EGEC

EGYPTION GROUP FOR Prepared by Eng. M.Sabri


ENGINEERING CONSULTATION

FM-200 Calculation Sheet

Project Name: Alghaith Tower


Space Name: Typical Floor 4-6 (Service Room TYP-004)

1- Total Flooding System

W = V/S*{C/(100-C)}

Where:
W = weight of clean agent [Ib (kg)].
V = net volume of hazard [ft3 (m3).
S = specific volume of the superheated agent vapor at 1 atmosphere and the temperature, t [ft3/Ib (m3/kg)].
(NFPA 2001, edition 2000, item 3-5.1)

S = 2.2075 (ft3/Ib) at t = 70 (Fo)


(NFPA 2001, edition 2000, Appendix A, table A-3-5.1(k))

Input Data

V= 12.3 m3
V= 434 ft3
S= 2.2075 If the room temp. will be not be less than 20oC
###
Output Data ###
W= 18 Ib ###
8 kg ###
###
###
The Required Cylinders Capacity (Ib.) ###
SUM
Clylider Sizes 17 17
###
###
Required No. of discharge nozzle ###
###
Agent flow rate = W/t ###
Where t = maximum discharge time (10 sec.) ###

Agent flow rate = 1.7 lb/sec

Required No. of discharge nozzle = Total flow rate / average flow rate per nozzle (20 Ib / Sec.)

Required No. of discharge nozzle = 1

Check the Room Concentration


Check for t = 90 (oF)

C= 8.3
EGEC
EGYPTION GROUP FOR Prepared by Eng. M.Sabri
ENGINEERING CONSULTATION
The Room Concentration is Accept
Co2 Calculation Sheet

1- Total Flooding System

CO2 quantity = Hazard remote volume (V) x Flooding Factor

Where:
Flooding Factor for room volume less than 56.6m3 the flooding factor should be 1.6kg CO2/m3
, and for room volume greater than 56.6m3 the flooding factor should be 1.33kg CO2/m3

(NFPA 12, Table 2-4.2.1 )

Input Data

V= 324 m3
V= 11442 ft3
Flooding Factor= 1.33

Output Data
CO2 Quantity 431 kg

The Required Number of Cylinders 10 Based on the recommended cylinder size is 45 kg


e 1.6kg CO2/m3

mmended cylinder size is 45 kg