132kV Transformers & Earthing/Aux. Transformers 1.5.1.1.2.01-Rev.

ll I

ANNEXURE - 2

LOSS EVALUATION, THEIR TOLERANCE AND PENALTIES


FOR EXCESS TRANSFORMER LOSS

Tbe :maximum. va1.ues of no 1.0ad 1.0ss and 1.0ad 1.0ss considered for the
transfozmers is given be1.ow ..

Transfozmer rating No 1.0ad 1.0ss Load Loss inc1.uding Fan 1.0sses


(kW) (kW)
35/50 MVA 132/12 kV 14 260
60/90 MVA 132/35.5 kV 25 320
60/90 MVA 132/35 kV 25 320
60/75 MVA 132/33 kV 22 280

Tolerances on Guaranteed Values of Losses and Penalty (app1.icab1.e on test


resu1.ts)

The admissible tolerances for component and total losses for each
transformer shall be as giv~n in lEe 60076 which is:

+ 10% for the total losses


+ 15% for each component loss, provided that the tolerance
for total losses is not exceeded

Each transformer with losses within the above mentioned tolerance


limits will be accepted subjected to the conditions that a sum will be
deducted from the contract price equal to:

Fe losses: 36,000 Dhs/kW within 5% in excess of guarantee


72,000 Dhs/kW above 5% in excess of guarantee

eu losses: 7,200 Dhs/kW within 5% in excess of guarantee


14,400 Dhs/kW above 5% in excess of guarantee

If any tolerance is exceeded above the lEe limits indicated above,


the transformer will be rejected. Each transformer shall fulfil the
above requirements and no rebate will be given to the tenderer if the
losses are less than the guaranteed values.