 2) 4 compressor 2) 4

Moisture protection IP24 IP24

Climate Type T1 T1
mm 44.5 54.1
Gas Pipe
Inch 7/4 17/8

Connection mm 22.2 25.4


Liquid Pipe
Pipes
Inch 7/8 1

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450+450 450+450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

63
Model Combined unit GMV-Rm1700W4/Na-M GMV-Rm1750W4/Na-M

GMV-Rm400W/Na-M+ GMV-Rm400W/Na-M GMV-Rm400W/Na-M+ GMV-Rm450W/Na-M


Model Single unit
+ GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M + GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M

Cooling 170.0 175.0


Capacity
Heating 185.0 190.0

Noise dB(A ) 65 65
R410A Filling Amount kg 18+18+20+20 18+20+20+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 16.1+16.1+18.0+18.0 16.1+18.0+18.0+18.0
Rated power
Heating kW 12.6+12.6+14.7+14.7 12.6+14.7+14.7+14.7
Cooling A 34.5+34.5+38.6+38.6 34.5+38.6+38.6+38.6
Rated current
Heating A 27.0+27.0+31.6+31.6 27.0+31.6+31.6+31.6

Dimensions(mm) (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
mm
W D H +(1340 770 1670)+(1340 770 1670) +(1340 770 1670)+(1340 770 1670)

(Digital scroll compressor 1 +constant speed scroll (Digital scroll compressor 1 +constant speed scroll
Compressor
compressor 2) 4 compressor 2) 4

Moisture protection IP24 IP24

Climate Type T1 T1
mm 54.1 54.1
Gas Pipe
Inch 17/8 17/8

Connection mm 25.4 25.4


Liquid Pipe
Pipes
Inch 1 1

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450+450 450+450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

64
Modular Digital Multi VRF Technical Sales Guide

Model Combined unit GMV-Rm1800W4/Na-M GMV-Rm1854W4/Na-M

GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M


Model Single unit
+ GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M + GMV-Rm450W/Na-M+ GMV-Rm504W/Na-M

Cooling 180.0 185.4


Capacity
Heating 195.0 200.0

Noise dB(A ) 65 65
R410A Filling Amount kg 20+20+20+20 20+20+20+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 18.0+18.0+18.0+18.0 18.0+18.0+18.0+18.8
Rated power
Heating kW 14.7+14.7+14.7+14.7 14.7+14.7+14.7+15.0
Cooling A 38.6+38.6+38.6+38.6 38.6+38.6+38.6+39.1
Rated current
Heating A 31.6+31.6+31.6+31.6 31.6+31.6+31.6+32.2

Dimensions(mm) (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
mm
W D H +(1340 770 1670)+(1340 770 1670) +(1340 770 1670)+(1340 770 1670)

(Digital scroll compressor 1 +constant speed scroll (Digital scroll compressor 1 +constant speed scroll
Compressor
compressor 2) 4 compressor 2) 4

Moisture protection IP24 IP24

Climate Type T1 T1
mm 54.1 54.1
Gas Pipe
Inch 17/8 17/8

Connection mm 25.4 25.4


Liquid Pipe
Pipes
Inch 1 1

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450+450 450+450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

65
Model Combined unit GMV-Rm1908W4/Na-M GMV-Rm1962W4/Na-M

GMV-Rm450W/Na-M+ GMV-Rm450W/Na-M GMV-Rm450W/Na-M+ GMV-Rm504W/Na-M


Model Single unit
+ GMV-Rm504W/Na-M+ GMV-Rm504W/Na-M + GMV-Rm504W/Na-M+ GMV-Rm504W/Na-M

Cooling 190.8 196.2


Capacity
Heating 205.0 210.0

Noise dB(A ) 65 65
R410A Filling Amount kg 20+20+20+20 20+20+20+20
Power Supply 380-415V3N~ 50Hz 380-415V3N~ 50Hz
Cooling kW 18.0+18.0+18.8+18.8 18.0+18.8+18.8+18.8
Rated power
Heating kW 14.7+14.7+15.0+15.0 14.7+15.0+15.0+15.0
Cooling A 38.6+38.6+39.1+39.1 38.6+39.1+39.1+39.1
Rated current
Heating A 31.6+31.6+32.2+32.2 31.6+32.2+32.2+32.2

Dimensions(mm) (1340 770 1670)+(1340 770 1670) (1340 770 1670)+(1340 770 1670)
mm
W D H +(1340 770 1670)+(1340 770 1670) +(1340 770 1670)+(1340 770 1670)

(Digital scroll compressor 1 +constant speed scroll (Digital scroll compressor 1 +constant speed scroll
Compressor
compressor 2) 4 compressor 2) 4

Moisture protection IP24 IP24

Climate Type T1 T1
mm 54.1 54.1
Gas Pipe
Inch 17/8 17/8

Connection mm 25.4 25.4


Liquid Pipe
Pipes
Inch 1 1

mm 9.52 9.52
Liquid Pipe
Inch 3/8 3/8

Connecting mode Brazing Connection Brazing Connection

Net Weight kg 450+450+450+450 450+450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5+10.0 5 10.0 5+10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

66
Modular Digital Multi VRF Technical Sales Guide

Model Combined unit GMV-Rm2016W4/Na-M

Model Single unit GMV-Rm504W/Na-M+ GMV-Rm504W/Na-M+ GMV-Rm504W/Na-M+ GMV-Rm504W/Na-M

Cooling 201.6
Capacity
Heating 215.0

Noise dB(A ) 65
R410A Filling Amount kg 20+20+20+20
Power Supply 380-415V3N~ 50Hz
Cooling kW 18.8+18.8+18.8+18.8
Rated power
Heating kW 15.0+15.0+15.0+15.0

Cooling A 39.1+39.1+39.1+39.1
Rated current
Heating A 32.2+32.2+32.2+32.2

Dimensions(mm) (1340 770 1670)+(1340 770 1670)


mm
W D H +(1340 770 1670)+(1340 770 1670)

Compressor (Digital scroll compressor 1 +constant speed scroll compressor 2) 4

Moisture protection IP24

Climate Type T1
mm 54.1
Gas Pipe
Inch 17/8

Connection mm 25.4
Liquid Pipe
Pipes
Inch 1

mm 9.52
Liquid Pipe
Inch 3/8

Connecting mode Brazing Connection

Net Weight kg 450+450+450+450

Recommended Power cord mm 3


10.0 5+10.0 5+10.0 5+10.0 5

Notes:

a. The data will change with the change of products. Refer to those parameters listed on nameplate.
b. Noise was tested in semi-silenced room, so the actual noise value will be a litter higher for
change of ambient.
c. The charge amount of refrigerant in the list is the datum when there is not drop height vertically
between indoor unit and outdoor unit, without consideration of connection pipe. So calculate the
additional charge amount according to actual condition during installation.
d. Section area of lead wire is only applicable for 15-m distance.If above, increase the section area
to avoid overload of current which would cause burnout of lead wire
e. The outdoor fan of this unit is without static pressure.If static pressure is required, please specially
notice it on purchase order.

67
9 CRICUIT DIAGRAW
GMV-Rm224W/Na-M GMV-Rm280W/Na-M

Line
Filter
Load

GMV-Rm335W/Na-M

68
Modular Digital Multi VRF Technical Sales Guide

GMV-Rm400W/Na-M GMV-Rm450W/Na-M GMV-Rm504W/Na-M

69
10 FAN CHARACTERISTICS
GMV-R22P/Na-K; GMV -R28P/Na-K; GMV-R36P/ Na-K;
GMV-R25P/Na-K; GMV -R32P/Na-K;
Standard air volume:450m /h 3
Standard air volume:570m3/h
70 70

60 60
Extermal static pressure (Pa)

Extermal static pressure (Pa)


50 50
Air volume limit (Max.)

Air volume limit (Max.)


40 40 mit
n li
Air volume limit (Min.)

Air volume limit (Min.)


atio
plic
Ap
it
30 lim 30
on
c at i
pli
Ap
S up

S up
stan

s ta
s ta
20 20

nda
s ta
er H

er H
dard

nda
nda

rd H
stan
s ta

tap
rd M
tap
H ta

rd L
dard
nda

tap
10 10

tap
p

tap
rd L

M ta
tap
p

0 0
0 126 270 326 450 496 732 983 0 216 372 498 570 620 768 983
3
Air volume (m /h) Air volume (m3/h)

GMV-R40P/ Na-K; GMV -R50P/Na-K; GMV -R56P/ Na-K; GMV -R71P/ Na-K;
GMV-R45P/ Na-K; GMV -R63P/ Na-K; GMV -R80P/ Na-K;
Standard air volume:700m /h 3
Standard air volume:1000m3/h
70 70

60 60
Extermal static pressure (Pa)
Extermal static pressure (Pa)

limit
50 tion 50
lica ion limit
A pp Applicat
Air volume limit (Max.)

Air volume limit (Max.)


40 40
Air volume limit (Min.)

Air volume limit (Min.)

30 30
S up
Su

s ta
s ta

20 20
per

nda
s ta

er H
s ta

nda
s ta

nda
Ht

rd H
nda

s ta

tap
rd M
nda

ap

rd L
nd
rd L

tap

10 10
rd H
ard

tap
tap
tap

Mt

tap
ap

0 0
0 307 637 700 762 896 1000 1475 0 424 818 933 1000 1194 1446
Air volume (m3/h) Air volume (m3/h)

GMV -R90P/ Na-K; GMV-R112P/ Na-K;


GMV -R100P/Na-K; GMV-R125P/ Na-K; GMV -R140P/ Na-K;
Standard air volume:1700m3/h Standard air volume:2000m3/h
140 140

120 120
mit
on li
Extermal static pressure (Pa)

Extermal static pressure (Pa)

it
lim licati
tion A pp
a
100 plic 100
Ap
Air volume limit (Max.)

Air volume limit (Max.)


Air volume limit (Min.)

Air volume limit (Min.)

80 80
st
an
da
rd
H

60 60
ta

sta
p
st

nd
an
da

s ta

ar
dH
rd

nd

40 40
M

ard

tap
Su

st

s ta
ta
an

p
pe

M
nd
da
rL

tap
rd

a rd
Su
ta

20
p

20
pe
ta

L ta
p

rL

p
tap

0 0
450 1039.7 1229.4 1519.5 1700 1836 2000 1025 1226 1557 2000 24422500
Air volume (m3/h) Air volume (m3/h)

70
Modular Digital Multi VRF Technical Sales Guide

GMV-R22P/ Na-K; GMV-R28P/ Na-K; GMV-R36P/Na-K;


GMV-R25P/ Na-K; GMV-R32P/ Na-K;
Standard air volume:265CFM Standard air volume:335CFM
0.28 0.28

0.24 0.24
Extermal static pressure(in.wg )

Extermal static pressure(in.wg )


0.20 0.20

Air volume limit (Max.)

Air volume limit (Max.)


0.16 0.16 mit
n li
Air volume limit (Min.)

Air volume limit (Min.)


atio
plic
Ap
it
0.12 im 0.12
nl
t io
li ca
pp
S up

S up
stan

sta
s ta
0.08 0.08

nda
s ta
er H

er H
dard

nda
nda

rd H
stan
s ta

tap
rd M
tap
H ta

rd L
dard
nda

tap
0.04 0.04

tap
p

tap
rd L

M ta
tap
p

0 0
0 74 159 192 265 292 431 579 0 127 219 293 335 365 452 579
Air volume (CFM) Air volume (CFM)

GMV-R40P/ Na-K; GMV-R50P/ Na-K; GMV-R56P/ Na-K; GMV-R71P/ Na-K;


GMV-R45P/ Na-K; GMV-R63P/ Na-K; GMV-R80P/Na-K;
Standard air volume:412CFM Standard air volume:589CFM
0.28 0.28

0.24 0.24
Extermal static pressure(in.wg )
Extermal static pressure(in.wg )

limit
0.20 tion 0.20
lica ion limit
A pp Applicat
Air volume limit (Max.)

Air volume limit (Max.)


0.16 0.16
Air volume limit (Min.)

Air volume limit (Min.)

0.12 0.12

S up
Su

sta
s ta

0.08 0.08
per

nda
s ta

er H
s ta

nda
s ta

nda
Ht

rd H
nda

sta

tap
rd M
nda

ap

rd L
nd
rd L

tap

0.04 0.04
rd H
ard

tap
tap
tap

Mt

tap
ap

0 0
0 180 375 412 448 527589 868 0 250 481 549 589 703 851
Air volume (CFM) Air volume (CFM)

GMV-R90P/Na-K; GMV-R112P/ Na-K;


GMV-R100P/Na-K; GMV-R125P/ Na-K; GMV-R140P/ Na-K;
Standard air volume:1000CFM Standard air volume:1177CFM
0.56 0.56

0.48 0.48
Extermal static pressure(in.wg )

Extermal static pressure(in.wg )

mit
it on li
lim licati
tion A pp
0.40 p lic a 0.40
Ap
Air volume limit (Max.)

Air volume limit (Max.)


Air volume limit (Min.)

Air volume limit (Min.)

0.32 0.32
st
an
da
rd
H

0.24 0.24
ta

sta
p
st

nd
an
da

s ta

ar
dH
rd

nd

0.16 0.16
M

ard

tap
Su

st

s ta
ta
an

p
pe

M
nd
da
rL

tap
rd

a rd
Su
ta

0.08 0.08
p

pe
ta

L ta
p

rL

p
tap

0 0
265 612 724 894 1000 1080 1177 603 722 916 1177 1437 1471
Air volume (CFM) Air volume (CFM)

71
11 DIMENSIONAL DRAWINGS

11.1 Indoor Unit


4 -way Air Discharge Cassette Type

Suction grille Air discharge port(4-way)


435

panel external dimension


790 hanging bolt pitch
950
295

Refrigerant pipe
connecting port
Drain pipe (Gas)
Refrigerant pipe
connecting port
(Liquid)

Bottom face of ceiling


Bottom face of ceiling
20 or more
20 or more

mm
1500 or more 1500 or more
Model A B C D

GMV-R28T/Na-K ~ GMV-R50T/Na-K 190 157 115.5 88.5


1800 or more

GMV-R56T/Na-K ~GMV-R80T/Na-K 240 204 142 115


GMV-R90T/Na-K ~GMV-R140T/ Na-K 320 200 142 115

Space required for installation and servicing

Check port
( 450)
200

72
Modular Digital Multi VRF Technical Sales Guide

Duct Type
Dimensions For:
GMV-R22P/Na-K; GMV-R25P/Na-K; GMV-R28P/Na-K; GMV-R32P/Na-K; GMV-R36P/Na-K

Hanging bolt 4-M10


(Procured locally) Refrigerant pipe
Refrigerant pipe
connecting port connecting port
(When attaching)

Hanging bolt pitch 856 7.5 (Gas side) (Liquid side)

Air

220
172
Air

100
suction discharge

790 600
875 Drain pipe connecting port

Ceiling open dimension 800 Ceiling opening 320

Air Inlet

inspection 150mm
600

openning

600

Air Outlet

Dimensions for :
GMV-R40P/Na-K; GMV-R45P/Na-K; GMV-R50P/Na-K; GMV-R56P/Na-K; GMV-R63P/Na-K;
GMV-R71P/Na-K; GMV-R80P/Na-K; GMV-R90P/Na-K; GMV-R100P/Na-K; GMV-R112P/Na-K;
GMV-R125P/Na-K; GMV-R140P/Na-K

Hanging bolt 4-M10


knockout hole (Procured locally) Refrigerant pipe
(When attaching

(For air taking-in air) A connecting port


(Liquid side)
directly)

Air Air
H
J

discharge
I

suction

Refrigerant pipe Drain pipe


connecting port connecting
tapping (Gas side) port
screw

Ceiling open dimension 900 Ceiling opening 320

E
G
B
F

C
D

73
Model A B C D E F G H I J
GMV-R40P/Na-K
GMV-R45P/Na-K 932 430 738 892 980 736 738 125 203 266
GMV-R50P/Na-K
GMV-R56P/Na-K
GMV-R63P/Na-K
1114 420 918 1074 1159 736 918 207 207 260
GMV-R71P/Na-K
GMV-R80P/Na-K
GMV-R90/Na-K
GMV-R100/Na-K
1350 430 1155 1310 1385 736 1155 207 207 260
GMV-R112/Na-K
GMV-R125/Na-K
GMV-R140P/Na-K 1382 420 1155 1340 1425 756 1278 207 250 300

Note:
Be sure to place a inspection openning at the position indicated in the following figure for maintenance
of the equipment.

Air inlet

inspection 150mm
600 openning

600

Air outlet

74
Modular Digital Multi VRF Technical Sales Guide

Wall-mounted

Installtion board
C

Gas pipe
Liquip pipe The wall hole for
Drain pipe the outlet pipe
At shipment The diameter showed on the fig.:
(When drawing pipe from left) ? 50mm for model 22,28,36; ? 65mm for model 45.
Upper end of installtion board
Including installtion board(Accessory)
A

Liquip pipe
Gas pipe
B

Drain pipe
Air discharge port Air suction port
(Air direction upward/downward
/leftward/rightward is adjustable)

Installtion board

SPace reguired for service

ceiling ceiling
>150

>150 >150 >3000 wall


>2000

unit:mm

ground ground

GMV-R22G/NaB-K GMV-R36G/NaB-K GMV-R50G/NaB-K GMV -R71G/Na-K


Model
GMV-R28G/NaB-K GMV-R45G/NaB-K GMV-R56G/NaB-K GMV -R80G/Na-K

A(mm) 770 830 1020 1178


B(mm) 250 285 310 326
C(mm) 190 189 228 227

75
Connect silencing box with liquid side pipe of indoor unit by connection pipe, and also connect it with
liquid side pipe of outdoor unit, tighten the connection pipe with joint nut.

Longest 5m
Prolonged wire for
To electic expand valve
outdoor

Liquid side
connection pipe

Gas side connection pipe

Floor Ceiling Type

76
Modular Digital Multi VRF Technical Sales Guide

Models A B C D E
GMV-R28Zd/Na-K 745 695 840 238 260
GMV-R36Zd/Na-K 745 695 840 238 260
GMV-R50Zd/Na-K 745 695 840 238 260
GMV-R71Zd/Na-K 1220 600 1300 188 260
GMV-R90Zd/Na-K 1500 695 1590 238 260
GMV-R112Zd/Na-K 1500 695 1590 238 260
GMV-R125Zd/Na-K 1500 695 1590 238 260

Connect silencing box with liquid side pipe of indoor unit by connection pipe, and also connect it with
liquid side pipe of outdoor unit, tighten the connection pipe with joint nut.

Longest 5m
Prolonged wire for
To electic expand valve
outdoor

Liquid side
connection pipe

Gas side connection pipe

Space reguired for service


>1.5m

>0.6m >0.6m
>1m
>0.3m

77
>0.2m
>0.6m
>0.6m >0.6m >0.3m

>2.3m

11.2 Outdoor Unit

Outline dimension of single-module outdoor unit


GMV-Rm224W/Na-M, GMV-Rm280W/Na-M

930
1670

770

78
Modular Digital Multi VRF Technical Sales Guide

Outline of
GMV-Rm335W/Na-M,GMV-Rm400W/Na-M,GMV-Rm450W/Na-M,GMV-Rm504W/Na-M

Installation hole site of single-module outdoor unit

722-737

Front Side Rear Side


792

Base

Ream beam of base


Foundation
beam of base beam of base

Installation hole site of outdoor unit GMV-Rm224W/Na-M, GMV-Rm280W/Na-M

79
Installation hole site of
GMV-Rm335W/Na-M, GMV-Rm400W/Na-M, GMV-Rm450W/Na-M, GMV-Rm504W/Na-M

1670

770

Installation space requirements for modular unit


Installation space of outdoor unit

Air outlet Air outlet

Electric box and outlet Electric box and outlet


pipe direction is at thia pipe direction is at thia
side side

Air outlet
(1) (2)

(1) DimesonrequirementforinstallationofoutdoorunitsGMV-Rm224W/Na-M,GMV-Rm280W/Na-M
(2) DimesonrequirementforinstallationofGMV-Rm335W/Na-M,GMV-Rm400W/Na-M,

80
Modular Digital Multi VRF Technical Sales Guide

Air outlet Air outlet

Electric box and outlet pipe Electric box and outlet pipe
direction is at thia side direction is at thia side

(3) (4)

GMV-Rm450W/Na-M, GMV-Rm504W/Na-M
(3) Dimeson requirement for installation of GMV-Rm560W2/Na-M
(4) Dimeson requirement for installation of GMV-Rm615W2/Na-M

Electric box and outlet pipe


direction is at thia side

(5)

(5) Dimeson requirement for installation of


GMV-Rm670W2/Na-M, GMV-Rm730W2/Na-M, GMV-Rm800W2/Na-M, GMV-Rm850W2/Na-M,
GMV-Rm900W2/Na-M, GMV-Rm954W2/Na-M, GMV-Rm1008W2/Na-M

81
Air outlet Air outlet

Electric box and outlet pipe


direction is at thia side

(6)

Dimeson requirement for installation of


GMV-Rm1070W3/Na-M, GMV-Rm1135W3/Na-M, GMV-Rm1200W3/Na-M, GMV-Rm1250W3/Na-M,
GMV-Rm1300W3/Na-M, GMV-Rm1350W3/Na-M, GMV-Rm1405W3/Na-M, GMV-Rm1458W3/Na-M,
GMV-Rm1512W3/Na-M

Air outlet Air outlet

Electric box and outlet pipe


direction is at thia side

(7)

Dimeson requirement for installation of


GMV-Rm1600W4/Na-M, GMV-Rm1650W4/Na-M, GMV-Rm1700W4/Na-M, GMV-Rm1750W4/Na-M,
GMV-Rm1800W4/Na-M, GMV-Rm1854W4/Na-M, GMV-Rm1908W4/Na-M, GMV-Rm1962W4/Na-M,
GMV-Rm2016W4/Na-M

82
Modular Digital Multi VRF Technical Sales Guide

If the unit is surrounded by walls, the above basic requirements for installation should be met.
For the state that front side and right/left side of the outdoor unit is open:

No limitation to wall height

If there is crown wall (air-damping obstacles) on the top of unit, keep crown wall more than
3000mm from the top of unit. If unit's front, rear, left and right side are in the open, Keep crown
wall more than1500mm from the top of the unit.If it is less than1500mm or there is not open
space around the unit, a piece of return duct should be connected for smooth ventilation.

Installation space for multiple modular outdoor units

(1) Keep top of units open, without air-damping obstacles for smooth ventilation.
(2) For the state that front right/left side sapce of the outdoor units is open:
(a) Install the unit at the same directions:

No limitation to wall height

Rear side

Front side
Rear side

Front side

Distance from the next outdoor unit Up to 3 units in a line

83
(b) Install the units back to back:

No limitation to wall height

Rear side

Front side
Rear side

Front side

Distance from the next outdoor unit Up to 3 units in a line

(3) For the state that the units are surrounded by walls, It is recommended to install the units at
the same directions.

No limitation to wall height


Rear side

Front side
Rear side

Front side

Up to 3 units in a line

84
Modular Digital Multi VRF Technical Sales Guide

In consideration of seasonal wind during installation of outdoor units

Correct Correct Incorrect

Protector

Fresh air inlet one side(rear side)


Fresh air inlet
one side(rear side)
Fresh air inlet
one side(rear side)

Fresh air inlet one side(rear side)


In this case,defrosting time will be prolonged

Skecth map of parallel connection among 3 units

Oil equalizing pipe

ML01 gas pipe Piping bwtween modular unit and connecting sub-assy
ML01 liquid pipe
Connecting piping of module connecting sub-assy

Connecting piping among outdoor modules should be kept level to avoid oil accumulated
in a module.

85
11.3 Controller

Wired Remote Controller Wireless Remote Controller

SWING FAN

AUTOFAN OPER
AUTO
AIR

ROOM TEMP SWING


TIMER
ON/OFF HR.

C
SET TEMP
SWING
C SWING

MELT
MODE ON/OFF

Outline size: 85mm 85mm 21mm Outline size: 160 mm 57 mm 22mm

Region Controller Central Remote Controller

SINGLE 1 2 3 4 5 6 7 8
INQUIRY
CENTER 9 10 11 12 13 14 15 16

FUNC

FAN ERROR ROOM TEMP SHIELD

SPEED
C

SET LOCK

TIMER C
HR
SWING ON/OFF

Outline size: 85mm 85mm 21mm Outline size: 185mm 135mm 70mm

86
Modular Digital Multi VRF Technical Sales Guide

11.4 Branching Joint

FQ01A/A

Gas side
Liquid side

FQ01B/A

Gas side Liquid side

87
FQ02/A

Gas side Liquid side

FQ03/A

Gas side Liquid side

88
Modular Digital Multi VRF Technical Sales Guide

FQ04/A

Gas side Liquid side

Ml01

Gas side Liquid side

Branching pipe ID(mm) Connected pipe size OD(Inch) Branching pipe ID(mm) Connected pipe size OD(Inch)
6.35 1/4 25.4 1
9.52 3/8 28.6 9/8
12.7 1/2 34.9 11/8
15.9 5/8 41.3 13/8
19.05 3/4 44.5 7/4
22.2 7/8 54.1 17/8

89