Beruflich Dokumente
Kultur Dokumente
What is Comfort?
Definition:
A State of Ease and Contentment
A satisfying and enjoyable experience
The feeling of comfort is clearly subjective.
Specifies
conditions likely
to be thermally
acceptable to at
least 80% of the
adult occupants
in a space
Design to ASHRAE 55-2010 : Thermal Environmental
Conditions for Human Occupancy in conjunction relevant
localised parameters as listed in MS 1525:2007
Principles of Refrigeration
The science of refrigeration is based upon the fact that a liquid can
be vaporised at any desired temperature by changing the pressure
on it.
Liquids boiling at low temperatures (Refrigerants) are the most
desirable medium for removing heat.
The large quantities of heat is absorbed when liquid is evaporated
(Changed to vapour).
2.What is a Refrigerant
.
PRESSURE psia
F Water HCFC-22 HFC-410A HFC-134a CO2 Propane
-40 0.00186 15.26 26 7.43 145.77 16.1
1 F
1 ton = 12,000 Btu/Hr.
RISE
= 3.517 kWr
1 lb
1 Btu
Latent Heat
Total Heat = Sensible Heat + Latent Heat
212 F
212 F
Not measured on
a thermometer
Change of State
4. Pressure/
flow control 2. Vapor
valve pump
Section 1 Introduction
Objectives
Understand the properties of air and water
vapor mixtures
Build the psychrometric chart
Use the psychrometric chart to determine
the properties of an air/water vapor mixture
Use the psychrometric chart to understand
the basic air conditioning processes
Understand how the processes can be
combined into a system using a system plot
diagram and psychrometric chart
Section 1 Introduction
Dry-Bulb Thermometer
wb dp
F
db F
Relative
Wet Bulb Temperature Humidity
Dew Point Specific
Temperature Humidity
wb dp
F
db F Dry Bulb
Temperature
Sensible Heat
qs 1.10 cfm t
db - Changes
wb - Changes
68% rh
dp - Constant 24% rh
gr - Constant
COOLING
HEATING 52 gr
wb dp
F 90 60 = 30
db F t
60 90
Sensible Heat Change
Latent Heat
q l 0.69 cfm grains
wb - Changes
dp - Changes
68% rh
gr - Changes 24% rh
89 gr
Condensation
db - Constant
Evaporation
Latent
grains Heat
89 30 = 60 Change
wb dp
30 gr
F
db F
75
Enthalpy Scale
hs = Enthalpy at saturation
hs = 27.5 Btu/lb
wb dp
F
db F
Relative Humidity Lines
Relative 60
Humidity 45%
132
Approx. 132 gr
45%
60 gr
wb dp
F
db F
75
Dew Point Example
95 F
db
100 gr
100 gr
wb dp
F
db F
55 67 95
Air Conditioning Processes
1. Sensible Heating
2. Sensible Cooling
3. Humidification
4. Dehumidification
5. Cooling and Humidification
(Evaporative Cooling)
6. Cooling and
Dehumidification
7. Heating and
Humidification
8. Heating and
Dehumidification
wb dp
F
db F
Total Heat
qt qs ql
Cooling
89 gr
Condensation
Evaporation
Latent
Grains
Heat
Change
t 30 gr
wb dp
F
Heating
db F
75 95
Sensible Heat Change
Using Enthalpy to Determine Total Heat
Removed
Latent Heat
1.7
Sensible Heat
5.0
wb dp
F
db F
55 75
Total Capacity or Load Formula
GTH = 4.5 cfm h
Where:
GTH = Grand Total Heat
4.5 = Constant
cfm = cubic feet per minute
h = Difference in enthalpy from
air entering to air leaving
conditions
Cooling Coils
Face Area = Length Height
Length
Height
Velocity
cfm / face area
Fins
Rows Refrigerant
Temperature
ASHRAE Comfort Zone
4.) Cooling Load Estimation
To design the effective HVAC design, the analysis of heat
load is carried out.
Cooling Load Components:
- Location/altitude/ orientation
Transmission through Building Components -
walls, glass, ceilings, roofs, doors and floors,
partitions from non conditioned spaces.
Solar Radiations on - glass, wall, roof, etc.
Human Comfort - Design
Ventilation Requirements.
Latent and Sensible heat losses from people.
Lighting and ballasts.
Appliances and equipment in the conditioned space.
Ducts and motor heat gain from cooling system itself.
Infiltration of outdoor air.
7.) TYPES OF AIR CONDITIONING
SYSTEMS
WRAC
Outdoor air
Condensing Unit
3.Air Cooled Split Units (ACSUs)
Ceiling Exposed
3. ACSUs : Fresh Air Intake ?
A fan may be
added if the
intake is far
away.
Advantages Other Systems
Low first cost Low Efficiency
Flexibilities No Fresh Air
Easy to maintain Potential IAQ
Short lead time issues
Ex Stock
5. Water-cooled Splits/Packaged Units
- WC Splits
- Typ. Capacity range
from 2.0 6 Hp
- Ducted/Under
ceiling
- WC Packaged
- Typ. Capacity range
from 20 100 Hp
- Floor Standing
Typical kw / ton around 1.0- 1.2 kw/ton
6. Variable Refrigerant System
On a single refrigerant pipe, many
80F
(26.7C) 54F 50F 110F 97F
(12.2C) (10C)(43.3C) (36.1C)
condenser
pump
Chilled Water Loop Refrigeration Loop Condenser Water Loop
Airside Loop (CHWP, Piping &
(AHU & Air Duct) (Water-cooled Chiller) (CWP, Piping & Cooling Tower)
Cooling Coil)
Packaged Air-Cooled Chiller
compressor
evaporator air-cooled
condenser
expansion
Chilled Water Loop device
Airside Loop (CHWP, Piping & Refrigeration Loop
(AHU & Air Duct) Cooling Coil) (Air-cooled Chiller)
Conventional chilled water system
44F
[6.7C]
54F
[12.2C]
3-way valve
Primary-Secondary Configuration
primary
pumps
Variable
secondary
production pump
loop
distribution
loop
two-way valve
Variable-Primary-Flow Systems
Variable-flow
pumps
check
valves
control
valve
two-way
valve
optional bypass
with three-way valve
Constant Primary Flow / Variable Secondary
Flow Chilled Water System
Secondary Pumps
(Variable Speed)
Isolation
Valves
Decoupling Bypass
Chiller Chiller
(Constant (Constant
Flow) Flow)
Load Load
(Variable (Variable DP
Flow) Flow)
Control
Valves
Primary Pumps
(Constant Speed)
13
Type of Chiller Compressors
(Hermetic or Semi-Hermetic)
Scroll
Reciprocating
Helical-Rotary
Screw Centrifugal
Compressor
Air-cooled Chiller
20 100RT for Scroll
70 500 RT for Screw
Typical Efficiency
range 1.1 1.3 kw/ton
Applications :
Retail, Commercial,
Industrial & Government
Applications :
Retail, Commercial,
Industrial & Govt.
Buildings
During low wetbulb temperature the lift changes, thus causing the compressor
to overspeed, which is similar to a car moving downhill. The new lift for the
refrigerant is achieved by reducing the compressor speed- thus, the
refrigerant will work more effectively during those periods of low wet bulb
temperature.
Low Ambient
( Air-Conditioning, Heating
and Refrigeration Institute)
Code of Practice on
Energy Efficiency and
Use of Renewable
Energy for Non-
Residential Buildings
(1st Revision)
Chillers Standard Rating Conditions
1.) MS 1525:2007 Code of Practice on Energy Efficiency and Use of
Renewable Energy for Non-Residential Buildings (1st Revision)
Pg. 36 Section 8.11.1
Kw/Ton at
Eurovent
JIS
GB
MS2449:2012
MS 2449:2012
Performance
rating of water-
chilling packages
using the vapor
compression cycle
Included in AHRI STD Certification Program for 50 Hz
Electrical Power
85F 87F
[29.4C] [30.6C]
ARI Malaysia
54F 54F
[12.2C] [12.2C]
conditions Conditions
evaporator 2.4 gpm/ton evaporator 2.4 gpm/ton
flow rate [0.043 L/s/kW] flow rate [0.043 L/s/kW]
condenser 3.0 gpm/ton condenser 3.0 gpm/ton
flow rate [0.054 L/s/kW] flow rate [0.054 L/s/kW]
Typical Schematic of Chilled Water HVAC System
Condenser water makeup
COOLING
TOWERS F
CHILLED
WATER F
F
T
FCU
T
F
15C
The
AHU T T AHU
importance
RETURN
F
T
F
T
AIR FAN F of
controlling
RETURN 9 - 12 C
15C 15C
By Air the flow of
MAIN RISER
MAIN RISER
FEED 6C
By Refrigerant
T
air and water
F
in HVAC
AHU T PRIMARY CHILLED
WATER PUMPS systems
CONDENSER WATER 35C
F
T
CONDENSER
EVAPORATOR
CONDENSER
WATER PUMPS
CHILLER 1
CHILLER 2
CHILLER 3
15C
SECONDARY
CHILLED
WATER PUMPS
By Air F
F F F RETURN CONDENSER WATER 30C
By Water
Chillers Flow Rates and Temperatures
Why use 10F and how much above can we go ?
10 F = 2.4 USgpm/RT
12 F = 2.0 USgpm/RT
14 F = 1.7 USgpm/RT
45%
25% Load 12% 100% Load
50% Load 1%
75% Load
42%
1-2
Full Load Vs Part Load
Both FullPart and Part Load Efficiency can be
important.
Full Load- Design Based On Consultant
Calculation. (With or Without diversity factor)
Air-cooled Water-cooled
Variable Frequency
Other Drive (VFD)/
Lighting Equipment
DHW 10% 15% Variable Speed Drive
12% (VSD)/ Speed
Controller
-Improve comfort levels
-Reduce operating costs,
2
Static Pressure2 Air Flow2
=
Static Pressure1 Air Flow1
Static Pressure is proportional to (Fan/Pump
Speed)2 e.g
3 80% speed
Input Power2 Air Flow2 Input power
=
Input Power1 Air Flow1 = (0.8x0.8x0.8)
Input Power is proportional to (Fan/Pump Speed)3
= 0.51 or 51%
w/o system effect
Air Distribution System Supply Fan Basics
is provided
T
The conditioned space receives Supply
Design air flow at all times Fan
Sensor may be in
return air duct.
However, for large single zone CAV
systems, its possible to convert them
to single zone VAV systems
VAV Variable Air Volume
To maintain thermally comfortable conditions,
VAV systems utilize a resetable constant
temperature of the delivered air to most
locations, while varying the quantity of air
delivered to the individual zones in the building.
Varying the air flow is controlled by using a
VFD/VSD in the fan motor.
VAV - Variable Air Volume
System
Components:
1. VAV Box
2. Zone Thermostat
3. Air Diffuser
4. Return Grille
5. Duct Static Pressure
Sensor
Zone 1 Zone 2 Zone 3 Zone 4
6. Supply Fan VFD
7. AHU
8. Supply Duct
Section 1 Introduction
Air Distribution System
systems
Az = Zone floor area: the net occupiable floor area of the zone
m2 ( ft2)
Pz = zone population: the largest number of people expected
to occupy the zone during typical usage.
Rp = outdoor airflow rate required per person as determined
from Table 6-1
Ra = outdoor airflow rate required per unit area as determined
from Table 6-1
ASHRAE Std 62.1-2010 Ventilation For
Acceptable Indoor Air Quality
Office
Buildings
Office
Space 5 2.5 0.06 0.3 5 17 8.5
Reception
areas 5 2.5 0.06 0.3 30 7 3.5
TABLE 6-1 MINIMUM VENTILATION RATES IN BREATHING ZONE
Supply Air
AHU
Fresh Air
Damper Actuator
Energy Monitoring
Energy meter
EFC3500
DA
NF
OS
S
Flowmeter
The operation principle of inline magnetic flowmeters
Qualities
Obstruction free
No moving parts
Wide flow range
Virtually no maintenance
Minimal installation requirements
Typical accuracy at 0.25% and 0.5%
Full BMS Integration
Measures the velocities across the When an electrical conductor
pipe line cross section
moved at velocity, perpendicular
Insensitivity to viscosity, specific to the lines of flux through a
gravity, temperature and pressure
magnetic field of strength, the
Respond well to fast changing flows
voltage is induced at the ends of
Lower life-cycle costs
the conductor
Type of Flow Meters
Electronic Flow Meters
Ultrasonic
Obstruction free
No moving parts
Wide flow range
Virtually no maintenance
Sensitive to pipe elbows and
control valves
Respond well to fast changing
flows
Full BMS Integration
Measuring Principle
Acoustic flow measuring procedures like
Low Cost of Ownership on
the ultrasonic-flow measurement use larger pipe (>DN300)
sound waves above the hearing barrier,
i.e.> 20 kHz for speed and flow
measurement. The velocity and direction
of the sound rays change due to the
transport of the sound waves in the fluid.
With the transit time procedure, the time
is measured in which a sound wave takes
to get around path 1. I.e. point A, the
sender
What is a Green Design or
Sustainable Design?
ASHRAE GreenGuide provides one definition for
sustainable building design:
Canada
LEED Canada
BREEAM Canada UK
Green Globe BREEAM
Korea
Italy
GBTool
USA Protocollo China Japan
LEED ITACA CASBEE
Energy Star India Hong Kong
Green Globe LEED-India HK-BEAM
Malaysia Taiwan
Brazil GBI
GBTool Singapore
Green Mark
Australia
Green Star
Australia: Nabers / Green Star
Brazil: AQUA / LEED Brasil
Canada: LEED Canada / Green Globes
China: GBAS
Finland: PromisE
France: HQE
Germany: DGNB / CEPHEUS
Hong Kong: HKBEAM
India: GRIHA
Italy: Protocollo Itaca / Green Building Counsil Italia
Malaysia: GBI Malaysia
Mexico: LEED Mexico
Netherlands: BREEAM Netherlands
New Zealand: Green Star NZ
Philippines: BERDE / Philippine Green Building Council
Portugal: Lider A
Singapore: Green Mark
South Africa: Green Star SA
Spain: VERDE
Switzerland: Minergie
United States: LEED / Living Building Challenge / Green Globes /
Build it Green / NAHB NGBS
United Kingdom: BREEAM
United Arab Emirates: Estidama
GLOBAL GREEN TOOLS
1. BREEAM, UK Building Research Establishment
Environmental Assessment Method (1990)
2. LEED, USA Leadership in Energy and Environmental
Design (1996)
3. BEAM, Hong Kong Building Environment Assessment
Method (2003)
4. EEWH, Taiwan Green Building Evaluation System (2003)
5. Green Star, Australia/New Zealand (2003)
6. CASBEE, Japan Comprehensive Assessment System for
Building Environmental Efficiency (2004)
7. Green Mark, Singapore (2005)
8. Green Building Index, Malaysia (2009)
9. Greenship, Indonesia (2010)
Building Energy Intensity