Standard Technical Specifications for Electrical Works

TRANSFORMERS / REACTORS / RESISTORS


( Data Sheets )

Power Transformers,
2 MVA, 33 + 5% - 5%/11.5 kV

ADWEA/ADDC/AADC STANDARD : D-AAA-TRAFO-33-11_2


(Rev.0-2015)

________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 1 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Table of Content

Page

1.00 GENERAL 3

2.00 RATINGS 3

3.00 TESTS 5

4.00 OPERATION DETAILS 6

5.00 DESIGN DETAILS AND FEATURES 7

6.00 BUSHINGS 9
6.01 Primary 9
6.02 Secondary (Lines and Neutral) 9

7.00 CURRENT TRANSFORMERS 10


7.01 For Protection Purposes 10
7.02 For Protection Purposes 10
7.03 For Protection Purposes 10
7.04 For Protection Purposes 11
7.05 For Protection Purposes 11

9.00 ON-LOAD TAP-CHANGER 11

10.00 SILICAGEL BREATHERS (maintenance-free) 12

11.00 MASSES, MEASURES AND DRAWINGS 12

_____________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 2 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

1.00 GENERAL

1.01 Manufacturer
1.01.1 name
1.01.2 country of manufacturing
1.02 Manufacturer quality system
1.02.1 applicable standards
1.02.1.1 certified by (Company Name)
1.02.1.2 validity till (year)
1.03 Applicable standard(s) for the Transformer IEC 60076

1.04 Place of testing


1.05 Kind of installation outdoor

1.06 Single or Three-Phase unit three-phase

1.07 Magnetic core


1.07.1 type of core core or shell form

1.07.2 type of stacking step-lap

1.07.3 three or five-limb core three

1.08 Type of tank upper flange type

1.09 Tank fully vacuum proof yes

1.10 Number of windings two power windungs

1.11 Insulation oil


1.11.1 manufacturer
1.11.2 type
1.11.3 specification of oil (general) IEC 60296, 62535

1.11.4 insulation oil meeting Special Applications yes

1.11.5 additional test method for corrosive sulfur ASTM D1275 B

2.00 RATINGS

2.01 Rated power


2.01.1 at ONAN cooling MVA 2

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 3 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

2.02 Rated frequency Hz 50

2.03 Maximum ambient temperature 0


C 50

2.04 Maximum service altitude m 1000

2.05 Temperature rise limits at all tap changer settings


2.05.1 oil / top K 45

2.05.2 windings / average K 55

2.05.3 windings / hot spot K 68

2.05.4 hot spot factor (H)


2.05.4.1 core of core-form type H 1.3

2.05.4.2 core of shell-form type H 1.5

2.06 Rated voltages (no-load)


2.06.1 primary kV 33

2.06.2 secondary kV 11.5

2.07 Rated current


2.07.1 primary
2.07.1.1 at tap -1- A

2.07.1.2 at tap -5- ( Principal tap ) A

2.07.1.3 at tap -9- A

2.07.2 secondary A

2.08 Voltage variation range kV 1.65

2.09 Tapping range % 5

2.10 Number of steps steps (+4/ -4x1.25%)

2.11 Principle tapping kV 33

2.12 Tapped winding HV

2.13 Continuous power at all taps yes

2.14 Permissible load of neutral point % 100

2.15 Vector group symbol Dyn11

2.16 Magnetic flux density at rated voltage TESLA max. 1.6


and frequency
2.17 No-load losses (max.) kW

2.18 No-load current (Io/In) %

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 4 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

2.19 Core losses (W17/50) W/kg max. 1.05

2.20 Impedance voltage-primary/secondary


(2 MVA basis)
2.20.1 at each tap % approx.. 6.5

2.21 Load losses (2 MVA basis)


2.21.1 tap changer position -1- kW

2.21.2 tap changer position -5- kW

2.21.3 tap changer position -9- kW

2.22 Power consumption of cooling plant kW N/A

2.23 Winding insulation design:


2.23.1 primary winding uniform

2.23.2 secondary winding uniform

2.24 Insulation Level / Primary winding


2.24.1 power frequency withstand voltage kV 70

2.24.2 lightning impulse level kV 200

2.25 Insulation Level / Secondary winding


2.25.1 power frequency withstand voltage kV 28/28
(line/neutral)
2.25.2 lightning impulse level (line/neutral) kV 75/75

3.00 TESTS

3.01 Lightning impulse test on one unit

3.02 Full wave


3.02.1 primary kV 200

3.02.2 secondary (lines/neutral) kV 75/75

3.03 Chopped wave (lines only)


3.03.1 primary kV 220

3.03.2 secondary kV 82.5

3.04 Separate source AC voltage withstand test on each unit

3.04.1 primary kV 70

3.04.2 secondary kV 28

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 5 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

3.05 Induced AC voltage withstand test, acc. to on each unit


IEC 60076-3, clause 11.2
3.05.1 test voltage / primary kV 70

3.05.2 test voltage / secondary kV 23

3.05.3 test frequency Hz

3.06 Test of temperature rise on one unit

3.07 Test of noise level (special test) on one unit

3.08 All other type, routine, and special tests yes


according to the specifications
3.09 Short circuit test
3.09.1 name of independent testing laboratory
who carried out the short circuit test on
similar transformer
3.09.2 test certificate attached yes

3.09.3 validity of quality control certificates


3.09.4 name of issuing authority

4.00 OPERATION DETAILS

4.01 Cooling method ONAN

4.02 Noise level (LpA) at a measuring distance dB(A) max. 60


of 0.3 m
4.03 Permissible over-load and duration
(in minutes)
4.03.1 20 % over-load
4.03.1.1 at 30 0C min.

4.03.1.2 at 40 0C min.

4.03.1.3 0 min.
at 50 C
4.03.2 30 % over-load
4.03.2.1 at 30 0C min.

4.03.2.2 at 40 0C min.

4.03.2.3 0 min.
at 50 C
4.03.3 40 % over-load

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 6 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

4.03.3.1 at 30 0C min.

4.03.3.2 0 min.
at 40 C
4.03.3.3 at 50 0C min.

4.03.4 50 % over-load
4.03.4.1 at 30 0C min.

4.03.4.2 0 min.
at 40 C
4.03.4.3 at 50 0C min.

5.00 DESIGN DETAILS AND FEATURES

5.01 Current densities at rated power


5.01.1 primary A/mm2 max. 3

5.01.2 regulation windings A/mm 2 max. 3

5.01.3 secondary A/mm 2 max. 3

5.02 Winding resistances at 75 0C


5.02.1 primary / Phase

5.02.2 regulation windings / Phase

5.02.3 secondary / Phase

5.03 Type of windings


5.03.1 primary
5.03.2 regulation windings
5.03.3 secondary
5.04 Winding conductor material (all windings) copper

5.05 Winding connections brazed or crimped

5.06 Banded or core bolt construction


5.07 Thermal class of insulation A

5.08 Insulation material


5.08.1 primary
5.08.2 secondary
5.08.3 tapping leads
5.08.4 core lamination

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 7 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

5.09 Radiators
5.09.1 wall thickness mm min 1.2

5.09.2 width mm 470 - 520

5.10 Type of valves


5.10.1 radiator valves butterfly valves

5.10.2 valves for silicagel breathers of conservators globe or gate valves

5.10.3 on tank and conservator globe or gate valves

5.10.4 oil sampling valves globe or gate valves

5.11 Efficiencies
5.11.1 at 25 % of rated power %

5.11.2 at 50 % of rated power %

5.11.3 at 75 % of rated power %

5.11.4 at 100 % of rated power %

5.11.5 at 125 % of rated power %

5.11.6 at 150 % of rated power %

5.12 Voltage regulation at 75 0C and rated power


5.12.1 at power factor 0.80 %

5.12.2 at power factor 0.85 %

5.12.3 at power factor 0.90 %

5.12.4 at power factor 0.95 %

5.13 Thickness of tank cover, walls and bottom


5.13.1 cover mm min. 16

5.13.2 walls mm

5.13.3 length of transformer less than 2500 mm mm min. 6

5.13.4 length of transformer more than 2500 mm mm min. 8

5.13.5 bottom mm

5.13.6 self-supporting tank bottom mm min. 25

5.13.7 cross-beam supported tank bottom mm min. 12

5.13.8 nominal internal pressure at full load max. bar

5.13.9 internal withstand test pressure at full load bar

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 8 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

6.00 BUSHINGS

6.01 Primary
6.01.1 Manufacturer
6.01.2 Type oil/air

6.01.3 Rated current A 630

6.01.4 Power frequency test voltage kV 95

6.01.5 Lightning impulse level kV 250

6.01.6 Minimum creepage distance mm 832

6.01.7 Bushing insulator


6.01.7.1 manufacturer
6.01.7.2 country of manufacturing
6.01.7.3 material porcelain

6.01.7.4 type DIN equivalent

6.01.7.5 length mm

6.01.7.6 weight kg

6.01.7.7 electrostatic capability

6.02 Secondary (Lines and Neutral)


6.02.1 Manufacturer
6.02.2 Type oil/air

6.02.3 Rated current A 630

6.02.4 Power frequency test voltage kV 50

6.02.5 Lightning impulse level kV 125

6.02.6 Minimum creepage distance mm 384

6.02.7 Bushing insulator porcelain

6.02.7.1 manufacturer EN (CENELEC)

6.02.7.2 country of manufacturing


6.02.7.3 material
6.02.7.4 type

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 9 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

6.02.7.5 length mm

6.02.7.6 weight kg

6.02.7.7 electrostatic capability

7.00 CURRENT TRANSFORMERS


(to be filled-in for each type of C.T.)
(C.T. data are subject to separate approval)

7.01 For Protection Purposes


7.01.1 Rated output VA

7.01.2 Ratio
7.01.2.1 primary A

7.01.2.2 secondary A

7.01.3 Class
7.01.4 Technical data to be co-ordinated with yes
switchgear C.T.

7.02 For Protection Purposes


7.02.1 Rated output VA

7.02.2 Ratio
7.02.2.1 primary A

7.02.2.2 secondary A

7.02.3 Class
7.02.4 Technical data to be co-ordinated with yes
switchgear C.T.

7.03 For Protection Purposes


7.03.1 Rated output VA

7.03.2 Ratio
7.03.2.1 primary A

7.03.2.2 secondary A

7.03.3 Class
7.03.4 Technical data to be co-ordinated with yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 10 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

switchgear C.T.

7.04 For Protection Purposes


7.04.1 Rated output VA

7.04.2 Ratio
7.04.2.1 primary A

7.04.2.2 secondary A

7.04.3 Class
7.04.4 Technical data to be co-ordinated with yes
switchgear C.T.

7.05 For Protection Purposes


7.05.1 Rated output VA

7.05.2 Ratio
7.05.2.1 primary A

7.05.2.2 secondary A

7.05.3 Class
7.05.4 Technical data to be co-ordinated with yes
switchgear C.T.

8.00 ON-LOAD TAP-CHANGER

8.01 Manufacturer
8.02 Type
8.03 Rated through current A

8.04 Rated switching capacity kVA

8.05 Lightning impulse level (1.2 / 50 s) kV min. 200

8.06 Power frequency withstand test voltage kV min. 70

8.07 Short-time current


8.07.1 3 s value kA

8.07.2 peak value kA

8.08 Type of connection mid or end winding

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 11 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

8.09 Type of switching rotary two vacuum switch principle

8.10 Type of regulation winding coarse and fine, or reversing

8.11 Contact life (operations) 600000

8.12 Auxiliary supply voltage V, AC 400/230

8.13 Number of tap position transmitters:


8.13.1 contact type transmitters No. min. one

8.13.2 additional contact type transmitter with diode- No. one


matrix for digital remote position indication
8.13.3 resistor type transmitters No. min. one

8.13.4 additional position transmitter of the No. one


resistor type with tap position transducer,
output: 4-20 mA

9.00 SILICAGEL BREATHERS

9.01 Main conservator


9.01.1 Manufacturer
9.01.2 Type
9.01.3 self learning type yes

9.02 OLTC conservator, cable boxes


9.02.1 Manufacturer
9.02.2 Type
9.02.3 self learning type no

10.00 MASSES, MEASURES AND DRAWINGS

10.01 Transformer masses


10.01.1 total mass kg

10.01.2 transportation mass kg

10.01.3 untanking mass kg

10.01.4 mass of core kg

10.01.5 mass of windings kg

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 12 of 13
TRANSFORMERS / REACTORS / RESISTORS
Power Transformers, 2 MVA, 33 + 5% - 5%/11.5 kV

Sl. No. REQUIRED TENDERED

10.01.6 mass of tank and fittings kg

10.01.7 mass of insulation liquid kg

10.02 Overall dimensions including bushings:


10.02.1 height mm

10.02.2 depth mm

10.02.3 width mm

10.03 Shipping dimensions


10.03.1 height mm

10.03.2 depth mm

10.03.3 width mm

10.04 Descriptions
10.04.1 dimensional drawings No.

10.04.2 connection diagram No.

10.04.3 pamphlet No.

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-TRAFO-33-11_2 (Rev.0-2015) Page 13 of 13