Sie sind auf Seite 1von 1

SMOKE MANAGEMENT DESIGN CALCULATION SHEET

Area Served: Car Park


Ventilation Type: Mechanical Ventilation Fans
Brief description: Exhaust through high temperature rated fans.
Fresh Air make-up through Supply Fans.

Design Parameters:

Fire Size (A) = 4 x 3.60


Fire Area = 14.39 m2
Heat Rate ( Qr) = 278.00 kw/m2
Heat Production (Q) = 3999.86 kw
Perimeter ( P ) = 15.19 m
Smoke Layer Height (Y) = 2.50 m
Smoke Layer Depth (Db) = 1.50 m
Air Specific Heat ( Cp) = 1.01 kj/kg.k
Outside Air Temp. (To) = 40 Deg.c 313 k

Calculations

Min. Smoke Flow Rate (Mf) = 0.188 x P x Y1.5


= 11.2912 kg/s

Temperature Rise (Tr) = Q / (Mf x Cp)


== 350.7388 Deg.c

Max. Smoke Temp. (Tc) = To + Tr


== 390.7388 Deg.0c 664 K

Air Volume Flow rate (Ma) = Mf x Tc / (1.2 x To)


= 19.95316 m3/s

= 42300 cfm
Note:
As per ANSI/ASHRAE standards 62.1.2004
Recommendation provide 3.7 lit/sec/m2
Parking Area= 18000 m2
139900 cfm
Shall be divided into 4 exhaust fans two speed fire protected each one is 38 000 cfm for ventilation.

Direct drive two speed smoke exhaust fans of 14.1 m3/s (64,000 cfm) rating shall be provided in each parking
zone , Fire rated for 300oC for 1 HR. Motor and Bearing shall be out of air stream.

Das könnte Ihnen auch gefallen