Sie sind auf Seite 1von 7

DIGITAL CONTROLLER DC1000

SERIES
PRODUCT MANUAL

Industrial Measurement & Control DC1010/1020/1030/1040 Product Manual

Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.

Symbol Definition

This CAUTION symbol on the equipment refers the user to the Product
Manual for additional information. This symbol appears next to required
information in the manual.

WARNING
PERSONAL INJURY: Risk of electrical shock. This symbol warns the user
of the potential shock hazard where HAZARDOUS LIVE voltages greater
than 30 Vrms, 42.4 Vpeak, or 60 Vdc may be accessible. Failure to
comply with these instructions could result in death or serious injury.

Protective Earth (PE) terminal. Provided for connection of the protective


earth (green or green/yellow) supply system conductor.

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


1. Installation 1.2 Specification
TECHNICAL DATA
CAUTION TC (K, J, R, S, B, E, N, T, W, PL II, U, L)
Type of Input RTD (Pt100, JPt100, JPt50)
Installation should be performed only by personnel who are technically competent to do PV Input Linear (-10~10mV, 0~10mV, 0~20mV, 0~50mV, 10~50mV)
so. Local Regulations regarding electrical & safety must be observed. Input Sampling Time 500 ms
Input Resolution 14 bit (each)
PV/SP Indication 4-digit, 7 segment display
Constant Value Storage
1.1 Model Number Interpretation Indication
System
Non-volatile memory (EEPROM)
Indication Accuracy 0.5%FS
Proportional Band (P) 0~200% (On/Off action at P=0)
DC10 0 - - - Integral Time (I) 0~3600 sec (PD action at I=0)
Control Mode Derivative Time (D) 0~900 sec (PI action at D=0)
Cycle Time 0~150 sec (4~20mA! 0, SSR!1, relay!10)
Dead Band Time 0~1000 sec (dead time compensation)
Relay Output Contact, SPDT, 3A/240VAC
Size
Table III Voltage Output Voltage Pulse, 20VDC/20mA
1 48*48 Output Linear Output 4~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Manual
2 48*96 Motor Control Output Servo motor valve control (open loop circuit)
E English Others 1 SSR, 3 SSR, 1 SCR, 3 SCR
3 72*72
C Chinese Alarm Channel 3 channels (optional)
4 96*96 Mode 17 alarm mode available
K Korean Timer Flicker alarm, continued alarm, on delay timer alarm
Output Signal SP, PV, MV
Aux. Output
Type of Output 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Program Input 2nd Input Type of Input 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
C None R RTD
(RSP) Sampling Time 250 m
Pattern/Segment 2 pattern/ 8 segment (each)
P Program T TC Program
Availability Pattern link & repeat, program/segment end alarm
L Linear Communication Type of Communication RS-232, RS-485
Rated Power Supply
AC 85~265V, 50/60Hz
Voltage & Frequency
General
Power Consumption 4VA
Table I Table II Specifications
Ambient Temperature -25C~65C
Output 1 Output 2 Alarm Aux. Input 2 Comm. Ambient Humidity 50~85% RH (no condensation)

0 None 0 None 0 None 0 None 0 None 0 None INPUT ACTUATIONS


1 Relay 1 Relay 1 1 alarm 1 4~20mA 1 4~20mA 1 RS-232 K 0.0~200.0, 400.0, 600.0, 800.0, 1000, 1200 C
J 0.0~200.0, 400.0, 600.0, 800.0, 1000, 1200 C
2 Volt Pulse 2 Volt Pulse 2 2 alarms 2 0~20mA 2 0~20mA 2 RS-485
R 0.0~1600, 1769 C
3 4~20mA 3 4~20mA 3 3 alarms A 0~5V A 0~5V S 0.0~1600, 1769 C
5 1 SSR A 0~5V B 0~10V B 0~10V B 0.0~1820 C
E 0.0~800, 1000 C
6 3 SSR B 0~10V C 1~5V C 1~5V TC
N 0.0~1200,1300 C
7 Motor V C 1~5V D 2~10V D 2~10V T -199.9~400.0, 200.0 C, 0.0~350.0 C
8 1 SCR D 2~10V W 0.0~2000, 2320 C
PL II 0.0~1300, 1390 C
9 3 SCR
U -199.9~600.0, 200.0 C, 0.0~400.0 C
A 0~5V L 0.0~400.0, 800.0 C
B 0~10V Pt100 -199.9~600.0, 400.0, 200.0 C, 0.0~200.0, 400.0, 600.0 C
C 1~5V
RTD JPt100 -199.9~600.0, 400.0, 200.0 C, 0.0~200.0, 400.0, 600.0 C
JPt50 -199.9~600.0, 400.0, 200.0 C, 0.0~200.0, 400.0, 600.0 C
D 2~10V
AN1 -10~10mV
AN2 0~10mV
Linear AN3 0~20mV
AN4 0~50mV 0~20mA, 0~1V, 0~5V, 0~10V
AN5 10~50mV 4~20mA, 1~5V, 2~10V

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


1 2

1.3 External Dimension 1.4 Mounting

# $ "

- Put the mounting bracket in the rail


on the top & bottom of the case.

- Bend the grip of the bracket & slide


the bracket along the rail until the
case is secured against the panel.

- Put the grip of the bracket on the


groove to fasten the case to the
panel.

Side View

1.5 Wiring Diagrams


Electrical Consideration / Precautions
The controller is considered rack and panel mounted equipment per EN61010-1, Safety
Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use,
Part 1: General Requirements. Conformity with 72/23/EEC, the Low Voltage Directive
requires the user to provide adequate protection against a shock hazard, The user shall
install this controllerin an enclosure that limits OPERATOR access to the rear terminals.
Controller Grounding
PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is
installed shall be in accordance with National and local electrical codes. To minimize
electrical noise and transients that may adversely affect the system, supplementary
2
bonding of the controller enclosure to a local ground, using a No.12(4 mm ) copper
conductor, is recommended

CAUTION
Applying 85-264Vac to a controller rated for 15-50Vdc will severely damage the controller
and is a fire and smoke hazard.

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


3 4
1.5.1 DC1010 1.5.2 DC1020

Noise
POWER Filter

AC 85 ~ 265V
(50 / 60Hz)

PV

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


5 6

1.5.3 DC1030 1.5.4 DC1040

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


7 8
2. Configuration 2.2 MODE Access
2.1 Operator Interface (1)
Operation Configuration 1
Upper Display 4 digits dedicated to display the PV. In configuration mode, this display indicates
the name of parameter. (2)
(3) (2)
Lower Display 4 digits dedicated to display the SP. In configuration mode, this display indicates
the value of parameter or the status of parameter selected
Program Configuration 2
Bar Graph A 10 green LEDs bargraph indicates the value of the output in percentage
LEDs (3)
OUT1 Status of Output 1
OUT2 Status of Output 2
AT When the LED is ON, it indicates the controller is in automatic tunning process
Set Up
AL1 Status of Alarm 1
AL2 Status of Alarm 2
AL3 Status of Alarm 3 How to move from a MODE to another
(1) Press SET key for 5 seconds, it grants access to Configuration 1 mode or return to
MAN When the LED is ON, it indicates the controller is in manual mode.
Operation mode from Configuration 1 mode.
PRO When a program is running, the LED flickers
(2) Press SHIFT key for 5 seconds while pressing SET key first, it grants access to
When a program is suspended, the LED is ON
Configuration 2 mode or return to Operation mode.
When no program is running, the LED is OFF
(3) All parameters related to program configuration will be displayed next to parameters in
Keys
Operation mode. (* These parameters will be shown in program model only)
SET SET key allows moving from one parameter to another or saving a new value of
parameter or a status of parameter changed.
A/M A/M key allows switching from automatic mode to manual mode or from manual CAUTION
mode to automatic mode. DO NOT access to Set Up mode without instruction from techical assistant.
SHIFT SHIFT key allows shifting the digits to modify parameters
UP Up key allows increasing the value of a digit selected or changing the status of
parameter.
DOWN DOWN key allows decreasing the value of a digit selected or changing the status
of parameter.

Upper Display

Lower Display

LEDs
Bar Graph SHIFT key
% %

SET key Up key

A/M key Down key

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


9 10

2.3 MODEs 2.3.2 Configuration 1


2.3.1 Operation Configuration 1 will be shown by pressing SET key for 5 seconds in Operation mode.

Parameter Description Parameter Description


Main Control (OUT1) Range: 0~200%
PV Display
P value (Proportional Band) P1=0, ON/OFF Control
SP Display SET
Main Control (OUT1) Range: 0~3600 seconds
SET I value (Integral Time) I=0, Integral off
Output Limit To limit the Maximum of Control Ouput SET
Main Control (OUT1) Range: 0~900 seconds
Percentage (%)
D value (Derivative Time) D=0, Derivative off
SET
SET
Main Control * DO NOT CHANGE THE VALUE
Auto Tuning
Dead-Band Time
Status * Default No SET
Main Control (OUT1) Range: 0~ Upper limit value (USPL)
SET Auto Tuning offset Prevent from Overshoot during auto tuning
Alarm 1 Enter deviation value or absolute value SET
Main Control (OUT1) Output type (SSR ! 1, 4~20mA!0, relay!10)
Value of alarm setpoint depending on alarm mode selected
Cycle of Control Output Range: 0~150 seconds
SET SET

Alarm 2 Main Control (OUT1) Just in case of ON/OFF control (P1=0) (Range: 0~1000)
Actuation of Hystersis ON : PV<=(SP-HYS1)
The same with Alarm1 SET OFF : PV > (SP+HYS1)

Sub Control (OUT2) The same with the method of P1 configuration


SET
P value (Proportional band)
Alarm 3 SET

The same with Alarm 1 Sub Control (OUT2) The same with the method of I1 configuration
I value (Integral Time)
SET
* The OUTL is not shown in default mode.
Sub Control (OUT2) The same with the method of D1 configuration
* AL2 & AL3 are shown only in the model the relevant options are taken. D value (Derivative Time)
SET
Sub Control (OUT2) The same with the method of CYT1 configuration
Cycle of Control Output
SET
Sub Control (OUT2) The same with the method of HYS1 configuration
Hysteresis
SET
Main Control (OUT 1) Control ouput is turned off before getting to SP
Gap Turning Point = SP-GAP1; OFF (OUT1=Heat)
SET

Sub Control (OUT2) Control Output to be turned on before getting to SP


Gap Turning Point = SP+GAP2; ON (OUT2=Cool)
SET
Function Lock * Refer to 2.3 Function Lock in P.10

SET
* The parameters are only for Output 2 function, so it will appear only in the model which has the OUT2 option.

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


11 12
2.3.3 Configuration 2
Configuration 2 mode will be shown by pressing SHIFT key for 5 seconds WHILE pressing SET key Parameter Description
FIRST in Operation or Configuration 2 mode.
Main Control (OUT1) To adjust the linear control output during the calibration

Parameter Description Lower limit of linear output * DO NOT change the value without technical assistant
SET
Input 1 (INP1) To define input type & input range
Main Control (OUT1) To adjust the linear control output during calibration
* Refer to * DO NOT change the value without techincal assistant
Upper limit of linear output
SET SET
Input 1 (INP1) To be used during the calibration for linear input
Sub Control (OUT2) The same configuration method with CL01
Lower limit of linear Input * DO NOT change this value without techincal assistant Lower limit of linear output
SET
SET
Input 1 (INP1) To be used during the calibration for linear input
Sub Control (OUT2) The same configuration method with CH01
Upper limit of linear Input * DO NOT change this value without technical assistant
Upper limit of linear output
SET SET
Decimal Point Available in linear input only Aux. Output The same configuration method with CL01
Lower limit of linear output
SET SET
Lower limit of Input range i.e) Linear input = 4~20mA, Aux. Output The same configuration method with CH01
when 4mA (0%), set the indication value for lower limit Upper limit of linear output
SET
SET
Upper limit of Input range when 20mA (100%), set the indication value for upper limit Timer for Motor Control Full actuation time of TPSC
Range: 5 200 sec
SET SET
Input 2 (INP2) To be used during the calibration for linear input
WAIT function To set wait for program operation
Lower limit of linear input * DO NOT change this value without techincal assistant
0= No wait, others = Wait volume
SET SET
Input 2 (INP2) To be used during the calibration for linear input
Extra SET DO NOT change the value of this parameter
Upper limit of linear input * DO NOT change this value without technical assistant
SET SET
Alarm Code of Alarm 1 * Refer to
ID Number Communication ID number

SET
SET
Time Set for Alarm 1 * Range: 0 - 99 min 59 sec Baud Rate DO NOT change the value of this parameter
0= flickering alarm, 99.59= continuant alarm
SET Others = Time delay of alarm SET
Alarm Code of Alarm2
SP compensation Range: -1000~1000

SET
SET
Time Set for Alarm 2 The same configuration method with ALT1
PV compensation Range: LSPL~USPL

SET SET
Alarm Code of Alarm 3
Unit of PV & SP Selection: C, F, and A (linear)

SET
SET
Time Set for Alarm 3 The same configuration method with ALT1 Soft Filter To adjust PV response time (Range: 0.05 1.00)
* The bigger value meanse the faster response.
SET SET
Hysteresis of alarms To set the hysteresis of alarm actuation (Range: 0 1000)
ON : PV<=(SP-HYS1)
OFF : PV > (SP+HYS1) * Those 2 parameters are only for adjusting the linear signal of control output, not for the limitation of the control output
SET
or any other purpose. Pls, DO NOT change the values without techincal assistant.

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


13 14

2.4.1.3 Lower Limit Deviation Alarm (Alarm Code 02, Alarm release in the first alarming situation)
Parameter Description

* DO NOT change the value

SET 2.4.1.4 Lower Limit Deviation Alarm (Alarm Code 12, No alarm release in the first alarming situation)
Operation Mode Heating (direct) or Cooling (reverse)

SET
Control Process PID or Fuzzy

2.4.1.5 Dev. Band Breakaway Alarm(Alarm Code 03, Alarm release in the first alarming situation)
SET
Frequency 50 or 60Hz
* Please, check whether the proper frequency is selected
SET

2.4.1.6 Dev. Band Breakaway Alarm(Alarm Code 13, No alarm release in the first alarming situation)
2.4 Alarms
2.4.1 Deviation Alarm
The Alarm SP (Set Point) is to be changed as the SP moves. In this case, the Alarm SP preserves a
certain deviation value with the SP. When an alarm is set, a certain deviation value with the preset SP 2.4.1.7 Deviation Band Alarm (Alarm Code 04, Alarm release in the first alarming situation)
should be defined.
Alarm SP moves along SP change
Deviation
(Lower limit)
2.4.1.8 Deviation Band Alarm (Alarm Code 14, No alarm release in the first alarming situation)

SP1 SP1 SP2


Alarm SP SP Change

Alarm SP moves along SP change


2.4.2 Absolute Value Alarm
Deviation
(Upper Limit) The Alarm SP (Set Point) is to be fixed even though the SP moves. When an alarm is set, the absolute
value of the Alarm SP should be defined.
SP1 SP1 SP2 Alarm Set Point (Fixed)
Alarm SP SP Change

2.4.1.1 Upper Limit Deviation Alarm (Alarm Code 01, Alarm release in the first alarming situation) SP1 SP2 SP3
2.4.2.1 Absolute Upper Limit Alarm (Alarm Code 05, Alarm release in the first alarming situation)
: Set Point

: Alarm Set Point

2.4.1.2 Upper Limit Deviation Alarm (Alarm Code 11, No alarm release in the first alarming situation)
2.4.2.2 Absolute Upper Limit Alarm (Alarm Code 15, No alarm release in the first alarming situation)

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


15 16
2.4.2.3 Absolute Lower Limit Alarm (Alarm Code 06, Alarm release in the first alarming situation)
2.5 Function Lock
According to the status of the parameter LCK in Configuration 1 mode, access to modes and change
of values can be prohibited.
2.4.2.4 Absolute Lower Limit Alarm (Alarm Code 16, No alarm release in the first alarming situation) LCK=0000 MODE ACCESS Access to Operation, Configuration1 & 2 modes allowed (* Default)
LCK=0100 MODE ACCESS Access to Operation & Configuration 1 mode allowed
VALUE CHANGE Every value change in each mode allowed
LCK=0110 MODE ACCESS Access to Operation & Configuration 1 mode allowed
2.4.3 Program Alarm VALUE CHANGE Value changes only in Operation mode allowed
2.4.3.1 Segment End Alarm (Alarm Code 07) LCK=0001 MODE ACCESS Access to Operation mode allowed
; Once the selected segment is completed, the alarm becomes actuated VALUE CHANGE Value change of SP (Set Point) allowed only
- ALD1 ALD3 Set the Alarm Code 07 LCK=1111 MODE ACCESS Access to Set Up mode allowed
- AL1 AL3 Enter Segment No. for alarms LCK=0101 All access & value changes prohibited except the change of LCK status
- ALT1 ALT3 Define the alarm timing
(0! Flickering, 99.59 ! Continuant, Others ! Time Delay) CAUTION
2.4.3.2 Program RUN Alarm (Alarm Code 17) Configuration should be performed only by personnel who are technically competent to
; While a program runs, the alarm becomes actuated do so. Local Regulations regarding electrical & safety must be observed.

2.4.4 System Alarm


2.4.4.1 System Error Alarm (Alarm Code 08)

2.4.4.2 System Error Alarm (Alarm Code 18)

2.4.4.3 Timer Alarm (Alarm Code 19)


; Once the PV reaches to the SP, the alarm becomes actuated after a certain time delay.
(Range: 00 hour 00 min 99 hour 59 min)

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


17 18

3. Input Codes
It requires that the input code in Configuration 2 mode be selected properly before the operation starts. 3.2 RTDs
3.1 Thermocouples TYPE CODE RANGE
TYPE CODE RANGE -199.9~600.0C -199.9~999.9F
0.0~200.0C 0.0~392.0F -199.9~400.0C -199.9~752.0F
0.0~400.0C 0.0~752.0F JIS -199.9~200.0C -199.9~392.0F

0~600C 0~1112F Pt100 0~200C 0~392F


K
0~800C 0~1472F 0~400C 0~752F
0~1000C 0~1832F 0~600C 0~1112F

0~1200C 0~2192F -199.9~600.0C -199.9~999.9F


0.0~200.0C 0.0~392.0F -199.9~400.0C -199.9~752.0F
0.0~400.0C 0.0~752.0F DIN -199.9~200.0C -199.9~392.0F

0~600C 0~1112F Pt100 0~200C 0~392F


J
0~800C 0~1472F 0~400C 0~752F
0~1000C 0~1832F 0~600C 0~1112F
0~1200C 0~2192F -199.9~600.0C -199.9~999.9F

0~1600C 0~2912F -199.9~400.0C -199.9~752.0F


R
0~1796C 0~3216F JIS -199.9~200.0C -199.9~392.0F
0~1600C 0~2912F Pt50 0~200C 0~392F
S
0~1796C 0~3216F 0~400C 0~752F

B 0~1820C 0~3308F 0~600C 0~1112F


0~800C 0~1472F * The default of Input Code is DP3 for the model of RTD input type. (DC10X0XR-XXX-XXX-X)
E
0~1000C 0~1832F

0~1200C 0~2192F 3.3 Linear Inputs


N
0~1300C 0~2372F CODE SIGNAL INPUT TYPE RANGE
-199.9~400.0C -199.9~752.0F -10 - 10mV -1999~9999
T -199.9~200.0C -199.9~392.0F 0 - 10mV -1999~9999
0.0~350.0C 0.0~662.0F 0 - 20mV -1999~9999
0~2000C 0~3632F 0 - 50mV 0-20mA, 0-1V, 0-5V, 0-10V -1999~9999
W
0~2320C 0~2372F 10 - 50mV 4-20mA, 1-5V, 2-10V -1999~9999
0~1300C 0~2372F * The default of Input Code is AN4 (4-20mA) for the model of linear input type.
PLII
0~1390C 0~2534F (DC10X0XL-XXX-XXX-X)
-199.9~600.0C -199.9~999.9F * DO NOT change the input type without technical assistant because it requires some hardware
U -199.9~200.0C -199.9~392.0F changes on the input board in order to select a certain linear input type.
0.0~400.0C 0.0~752.0F

L 0~400C 0~752F

0~800C 0~1472F

* The default of Input Code is K2 for the model of themocouple input type. (DC10X0XT-XXX-XXX-X)

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


19 20
4. Operation 5. Error Message
4.1 Type of Control In case the following messages comes up in the upper display of controller, please check the points as
4.1.1 Manual Operation guided below or give us a call for techincal service.
The control ouput can be managed manually. If pressing A/M key, the parameter of OUTL Sign Description Solution
comes up in the upper display and a fixed control output is shown in lower display (% value). Open the circuit of INPUT 1 (sensor) Check the wiring
Once the value is changed, the control output is changed and fixed again. * A/D Convert Failure Service Call required
4.1.2 ON/OFF Control * Cold junction compensation failure Service Call required
The output type must be the relay output (DC10X0XX-1XX-XXX-X). Then, change P value to 0 Open the circuit of INPUT 2 (sensor) Check the wiring
in Configuration 1 mode. Until PV reaches SP, the control output is just ON (100%), and then Excess of PV over upper limit (INPUT 1) - Check sensor wiring
the control output becomes OFF (0%). Shortage of PV under lower limt (INPUT1) & input code

* To prevent the control ouput from flickering too mufrequently, the hysteresis (HYS1 in Excess of PV over upper limit (INPUT2) - Adjust the range of
Operation mode) is to be set Shortage of PV under lower limt (INPUT2) indication

4.1.2 PID Control * Memory (RAM) failure Service call required


PID control is the default control type of this controller. If AT in Operation mode becomes YES, Interface failure Check wiring of input
the auto tuning process will start. After the auto tuning is completed, the controller gets optimum Auto tuninig failure Check wiring of output
PID values for the control system and starts the operation automatically. (PID values can be set
manually in Configuration 1 mode without auto tuning procedure.)
4.2 Set Point
After all the wiring connection is completed and power is applied, the targetted SP (Set Point) is
to be entered. When power is applied, the default display is PV & SP display and ready to enter
the SP. (Change the value targetted, and press SET key for saving)
4.3 Alarm Set Point
If necessary, each alarm should be set properly.
- Set the Alarm Code required in ALd1 (ALd2 / ALd3) in Configuration 2 mode
(Alarm Code: 00 to 19)
- Define the alarm timing required for ALt1 (ALt2 / ALt3) in Configuration 2 mode
0000 ! flickering alarm, 9959 ! continuant alarm
XXXX ! XX min XX sec (Time Delay)
- Enter the deviation value or absolute value in AL1 (AL2 / AL3) in Operation mode depending
on the Alarm Code selected above.
- Set the hysteresis of alarms in HYSA in Configuration 2 mode. (If necessary)

DC1010/1020/1030/1040 Product Manual DC1010/1020/1030/1040 Product Manual


21 22

Warranty/Remedy Sales and Service


Honeywell warrants goods of its manufacture as being free of Honeywell serves its customers through a worldwide network of
defective material and faulty workmanship. Contact your local sales sales offices and distributors. For application assistance, current
office for warranty information. If warranted goods are returned to specifications, pricing, or name of the nearest Authorized Distributor,
Honeywell during that period of coverage, Honeywell will repair or contact your local sales office or:
replace without charge those items it finds defective. The foregoing INTERNET: www.honeywell.com/sensing
is Buyers sole remedy and is in lieu of all other warranties, E-mail: info.sc@honeywell.com
expressed or implied, including those of merchantability and
fitness for a particular purpose.
While we provide application assistance, personally and through our
literature, it is up to the customer to determine the suitability of the
product in the application.
Specifications may change at any time without notice. The
information we supply is believed to be accurate and reliable as of
this printing. However, we assume no responsibility for its use.

HONEYWELL ASIA PACIFIC AFFILIATES


Australia India Sensing&Control
Honeywell Limited TATA Honeywell Ltd. Asia Pacific Headquarters
5 Thomas Holt Drive 55A 8&9 Honeywell Building
North Ryde NSW 2113 Hadapsar Industrial Estate 17 Changi Business Park, Central 1
Phone: (61) 2-9370-4500 Pune 411013, India Singapore 486073
Fax: (61) 2-9370-4525 Phone: (91) 20 6875-532 Phone: (65) 355-2828
Toll Free: 1300-36-39-36 Fax: (91) 20 6875-535 Fax: (65) 445-3033
Toll Free Fax: 1300-36-04-70 e-mail: ashutoshd@tatahoneywell.co.in Web: www.honeywell.com/sensing
e-mail: salomon.ayach@honeywell.com e-mail: info.sc@honeywell.com
Web: www.honeywell.com.au Japan
Honeywell Inc. Sensing&Control Singapore
China PRC Beijing TF B/D 14-6 Shibaura 1-Chome Honeywell South East Asia
Honeywell China Inc. Minato Ku Tokyo 105-0023 Japan Honeywell Private Limited
15F Han Wei Plaza, East Tower Phone: (81) 3 5440-1425 Honeywell B/D
No.7 Guang Hua Road Fax: (81) 3 5440-1368 17 Changi Business Park, Central 1
Choyang District e-mail: tetsuo.shinno@honeywell.com Singapore 486073
Beijing 100020, P.R.C. Phone: (65) 355-2828
Phone: (86) 10 6561-0208 Ext. 205 South Korea Fax: (65) 445-3033
Fax: (86) 10 6561 0618 Honeywell Korea Co. Ltd. Web: www.honeywell.com/sensing
e-mail: jin.gui.wang@honeywell.com 18F KukJe Center B/D e-mail: info.sc@honeywell.com
191 HanGangRo-2Ga
China PRC Shanghai YongSan-Gu, Seoul, 140-702, Korea Thailand
Honeywell (Tianjin) Ltd. Phone: (82) 2 799-6176 Honeywell Systems (Thailand) Ltd.
23F Tower B City Center, Fax: (82) 2 792-9013 252/121
100 Zun Yi Road, e-mail: byeongdeok.choi@honeywell.com 25F Muang Thai-Phatra Office Tower II
Shanghai 200051, P.R.C. Web: www.honeywell.co.kr Ratchadapis Road, Huay Khwang
Phone: (86) 21 6237-0237 Ext. 305 Bangkok 10320, Thailand
Fax: (86) 21 6236 1237 Malysia Phone: (662) 693-3099
e-mail: jing.sheng.qiao@honeywell.com Honeywell Engineering Sdn Bhd Fax: (662) 693-3085
2F Wisma CSA e-mail:
China Hong Kong S.A.R No.4 Jalan Bersatu 13/4 somboon.rungjaraspan@honeywell.com
Honeywell Ltd. 46200 Petaling Jaya
25F Honeywell Tower Olympia Plaza Selangor Darul Ehsan Taiwan R.O.C.
255 Kings Road Phone: (603) 7950 4759 Honeywell Taiwan Ltd.
North Point, HongKong Fax: (603) 7958 8922 10F Honeywell B/D
Phone: (852) 2331-9133 e-mail: ks.yong@honeywell.com 168-1 Lien Chen Road, Chung Ho City
Fax: (852) 2331-9998 Taipei Hsien, Taiwan R.O.C.
e-mail: wilson.chow@honeywell.com New Zealand Phone: (886) 2 2245-1000
Honeywell Limited Fax: (886) 2 2245-3242
China PRC Shenzhen 264 Mt. Eden Road e-mail: steven.chi@honeywell.com
Honeywell China Inc. Mt. Eden Auckland
Units 04-07, 32F Shenzhen Kerry Center New Zealand For Countries (SEAsia) Listed below,
Renminnan Road, Luo Hu District Phone: (64) 9 623-5050 See Honeywell SEAsia Regional Office
Shenzhen 518001, P.R.C. Fax: (64) 9 623-5060 Bangladesh
Phone: (86) 755-518-1226 Toll Free: 0800 202-088 Cambodia
Fax: (86) 755-518-1221 e-mail: Guam
e-mail: robin.tu@honeywell.com ProductCustomerService@honeywell.com. Laos
au Myanmar
Indonesia Nepal
Honeywell Indonesia Pte Ltd. Philippines Pakistan
Wisma Budi, #405 4th Floor Honeywell Systems (Philippines) Inc. Sri Lanka
H.R. Rasuna Said Kav C-6 E-1507A, 15F Tektite Tower 1 Vietnam
Jakarta 12940, Indonesia Exchange Road, Ortigas Center East Timor
Phone: (6221) 521-3330 Pasig City 1605, Philippines
Fax: (6221) 521-3735 Phone: (63) 2 636 1649
e-mail: arianto.wibowo@honeywell.com Fax: (63) 2 636 1650
e-mail: melchor.nicolas@honeywell.com

Industrial Measurement & Controls


Honeywell Korea
191 HanGangRo 2ga YongSanGu
Seoul, Korea
http://www.honeywell.co.kr

Das könnte Ihnen auch gefallen