Sie sind auf Seite 1von 2

Ea

St Resi
rth

N
ep st
/ C anc
MI 3295 Step Contact Voltage

on e M
EW
Safe

ta e
ct as
Measuring System

Vo ur
Low weight

lta em
ge en
High accuracy

, ts
Autonomous meter
Excellent noise immunity

STANDARDS / REGULATIVES:
Functionality:
RAT 2008;
MI 3295 Step Contact Voltage Measuring System is a voltage meas- HD 637 S1;
uring system for testing and verification of protective earthing of ANSI/IEEE Std 81;
power stations, substation and other power systems. EN 61557-5

MEASURING FUNCTIONS: Electromagnetic compatibility


Measurement of step voltage and contact voltage. (EMC):
Measurement of earthing resistance with resolution of 1 m. EN 61326
Measurement of specific earth resistance.
Safety (LVD):
KEY FEATURES: EN 61010-1;
High accuracy of the measurements due to a high current of up to EN 61010-031
50 A and effective suppression of noise.
Step and Contact Voltages in case of
Excellent immunity even against changing earth currents. failure
Autonomous Step Voltage meter: no need for long voltage leads.
Low weight.
High safety due to low output voltage (55 V).
Downloads test results directly to the PC with the help of the profes-
sional PC SW package HVLink which enables analysis and documenta-
tion of test results.

APPLICATION:
Measurement of protective earthing of:
Power stations,
Substations,
Distribution towers, RoHS
Other power systems COMPLIANT
2002 / 95 / EC
ORDERING INFORMATION:
Technical Specification
MI 3295 Standard set

Function Measuring range Resolution Accuracy


0.01 19.99 mV 0.01 mV
Step voltage, 20.0 ... 199.9 mV 0.1 mV
Contact voltage 200 ... 1999 mV 1 mV (2% of reading + 2 digits)
(measuring range Um) 2.00 ... 19.99 V 0.01 V
20.0 V 59.9 V 0.1 V
Step voltage,
Contact voltage 0.0 199.9 V 0.1 V
calculated value*
(calculated measuring 200 999 V 1V
range U)
Test current 55 A max
Test voltage < 55 V
Test frequency 55 Hz Instrument MI 3295M
Input resistance Selectable 1 M / 1k Instrument MI 3295S
0.00 ... 9.99 A 0.01 A (3% of reading + 5 digits) Mains cable
Current
10.0 ... 99.9 A 0.1 A (3% of reading + 3 digits) Step voltage probe (25 kg), 2 pcs
0.001 1.999 0.001 (2% of reading + 5 digits) Current earth spike
2.00 ... 19.99 0.01 (2% of reading + 5 digits) Potential earth spike
Resistance to earth
20.0... 99.9 0.1 (2% of reading + 5 digits) Current test lead, 50 m, black, 10 mm2, with
100.0 ... 199.9 0.1 (5% of reading)
crocodile clip, on wheel
0.00 9.99 m 0.01 m Current test lead, 10 m, black, 10 mm2, with
10.0 99.9 m 0.1 m Calculated value, consider ac-
Specific earth crocodile clip
100 999 m 1 m curacy of Resistance to earth
resistance Test lead, black, 2 x 3 m
1.00 k 9.99 km 10 m function.
10.0 k 99.9 km 100 m Test lead, green, 10 m
Open circuit Test lead, black, 1.5 m
< 50 VAC
voltage Test lead, red, 50 m
Test current < 7.5 A Connection lead with crocodile clip, red, 1 m
Test frequency 55 Hz Crocodile clip, 4 pcs
General RS232 cable
STATION USB cable
Soft carrying bag, 2 pcs
Power supply 230 V / 50 or 60 Hz
Soft carrying neck belt
Communication port RS232
NiMH battery cells, type AA, 6 pcs
Memory 1000 memory locations Power supply adapter
Overvoltage category CAT II / 300 V CD with instruction manual and PC SW HVLink PRO
Measuring category CAT IV / 50 V Instruction manual
Protection degree IP 30 Calibration certificate
Display LCD, 128 x 64 dots, with backlight
Dimensions 563 x 275 x 257 mm
Weight 29.5 kg Optional accessories:
METER
Photo Order No. Decription
Power supply 6 x 1.2 V rechargeable battery, type AA
Operation time 12 h (typical)
Current and voltage earth
Communication ports USB, RS232 A 1323
spikes (with 3 m lead)
Memory 1500 memory locations
Measuring category CAT IV / 50 V
Protection degree IP 40
A 1324 Hand trolley
Display LCD, 128 x 64 dots, with backlight
Dimensions 230 x 103 x 115 mm
Weight 1.3 kg
Step voltage probe (25 kg),
A 1353
2 pcs
*Note:
Displayed Step / Contact voltage is obtained on base of calculation: Step Contact Meter
US = Umeas Ifault / Imeas; UC = Umeas Ifault / Imeas; Measuring Set
Ifault (selectable)....... 1 A ... 200 kA - Instrument MI 3295M
MI 3295M - Test lead, 2 x 3 m
Set - Soft carrying bag
- Soft carrying neck belt
- NiMH battery, type AA, 6 pcs
- Power supply adapter

Measuring and Regulation Equipment Manufacturer


METREL d.d.
Ljubljanska 77
SI-1354 Horjul
Tel: + 386 (0)1 75 58 200
Fax: + 386 (0)1 75 49 226
E-mail: metrel@metrel.si Note! Photographs in this catalogue may slightly differ
http://www.metrel.si from the instruments at the time of delivery.
Subject to technical change without notice.