Beruflich Dokumente
Kultur Dokumente
Unidrive
model sizes 1 to 5
Unidrive LV
model sizes 1 to 3
Important...
Drive software version
This product is supplied with the latest version of
user-interface and machine-control software. If this
product is to be used with other Control Techniques
variable speed drives in an existing system, there
may be some differences between their software
and the software in this product. These differences
will cause a difference in functions. This may also
apply to variable speed drives returned from a
Control Techniques Service Centre.
Author: RFD
More information:
When using the Unidrive with the ramps disabled (Pr 2.02 = 0), the stop mode at the default value
(Pr 6.01= rP) and the Drive running with full reference in the reverse direction; on the removal of the
run reverse command the final speed reference will momentarily go positive and will return to zero at a
rate dependant on the deceleration ramp (default setting = Pr 2.21).
If an application requires the ramps to be disabled (either in Closed-Loop Vector or Servo mode), the
stop mode [06.01] should be set to no.rP.
Printed copies of the Unidrive Advanced User Guide UNI 3404 30.0 40
(which includes the Advanced Parameter Descriptions UNI 3405 37.0 50
plus additional information) are available from the
UNI 4401 45.0 75
Drive Centres and distributors listed at the end of
this User Guide. UNI 4402 55.0 100
UNI 4403 75.0 125
Variable speed drives may be UNI 4404 90.0 150
hazardous if misused. Carefully UNI 4405 110.0 150
follow the instructions in this
User Guide and the Installation UNI 5401 132.0 200
Warning
Guide.
Unidrive LV
Model size Model code Nominal rating
for standard
AC motors
KW HP
UNI 1201 0.37 0.5
UNI 1202 0.55 0.75
UNI 1203 0.75 1.0
UNI 1204 1.1 1.5
UNI 1205 2.2 3.0
UNI 2201 3.0 4.0
UNI 2202 4.0 5.0
UNI 2203 5.5 10.0
UNI 3201 7.5 15.0
UNI 3202 11 20.0
UNI 3203 15 25.0
UNI 3204 22 30.0
1. Default configuration
Open-loop
2. Operating mode
For use with standard AC induction motors.
3. User-interface mode
This is the operating mode of the Drive when
4. Macro configuration despatched from the factory.
Each of the upper layers (2, 3, 4) is superimposed on The Drive applies power to the motor at frequencies
its preceeding layer. which are controlled by the user. The motor speed
is a result of the output frequency of the Drive and
motor slip due to the mechanical load.
1.4 Default configurations
The Drive can power a number of motors connected
The Drive has a separate default configuration for the in parallel (each motor must be protected against
AC supply conditions in Europe or in the USA. These overload; this is described in the Installation Guide).
two default configurations are distinguished as
follows: The Drive can improve the performance of the
motor by applying the following:
European AC supply voltage at 50Hz
Slip compensation
USA AC supply voltage at 60Hz
Fixed boost or Open-loop Vector operation
The Drive is despatched from the factory in the
appropriate default configuration for the continent Fixed boost applies a fixed voltage boost at low
in which it is to be sold. The default configuration frequencies.
is Macro 0 (described in Macro configurations later in Open-loop Vector operation maintains almost
this chapter). constant flux by dynamically adjusting the
motor voltage according to the load on the
The default configuration also defines the following
motor.
functions:
The Regeneration mode is used for four-quadrant Each macro configuration requires specific signal
operation. A Drive can be operated in Regeneration connections to be made to the Drive.
mode only when it is connected to other Drive(s)
operating in one of the other (motoring) modes. Notes
Regeneration mode allows the following: This User Guide refers to operating the
Drive with these macro configurations and
AC supply to be fed from the Regeneration
does not include advanced programming of
Drive to the Drive(s) that are controlling the
the Drive.
motor
Regenerated power to be returned to the Changing advanced parameters may affect
AC supply by the Regeneration Drive instead operation of a macro. Information in this
of being dissipated in braking resistors User Guide may then not be valid.
For information on using the Drive in this mode, The macro configurations are as follows:
contact the supplier of the Drive.
Macro 0
Key used in this User Guide General purpose
(default configuration)
The following key denotes reference to the
operating modes: Analog frequency/speed control for
general-purpose applications.
OL> Applies to Open-loop only
CL> Applies to Closed-loop Vector and When the Drive is operating in open-loop, the
Closed-loop Servo output frequency of the Drive is controlled by a
VT> Applies to Closed-loop Vector only frequency reference. When the Drive is operating in
SV> Applies to Closed-loop Servo only closed-loop, the motor speed is controlled by a
speed reference. In both cases, the motor speed will
When no key is stated, the information applies to all follow the frequency/speed reference so long as the
three operating modes. maximum permissible output current of the Drive is
not exceeded. These principles also apply to all
other macro configurations except Macro 4.
The frequency/speed is controlled incrementally by The principles of controlling motor speed are the
operation of up and down contacts. same as for Macro 0.
The macro configuration can be used for open-loop
Macro 7
or closed-loop operation, and in Terminal mode
only.
Brake control
The principles of controlling motor speed are the Frequency/speed control with brake control for
same as for Macro 0. crane or hoist applications.
Frequency/speed Drive
Functions of the software
reference selection (controlled by the macro configurations)
Skip frequencies/speeds
Acceleration and
deceleration ramps
User
control
S-ramp
Monitoring
Current limit
Stop mode
Spinning motor sync.
External
control and
monitoring OL> Voltage control
(analog and CL> Speed-loop gains
digital)
Motor parameters
PWM switching
frequency
CL> Encoder
Control
Monitoring
AC supply DC bus
Optional braking
Power circuits resistor
Figure 11 Block diagram of the Drive showing the main functions of the software,
and power connections (signal connections vary according to the
macro configuration)
Notes
Keep a note of changes
When changing the values of parameters,
make a note of the new values in case they
need to be entered again.
Closed-loop Servo
Quadrature EIA485/EIA422 standard
encoder with (formerly RS485/RS422)
commutation Additional
5VDC (or 15 VDC) supply requirement commutation
signals signal
See Figure 24 for connecting the connections for
encoder to the 15-way D-type use with servo
connector on the Drive motors only
Status relay
Drive healthy Optional
RFI filter
Analog frequency/speed Signal
reference 1 connector
(remote)
Connections for
single-ended input
signal Thermal
protection
device
0V common
Connections for
differential input signal Stop Start /
Reset
0V common
Analog
frequency/speed
reference 2 Optional braking resistor
(local)
Refer to the Installation Guide for sizing
of the optional braking resistor
Power
0V common terminals
SPEED
TORQUE
Encoder
Encoder
0V common connector
OL> AT SPEED 15-way Signal
CL> AT ZERO SPEED D-type connections for
all encoders
RESET
JOG SELECT
RUN FORWARD
RUN REVERSE
Figure 25 Power connections, and signal connections for Terminal mode (Macro 1 only)
Status relay
Drive healthy Optional
RFI filter
Signal
connector
Thermal
protection
device
Stop Start /
Reset
SPEED
TORQUE
Encoder
Encoder
0V common connector
OL> AT SPEED 15-way Signal
CL> AT ZERO SPEED D-type connections for
all encoders
RESET
Additional
commutation
OL> External trip signal
CL> Drive enable connections for
use with servo
0V common motors only
Figure 26 Power connections, and signal connections for Keypad mode (Macro 1 only)
Select a parameter
Increase the value of a digit
Upper display
Lower display Select a parameter
Decrease the value of a digit
Programming keys
Control keys
Figure 27 Display and keypad
The functions of the control keys are as follows:
Display
(RUN) Start the Drive running.
The display has three display modes as follows...
The RUN key is active only when the Drive is
Status mode operating in Keypad mode (parameter 0.05
Used to indicate the status of the Drive Reference select set at 4).
Parameter mode
Used for selecting a parameter to edit
(STOPRESET) The three functions of
Edit mode this key are as follows:
Used for editing the selected parameter
Stop the Drive
... and shows the following:
Reset the Drive after it has tripped
Display Display mode Make new parameter-values take effect
Status Parameter Edit The STOP-RESET key is active when the Drive
Upper Value of Value of Value of is operating in Keypad mode. This key acts only
parameter 0 parameter 0 parameter 0 as RESET when the Drive is operating in
(selected digit Terminal mode (parameter 0.05 Reference select
flashes) set at 0, 1, 2, 3 or 5).
Lower Status of the Parameter Parameter
Drive number number
rdY 0.10 0.10 (FWD/REV) Change the direction of
rotation of the motor. (This is not enabled by
Operating instructions for the display and keypad default, and is described later in this chapter in
are given in Appendix A Programming Instructions. Enabling reverse direction in Keypad mode.)
Macro 1
Note
When Macro 1 Easy Mode is enabled, none of the
Do not confuse the term Macro with the re-programmable parameters are available.
term Menu. Menu 0 contains parameters;
macro configurations re-define some of Macros 2 to 8
these parameters to perform specific
functions. Menu 0 always exists, but is When one of these macro configurations is enabled,
affected by the macro configuration that is the functions of some re-programmable parameters
enabled. are specific to the macro configuration.
Only one macro configuration can be Other factors that affect the
enabled at a time. re-programmable parameters
Menu 0 contains 51 parameters which are arranged In addition to the changes caused by the macro
in four groups, as shown in Figure 28. configurations, the functions of some
re-programmable parameters are changed by the
following:
Common to The default configuration of the Drive
all macros 0.00 (EUR or USA)
Configuration and saving
The operating mode that is selected
parameter (Open-loop, Closed-loop Vector or
Closed-loop Servo)
These are are shown in Appendix D Menu 0
0.01 ~ 0.10 Parameters.
Common
to all
macros
0.31 ~ 0.50
Fixed-function parameters
Note
The main function of parameter 0.05 is a
reference selector which has other settings
that operate the Drive in Terminal mode.
At this stage, do not use any of these other
settings.
Use of parameter 0.05 is described for 9. Ensure parameter 0.10 Motor speed is displayed
Macros 0 and 1 in Chapter 3 Setting Up the (default).
Drive.
Braking resistor
0.02 Default value Range Unit
Note
OL> 50 Hz (EUR) 0 ~ 1000 Hz
60 Hz (USA) If the application requires a braking
VT> 1500RPM (EUR) 0 ~ 30 000 rpm resistor, an external braking resistor must
1800RPM (USA) be connected to the Drive (see the
SV> 3000 0 ~ 30 000 rpm Installation Guide); the Drive does not
contain a braking resistor.
. ) 2 (1 cos 2 )
(175 FLC
[0.06]MAX = 100 (%)
cos [ 0.46]
. ) 2 (1 cos 2 )
(15 FLC
[0.06]MAX = 100 (%)
cos [ 0.46]
Procedure
Excessive proportional
gain [0.07]
Inappropriate values
entered in the parameters
for the speed-loop PID gains
Caution
can cause the control system
to become unstable. Excessive integral gain
[0.08]
For new parameter-values to apply after 1. To enable a different macro configuration, set
the AC supply to the Drive is interrupted, parameter 0.00 as follows:
new values must be saved. Refer to
Macro Function Setting
Saving new parameter-values in Appendix A
Programming Instructions. 2 Motorized potentiometer 2002
(frequency/speed control by up
and down contacts)
3.1 How to use this chapter 3 Four preset speeds (selected by 2003
digital control signals)
When setting up the Drive for the first time, you 4 Torque control 2004
must first have followed Chapter 2 Getting Started;
Macro 1 Easy mode will then be enabled. Whether 5 PID (set-point) control 2005
you keep Macro 1 or enable a different macro 6 Axis-limit control 2006
configuration, the settings you made in Chapter 2 7 Brake control 2007
will remain unchanged. During the course of setting
8 CL> Digital lock 2008
up the Drive, you may need to change some of these
CL> Shaft orientation
settings. If so, refer again to Chapter 2.
0 General purpose 2009
It is recommended that you follow the instructions (USA default configuration)
in this chapter in the order that they appear. You General purpose 2010
will be led through the following: (EUR default configuration)
Enabling the required macro
configuration (if a macro other than Note
Macro 1 is required) The values of the fixed parameters are not
Changing the signal connections changed when any one of these macro
accordingly configurations is enabled.
Adjusting parameters that are
specific to the macro configuration When Macro 0 is enabled, the
A list of subsidiary functions that functions of parameters
can be set up 0.27 to 0.29 differ between
Caution the EUR and USA default
configurations.
Status relay
Features Drive healthy
Analog frequency/speed
Specific features reference 1
(remote)
Macro 0 places the Drive in a default configuration
Connections for
for general-purpose use. single-ended input
signal
Standard features
0V common
Macro 0 operates in Terminal or Keypad
mode Connections for
differential input signal
In Terminal mode, digital control by
RUN FORWARD, RUN REVERSE and 0V common
JOG SELECT contacts
Local and remote analog frequency/speed Analog
frequency/speed
inputs, or setting of frequency/speed by use reference 2
of the keypad (local)
Skip frequencies/speeds
Selection of stopping modes OL> AT SPEED
CL> AT ZERO SPEED 0V common
Selection of braking mode
Motor thermistor input
RESET
Negative logic for the digital inputs
JOG SELECT
(EUR> positive logic can be selected)
EUR> Adjustment of current-loop PI gains RUN FORWARD
Frequency/speed ref. 2
(local)
0.38 0.21
0.14
Jog
reference
Key
X X Input terminals
The parameters are shown at their default settings.
The logic diagram is valid when all parameters are
at their default settings but may not be valid when X X Output terminals
certain parameters are adjusted.
0.06
S-ramp Torque Current
mode limit
S-ramp selector
Ramps enable
0.17 0.16
0.18
Stop mode
selector
0.39
Menu 4
Synchronize
to a spinning
0.03 motor
Acceleration
rate
CL> Speed-loop PID gains
Motor parameters
0.04
0.19 Speed-loop
Deceleration 0.07 0.42 ~ 0.47
proportional
rate S-ramp
da/dt limit gain No. of poles
Power factor
0.15 Speed-loop Rated voltage
0.08 Rated speed
integral gain
Ramp mode Rated current
selector Rated frequency
Motor
Motor speed active-current
Power stage
REVERSE SELECT
Jog/Preset frequency/speed
Figure 32 Connections for control by 3-wire
The jog function can be used for low-speed jogging momentary contacts
or as a preset frequency/speed at any value up to (see Figure 31 for
the maximum. other connections)
Status relay
Drive healthy
Specific features
Analog
Easy mode gives the simplest operation of the Drive frequency/speed
reference 1
for basic applications. (remote) 0 ~ 10V
Standard features
Analog 0V common
Macro 1 operates in Terminal or Keypad frequency/speed
reference 2
mode (local) 4 ~ 20mA
In Terminal mode, digital control by
RUN FORWARD, RUN REVERSE and
0V common
JOG SELECT contacts
Local and remote analog frequency/speed SPEED
inputs, or setting of frequency/speed by use
of the keypad TORQUE
Keypad control of speed is uni-directional
only OL> AT SPEED
CL> AT ZERO SPEED 0V common
Fixed analog input modes
Fixed jog frequency/speed
RESET
Adjustment of minimum and maximum
frequencies/speeds JOG SELECT
Frequency/speed ref. 2
(local)
Preset references
(use Macro 3)
0.38
0.35 Power up
parameter
display
Keypad setting
reference
Precision reference
(not used with Menu 0)
Key
X X Input terminals
The parameters are shown at their default settings.
The logic diagram is valid when all parameters are
at their default settings but may not be valid when X X Output terminals
certain parameters are adjusted.
Motor control
0.06
Current
limit
Ramps
0.39
Synchronize
to a spinning
motor
0.03
Acceleration
rate
CL> Speed-loop PID gains
Motor parameters
0.04
0.07 Speed-loop
Deceleration proportional 0.42 ~ 0.47
rate gain No. of poles
Power factor
Speed-loop Rated voltage
0.08 Rated speed
integral gain
Rated current
Rated frequency
Motor speed
Power stage
0.10 0.41
PWM switching
frequency
Reference selection
Use 0.05 Reference selector to select the required
frequency/speed source, as follows:
Frequency/speed references
Keypad mode
Terminal mode
Jog
To use jog, close the JOG SELECT contact
(terminal 26) before closing the RUN FORWARD
contact (terminal 27) or RUN REVERSE contact
(terminal 28).
0.20
Motorized pot.
0.25
reset indicator Skip frequency/
speed 1
Motorized pot.
0.30
output scale factor
0.38
Power up
parameter
display
setting
Key
X X Input terminals
X X Output terminals
0.06
S-ramp Current
limit
S-ramp
Ramps enable
0.16
0.18
Stop mode
selector
0.39
Synchronize
to a spinning
0.03 motor
Acceleration
rate
CL> Speed-loop PID gains
Motor parameters
0.04
0.19 Speed-loop
Deceleration 0.07 0.42 ~ 0.47
proportional
rate S-ramp
gain No. of poles
da/dt limit
Power factor
0.15 Speed-loop Rated voltage
0.08 Rated speed
integral gain
Ramp mode Rated current
selector Rated frequency
0.10 OL> Estimated motor speed [M] 0.14 Jog reference (not used)
CL> Motor speed 0.15 Ramp mode selector
0.16 Stop mode selector
0.17 Status relay invert
0.18 S-ramp enable
0.19 S-ramp da/dt
0.20 Skip frequency/speed 1
0.21 Skip freq./speed band 1
The following may require attention in addition to For correct operation of this macro configuration,
the settings made in Chapter 2. the setting of parameter of 0.05 Reference selection
should be at 0.
Motorized potentiometer settings
Analog input modes
1. By default, the Drive operates in
frequency/speed control. To disable this and The analog input can be configured for the
enable the motorized potentiometer, close the following input signals:
MOT. POT. ENABLE contact (terminal 29). 0 ~ 20mA, 4 ~ 20mA or 0 ~ 10V
2. If required, change the value of 0.29 Motorized Refer to the following parameter in Appendix D
pot. rate to change the rate of increase and Menu 0 Parameters for selecting the required mode:
decrease. Increasing the value reduces the rate
of change of speed. Analog Terminal(s) Parameter
input
Default value: 20 s
1 5, 6 0.24
Range: 0 ~ 250 s
Analog input 1 mode selector
3. If bipolar operation is required, set 0.28
Motorized pot. bipolar select at 1. Jog frequency/speed
4. By default, every time the Drive is powered-up There is no need to adjust 0.14 Jog reference since
and enabled, the frequency/speed will return the jog function cannot be used.
under ramp control to the last setting of the
motorized potentiometer. If the Drive is Stopping and braking modes
required to start at zero, set 0.27 Motorized
pot. zero-start select at 1. Refer to the following parameters in Appendix D
Menu 0 Parameters:
5. To reset the motorized potentiometer,
momentarily close the RESET contact. (This Parameter Setting Function
also resets the Drive.) 0.15 Stnd.Ct (Standard controlled)
Ramp mode selector Deceleration time is
6. If required, change the scaling of the extended if the DC-bus
motorized potentiometer output by adjusting voltage reaches its
0.30 Motorized pot. output scale factor. maximum permissible
value during braking.
7. If required, monitor the output value of the
0.16 rP Ramp to stop then the
potentiometer by reading 0.26 Motorized pot. Stop mode selector Drive is disabled
output indicator.
Status relay
Special features Drive healthy
Analog
Selection can be made between preset frequency/speed
reference 1
frequencies/speeds and analog frequency/speed (remote) 0 ~ 10V
control. In both cases, analog input 1 remains
configured for an analog frequency/speed reference
signal (0 to 10V). 0V common
Motor thermistor
Up to four preset frequencies/speeds can be used;
their values must be programmed into individual
parameters. Selection is made by external contacts 0V common
operating in binary logic.
SPEED
Standard features
Macro 3 operates in Terminal mode only TORQUE
29 27 28 25 30
Reference selection Reference
selector 0.02 Maximum
Frequency/speed ref. 1 freq./speed
(remote) 0.05 clamp
Analog input 1 Minimum
mode selector frequency/
5 speed clamp
0.24
6 0.01 Skip
frequencies/
speeds
Preset
0.25 0.20
reference 1
Skip frequency/
speed 1
PRESET Preset
24 0.26
SELECT A reference 2
0.21
Preset Skip freq./speed
0.27
reference 3 band 1
PRESET 26
SELECT B 0.22
0.28 Preset
reference 4 Skip frequency/
speed 2
0.38
Power up
parameter
display setting
Key
X X Input terminals
X X Output terminals
0.06
S-ramp Current
limit
S-ramp
Ramps enable
0.16
0.18
Stop mode
selector
0.39
Synchronize
to a spinning
0.03 motor
Acceleration
rate
CL> Speed-loop PID gains
Motor parameters
0.04
0.19 Speed-loop
Deceleration 0.07 0.42 ~ 0.47
proportional
rate S-ramp
da/dt limit gain No. of poles
Power factor
0.15 Speed-loop Rated voltage
0.08 Rated speed
integral gain
Ramp mode Rated current
selector Rated frequency
Motor
Power stage active-current
Power stage
0.10 OL> Estimated motor speed [M] 0.14 Jog reference (not used)
CL> Motor speed 0.15 Ramp mode selector
0.16 Stop mode selector
0.17 Status relay invert
0.18 S-ramp enable
0.19 S-ramp da/dt
0.20 Skip frequency/speed 1
0.21 Skip freq./speed band 1
The following may require attention in addition to For correct operation of this macro configuration,
the settings made in Chapter 2. the setting of parameter of 0.05 Reference selection
should be at 0.
Preset references
Analog input modes
1. By default, the Drive operates in
frequency/speed control. To disable this and The analog input can be configured for the
enable the preset references, close the following input signals:
PRESET ENABLE contact (terminal 29). 0 ~ 20mA, 4 ~ 20mA or 0 ~ 10V
2. Enter the required values in the following Refer to the following parameter in Appendix D
parameters: Menu 0 Parameters for selecting the required mode:
0.25 Preset frequency/speed 1 Analog Terminal(s) Parameter
0.26 Preset frequency/speed 2 input
27 28 25 30
Reference selection Reference
selector Maximum
0.02
Analog torque Analog frequency/speed
reference input 1 Analog 0.05 clamp
mode input 1 Minimum
selector scaling frequency/speed
5 clamp
0.24 0.29
6 0.01
Analog
7 0.26 input 2
scaling
Analog
Freq./speed control: input 2
Frequency /speed mode
reference selector
Torque control:
OL> (Not used)
CL> Speed over-ride
0.20
0.21
Skip freq./speed
band 1
0.22
Skip frequency/
speed 2
0.23
Skip freq./speed
band 2
0.38
Power up
parameter
display
setting
Key
0.XX Read-write
parameter (RW)
0.XX Read-only
parameter (RO)
X X Input terminals
X X Output terminals
0.06
S-ramp Current
limit
S-ramp
Ramps enable
0.16
0.18
Stop mode
selector
0.39
Synchronize
to a spinning
0.03 motor
Acceleration
rate
CL> Speed-loop PID gains
Motor parameters
0.04
0.19 Speed-loop
Deceleration 0.07 0.42 ~ 0.47
proportional
rate S-ramp
da/dt limit gain No. of poles
Power factor
0.15 Speed-loop Rated voltage
0.08 Rated speed
integral gain
Ramp mode Rated current
selector Rated frequency
0.10 OL> Estimated motor speed [M] 0.14 Jog reference (not used)
CL> Motor speed 0.15 Braking mode selector
0.16 Stop mode selector
0.17 Status relay invert
0.18 S-ramp enable
0.19 S-ramp da/dt
0.20 Skip freq./speed 1
0.21 Skip freq./speed band 1
Analog
input 2 Analog
input 1
0.18 PID
0.20
PID PID proportional
reference Analog input 2 gain
mode selector
0.15 0.21
7
PID integral
Analog gain
input 2 0.28
scaling
0.22
PID derivative
gain 0.38
Power up
0.23 parameter
Analog display
input 3 0.29 PID output high setting
scaling limit
8 0.16 0.24
Analog input 3 PID output
PID mode selector low limit
feedback
0.25
Analog
input 3
Key
X X Input terminals
The parameters are shown at their default settings.
The logic diagram is valid when all parameters are
at their default settings but may not be valid when X X Output terminals
certain parameters are adjusted.
0.06
Current
limit
Ramps
0.39
Synchronize
to a spinning
motor
0.03
Acceleration
rate
CL> Speed-loop PID gains
Motor parameters
0.04
0.07 Speed-loop
Deceleration proportional 0.42 ~ 0.47
rate gain No. of poles
Power factor
Speed-loop Rated voltage
0.08 Rated speed
integral gain
Rated current
Rated frequency
After these two stages, the error is added to the 5. Enter the required values in the following two
frequency/speed reference. parameters:
Reference selection
For correct operation of this macro configuration,
the setting of parameter of 0.05 Reference selection
should be at 0.
Signal Signal
connector connector
0V
0V common 0V common
Analog 10V
frequency/speed
reference 2 0V common
(local) 0 ~ 10V
SPEED
0V common
TORQUE
SPEED
TORQUE
Motor thermistor
OL> AT SPEED
CL> AT ZERO SPEED
Motor thermistor
OL> AT SPEED
RESET
CL> AT ZERO SPEED
LIMIT FORWARD
RESET RUN
RUN FORWARD
OL> External trip
RUN REVERSE CL> Drive enable
LIMIT REVERSE 0V common
27 28 26 29
Limit Limit
forward reverse
invert invert
0.15 0.16 0.14 0.21 0.22 0.17
0 = RUN enabled
1 = RUN disabled (at limit)
Frequency/speed
Bi-directional
7 reference
frequency/speed
Direction control reference
Frequency/speed ref. 2
(local)
Reverse
freq./speed
reference
0.38
Power up
parameter
display
setting
Key
X X Input terminals
The parameters are shown at their default settings.
The logic diagram is valid when all parameters are
at their default settings but may not be valid when X X Output terminals
certain parameters are adjusted.
0.39
Synchronize
to a spinning
0.03 motor
Acceleration
rate CL> Speed-loop PID gains
Motor parameters
0.20 Speed-loop
0.07 0.42 ~ 0.47
proportional
OL> Limit
gain No. of poles
deceleration
rate Power factor
Speed-loop Rated voltage
0.08 Rated speed
0.04 integral gain
Rated current
CL> Rated frequency
Deceleration
rate
Speed-loop
0.09 derivative OL> Motor-voltage control
gain
0.07
Voltage mode
selector
0.40 Autotune
0.41 PWM switching frequency selector
0.42 Motor number of poles
0.43 Motor power factor
0.44 Motor rated voltage
0.45 Motor rated full load RPM
0.46 Motor rated current
0.47 OL + VT> Motor rated frequency
0.48 Drive operating mode selector
0.49 Security status [M]
0.50 Drive software version [M]
The analog inputs are configured for 0 ~ 10V; see the Hold zero speed
Unidrive Advanced User Guide for selecting other
modes. Refer to parameter 0.19 Hold zero speed enable in
Appendix D Menu 0 Parameters.
Limit switch types
The default setting is as follows:
By default, the Drive requires normally-open limit
switches. When either or both limit switches are to Operating 0.19 Effect on motor...
be normally-closed, set the following parameters mode
at 1, as appropriate: OL 0 Free to rotate
LIMIT FORWARD 0.21 VT 0 Free to rotate
LIMIT REVERSE 0.22 SV 1 Held at zero speed
Deceleration rates
Specific features
Analog
frequency/speed
Brake control is used for controlling the application reference 1
(remote) 0 ~ 10V
and release of a mechanical brake in hoist or crane
applications. The Drive issues a brake release signal
when all of the following conditions are met: 0V common
Analog
The Drive has not tripped (ie. healthy) frequency/speed
reference 2
The motor is at zero speed (local) 0 ~ 10V
(closed-loop only)
Current above a user-defined threshold is 0V common
Frequency/speed ref. 2
(local)
Preset references
(see the Unidrive
Advanced User Guide)
0.38
Power up
parameter
display
0.35 setting
Current detected
Keypad indicator
reference
0.15
Current 0.19
Precision reference threshold
(not used with Menu 0)
Motor current
magnitude 0.14
1.05
Jog reference
(see the Unidrive
Advanced User Guide)
0.18
Drive healthy
0.16
indicator Brake release
indicator
0.20
Brake
At zero speed release
0.17 delay
indicator
Reference enabled
indicator 1.11
(see the Unidrive
Advanced User Guide)
0.20
Brake
At zero speed application
0.17 delay
indicator
0.06
Current
limit
Ramps 0.39
Synchronize
to a spinning
motor
0.03
Acceleration
rate
CL> Speed-loop PID gains
Motor parameters
0.04 Speed-loop
Deceleration 0.07 proportional 0.42 ~ 0.47
rate gain
No. of poles
Power factor
Speed-loop Rated voltage
0.08 Rated speed
Other parameters integral gain
Rated current
Rated frequency
0.31 Macro number
0.32 Serial comms. mode
0.33 Drive rated current
0.34 User security code Speed-loop
0.09 derivative OL> Motor-voltage control
0.36 Serial comms. baud rate gain
0.37 Serial comms. address
0.07
0.40 Autotune
Voltage mode
0.48 Drive operating mode selector
selector
0.49 Security status
0.50 Software version number 0.10 0.08
Boost voltage
Estimated
motor
0.09
speed
Dynamic V/f
Key select
The analog inputs are configured for 0 ~ 10V; see the OL Ramp to a stop
Unidrive Advanced User Guide for selecting other VT Ramp to a stop
modes. SV Stop under current limiting
(no ramp)
Brake-control settings
1. The default setting of 10% for parameter 0.19 Jog
Current threshold is suitable for the majority of
The jog function is available only when the Drive is
applications. If required, change the value to
operating in a closed-loop mode. The default jog
the required percentage of Imax (see below).
speed is 50 RPM. To change the jog speed, see the
This value must ensure that adequate current
Unidrive Advanced User Guide.
will flow through the motor to control the load
when the brake is released.
OL> IMAX = FLC x 150%
CL> IMAX = FLC x 175%
Digital lock
Shaft orientation Master
Features Time
Digital lock
The Drive operates as a slave in closed-loop Slave
master-slave systems. The slave motor is
digitally locked to the master motor.
Time
Shaft orientation
The motor speed is controlled in the same way Figure 319 Rigid digital lock response of the
as for Macro 1, but the motor shaft can be slave motor to a position error
orientated to a specified angular position
before and/or after running the motor.
Non-rigid digital lock
Digital lock specific features The speed of the slave motor is locked to the
speed of the master motor. When a speed error
Closed-loop operation occurs, the behaviour of the system depends on
the amount of error, as follows:
For simplicity, both Drives must be operated in the Speed errors within 5RPM Rigid digital
same closed-loop mode (closed-loop vector or lock occurs (as described above).
closed-loop servo). A feedback encoder or resolver
Speed errors exceeding 5RPM
must be fitted to each motor and connected to the
Rigid digital lock ceases; the correct speed
related Drive. The slave Drive should be fitted with
will subsequently be regained but without
one of the following:
any correction for change of relative angular
UD51 Second encoder small option module position. The slave motor will continue to
UD53 Resolver small option module run at the new relative angular position until
a new speed error exceeding 5RPM occurs.
The master Drive can be operated with any of the
other macros, as appropriate for the application.
Speed Master
Digital-lock modes
Figure 322 Master-slave signal connections for digital lock when encoders are used
Encoder 1 inputs
(Reference encoder)
Resolver Resolver
Master-slave signal connections for digital lock when resolvers are used
Signal
connector
Status relay
Drive healthy
Analog speed
reference 1
(remote) 0 ~ 10V
0V common
Analog speed
reference 2
(local) 0 ~ 10V
0V common
SPEED
TORQUE
ORIENTATION
COMPLETE
RESET
JOG SELECT
RUN FORWARD
RUN REVERSE
LOCAL
Drive enable
0V common
Speed reference 2
(local)
Preset references
(see the Unidrive 0.38
Advanced User Guide) Power up
parameter
display
setting
0.35 Digital
feed-forward
Keypad
reference Positioning
speed limit
Precision reference
(not used with Menu 0) 0.25
Orientation
Reference 0.27 acceptance
encoder/resolver 0.29 window
Reference-encoder /
Feedback-resolver 0.21 revolution counter
position
Feedback-encoder /
Reference-resolver 0.19 Position-
position loop gain 0.24
0.17
Reference-encoder /
Feedback-resolver 0.22 Reference
speed encoder/resolver
ratio
Feedback-encoder / Digital-lock modes: 0
Reference-resolver 0.18 Orientation modes: 1
speed
Feedback
encoder/resolver
0.30
revolution counter
Orientation 0.26
reference
UD53
Position
0.20
Not fitted: 0 error
Fitted: 1
0.06
Current
limit
Speed-loop PID gains
Ramps
Speed-loop 0.39
0.07 proportional Synchronize
gain to a spinning
motor
0.08 Speed-loop
integral gain
0.03
Acceleration
rate
Speed-loop Motor parameters
0.04 0.09 derivative
gain
Deceleration 0.42 ~ 0.47
rate No. of poles
Power factor
Rated voltage
Rated speed
Rated current
Rated frequency
Key
X X Output terminals
Other parameters
To run the slave slower than the master, 1. Close the DRIVE ENABLE contact.
increase the value
2. Close the appropriate RUN contact.
To run the slave faster than the master,
decrease the value 3. Close the (RELATIVE) JOG SELECT contact.
Positioning speed-limit
When a position error is being corrected, the
position loop produces a correction term which is
added to the speed reference that is applied to the
slave Drive. By default, the maximum value of the
correction term is limited to 150RPM. If required,
change the value of this limit by adjusting parameter
0.25 Positioning speed limit from 0 to 250RPM.
Dynamic response to correcting
position errors
Normally, there is no need to adjust the dynamic
response to the correction of position errors. If
required, adjust 0.24 Position-loop gain as follows:
Increase the value for a faster response, but
take care not to induce instability
Decrease the value for a slower response
Orientation speed
The default orientation speed is 150RPM. If required,
adjust parameter 0.25 Positioning speed limit from
0 to 250RPM.
The terminal cover must be (When the Drive is operated in the Closed-loop
fitted to the Drive before the Servo mode, the lower display shows StoP
AC supply is connected. If the instead of rdY.)
cover needs to be removed, the
Warning If the lower display shows triP and the upper
AC supply must first be
disconnected for ten minutes. display shows one of the following, check the
cause and attend to the remedy:
The AC supply must be
Display Cause and remedy
connected to the Drive with
appropriate fuses or th Motor thermistor not connected, or terminal 8
Warning not connected to terminal 11. Make the
protection, as described in the
necessary connections.
Installation Guide.
Et External trip signal received, or terminal 30 not
Adjustment of parameter connected to terminal 31. Make the necessary
values must be performed only connections.
by suitably trained or rS Motor is not connected, one phase is not
Warning
experienced personnel. connected or the motor is open-circuit.
Incorrect values could be
hazardous.
7. Press to reset the Drive. The display
should now show:
OL + VT> rdY
SV> StoP
or
2. To show the status, press: . The status is 2. Do not press any keys. After eight seconds, the
shown immediately. display returns to Status mode. This shows
that the display always returns from Parameter
mode to Status mode when no keys are pressed
within eight seconds.
You may repeat these two steps as many times
as required to obtain an understanding of the
operation.
and
Parameter 0.00 is displayed.
On the first press, the display will re-enter 3. Press and hold down
Parameter mode where parameter 0.06 will The value scrolls downward. Release the key
again be displayed; on the second press, the when the required value is reached.
display will enter Edit mode.)
The upper display still shows the value of the To increase the value, press
parameter, but the least-significant digit
4. When the required value is displayed, press:
flashes. (The value shown is the default value
for 0.06; the value displayed may be different if
the Drive has been used previously.)
5. The display returns to Parameter mode. If no
keys are pressed within eight seconds, the
display enters Status mode.
Making large changes in value quickly
So far, you have changed the value by incrementing
or decrementing the least significant digit. The
speed of change can be increased by selecting, then
scrolling either of the more significant digits, as
follows:
and
The new parameter-value(s) are now saved.
Set-up User Security as follows: Lock Standard and User Security without removing
AC power, as follows:
1. Select parameter 0.34 User security code. The
default value 149 is displayed. 1. Select parameter 00 in any menu.
2. Change the value to the required User Security 2. Set the value at 2000.
number which must be within the range 0 to
255. Do not use the default value 149.
26 Macro Function
018 JOG SELECT input 31 0V common (digital)
2 DOWN input Common connection for external digital devices.
3 PRESET SELECT B input
4 AT MIN. SPEED output
6 LIMIT FORWARD input
27 RUN FORWARD input
28 RUN REVERSE input
29 Macro Function
0178 LOCAL/REMOTE input
2 MOT. POT. ENABLE input
3 PRESET ENABLE input
4 TORQUE ENABLE input
5 PID ENABLE input
6 LIMIT REVERSE input
Macro Condition
0 Required
1 May be connected but is not used by the Drive
2 Required
3 Required
4 Required
5 Do not connect
6 Required
Encoder connector
15-way D-type 7 Required
Encoder 8 Required
Descriptions of the
Encoder connections
Additional
1 Quadrature channel A
commutation
signal 2 Quadrature channel A
connections for
use with servo 3 Quadrature channel B
motors only
4 Quadrature channel B
5 Marker pulse channel Z
6 Marker pulse channel Z
7 Commutation channel U
14 0V common
Frequency
reference
15 Motor thermistor input
Direction
reference
Master
Frequency
reference
Direction
reference
Slave
Signal connector
Macro Condition
0 Required
1 May be connected but not required by the
Drive
2 Required
3 Required
4 Required
5 Do not connect
6 Required
7 Required
8 Required
14 0V common
15 Motor thermistor
Range of values
D.1 Introduction [...] Indicates the value of the parameter
In the parameter descriptions in this chapter, the ~ Indicates a range of values (in the case of bit
number of the equivalent advanced parameter is parameters, ~ indicates or)
shown in brackets under the Menu 0 parameter
number.
Categories of the
The functions of parameters 0.11 to 0.30 can be fixed-function parameters
altered independently of any macro that is enabled
by programming the parameters 11.01 to 11.20 (see The parameters are arranged in the following
the Unidrive Advanced User Guide). categories:
Open-loop
0.00 Operating mode,
Macro selection,
Configuration, Minimum frequency clamp RW Uni
Saving OL> 0 ~ [0.02] 0 Hz
1253 Enable the operating mode of the Drive to CL> 0 ~ [0.02] 0 RPM
be changed and restore parameters to their
default values for 50Hz AC supply Set 0.01 at the required minimum motor speed for
frequency (Europe) both directions of rotation. The motor runs at the
minimum speed when the speed reference is zero.
1254 Enable the operating mode of the Drive to
be changed and restore parameters to their
default values for 60Hz AC supply
0.02 OL> Maximum frequency clamp
frequency (USA) (1.06) CL> Maximum speed clamp
2001 Macro 1
Easy mode
(The Drive has additional over-speed protection.)
2002 Macro 2
Motorized potentiometer Open-loop
2003 Macro 3
Preset speeds Maximum frequency clamp RW Uni
2004 Macro 4 OL> 0 ~ 1000.0 50 (EURO) Hz
Torque control
60 (USA)
2005 Macro 5
PID control Set 0.02 at the required maximum output
2006 Macro 6
frequency for both directions of rotation. The
Axis-limit control frequency reference cannot cause the Drive to run
at a frequency higher than [0.02].
2007 Macro 7
Brake control [0.02] is a nominal value; slip compensation may
2008 Macro 8
cause the actual frequency to be higher.
CL> Digital lock
CL> Shaft orientation
2009 Macro 0
General purpose (USA default configuration)
2010 Macro 0
General purpose (EUR default configuration)
RW Uni
OL> 0 ~ 3200.0 10 s/100Hz
VT> 0 ~ 3200.0 2 s/1000RPM 0.06 Current limit
SV> 0 ~ 32.000 0.2 s/1000RPM
(4.07)
Where:
TR Required maximum torque Motor voltage
IR
[0.06] = 100 (%)
I RATED
[0.08] Frequency
Voltage boost
Where:
IR Required maximum active current Figure D1 Effect of fixed voltage boost on
IRATED Motor rated active current the voltage-to-frequency
Refer to Setting the torque-producing current limit in characteristic
Chapter 3 Setting up the Drive.
Vector control causes the voltage boost to be
Voltage boost (open-loop), automatically regulated according to the load on
the motor.
Speed-loop PID gains (closed-loop)
Vector control requires the value of stator winding
resistance to be stored in a parameter in the Drive.
0.07 OL> Voltage mode selector
(5.14)
The three Vector modes allow the resistance to be
CL> Speed-loop proportional gain
(3.10) measured under different circumstances.
Closed-loop
Open-loop
Speed-loop RW Uni
Voltage mode selector RW Uni P
proportional gain
OL> (See below) Ur_I CL> 0 ~ 32000 200
Setting Function
Open-loop AC supply
voltage
IMOTOR
Boost voltage RW Uni
OL> 0 ~ 25.0 3.0 % x [0.44]
Open-loop
0.42 Motor no. of poles Use the following modes to transfer the value of a
parameter in one Drive to a parameter in another Drive:
The value of 0.10 is applied to the analog output on
terminal 9 to indicate estimated speed. OUtPUt Transmit the value of the parameter specified
by the setting of 11.27 Serial comms. source/
destination selector (CT protocol)
Closed-loop
INPUt Apply the received value to the parameter
specified by the setting of 11.27 Serial comms.
Motor speed RO Bi source/ destination selector (CT protocol)
CL> 30 000 RPM
For the Drive to operate correctly during Set 0.40 at 1 to start the Autotune sequence. See
and after synchronization, parameter Autotune in Chapter 2 Getting Started.
0.07 Voltage mode selector must be set at Fd.
0.40 is related to the advanced parameters as
The Drive starts a sequence of operations at one follows:
quarter of the rated motor voltage in order to
detect the frequency associated with the speed of OL + CL> 5.12 Magnetizing current test enable
the motor. The sequence is stopped when the SV> 3.25 Encoder phasing test enable
motor frequency is detected. The stages in the
sequence are as follows: Note
1. The frequency of the Drive is set at maximum OL + VT> If the settings of parameters 0.41
(the value of 0.02) in the direction that the to 0.47 are changed by a user after
motor was last driven. (If the AC supply to the Autotune has been performed, it is
Drive was interrupted before an attempt is essential that Autotune is repeated.
made to synchronize to a spinning motor, the
Drive always starts in the forward direction.)
0.41 PWM switching frequency
(5.18)
2. The frequency is reduced to zero. If the motor
frequency is detected during the reduction in
RW Txt P
Drive frequency, the test is stopped. The Drive
frequency is set at the detected motor 3, 4.5, 6, 9, 12 3 kHz
frequency and the Drive takes control of the
motor. See PWM switching frequency in Planning the installation
in Chapter 2 Installing the Drive in the Installation
3. If the motor frequency is not detected, the Guide.
Drive is set at maximum frequency in the
opposite direction, and the test is repeated.
Thermal protection
4. If the motor frequency is still not detected, the
Intelligent thermal modelling in the Drive effectively
Drive frequency is set at 0Hz, and the Drive
monitors the junction temperature of the IGBTs in
takes control of the motor.
the power stage. When the junction temperature is
calculated to reach the maximum permissible value,
Closed-loop
two levels of protection occur, as follows:
0.39 is set at 1 by default. The value of 0.12 Post-
1. When a PWM switching frequency of 6kHz, 9kHz
ramp reference is automatically set at the value of
or 12kHz is selected, the PWM switching
speed feedback. The Drive then takes control of the
frequency is automatically halved. This reduces
motor.
switching losses in the IGBTs. (The value of
When 0.39 is set at 0, the motor will be decelerated parameter 0.41 PWM switching frequency remains
under current limit until the motor speed meets the at the value set by the user.)
value of 0.12 Post-ramp reference. Then at one-second intervals, the Drive will
attempt to return the PWM switching frequency
to the original value. This will be successful
when the thermal modelling has calculated that
the temperature has reduced sufficiently.
RW Txt P
VT> 0 ~ 30 000 1450 (EUR) RPM
OL> 2 ~ 32 4 poles
1770 (USA)
VT> 2 ~ 32 4 poles
SV> 0 ~ 30 000 0 RPM
Open-loop RW Uni
Closed-loop Vector 0 ~ FLC FLC A
When Autotune is used, the power factor of the FLC is the maximum permissible continuous output
motor is measured by the Drive and stored in 0.43. current of the Drive up to 40C ambient
The value can be seen when 0.43 is accessed. The temperature and 3kHz PWM switching frequency.
value may be higher than the value stated on the
motor rating plate. Enter the value from the rating plate of the motor.
(See Configuring the Drive for the motor in Chapter 2
If Autotune is not used, enter the value in 0.43. Getting Started.)
RW Uni RW Uni
Unidrive OL> 0 ~ 1000.0 50 (EUR) Hz
OL> 0 ~ 480 400 (EUR) V 60 (USA)
460 (USA) VT> 0 ~ 1000.0 50 (EUR) Hz
400 (EUR) 60 (USA)
VT> 0 ~ 480
460 (USA)
V
SV> 0 0 Hz
SV> 0 0 V
Unidrive LV Open-loop
OL> 0 ~ 240 220 V
Closed-loop Vector
VT> 0 ~ 240 220 V Enter the value from the rating plate of the motor.
SV> 0 0 V (See Configuring the Drive for the motor in Chapter 2
Getting Started.)
Open-loop
Closed-loop Vector
Enter the value from the rating plate of the motor.
(See Configuring the Drive for the motor in Chapter 2
Getting Started.)
RO Bi
See Changing the operating mode in Chapter 2 Getting OL> 1000.0 HZ
Started.
CL> 30 000 RPM
The operating mode cannot be changed while the
Drive is running.
Applicable to Macros......
0.49 Security status When the frequency/speed is constant,
[0.12] = [0.11]. During acceleration and deceleration,
RO Uni the two values may differ.
0~1 1
OL> [0.12] differs from [0.11] also under either of
0.49 normally indicates 1. This shows that access the following conditions:
to the advanced parameters is not possible. (See When the Drive is in current limit
the Unidrive Advanced User Guide.
During braking in a standard ramp (Stnd.Hd
or Std.Ct) mode.
0.50 Software version number
(11.29)
RO Uni P
1 .00~ 99.99
RO Bi RO Bit P
FLC A 0~1
When the motor is being driven below its rated 0.14 indicates the state of the LIMIT FORWARD
speed, the torque is proportional to [0.13]. contact, as follows:
Applicable to Macros...
0.14 Motor current magnitude
0 1 2 3 4 5 6 7 8 (4.01)
OL>
CL> RO Uni P
0 ~ Imax A
Enter the required value of jog frequency/speed.
The frequency/speed limits affect the Drive when
jogging as follows: Applicable to Macros...
Applicable to Macros...
RW Txt P
(See below) VOLt
0 1 2 3 4 5 6 7 8
Applicable to Macros... Select the required ramp mode as follows:
0 1 2 3 4 5 6 7 8 Standard ramp with ramp hold
Stnd.Hd (0)
FASt (1) Fast ramp
Set the required mode as follows: Stnd.Ct (2) Standard ramp with proportional
control (refer to the Unidrive Advanced
Setting Input signal When current User Guide)
signal 3mA...
Set 0.15 Ramp mode selector for the required means
VOLt 0 0V to 10V
of controlling regenerated energy. Regeneration
020 1 0 to 20mA Signal treated as zero arises when the Drive is braking the motor. This
200 2 20mA to 0 Signal treated as zero occurs when the Drive decelerates the motor, or
prevents the speed of the motor from being
420.tr 3 4mA to 20mA Drive trips
increased as a result of mechanical influences.
204.tr 4 20mA to 4mA Drive trips
Regeneration causes the DC-bus voltage to be
420.Lo 5 4mA to 20mA Drive runs at minimum
or low speed increased. The settings for 0.15 determine the
braking action in relation to a DC-bus threshold level
204.Lo 6 20mA to 4mA Drive runs at minimum
known as the standard ramp voltage which is fixed at
or low speed
750V.
420.Pr 7 4mA to 20mA Drive runs at previous
speed
Care should be taken when
204.Pr 8 20mA to 4mA Drive runs at previous changing the setting of
speed parameter 2.08. The value
Warning
th.SC 9 Thermistor with trip on short circuit entered in this parameter
detection (Analog input 3 only) must be greater than the
th 10 Thermistor without short circuit voltage produced on the
detection (Analog input 3 only) DC bus by the highest
AC supply voltage. Normally,
the DC-bus voltage will be
approximately the RMS AC
supply voltage x 2. It is
recommended that the value
entered in parameter 2.08
should be at least 50V
higher than the maximum
expected level of the DC-bus
voltage.
0 Open
1 Closed Select the required stop mode as follows:
Open loop
COASt 0 The motor is allowed to coast
0.15 Current detected indicator
(12.01) rP 1 Ramp to a stop
rP-dcI 2 Ramp followed by 1 second DC injection
RO Bit P
dcI 3 AC injection braking followed by 1 second
0~1 DC injection braking
RW Uni
RO Bit P
0~1 OL> 0~1 0
CL> 0~4 0
Applicable to Macros...
Applicable to Macros...
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
0.16 indicates as follows:
Set 0.17 as follows:
0.16 Drive...
1 Operating normally Setting Open-loop Closed-loop
Applicable to Macros...
RO Bit P
OL> 0~1 0 1 2 3 4 5 6 7 8
Applicable to Macros... These parameters indicate the values of the
0 1 2 3 4 5 6 7 8 following inputs as percentages of the full-scale
values:
0.17 Frequency/speed reference
0.17 indicates as follows: 0.18 PID reference
0.19 PID feedback
Open-loop
0.17 0.12
0 Above 2Hz
1 Below 2Hz
Applicable to Macros...
0 1 2 3 4 5 6 7 8
0.18 Feedback-encoder /
(13.07) Reference-resolver speed
RO Bi P
Set at 1 to enable S-ramp. See 0.19 S-ramp da/dt
limit. CL> 0 ~ 30 000 RPM
Acceleration
Applicable to Macros...
0 1 2 3 4 5 6 7 8
Set 0.19 at the required percentage of Imax (see
below). This value must ensure that adequate
current will flow through the motor to control the
load when the brake is released.
OL> IMAX = FLC x 150%
Actual speed Time
CL> IMAX = FLC x 175%
[ 0.19]
t=
[0.03] Applicable to Macros...
For deceleration: 0 1 2 3 4 5 6 7 8
[0.19]
t=
[0.04] 0.19 indicates position as a count in 1/16384 revolution.
In comparison with a normal ramp, S-ramp increases When a Z marker pulse is detected by the small
the total ramp time by the value of t, since an option module, the position is counted from the
t
additional /2 is added at the beginning and end of pulse. Otherwise, the position is counted from the
the ramp. position at the moment the Drive was last
powered-up.
0.19 Hold zero speed enable For digital-lock operation, 0.19 indicates one of the
(6.08) following, depending on which type of feedback
device is used:
RW Bit
Feedback-encoder position
OL> 0~1 0
Reference-resolver position
VT> 0~1 0
SV> 0~1 1
For shaft orientation, 0.19 indicates
feedback-encoder position.
When a feedback encoder is used, correct indication
Applicable to Macros... depends on the correct value having been entered in
0 1 2 3 4 5 6 7 8 0.16 Feedback encoder No. of lines / pulses per
revolution.
0.20 PID proportional gain 0.16 Drive healthy indicator changes state to 1
(14.10) 0.17 At zero speed changes state to 0
CL> If required, change the setting of 0.20 Brake
RW Uni
application delay to a suitable value (between 0 and
0~4 1 25 seconds) that will ensure a brake release signal is
not removed if the following occur simultaneously
under transient conditions:
Applicable to Macros...
0 1 2 3 4 5 6 7 8
1.11 Reference enabled indicator changes state
to 1
0.17 At zero speed change state to 1
Refer to the setting up instructions for Macro 5 in
Chapter 3 Setting Up the Drive. 0.20 Position error
(13.01)
0.21 Reference-encoder /
(16.03) Feedback-resolver position
RO Uni P
Applicable to Macros...
Input reference 0 1 2 3 4 5 6 7 8
Figure D4 Action of skip frequency/speed 1 1
and skip freq./speed band 1 0.21 indicates position as a count in /16384 revolution.
When a Z marker pulse is detected by the small option
When the frequency/speed (input) reference module, the position is counted from the pulse.
ascends into a skip band, the resulting (output) Otherwise, the position is counted from the position at
reference remains at the lower edge of the band the moment the Drive was last powered-up.
until the input reference has reached the upper edge For digital-lock operation, 0.21 indicates one of the
of the band. The output reference then jumps to following, depending on which type of feedback
the value of the input reference. device is used:
When the frequency/speed (input) reference Reference-encoder position
descends into a skip band, the resulting (output) Feedback-resolver position
reference jumps immediately to the lower edge of For shaft orientation, 0.19 indicates
the band. feedback-encoder/resolver position.
RW Uni RW Uni
0~4 0 0 ~ 100 100 %
0 1 2 3 4 5 6 7 8
0.23
Quadrature Frequency + Working-speed
For digital-lock operation, 0.22 indicates the direction range
following, depending on which type of feedback 5000 10000 0 ~ 3000
device is used:
2500 5000 3001 ~ 6000
Reference-encoder speed
Feedback-resolver speed 1250 2500 6001 ~ 12000
When a reference-encoder is used (ie. a feedback 625 1250 12001 ~ 24000
encoder is used in the master Drive), correct 500 1000 24001 ~ 30 000
indication of 0.22 (in the slave Drive) depends on
the correct value having been entered in Operation below a specified working-speed range
3.21 Feedback encoder No. of lines / pulses per revolution will result in progressively reducing resolution.
in the master Drive as well as in 0.23 Reference Operation cannot occur above a specified
encoder No. of lines / pulses per revolution in the slave working-speed range because of a limit on the
Drive. maximum possible pulse repetition frequency.
For shaft orientation, 0.18 indicates For operation with frequency and direction signals,
feedback-encoder/resolver speed. see the Unidrive Advanced User Guide.
Applicable to Macros...
RW Uni
0 1 2 3 4 5 6 7 8
CL> 0 ~ 4.000 0.1
Refer to the setting up instructions for Macro 5 in Applicable to Macros...
Chapter 3 Setting Up the Drive. 0 1 2 3 4 5 6 7 8
Applicable to Macros...
0 1 2 3 4 5 6 7 8
When 0.25 is set at 1, this indicates that the
motorized potentiometer output is reset to 0%.
The motorized potentiometer is reset when the
RESET contact is closed (terminal 25) (only when
Macro 2 is enabled).
Applicable to Macros...
100 %
0 1 2 3 4 5 6 7 8
Applicable to Macros...
0 1 2 3 4 5 6 7 8
0.25 indicates the value of the torque reference
applied to terminals 5 and 6 of the signal connector.
0.25 Positioning speed limit 0.26 indicates the value of the output of the
(13.09) motorized potentiometer as a percentage of the
maximum value.
RW Uni
CL> 0 ~ 250 150 RPM 0.26 Analog input 2 mode selector
(7.11)
Applicable to Macros...
RW Txt P
0 1 2 3 4 5 6 7 8
(See below) VOLt
For digital-lock operation, use 0.25 to determine Applicable to Macros...
the maximum variation in slave speed in relation to
0 1 2 3 4 5 6 7 8
that of the master when position errors are being
corrected. This speed limit can be used to suppress
large variations in speed that would otherwise arise
when high values of 0.24 Position-loop gain are used.
RW Uni
Sequencing mode RW Uni P
CL> 0 ~ 4095 0
1
/4096 REV. selector
0~4 4
Applicable to Macros...
Use 0.27 (6.04) to change the functions of the
0 1 2 3 4 5 6 7 8 digital inputs; these functions determine the digital
control mode.
Adjust 0.26 for the required shaft orientation The default setting (4) gives the functions shown in
relative to the zero position of the (absolute) the signal connection diagrams in Chapter 3 Setting
encoder or resolver fitted to the motor. See also up the Drive.
0.27 Orientation acceptance window.
Set 0.27 at 0 for digital control by momentary
Not used for digital lock. contacts. See Macro 0 in Chapter 3 Setting up the
Drive.
0.26 Preset reference 7 It is essential that you see 0.29 USA> Terminal-29
(1.27) destination selector in order to set up a RUN PERMIT /
0.27 Preset reference 8 STOP input.
(1.28)
For other settings of 0.27, refer to parameter 6.04
RW Bi in the Unidrive Advanced User Guide.
OL> 1000 0 Hz
CL> 30 000 0 RPM
0.27 Motorized potentiometer
(9.21) zero-start select
0 1 2 3 4 5 6 7 8
0~1 0
Applicable to Macros...
These parameters are used as preset references for 0 1 2 3 4 5 6 7 8
the frequency/speed reference and PID reference.
Refer to Macro 5 in Chapter 3 Setting Up the Drive.
Set 0.27 for the way the motorized potentiometer
is to behave at power-up of the Drive as follows:
0.27 Analog reference 2 The values of 0.28 and 0.29 affect the dynamic
(1.37) performance of the Drive in the following
conditions:
RO Bi Current-limit in frequency/speed control
100 Hz Torque control
30,000 RPM Braking when 0.15 Ramp mode selector is set
at Stnd.Ct (default)
Synchronizing the Drive to a spinning motor
Applicable to Macros...
(0.39 set at 1)
0 1 2 3 4 5 6 7 8
Loss of AC supply when 6.03 AC supply loss
mode selector is set at ridE.th.
0.27 indicates the value of the torque reference For information on adjusting these parameters, refer
applied to terminal 7 of the signal connector. to parameters 4.13 and 4.14 in the Unidrive Advanced
User Guide.
RW Uni
Applicable to Macros...
0 1 2 3 4 5 6 7 8
0 ~ 250 20 s
Applicable to Macros...
Set 0.28 as follows:
0 1 2 3 4 5 6 7 8
0 Unipolar output (0 ~ 100%)
1 Bipolar output (100%)
Enter the required time for the
motorized-potentiometer output to change by
100%.
0.28 Overspeed threshold
(3.08)
0.28 Analog input 2 (PID reference)
RO Bi (7.12) scaling
OL> 0 ~ 1000 1000 HZ 0.29 Analog input 3 (PID feedback)
VT> 0 ~ 30000 2000 RPM (7.16) scaling
SV> 0 ~ 30000 4000 RPM
RW Uni
0~4 1
Applicable to Macros...
0 1 2 3 4 5 6 7 8 Applicable to Macros...
0 1 2 3 4 5 6 7 8
RW Txt RO Uni P
VT> (See below) rP CL> 0 ~ 16384 revolutions
SV> no.rP
Applicable to Macros...
Applicable to Macros... 0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
For digital-lock operation, the value of 0.29 is
For digital-lock operation, the default setting of incremented by 1 for each forward revolution of the
0.28 should be used.
RW Uni
0~4 1
Applicable to Macros...
0 1 2 3 4 5 6 7 8
By default, when the motorized potentiometer
output is 100%, the frequency/speed is set at 100%.
If necessary, enter the required value to reduce the
frequency/speed range.
0.22 Skip freq./speed 2 (1.31) Skip freq./speed 2 (1.31) Skip freq./speed 2 (1.31) Skip freq./speed 2 (1.31)
0.23 Skip freq./speed band 2 Skip freq./speed band 2 Skip freq./speed band 2 Skip freq./speed band 2
(1.32) (1.32) (1.32) (1.32)
0.24 Analog input 1 mode Analog input 1 mode Analog input 1 mode Analog input 1 (torque
selector (7.06) selector (7.06) selector (7.06) reference) mode selector
(7.06)
0.25 Analog input 2 mode Motorized pot. reset Preset reference 1 (1.21) Analog reference 1
selector (7.11) indicator (9.28) (torque reference) (1.36)
0.26 Analog input 2 destination Motorized pot. output Preset reference 2 (1.22) Analog input 2 mode
selector (7.14) indicator (9.03) selector (7.11)
0.27 EUR> Positive logic select Motorized pot. zero-start Preset reference 3 (1.23) Analog input 2
(8.27) select (9.21) (CL> Speed over-ride)
(1.37)
USA> Sequencing mode
selector (6.04)
0.28 EUR> Current-loop Motorized pot. bipolar Preset reference 4 (1.24) Over-speed threshold
proportional gain (4.13) select (9.22) (3.08)
USA> Freq./speed demand
(1.01)
0.29 EUR> Current-loop Motorized pot. rate (9.23) Analog input 1 scaling
integral gain (4.14) (7.08)
USA> Terminal-29
destination selector (8.23)
0.30 FWD/REV key enable (6.13) Motorized pot. output Analog input 2 scaling
scale factor (9.24) (7.12)
0.15 Analog input 2 Run forward indicator Current detected indicator Position-loop mode
(PID reference) mode (8.04) (12.01) selector (13.08)
selector (7.11)
0.16 Analog input 3 Run reverse indicator (8.05) Drive healthy indicator Feedback encoder No. of
(PID feedback) mode (10.01) lines / pulses per
selector (7.15) revolution (3.21)
0.17 Analog input 1 Limit reverse indicator At zero speed indicator Reference encoder/
(frequency/speed (8.06) (10.03) resolver ratio (13.07)
reference) (7.01)
0.18 Analog input 2 Stop mode selector (6.01) Brake release indicator Feedback-encoder /
(PID reference) (7.02) (9.01) reference-resolver speed
(3.26)
0.19 Analog input 3 Hold zero speed enable Current threshold (12.04) Feedback-encoder /
(PID feedback) (7.03) (6.08) reference-resolver position
(3.27)
0.20 PID proportional gain Limit deceleration rate OL> Brake release delay Position error (13.01)
(14.10) (2.22) CL> Brake application
delay
(9.19)
0.21 PID integral gain (14.11) Limit forward invert (8.17) Reference-encoder /
Feedback-resolver position
(16.03)
0.22 PID derivative gain (14.12) Limit reverse invert (8.24) Reference-encoder /
Feedback-resolver speed
(16.02)
0.23 PID output high limit (14.13) Reference encoder No. of
lines / pulses per
revolution (16.04)
0.24 PID output low limit (14.14) Position-loop gain (13.09)
0.25 PID output scale factor Positioning speed limit
(14.15) (13.10)
0.26 Preset reference 7 (1.27) Orientation reference
(13.11)
0.27 Preset reference 8 (1.28) Orientation acceptance
window (13.12)
0.28 Analog input 2 scaling Stop mode selector (6.01)
(7.12)
0.03 Acceleration rate value too low connected incorrectly or the phase sequence of the motor
is reversed.
0.04 Deceleration rate value too low
CL> 0.27 Proportional gain too high ENC.PH8 18
(used in Macro 0 only) Autotune fail (wrong test for operating mode,
Excessive motor-cable capacitance limit-switch operated, trip, etc).
Short-circuit at the output of the Drive Resolver phasing test or magnetizing current test ended
4 prematurely.
OI.br
Excessive current in the braking resistor. It.br 19
PS 5 It.AC 20
Internal power supply fault. The [I x t] thermal overload accumulator has reached 100%
(see the OVLd alarm).
Remove and re-connect the AC supply. If the trip persists,
contact the supplier of the Drive. Oh1 21
Et 6 Excessive heatsink temperature due to excessive [I xt]
(see the hot alarm).
OL> External trip signal applied to terminal 30.
Oh2 22
Remove the trip signal, then reset the Drive.
Excessive heatsink temperature detected by thermistor.
OV.SPd 7
OA 23
The motor has exceeded the over-speed threshold.
This can be caused by the following: The temperature of the air around the control circuits is
excessive (see the Air alarm).
Sudden removal of a large mechanical load
0.04 Deceleration rate value too low th 24
Inappropriate setting for 0.16 Stop mode selector The motor thermistor has detected excessive motor
0.19 S-ramp da/dt too high (not used in Macro 5) temperature (or the thermistor or wiring is open-circuit).
Prc2 8 thS 25
Trip in Processor-2 large option module. The motor thermistor or wiring is short-circuit.
SEP 9 OP.OVLd 26
Trip in the small option module. See the User Guide for The total current drawn from terminals 22 and 24
the relevant small option module. exceeds 200mA.
Incorrect DC supply voltage for the encoder (parameter VT> Loss of resolver output signals
16.15) SV> Resolver and/or motor phase connections incorrect,
After rectifying the fault, remove, then re-apply the causing reverse torque to be produced
AC supply to the Drive in order to obtain absolute position FSH.Err 182
information.
The memory of the UD55 small option module has been
SEP EF 36 found to be corrupt. If the trip has occurred at power-up,
Fault in the SIN-COS encoder. the memory is automatically re-formatted and all the
parameter-sets are erased. If the trip occurs after power-
AN1.diS 37 up, the memory and parameter-sets are unaffected. See
Servo large option module removed. the UD55 User Guide.
Regeneration sinusoidal rectifier failed to synchronize to No values have been found in the selected parameter-set in
the AC supply. the UD55 small option module. Consequently, no values
have been copied to the destination Drive.
FSH.rng 188