K02 - DESFIBRADOR_prn

PRINT - CONTENTS
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

PRINT - CONTENTS
1 Device Configuration .................................................................................................................................................. 2
2 Power System Data 1 ................................................................................................................................................ 3
2.1 Group Power System Data 1; Group Power System ................................................................................................. 3
2.2 Group Power System Data 1; Group Prot.Op. quant. ................................................................................................ 3
2.3 Group Power System Data 1; Group CT's ................................................................................................................. 3
2.4 Group Power System Data 1; Group VT's ................................................................................................................. 4
2.5 Group Power System Data 1; Group Breaker ............................................................................................................ 4
2.6 Group Power System Data 1; Group Threshold BI .................................................................................................... 4
3 Settings groups .......................................................................................................................................................... 5
3.1 Group Power System Data 2; Group General ........................................................................................................... 5
3.2 Group DMT / IDMT Phase/Earth Overcurrent; Group General .................................................................................. 5
3.3 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph .................................................................................. 5
3.4 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph ................................................................................. 6
3.5 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT E .................................................................................... 6
3.6 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E ................................................................................... 7
3.7 Group Unbalance Load (Negative Sequence); Group General ................................................................................. 7
3.8 Group Unbalance Load (Negative Sequence); Group DMT ...................................................................................... 7
3.9 Group Motor Protection; Group General .................................................................................................................... 7
3.10 Group Motor Protection; Group Startup Sup. ............................................................................................................. 8
3.11 Group Motor Protection; Group Startup Counter ....................................................................................................... 8
3.12 Group Motor Protection; Group Load Jam Prot. ........................................................................................................ 8
3.13 Group Thermal Overload; Group General ................................................................................................................. 9
3.14 Group Thermal Overload; Group Therm Over Load .................................................................................................. 9
3.15 Group Measurement Supervision; Group General .................................................................................................... 9
3.16 Group Measurement Supervision; Group MeasSupervision .................................................................................... 10
3.17 Group Measurement Supervision; Group Fuse Fail Mon. ....................................................................................... 10
3.18 Group RTD-Box; Group RTD 1-3 ............................................................................................................................. 10
3.19 Group RTD-Box; Group RTD 4-6 ............................................................................................................................. 11
3.20 Group Energy; Group Measurement ........................................................................................................................ 11

Page 1 of 11
K02 - DESFIBRADOR_prn
Device Configuration
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0104 Oscillographic Fault Records Enabled
0112 DMT / IDMT Phase Time Overcurrent Curve IEC
0113 DMT / IDMT Earth Time Overcurrent Curve IEC
0116 DMT / IDMT Directional Earth Disabled
0117 Cold Load Pickup Disabled
0122 2nd Harmonic Inrush Restraint Disabled
0131 (sensitive) Earth fault Disabled
0130 (sens.) Earth fault dir. characteristic cos phi / sin phi measurement (standard)
0140 Unbalance Load (Negative Sequence) Definite Time only
0141 Startup Time Supervision for Motors Enabled
0142 Thermal Overload Protection Without ambient temperature measurement
0143 Startup Counter for Motors Enabled
0144 Load Jam Protection Enabled
0150 Under / Overvoltage Protection Disabled
0154 Over / Underfrequency Protection Disabled
0170 Breaker Failure Protection Disabled
0172 Circuit Breaker Wear Monitoring Disabled
0182 Trip Circuit Supervision Disabled
0190 External Temperature Input Enabled
0191 Ext. Temperature Input Connection Type Internal Temperature Measurement
0192 Capacitive voltage measurement NO
Flexible Function

Page 2 of 11
K02 - DESFIBRADOR_prn
Power System Data 1
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

2 Power System Data 1

2.1 Group Power System Data 1; Group Power System


Group Power System Data 1; Group Power System
No. Settings Value Group

0214 Rated Frequency 60 Hz All


0209 Phase Sequence L1 L2 L3 All
0276 Unit of temperature measurement Degree Celsius All
0201 CT Starpoint towards Line All
0280 Holmgreen-conn. (for fast sum-i-monit.) NO All
0251A CT Connection IL1, IL2, IL3, (IE) All
0213 VT Connection, three-phase U12, U23, UE All
0235A Storage of th. Replicas w/o Power Supply YES All

2.2 Group Power System Data 1; Group Prot.Op. quant.


Group Power System Data 1; Group Prot.Op. quant.
No. Settings Value Group

0250A Time Overcurrent with 2 phase prot. OFF All


0613A (I) DMT Earth Overcurrent with IE (measured) All

2.3 Group Power System Data 1; Group CT's


Group Power System Data 1; Group CT's
No. Settings Value Group

0204 CT Rated Primary Current 400 A All


0205 CT Rated Secondary Current 5A All
0217 IE-CT rated primary current 100 A All
0218 IE-CT rated secondary current 5A All

Page 3 of 11
K02 - DESFIBRADOR_prn
Group Power System Data 1; Group VT's
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

2.4 Group Power System Data 1; Group VT's


Group Power System Data 1; Group VT's
No. Settings Value Group

0202 Rated Primary Voltage 13,80 kV All


0203 Rated Secondary Voltage (L-L) 115 V All
0206A Matching ratio Phase-VT To Open-Delta-VT 1,73 All

2.5 Group Power System Data 1; Group Breaker


Group Power System Data 1; Group Breaker
No. Settings Value Group

0210A Minimum TRIP Command Duration 0,15 sec All


0212 Closed Breaker Min. Current Threshold 0,20 A All

2.6 Group Power System Data 1; Group Threshold BI


Group Power System Data 1; Group Threshold BI
No. Settings Value Group

0220 Threshold for Binary Input 1 Threshold for Binary Input: 88V All
0221 Threshold for Binary Input 2 Threshold for Binary Input: 88V All
0222 Threshold for Binary Input 3 Threshold for Binary Input: 88V All

Page 4 of 11
K02 - DESFIBRADOR_prn
Settings groups
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

3 Settings groups

3.1 Group Power System Data 2; Group General


Group Power System Data 2; Group General
No. Settings Value Group

1101 Measurement: Full Scale Voltage (100%) 15,00 kV A


1102 Measurement: Full Scale Current (100%) 400 A A
1107 Motor Start Current (BLK OVL,Start Mon.) 12,50 A A
1108 P,Q operational measured values sign not reversed A

3.2 Group DMT / IDMT Phase/Earth Overcurrent; Group General


Group DMT / IDMT Phase/Earth Overcurrent; Group General
No. Settings Value Group

1201 Phase Time Overcurrent ON A


1213A Manual Close Mode I>> instantaneously A
1215A Dropout Time Delay DMT Phase 0,05 sec A
1301 Earth Time Overcurrent ON A
1313A Manual Close Mode IE>> instantaneously A
1315A Dropout Time Delay DMT Earth 0,05 sec A

3.3 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph


Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph
No. Settings Value Group

1219A I>>> measurement of Fundamental component A


1216A I>>> active Always A
1217 I>>> Pickup 12,72 A A
1218 T I>>> Time Delay 0,05 sec A
1220A I>> measurement of Fundamental component A
1214A I>> active Always A
1202 I>> Pickup 12,72 A A
1203 T I>> Time Delay 0,05 sec A

Page 5 of 11
K02 - DESFIBRADOR_prn

ABENGOA SAO LUIZ / Preparo / K02


SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph(2)


No. Settings Value Group

1221A I> measurement of Fundamental component A


1204 I> Pickup 2,59 A A
1205 T I> Time Delay 7,35 sec A

3.4 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph


Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph
No. Settings Value Group

1222A Ip measurement of True RMS A


1207 Ip Pickup 2,00 A A
1208 T Ip Time Dial 1,30 sec A
1210 Drop-Out Characteristic Instantaneous A
1211 IEC Curve Very Inverse A

3.5 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT E


Group DMT / IDMT Phase/Earth Overcurrent; Group DMT E
No. Settings Value Group

1319A IE>>> measurement of Fundamental component A


1317 IE>>> Pickup oo A A
1318 T IE>>> Time Delay 0,05 sec A
1320A IE>> measurement of Fundamental component A
1302 IE>> Pickup oo A A
1303 T IE>> Time Delay 0,10 sec A
1321A IE> measurement of Fundamental component A
1304 IE> Pickup oo A A
1305 T IE> Time Delay 0,50 sec A
1314A IE>> active Always A
1316A IE>>> active Always A

Page 6 of 11
K02 - DESFIBRADOR_prn
Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

3.6 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E


Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E
No. Settings Value Group

1322A IEp measurement of True RMS A


1307 IEp Pickup 1,00 A A
1308 T IEp Time Dial 0,05 sec A
1310 Drop-Out Characteristic Instantaneous A
1311 IEC Curve Very Inverse A

3.7 Group Unbalance Load (Negative Sequence); Group General


Group Unbalance Load (Negative Sequence); Group General
No. Settings Value Group

4001 Unbalance Load (Negative Sequence) ON A


4012A Dropout Time Delay DMT 0,00 sec A

3.8 Group Unbalance Load (Negative Sequence); Group DMT


Group Unbalance Load (Negative Sequence); Group DMT
No. Settings Value Group

4002 I2> Pickup 0,50 A A


4003 T I2> Time Delay 5,00 sec A
4004 I2>> Pickup 1,00 A A
4005 T I2>> Time Delay 1,50 sec A

3.9 Group Motor Protection; Group General


Group Motor Protection; Group General
No. Settings Value Group

4101 Startup Time Supervision for Motors ON A


4301 Startup Counter for Motors ON A
4401 Load Jam Protection ON A

Page 7 of 11
K02 - DESFIBRADOR_prn

ABENGOA SAO LUIZ / Preparo / K02


SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

3.10 Group Motor Protection; Group Startup Sup.


Group Motor Protection; Group Startup Sup.
No. Settings Value Group

4102 Startup Current 10,00 A A


4103 Startup Time 7,0 sec A
4104 Permissible Locked Rotor Time 10,0 sec A
4105 Startup Time for warm motor 7,0 sec A
4106 Temperature limit for cold motor 25 % A

3.11 Group Motor Protection; Group Startup Counter


Group Motor Protection; Group Startup Counter
No. Settings Value Group

4311 Rotor Overload Protection ON A


4302 I Start / I Motor nominal 5,50 A
4303 Maximum Permissible Starting Time 8 sec A
4304 Temperature Equalizaton Time 1,0 min A
4305 Rated Motor Current 1,81 A A
4306 Maximum Number of Warm Starts 2 A
4307 Number of Cold Starts - Warm Starts 1 A
4308 Extension of Time Constant at Stop 5,0 A
4309 Extension of Time Constant at Running 2,0 A
4310 Minimum Restart Inhibit Time 10,0 min A

3.12 Group Motor Protection; Group Load Jam Prot.


Group Motor Protection; Group Load Jam Prot.
No. Settings Value Group

4406 Load Jam Blocking after motor start 10,00 sec A


4402 Load Jam Tripping Threshold 8,00 A A
4403 Load Jam Trip Delay 3,00 sec A
4404 Load Jam Alarm Threshold 6,00 A A

Page 8 of 11
K02 - DESFIBRADOR_prn

ABENGOA SAO LUIZ / Preparo / K02


SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

Group Motor Protection; Group Load Jam Prot.(2)


No. Settings Value Group

4405 Load Jam Alarm Delay 1,00 sec A

3.13 Group Thermal Overload; Group General


Group Thermal Overload; Group General
No. Settings Value Group

4201 Thermal overload protection ON A

3.14 Group Thermal Overload; Group Therm Over Load


Group Thermal Overload; Group Therm Over Load
No. Settings Value Group

4202 K-Factor 1,10 A


4203 Time Constant 100,0 min A
4204 Thermal Alarm Stage 90 % A
4205 Current Overload Alarm Setpoint 1,81 A A
4207A Kt-FACTOR when motor stops 1,0 A
4208A Emergency time 100 sec A

3.15 Group Measurement Supervision; Group General


Group Measurement Supervision; Group General
No. Settings Value Group

8101 Measurement Supervision ON A


5301 Fuse Fail Monitor OFF A
5310 Block protection by FFM NO A

Page 9 of 11
K02 - DESFIBRADOR_prn
Group Measurement Supervision; Group MeasSupervision
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

3.16 Group Measurement Supervision; Group MeasSupervision


Group Measurement Supervision; Group MeasSupervision
No. Settings Value Group

8102 Voltage Threshold for Balance Monitoring 50 V A


8103 Balance Factor for Voltage Monitor 0,75 A
8104 Current Balance Monitor 2,50 A A
8105 Balance Factor for Current Monitor 0,50 A

3.17 Group Measurement Supervision; Group Fuse Fail Mon.


Group Measurement Supervision; Group Fuse Fail Mon.
No. Settings Value Group

5302 Zero Sequence Voltage 30 V A


5303 Residual Current 0,50 A A
5307 I> Pickup for block FFM 5,00 A A

3.18 Group RTD-Box; Group RTD 1-3


Group RTD-Box; Group RTD 1-3
No. Settings Value Group

9011A RTD 1: Type Pt 100 Ohm A


9012A RTD 1: Location Bearing A
9013 RTD 1: Temperature Stage 1 Pickup 100 C A
9015 RTD 1: Temperature Stage 2 Pickup 115 C A
9021A RTD 2: Type Pt 100 Ohm A
9022A RTD 2: Location Bearing A
9023 RTD 2: Temperature Stage 1 Pickup 100 C A
9025 RTD 2: Temperature Stage 2 Pickup 115 C A
9031A RTD 3: Type Pt 100 Ohm A
9032A RTD 3: Location Winding A
9033 RTD 3: Temperature Stage 1 Pickup 120 C A
9035 RTD 3: Temperature Stage 2 Pickup 140 C A

Page 10 of 11
K02 - DESFIBRADOR_prn
Group RTD-Box; Group RTD 4-6
ABENGOA SAO LUIZ / Preparo / K02
SIMATIC - DESFIBRADOR/7SK806 04.05.17 15:48:38

3.19 Group RTD-Box; Group RTD 4-6


Group RTD-Box; Group RTD 4-6
No. Settings Value Group

9041A RTD 4: Type Pt 100 Ohm A


9042A RTD 4: Location Winding A
9043 RTD 4: Temperature Stage 1 Pickup 120 C A
9045 RTD 4: Temperature Stage 2 Pickup 140 C A
9051A RTD 5: Type Pt 100 Ohm A
9052A RTD 5: Location Winding A
9053 RTD 5: Temperature Stage 1 Pickup 120 C A
9055 RTD 5: Temperature Stage 2 Pickup 140 C A

3.20 Group Energy; Group Measurement


Group Energy; Group Measurement
No. Settings Value Group

8315 Meter resolution Standard A