Sie sind auf Seite 1von 3

barras

Name In Folder Grid Nom.L-L Volt.Ul, Magnitudu, MagnitudeU, Angle


kV kV p.u. deg
BB2 N3 red 110KV 110 106.1578 0.9650706 -2.800496
BB2 N2 red 110KV 110 106.5973 0.9690663 -3.032677
N1 Single Busbared 110KV 380 387.6 1.02 0
N2 N2 red 110KV 110 106.5973 0.9690663 -3.032677
N3 N3 red 110KV 110 106.1578 0.9650706 -2.800496
N4 N4 red 110KV 110 101.552 0.9231997 -4.836353
N5 N5 red 110KV 10 10 1 -150.588
N6 N6 red 110KV 10 10 1 -150.588

lineas
Name Grid Terminal i Terminal i Terminal j Terminal j u, Magnitudeu, MagnitudeLoading
StaCubic Busbar StaCubic Busbar Terminal i in Terminal j in %
L1 red 110KV N2 N2 N3 BB2 0.9690663 0.9650706 10.59017
Line2 red 110KV N2 N2 N3 BB2 0.9690663 0.9650706 10.59017
Line3 red 110KV N2 N2 N4 N4 0.9690663 0.9231997 38.35112
Line4 red 110KV N2 N2 N4 N4 0.9690663 0.9231997 36.90873
Line5 red 110KV N3 N3 N4 N4 0.9650706 0.9231997 49.92174

transformadores
Name Grid HV-Side HV-Side LV-Side LV-Side u, Magnitudeu, MagnitudeLoading
StaCubic Busbar StaCubic Busbar HV-Side in p. LV-Side in p.u%
T1 red 110KV Single Busba N1 N2 BB2 1.02 0.9690663 77.08288
T2 red 110KV N3 N3 N6 N6 0.9650706 1 53.80676
T3 red 110KV N3 N3 N5 N5 0.9650706 1 53.80676

generadores
Name Grid Terminal Terminal Bus T. Active PowerReactive PowApparent Po Par.no.
StaCubic Busbar MW Mvar MVA
G1 red 110KV N6 N6 PV 30 6.735035 30.74672 1
G2 red 110KV N5 N5 PV 30 6.735035 30.74672 1

cargas
Name Grid Terminal Terminal u, MagnitudeActive PowerReactive PowApparent Po Power Factor
StaCubic Busbar p.u. MW Mvar MVA
C1 red 110KV N4 N4 0.9231997 50 30.98721 58.82353 0.85
C2 red 110KV N4 N4 0.9231997 46.4 28.75613 54.58823 0.8500001
C3 red 110KV N3 BB2 0.9650706 10 4.843222 11.11111 0.9
C4 red 110KV N2 N2 0.9690663 35 18.891 39.77273 0.88
Capacitive Loading
Mvar
0.4799382
0.4799382
1.225737
1.753485
0.9153365

Tap 1, CurrenTap 1, Min. PTap 1, Max. PActive PowerReactive PowActive PowerReactive Power
HV-Side in HV-Side in M LV-Side in M LV-Side in Mvar
0 -9 9 84.32461 82.45271 -84.13169 -73.84744
0 -9 9 -29.93005 -5.490042 30 6.735035
0 -9 9 -29.93005 -5.490042 30 6.735035

App.Pow. u, MagnitudePower FactorLoading


MVA p.u. %
46.55 1 0.9757139 66.05096
46.55 1 0.9757139 66.05096

Das könnte Ihnen auch gefallen