Sie sind auf Seite 1von 2

556

DEEP SEA ELECTRONICS ATS / MAINS


CONTROLLER

FEATURES DESCRIPTION Issue 1


AM 28/10/03
 Automatically senses mains The Model 556 is an Automatic
(utility) failure and starts the
backup generators (controlled by
Transfer switch and Mains
DSE model 550 controllers). controller with comprehensive
instrumentation and load control
 Allows precise changes to be features.
made to the generator bus/mains
supply load share (import/export The module is used to monitor a mains
control) supply and automatically start and
 Can maintain a specific mains stop the system’s generating sets
(utility) or generator power factor. (controlled by DSE 550 load sharing
controllers). It indicates the
 ATS / Peak lopping control for 550
controlled generator bus
operational status by means of an SPECIFICATION
LCD display, and LEDs on the front
 Will synchronise multiple 550 panel. DC Supply:
controlled gensets with the 8V to 35V Continuous.
returning mains (utility) supply to Able to survive 0V for 50mS, providing
The system is used to ‘manage’ the
provide no-break changeover supply was at least 10V before dropout
generator bus, which is fed by DSE and supply recovers to 5V. This is
back to the mains supply.
550 load sharing controllers. achieved without the need for internal
 ‘Soft transfer’ (load ramping) both batteries.
to and from the generator supply. The 556 instructs the 550 controllers
to make precise changes to the Max. Operating Current:
 Can be used to load test the
generating set outputs which can be 513mA at 12V. 263mA at 24V.
synchronised generator bus
without removing power from the used in many applications including:
Max. Standby Current:
load. Peak lopping. The generating sets 370mA at 12V. 210mA at 24V.
are used to ensure the mains load
 Clear, backlit LCD display to show
is kept below a specific, Generator bus Input Range:
the status of the load switches,
configurable level. 15V(L-N) to 277V(L-N) AC (+20%)
and mains (utility) supply as well
as to annunciate alarm conditions No-break return to mains supply.
Generator bus Input Frequency:
should they occur. The generator bus is voltage
50Hz - 60Hz at rated engine speed
matched and synchronised with (Minimum: 15V AC L-N)
 Integral, configurable starting and
the returned mains supply to allow
stopping timers.
transfer back to mains with no Mains Sensing Input Range:
 Configurable inputs and outputs break in supply to the load. 15V(L-N) to 277V(L-N) AC (+20%)
to help meet complex
specifications. Selected operational sequences, Mains Sensing Input Frequency:
50Hz - 60 Hz (Minimum: 15V AC L-N)
 Integral log for viewing event timers and alarms can be altered by
history. the customer. Alterations to the Auxiliary Relay Outputs:
system are made using the 810 5 Amp DC at supply voltage.
INSTRUMENTATION interface and a PC. This interface
also provides real time diagnostic Generator bus loading Relay Output:
The 556 module provides the following facilities. 8 Amp AC 250V – normally open.
instrumentation LCD displays, accessed
via the LCD PAGE and DISPLAY Mains loading Relay Output:
Operation of the module is via 8 Amp AC 250V – changeover
SCROLL push buttons: pushbutton controls (with security
Mains Volts L1-N, L2-N, L3-N
locking facility) mounted on the front Operating Temperature Range:
Mains Volts L1-L2, L2-L3, L3-L1
panel with STOP/RESET, AUTO, -30°C to +70°C
Mains Amps L1,L2,L3
Mains Frequency Hz
TEST, MANUAL and START
functions. The first four pushbuttons Dimensions:
Mains kVA L1,L2,L3, Total 192mm x 144mm x 162.5mm
Mains kW L1,L2,L3, Total feature LED ‘selected’ indications.
Further pushbuttons provide (7.6” x 5.7” x 6.4”)
Mains pf L1,L2,L3,Average Panel cutout:
Mains kVAr L1,L2,L3, Total MUTE/LAMP TEST, LCD PAGE and
DISPLAY SCROLL functions. 185mm x 138mm (7.3” x 5.5”)
Mains KWh, KVAh, KVArh
Mains Phase Sequence
The 500 series modules have been
Synchroscope Display The module features 32-Bit designed for front panel mounting. The
Bus Volts L1-N, L2-N, L3-N Microprocessor control and a module is fitted into the cutout with the fixing
Bus Volts L1-L2, L2-L3, L3-L1 comprehensive list of timers and pre- clips removed. These are then fitted from
Bus Frequency Hz configured sequences. User the rear. Connection is via locking plug and
Bus kW total and % of capacity socket connectors.
configurable expansion facilities are
Bus kVAr total and % of capacity also provided. Deep Sea Electronics reserve the right to change
Bus Phase Sequence specification without prior notice.
CASE DIMENSIONS

192mm x 144mm x 162.5mm (7.6” x 5.7” x 6.4”)


Panel cutout – 185mm x 138mm (7.3” x 5.5”)

144.0mm
137mm

155.0mm 185.0mm

192.0mm

7.5mm Panel Cu t-o ut:138mmx185mm

SINGLE LINE DIAGRAM OF TYPICAL MULTISET SYSTEM

Multiset Communications Link


From 1 to 16 sets can be connected to the MSC Link. Only three are shown for clarity
For typical connections to the 556
controller, refer to the product
AVR / Governor control Bus monitoring operators manual.

Generator breaker control Bus monitoring Mains monitoring

AVR / Governor control Bus monitoring

Bus and Mains


Breaker control

Generator breaker control

AVR / Governor control Bus monitoring

Generator breaker control

Deep Sea Electronics Plc. Deep Sea Electronics inc.


Highfield House, Hunmanby Industrial Estate, 5301 E. State St. – Suite 202
North Yorkshire. YO14 0PH. ENGLAND Rockford, Illinois 61108 U.S.A.
Tel +44 (0)1723 890099. Phone +1 (815) 316-8706
Fax +44 (0)1723 893303. Fax +1 (815) 316-8708
Email - sales@deepseaplc.com Email – dsesales@deepseausa.com
Web - www.deepseaplc.com Web – www.deepseausa.com